VG1000 Series Two-Way, Stainless Steel Trim, NPT End Connections Ball Valves with Non-Spring-Return Electric Actuators
Description
VG1000 Series Ball Valves are designed to regulate the flow of hot or chilled water and, for some models, low-pressure steam in response to the demand of a controller in HVAC systems. Available in sizes 1/2 through 2 in. (DN15 through DN50), this family of two- and three-way forged brass valves is factory or field mounted to Johnson Controls® VA9104, M9106, M9109, and M9100 Series Non-Spring-Return and VA9203 and VA9208 Series Spring-Return Electric Actuators for on/off, floating, or proportional control.
Refer to the VG1000 Series Forged Brass Ball Valves Product Bulletin (LIT-977132) for important product application information.
Selection Charts
Two-Way Stainless Steel Trim Ball Valves, Non-Spring Return, VA9104 Actuators without Switches
Fluid Temperatures: -4 to 212°F (-20 to 100°C) Not Rated for Steam Service
Valve Size, in. Cv Closeoff
Actuators with M3 Screw Terminals VA9104-AGA-3S VA9104-IGA-3S VA9104-GGA-3S VG1245AD 1/2 1.2 VG1245AE 1.9
Actuators
Actuators
VG1245AF 2.9 VG1245AG 4.7
Threaded Ball Valves and
Threaded Ball Valves and
VG1245AL 7.4 VG1245AN 11.7 VG1245AN+9T4AGA VG1245AN+9T4IGA VG1245AN+9T4GGA VG1245BG 3/4 4.7 VG1245BL 7.4 VG1245BN 11.7 VG1245BN+9T4AGA VG1245BN+9T4IGA VG1245BN+9T4GGA VG1245CL 17.4 VG1245CN 11.7 VG1245CP 18.7 VG1245CP+9T4AGA VG1245CP+9T4IGA VG1245CP+9T4GGA Actuators with 48 in. (1.2 m) 18 AWG Plen um Cable VA9104-AGA-2S VA9104-IGA-2S VA9104-GGA-2S VG1245AD 1/2 1.2 VG1245AE 1.9 VG1245AF 2.9 VG1245AG 4.7 VG1245AL 7.4 VG1245AN 11.7 VG1245AN+9A4AGA VG1245AN+9A4IGA VG1245AN+9A4GGA VG1245BG 3/4 4.7 VG1245BL 7.4 VG1245BN 11.7 VG1245BN+9A4AGA VG1245BN+9A4IGA VG1245BN+9A4GGA VG1245CL 17.4 VG1245CN 11.7 VG1245CP 18.7 VG1245CP+9A4AGA VG1245CP+9A4IGA VG1245CP+9A4GGA
1. To avoid excessive wear or drive time on the motor for the AGx models, use a controller or software that provides a timeout function to remove the signal at the
2. Valve has a characterizing disk.
end of rotation (stall).
Threaded Ball Valves and Actuators
Features
• Forged Brass Body — provides 580 psig static pressure rating.
• 200 psi Closeoff Pressure Rating — provides tight shutoff.
• 300 Series Stainless Steel Ball and Stem Assembly — tolerates high-temperature water or 15 psi saturated steam with fluid temperatures of -22 to 284F (-30 to 140C) or where a higher degree of corrosion protection is desired.
• 500:1 Rangeability — provides accurate control under all load conditions.
Repair Information
If the VG1000 Series Ball Valve Assembly fails to operate within its specifications, replace the valve body, actuator, or entire assembly. For replacement parts, contact the nearest Johnson Controls representative.
AC 24 V On/Off (Floating)
psig
2 2 2 2 2
2 2
2
2
2 2 2 2 2
2 2
2
2
200 VG1245AD+9T4AGA VG1245AD+9T4IGA VG1245AD+9T4GGA
200 VG1245BG+9T4AGA VG1245BG+9T4IGA VG1245BG+9T4GGA
200 VG1245CL+9T4AGA VG1245CL+9T4IGA VG1245CL+9T4GGA
200 VG1245AD+9A4AGA VG1245AD+9A4IGA VG1245AD+9A4GGA
200 VG1245BG+9A4AGA VG1245BG+9A4IGA VG1245BG+9A4GGA
200 VG1245CL+9A4AGA VG1245CL+9A4IGA VG1245CL+9A4GGA
without Timeout
VG1245AE+9T4AGA VG1245AE+9T4IGA VG1245AE+9T4GGA VG1245AF+9T4AGA VG1245AF+9T4IGA VG1245AF+9T4GGA VG1245AG+9T4AGA VG1245AG+9T4IGA VG1245AG+9T4GGA VG1245AL+9T4AGA VG1245AL+9T4IGA VG1245AL+9T4GGA
VG1245BL+9T4AGA VG1245BL+9T4IGA VG1245BL+9T4GGA
VG1245CN+9T4AGA VG1245CN+9T4IGA VG1245CN+9T4GGA
VG1245AE+9A4AGA VG1245AE+9A4IGA VG1245AE+9A4GGA VG1245AF+9A4AGA VG1245AF+9A4IGA VG1245AF+9A4GGA VG1245AG+9A4AGA VG1245AG+9A4IGA VG1245AG+9A4GGA VG1245AL+9A4AGA VG1245AL+9A4IGA VG1245AL+9A4GGA
VG1245BL+9A4AGA VG1245BL+9A4IGA VG1245BL+9A4GGA
VG1245CN+9A4AGA VG1245CN+9A4IGA VG1245CN+9A4GGA
Code No. LIT-1900220
1
On/Off (Floating) with Timeout
0 to 10 VDC Proportional
The performance specifications are nomina l and con form to accep table ind ustry stand ards. For applicati ons at con ditions be yond these specification s, consult th Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2014 Johnson Controls, Inc.
