Johnson Controls VG1000 Series, VG1841 Series, VG1644 Series, VG1845 Series, VA9104 Series Installation Instructions Manual

...
Figure 1: Mounting Positions for Chilled Water and Condensing Atmosphere Applications
*1412015RevX*
14-1201-5 Rev. X
VG1000 Series Forged Brass Ball Valves
Installation Instructions
Part No. 14-1201-5, Rev. X
Issued December 2018
Refer to the QuickLIT website for the most up-to-date version of this document.
Applications
The VG1000 Series Ball V alves are designed to regulate the flow of hot or chilled water (and for some models, low pressure steam) in response to the demand of a controller in HVAC systems.
IMPORTANT: Use the VG1000 Series Valves as an operating control. Where failure or malfunction of the VG1000 Series Valve could lead to personal injury or property damage to the controlled equipment or other property, additional precautions must be designed into the system. Incorporate and maintain other devices, such as supervisory or alarm systems or safety or limit controls, intended to warn of or protect against failure or malfunction of the VG1000 Series Valve.
Installation
Install VG1000 Series Ball Valves with the actuator at or above the centerline of the horizontal piping, as shown in Figure 1.
IMPORTANT: In steam applications, install the valve with the stem horizontal to the piping. Failure to follow these guidelines may shorten the life of the actu at or.
To minimize heat transfer in steam applications, wrap the valve and piping with insulation. Allow sufficient clearance to remove the actuator (as illustrated in the dimension drawings, Figure 6 through Figure 11).
When mounting the actuator in the field (befo re installation ), use an adjustab le wrench to manu ally rotate the valve stem several times. This rotation breaks the torque that may have built up during long-term storage.
For the valve to move in the proper direction, wire the input lines to the electric actuator correctly.
VG1000 Series Forged Brass Ball Valves Installation Instructions
s
o p
t n m
: G
I F
1
IMPORTANT: Take care to prevent foreign material such as weld slag, thread burrs, metal chips, and scale from entering the piping system. This debris can damage or severely impede the operation of the valve by embedding itself in the seats, scoring the valve, and ultim at ely resu ltin g in se at leaka g e. If the debr is be co me s embedded in the seats, subsequent flushing and filtering of the piping system with the valve installed does not remedy the problem.
For more detailed installation information about the specific equipment used, refer to the appropriate document from the following list:
VA9104-xGA-2S Series Electric Non-Spring Return Valve Actuators Installation Instructions
(Part No. 14-1336-15)
VA9104-xGA-3S Series Electric Non-Spring Return Valve Actuators Installation Instructions (Part No. 14-1336-23)
M9102-AGA-2S and M9104-xGA-2S Series Electric Non-Spr ing Return Actuators Installation Instructions (Part No. 34-636-1220)
M9102-AGA-3S and M9104-xGA-3S Series Electric Non-Spr ing Return Actuators Installation Instructions (Part No. 34-636-1433)
VA9300 Series Electric Non-Spring Return Valve Actuators Installation Instructions (Part No. 34-636-2421)
VA9203 -AGx-2Z Series On/Off and Floating Point Electric Spring Return Valve Actuators Installation Instructions (Part No. 14-1380-8)
VA9203-Bxx-2 Series On/Off Spring Return Valve Actuators Installation Instructions (Part No. 14-1380-16)
VA9203-GGx-2Z Series Proportional Spring Return Valve Actuators Installation Instructions (Part No. 14-1380-24)
VA9208-AGx-x Series On/Off and Floating Point Electric Spring Return Valve Actuators Installation Instructions (Part No. 14-1379-5)
VA9208-Bxx-x Series On/Off Spring Return Valve Actuators Installation Instructions (Part No. 14-1379-13)
VA9208-GGx-x Series Proportional Spring Return Valve Actuators Installation Instructions (Part No. 14-1379-21)
M9000-560 Ball Valve Linkage Kit and M9000-561 Thermal Barrier Installation Instructions (Part No. 34-636-2227)
M9000-342 Series Weather Shield Enclosures Installation Instructions (Part No. 34-636 -2499)
M9000-551 Ball Valve Linkage Kit Installation Instructions (Part No. 34-636-1816)
Note: To avoid excessive wear or drive time on the motor for VA9104 and M9104 models, use a controller or software that provides a time-out funct ion to re mo ve the signal at the end of rotation (stall). The IGx and GGx models have an auto shutoff to avoid excessive wear or drive time on the motor.
On models with the flow-characterizing disk, the disk is located in Port A. Port A must be the inlet. On three-way models, use Port A as the coil inlet and Port B as the bypass inlet.
VG1000 Series Forged Brass Ball Valves Installation Instructions
2
VG1841 and VG1845 Series Three-W ay Ball Valves have a different port configuration from VG1644 Series Three-
Port A
Coil
Figure 2: VG1841 or VG1845 Series Three­Way Ball Valve (Port A Connected to Port C)
Port A
Coil
F
I
G
:
v
g
B
t
o
C
Figure 3: VG1841 or VG1845 Series Three­Way Ball Valve (Port B Connected to Port C)
Port
Normally Open Port
Normally
F
I
G
:
v
g
1
6
4
4
c
c
w
Figure 4: Top View of VG1644 Series Three-
Way Ball Valve (Actuator Fully
Way valves. See Figure 2, Figure 3, and Figure 4 for details.
Port C
Common
C
o
t A G V
: G
Port B Bypass
I F
Port C
Common
IMPORTANT: Protect the actuator from dripping water, condensation, and other moisture. Water or moisture could result in an electrical short, which may damage or affect the operation of the actuator.
IMPORTANT: Do not cover the actuator with thermal insulating material. High ambient temperatures may damage the actuator, and a hot water pipe, steam pipe, or other heat source may overheat it.
Contact your local Johnson Controls® representative for compatibility concerns before using VG1000 Series Ball Valves to control the flow of fluids other than those outlined in the Technical Specifications
Port B Bypass
Common
Closed Port
table in this document.
VG1000 Series Forged Brass Ball Valves Installation Instructions
3
Press Valve Installation
Figure 5: Sweat Valve Installation
g
tempera tu r e soft solder.
the neck of th e valve.
FIG:sv_ins
VG1000 press end connection valves are installed using RIDGID® press tools. Always refer to the operator’s manual supplied with the RIDGID press tool that is used to make the valve end connections. The manual should provide proper instructions for the safe operation of the tool, proper crimping procedures, and methods of inspecting the finished connection. If you use a battery-operated press tool, ensure its proper operation by fully charging the unit. To avoid damage to the integral O-ring, never use sealant or pipe dope with a press connection. Always inspect the end connections of the valve before making the connection. The end connection should not be deformed, and the internal, integral O-ring must be in place for a proper seal.
Sweat Valve Installation
When soft soldering sweat ball valves, be sure to use a low temperature solder with a melting point that does not exceed 450°F (232°C). For lead-free RoHS compliance, a 96.5% tin/3.5% silver solder is recommended. Never install the actuator on the valve until you have completed the soldering operation and the valve body has cooled. Before soldering, minimize the risk of damage to the ball seals by positioning the ball so that Port A is fully open. When soldering, always apply a wet rag around the valve’s neck and cover as much of the valve body with the rag as possible. Direct the tip of the flame away from the valve and always heat the copper tubing directly, but never the valve body. Solder Port A first, then the remaining ports. These steps provide maximum protection to the internal valve components. See Figure 5 for details.
Use only low meltin
Place a wet r ag around
t
VG1000 Series Forged Brass Ball Valves Installation Instructions
4
See Figure 6 for dimension drawings of the Non-Spring Return VA9104 Series Actuated VG1241, VG1245,
Figure 6: VA9104 Actuated VG1241, VG1245, VG1841, and VG1845 Series Ball Valve
with NPT End Connections Dimensions, in. (mm)
2-13/16
(71)
3-1/2 (89 )
Clearance Required
Port Marking
Locations
F
I
G
V
A
9
1
0
4
X
_
d
i
m
s
6-1/2
(153.5)
D
A
VG1841, and VG1845 Series NPT End Connection Ball Valves. See T able 1 and Table 2 for specific model linkage dimensions.
Table 1: VA9104 or M9104 Actuated VG1241, VG1245, VG1841, and VG1845 Series Ball Valve with
Optional M9000-551 Linkage Dimensions, in. (mm)
Valve Size, in. (DN)
1
A
(Without
Thermal
Barrier)
1/2 (DN15) 3-7/8
(98)
3/4 (DN20) 3-7/8
(98)
1 (DN25) 3-11/16
(100)
1. Port A must always be connected to the coil.
A
(With
Thermal
Barrier)
5-11/32 (135)
5-11/32 (135)
5-27/64 (137)
BC D E F G
21/32 (17)
21/32 (17)
3/4 (19)
1-7/32 (31)
1-7/32 (31)
1-19/64 (33)
5-7/64 (129)
5-7/32 (133)
5-9/16 (141)
2-33/64 (64)
2-51/64 (71)
3-13/32 (87)
11/32 (9)
11/32 (9)
11/32 (9)
T able 2: V A9104 Act uated VG1275 and VG1875 Se ries Ball Valve with Sweat End Connections and VA9104
Actuated VG1295 and VG1895 Series Ball Valves with Press End Connections Dimensions, in. (mm)
Valve Size, in. (DN)
1/2 (DN15) 3-7/8 (98) 21/32 (17) 1-7/32 (31) 5-45/64 (145) 3-25/32 (96) 11/32 (9) 2-13/16 (55) 3/4 (DN20) 3-7/8 (98) 21/32 (17) 1-7/32 (31) 5-57/64 (150) 4-3/32 (104) 11/32 (9) 2-15/32 (62) 1 (DN25) 3-15/16 (100) 3/4 (19) 1-19/64 (33) 6-1/8 (156) 4-21/32 (118) 11/32 (9) 2-27/32 (72)
1
ABC D EFG
1-1/4 (32)
1-13/32 (36)
1-11/16 (43)
1. Port A must always be connected to the coil.
VG1000 Series Forged Brass Ball Valves Installation Instructions
5
See Figure 7 for dimension drawings of the Spring Return VA9203 Series Actuated VG1241, VG1245, VG1841,
Figure 7: Spring Return VA9203 Actuat ed VG1241, VG1245, VG1841, and VG1845 Ser ies Ball V alve with
Optional M9000-561 Thermal Barrier Installed Dimensions, in. (mm)
Port Marking
Locations
F
I
G
:
V
A
9
2
0
3
X
_
d
i
m
s
t
h
b
r
2-7/8
(73)
3-1/4
(82)
A
D
3-1/2 (89)
Clearance Required
and VG1845 Series NPT End Connection Ball Valves. See Table 3 and Table 4 for specific model linkage dimensions.
Table 3: VA9203 Actuated VG1241, VG1245, VG1841, and VG1845 Series Ball Valve with NPT End
Connections Dimensions, in. (mm)
Valve Size, in. (DN)
1
(Without
Thermal
Barrier)
1/2 (DN15) 4-1/4
(108)
3/4 (DN20) 4-1/4
(108)
1 (DN25) 4-9/32
(109)
A
A
(With
Thermal
Barrier)
6 (152)
6 (152)
6-1/16 (154)
1. Port A must always be connected to the coil.
BCDEFG
21/32 (17)
21/32 (17)
3/4 (19)
1-7/32 (31)
1-7/32 (31)
1-19/64 (33)
6-23/32 (171)
6-7/8 (175)
7-7/64 (181)
2-33/64 (64)
2-51/64 (71)
3-13/32 (87)
11/32 (9)
11/32 (9)
11/32 (9)
Table 4: VA9203 Actuated VG1271, VG1275, VG1871, and VG1875 Series Sweat Ball Valve and VA9203
Valve Size, in. (DN)
1/2 (DN15) 4-5/8 (117) 21/32 (17) 1-7/32 (31) 7-13/64 (183) 3-25/32 (96) 11/32 (9) 1-1/4 (32) 3/4 (DN20) 4-5/8 (117) 21/32 (17) 1-7/32 (31) 7-3/4 (197) 4-3/32 (104) 11/32 (9) 1-13/32 (36) 1 (DN25) 4-11/16 (119) 3/4 (19) 1-19/64 (33) 8-3/16 (208) 4-41/64 (118) 11/32 (9) 1-45/64 (43)
1. Port A must always be connected to the coil.
Actuated VG1291, VG1295, VG1891, and VG1895 Series Press Ball Valve Dimensions, in. (mm)
1
ABC D EFG
1-1/4 (32)
1-13/32 (36)
1-45/64 (43)
VG1000 Series Forged Brass Ball Valves Installation Instructions
6
See Figure 8 for dimensions of the Non-Spring Return VA9300 Actuated VG1241, VG1245, VG1841, and VG1845
Figure 8: Non-Spring Return VA9300 Actuated VG1241, VG1245, VG1841, and VG1845 Series Ball
Valve with Optional M9000-561 Thermal Barrier Dimensions, in. (mm)
B
D
A
3-1/2 in. (89 mm)
C
Optional Thermal Barrier
Optional Thermal Barrier
Locations
Series Ball Valve with Optional M9000-561 Thermal Barrier. See Table 5 for specific model linkage dimensions.
Port Marking
B
FIG:Thermal Barrie r
Table 5: VA9300 Actuated VG1241, VG1245, VG1841, and VG1845 Series Ball Valve with Optional
M9000-561 Thermal Barrier Dimensions, in. (mm)
Valve Size, in. (DN)
1/2 (DN15)
3/4 (DN20)
1 (DN25)
1-1/4 (DN32)
1-1/2 (DN40)
2 (DN50)
A (Wit h
Thermal
Barrier)
A (Without
Thermal
Barrier)
BC D EFG
5-3/4 (146) 4-3/8 (111) 21/32 (17) 1-7/32 (31) 6-1 3/32 (163) 2-33/64 (64) 11/32 (9) 1-1/4 (32)
5-3/4 (146) 4-3/8 (111) 21/32 (17) 1-7/32 (31) 6-1 3/32 (163) 2-51/64 (71) 11/32 (9) 1-13/32 (36)
5-13/16 (148) 4-7/16 (113) 3/4 (19) 1-5/16 (33) 6-13/32 (163) 3-13/32 (87) 11/32 (9) 1-45/64 (43)
6-1/4 (159) 4-7/8 (124) 1-1/32 (26) 1-23/32 (44) 6-13/32 (163) 3-15/16 (100) 11/32 (9) 1-31/32 (50)
6-13/32 (163) 5-1/32 (128) 1-1/8 (29) 1-7/8 (48) 6-13/32 (163) 4-21/64 (110) 11/32 (9) 2-11/64 (55)
6-5/8 (168) 5-1/4 (133) 1-15/32 (37) 2- 1/16 (53) 6-13/32 (163) 4-27/32 (123) 11/32 (9) 2-27/64 (62)
VG1000 Series Forged Brass Ball Valves Installation Instructions
7
See Figure 9 for dimensions of the Non-Spring Return VA9300 Actuated VG1241, VG1245, VG1841, and VG1845
Figure 9: Non-Spring Return VA9300 Actuated VG1241, VG1245, VG1841, and VG1845 Series Ball
Valve with Optional M9000-561 Thermal Barrier and M9300-2 Switch Kit Dimensions, in. (mm)
B
D
C
Locations
Series Ball V alve with Optional M9000-5 61 Thermal Barrie r and M9300-2 Switch Kit. See Table 6 for specific model linkage dimensions.
Port Marking
B
Table 6: VA9300 Actuated VG1241, VG1245, VG1841, and VG1845 Series Ball Valve with Optional
M9000-561 Thermal Barrier and M9300-2 Switch Kit Dimensions, in. (mm)
Valve Size, in. (DN)
1/2 (DN15)
3/4 (DN20)
1 (DN25)
1-1/4 (DN32)
1-1/2 (DN40)
2 (DN50)
A (Wit h
Thermal
Barrier)
6-3/25 (155.7)
6-3/25 (155.7)
6-1/5 (157.7)
6-16/25 (168.7)
6-4/5 (172.7)
6 (177.2)
A (Without
Thermal
Barrier)
4-3/4 (120.7)
4-3/4 (120.7)
4-21/25 (122.7)
5-1/4 (133.7)
5-3/7 (137.7)
5-5/8 (142.7)
BCDEFG
21/32 (17)
21/32 (17)
3/4 (19)
1-1/32 (26)
1-1/8 (29)
1-15/32 (37)
1-7/32 (31)
1-7/32 (31)
1-5/16 (33)
1-23/32 (44)
1-7/8 (48)
2-1/16 (53)
6-21/32 (169)
6-21/32 (169)
6-21/32 (169)
6-21/32 (169)
6-21/32 (169)
6-21/32 (169)
2-33/64 (64)
2-51/64 (71)
3-13/32 (87)
3-15/16 (100)
4-21/64 (110)
4-27/32 (123)
11/32 (9)
11/32 (9)
11/32 (9)
11/32 (9)
11/32 (9)
11/32 (9)
1-1/4 (32)
1-13/32 (36)
1-45/64 (43)
1-31/32 (50)
2-11/64 (55)
2-27/64 (62)
FIG:Thermal Barrie r
VG1000 Series Forged Brass Ball Valves Installation Instructions
8
See Figure 10 for dimension drawings of the Spring Return VA9208 Actuated VG1241, VG1245, VG1841, and
Figure 10: Spring Return VA9208 Actuated VG1241, VG1245, VG1841, and VG1845 Series Ball Valve with
Optional M9000-561 Thermal Barrier Installed Dimensions, in. (mm)
3-29/32
(99)
A
B
3-1/2 (89)
Clearance Required
GCFBC
E
Port Marking
Locations
D
VG1845 Series NPT End Connection Ball Valves with M9000-561 Thermal Barrier. See Table 7 for specific model linkage dimensions.
Table 7: VA9208 Actuated VG1241, VG1245, VG1841, and VG1845 Series Ball Valve with Optional
M9000-561 Thermal Barrier Installed Dimensions, in. (mm)
Valve Size in.
1
(DN)
1-1/4 (DN32)
1-1/2 (DN40)
2 (DN50)
Valve
Style
A
(With
Thermal
Barrier)
All 9-17/64
(235)
All 9-15/16
(240)
2-way 9-31/32
(244)
A
(Without
Thermal
Barrier)
7-11/16 (195)
7-7/8 (200)
8-1/32 (204)
3-way 7-7/8
BCDEFG
1-1/32 (26)
1-9/64 (29)
1-15/32 (37)
1-23/32 (44)
1-57/64 (48)
2-1/8 (54)
7-1/4 (184)
7-7/16 (189)
7-11/16 (195)
(200)
3-15/16 (100)
4-21/64 (110)
4-27/32 (123)
11/32 (9)
11/32 (9)
11/32 (9)
1. Port A must always be connected to the coil.
1-31/32 (50)
2-11/64 (55)
N/A
2-27/64 (62)
VG1000 Series Forged Brass Ball Valves Installation Instructions
9
Piping
Port C
Port
B
Port A
Typical Three-Way Ball Valve Application
Typical Two-Way Ball Valve Application
VG124x Two- Way Valve
F
I
G
:
V
G
1
0
0
0
_
t
y
p
p
i
p
Figure 11: Typical VG1000 Piping
VG184x Three-Way Valve
Return
Supply
Note: Mount the valve downstream from the coil to minimize heat transfer to the actuator.
Port BPort A
Return
Supply
VG1000 Series Forged Brass Ball Valves Installation Instructions
10
Wiring
This product is made of copper alloy, which contains lead. The product is therefore not to be used on drinking water.
This product can expose you to chemicals including lead, which is known to the State of California to cause cancer, birth defects, or other reproductive harm. For more information, go to www.P65Warnings.ca.gov.
WARNING: BRASS MAY CONTAIN LEAD
To fulfill our obligations towards Article 33, in accordance to the European REACH Regulation No 1907/2006 EC, we hereby inform you that this article contains the following Substances of Very High Concern mentioned on the Candidate list:
• Lead
Be sure to wire the input lines to the electric actuator correctly for the valve to move in the proper direction.
IMPORTANT: Use copper conductors only. Make all wiring connections in accordance with local, national, and regional regulations. Do not exceed the actuator’s electrical ratings.
Risk of Electric Shock.
Disconnect the power supply before making electrical connections. Contact with components carrying hazardous voltage can cause electric shock and may result in severe personal injury or death.
Risque de décharge électrique.
Débrancher l'alimentation avant de réaliser tout branchement électrique. Tout contact avec des composants conducteurs de tensions dangereuses risque d'entraîner une décharge électrique et de provoquer des blessures graves, voire mortelles.
Troubleshooting
Servicing the Actuator or Piping System
When servicing the electric actuator or the piping system:
disconnect the power supply to the actuator
relieve the pressure in the piping system
IMPORTANT: Do not attempt to manually rotate the drive shaft while the actuator is installed without first releasing the actuator gears. Manually rotating the drive shaft without releasi ng the actuator gears may result in permanent damage to the actuator.
Repair Information
If the VG1000 Series Forged Brass Ball Valve fails to operate within its specifications, replace the unit. For a replacement valve, contact the nearest Johnson Controls® representative.
VG1000 Series Forged Brass Ball Valves Installation Instructions
11
Technical Specifications
VG1000 Series Forged Brass Ball Valves (Part 1 of 2 )
Service
Fluid Temperature Limits Water VG12x1 and VG18x1 Series: 23 to 203F (-5 to 95C)
Maximum Fluid Temperature Limits
Valve Body Pressure/ Temperature Rating
Maximum Closeoff Pressure 200 psig (1,378 kPa) Maximum Recommended Operating Pressure
Drop Flow Characteristics Two-Way Equal Percentage
Rangeability Minimum Ambient Operating
Temperature
Maximum Ambient Operating Temperature
Leakage 0.01% of Maximum Flow per ANSI/FCI 70-2, Class 4
End Connections National Pipe Thread (NPT): 1/2 to 2 in. (DN15 to DN50)
1
Steam VG12x1 Series: Not Rated for Steam Service
212°F (100°C) VA9104
284°F (140°C) VA9104 with M9000-561 Thermal Barrier
Water VG1241, VG1245, VG1841, and VG1845 Series:
Steam 15 psig (103 kPa) Saturated Steam
Three-Way Equal Percentage Flow Characteristics of In-line Port A (Coil) and
2
-4°F (-20°C) VA9104 and M9104 Series Non-Spring Return Actuators
-22°F (-30°C) VA9203 Series Spring Return Actuators
-40°F (-40°C) VA9208 Series Spring Return Actuators
3
140°F (60°C) VA9104 and VA9300 Series Non-Spring Return Actuators
Hot Water, Chilled Water, 50/50 Glycol Solutions, and 15 psig (103 kPa) Saturated Steam for HVAC Systems
VG12x5 and VG18x5 Series: -22 to 284F (-30 to 140C)
VG12x5 Series: 15 psig (103 kPa) at 250°F (121°C)
VA9300 VA9203 VA9208
VA9300 with M9000-561 Thermal Barrier VA9203 with M9000-561 Thermal Barrier VA9208 with M9000-561 Thermal Barrier
580 psig (4,000 kPa) at 203°F (95°C) (PN40) 464 psig (3,196 kPa) at 284°F (140°C) (PN40)
VG1275 and VG1875 Series:
300 psig (2,067 kPa)
VG1295 and VG1895 Series:
300 psig (2,067 kPa)
50 psig (340 kPa)
Linear Flow Characteristics of Angle Port B (Bypass) Greater than 500:1
VA9300 Series Non-Spring Return Actuator s
VA9203 and VA9208 Series Spring Return Actuators
(Two- and Three-Way Control Port) 1% of Maximum Flow for Three-Way Bypass Port
Sweat: 1/2 to 1 in. (DN15 to DN25) Use a low melting point solder. Press (ProPress compatible): 1/2 to 1 in. (DN15 to DN25) Press end connections are designed to work with RIDGID pressing
tools.
VG1000 Series Forged Brass Ball Valves Installation Instructions
12
Metasys® and Johnson Controls® are registered trademarks of Johnson Controls.
All other marks herein are the marks of their respective owners. © 2018 Johnson Controls.
Building Technologies & Solutions
507 E. Michigan Street, Milwaukee, WI 53202
VG1000 Series Forged Brass Ball Valves (Part 2 of 2 )
Materials Body Forged Brass
Ball VG12x1 and VG18x1 Series: Chrome Plated Brass
VG12x5 and VG18x5 Series: 300 Series Stainless Steel
Blowout-Proof Stem
Seats Graphite-Reinforced PTFE with Ethylene Propylene Diene Monomer
Stem Seals EPDM Double O-Rings Characterizing
Disk
Compliance CRN For NPT threaded valves with Stainless Steel Ball (VG1x45...):
1. Proper water treatment is recommended; refer to the VDI 2035 Guideline.
2. Rangeability is defined as the ratio of maximum controllable flow to minimum controllable flow.
3. In steam applications, install the valve with the stem horizontal to the piping and wrap the valve and piping with insulation.
European Single Point of Contact: NA/SA Single Point of Contact: APAC Single Point of Contact:
JOHNSON CONTROLS WESTENDHOF 3 45143 ESSEN GERMANY
JOHNSON CONTROLS 507 E MICHIGAN ST MILWAUKEE WI 53202 USA
VG12x1 and VG18x1 Series: Nickel Plated Brass VG12x5 and VG18x5 Series: 300 Series Stainless Steel
(EPDM) O-Ring Backing
Amodel AS-1145HS Polyphthalamide Resin
0C16910.5C
JOHNSON CONTROLS C/O CONTROLS PRODUCT MANAGEMENT NO. 22 BLOCK D NEW DISTRICT WUXI JIANGSU PROVINCE 214142 CHINA
The performance specifications are nominal and conform to acceptable industry standard. For application at conditions beyond these specifications, consult the local Johnson Controls office. Johnson Controls shall not be liable for damages resulting from misapplication or misuse of its products.
VG1000 Series Forged Brass Ball Valves Installation Instructions
Published in U.S.A. www.johnsoncontrols.com
13
Loading...