V–108
Page 2
Threaded Ball Valves and Actuators
VG1000 Series Two-Way, Stainless Steel Trim, NPT End Connections Ball Valves with Non-Spring-Return Electric Actuators (Continued)
Two-Way Stainless Steel Trim Ball Valves, Non-Spring Return, VA9104 Actuators without Switches with Optional M9000-561 Thermal Barrier
Fluid Temperatures: -22 to 284°F (-30 to 140°C) Water and 15 psi Saturated Steam
Valve Size, in. Cv Closeoff
psig
Actuators with M3 Screw Terminals VA9104-AGA-3S VA9104-IGA-3S VA9104-GGA-3S VG1245AD 1/2 1.2 VG1245AE 1.9 VG1245AF 2.9 VG1245AG 4.7 VG1245AL 7.4 VG1245AN 11.7 VG1245ANH9T4AGA VG1245ANH9T4IGA VG1245ANH9T4GGA VG1245BG 3/4 4.7 VG1245BL 7.4 VG1245BN 11.7 VG1245BNH9T4AGA VG1245BNH9T4IGA VG1245BNH9T4GGA VG1245CL 17.4 VG1245CN 11.7 VG1245CP 18.7 VG1245CPH9T4AGA VG1245CPH9T4IGA VG1245CPH9T4GGA Actuators with 48 in. (1.2 m) 18 AWG Plenum Cable VA9104-AGA-2S VA9104-IGA-2S VA9104-GGA-2S VG1245AD 1/2 1.2 VG1245AE 1.9 VG1245AF 2.9 VG1245AG 4.7 VG1245AL 7.4 VG1245AN 11.7 VG1245ANH9A4AGA VG1245ANH9A4IGA VG1245ANH9A4GGA VG1245BG 3/4 4.7 VG1245BL 7.4 VG1245BN 11.7 VG1245BNH9A4AGA VG1245BNH9A4IGA VG1245BNH9A4GGA VG1245CL 17.4 VG1245CN 11.7 VG1245CP 18.7 VG1245CPH9A4AGA VG1245CPH9A4IGA VG1245CPH9A4GGA
1. To avoid excessive wear or drive time on the motor for the AGx models, use a controller or software that provides a timeout function to remove the signal at the end of rotation (stall).
2. Valve has a characterizing disk.
2 2 2 2 2
2 2
2
2
2 2 2 2 2
2 2
2
2
200 VG1245ADH9T4AGA VG1245ADH9T4IGA VG1245ADH9T4GGA
200 VG1245BGH9T4AGA VG1245BGH9T4IGA VG1245BGH9T4GGA
200 VG1245CLH9T4AGA VG1245CLH9T4IGA VG1245CLH9T4GGA
200 VG1245ADH9A4AGA VG1245ADH9A4IGA VG1245ADH9A4GGA
200 VG1245BGH9A4AGA VG1245BGH9A4IGA VG1245BGH9A4GGA
200 VG1245CLH9A4AGA VG1245CLH9A4IGA VG1245CLH9A4GGA
Two-Way Stainless Steel Trim Ball Valves, Non-Spring Return, M9106 and M9109 Actuators without Switches
Fluid Temperatures: -22 to 284°F (-30 to 140°C) Water and 15 psi Saturated Steam
Valve Size, in. Cv Closeoff
psig
VG1245DN 1-1/4 11.7 VG1245DP 18.7
VG1245DR 29.2 VG1245DR+906AGA VG1245DR+9064IGA VG1245DR+906GGA VG1245EP 1-1/2 18.7 VG1245ER 29.2 VG1245ES 46.8 VG1245ES+906AGA VG1245ES+906IGA VG1245ES+906GGA VG1245FR 2 29.2 VG1245FS 48.8 VG1245FT 73.7 VG1245FT+909AGA VG1245CPH9A4GGA
1. To avoid excessive wear or drive time on the motor for the AGx models, use a controller or software that provides a timeout function to remove the signal at the end of rotation (stall).
2. Valve has a characterizing disk.
2 2
2 2
2 2
200 VG1245DN+906AGA VG1245DN+906IGA VG1245DN+906GGA
200 VG1245EP+906AGA VG1245EP+906IGA VG1245EP+906GGA
200 VG1245FR+909AGA VG1245CLH9A4GGA
AC 24 V On/Off (Floating)
without Timeout
VG1245AEH9T4AGA VG1245AEH9T4IGA VG1245AEH9T4GGA VG1245AFH9T4AGA VG1245AFH9T4IGA VG1245AFH9T4GGA VG1245AGH9T4AGA VG1245AGH9T4IGA VG1245AGH9T4GGA VG1245ALH9T4AGA VG1245ALH9T4IGA VG1245ALH9T4GGA
VG1245BLH9T4AGA VG1245BLH9T4IGA VG1245BLH9T4GGA
VG1245CNH9T4AGA VG1245CNH9T4IGA VG1245CNH9T4GGA
VG1245AEH9A4AGA VG1245AEH9A4IGA VG1245AEH9A4GGA VG1245AFH9A4AGA VG1245AFH9A4IGA VG1245AFH9A4GGA VG1245AGH9A4AGA VG1245AGH9A4IGA VG1245AGH9A4GGA VG1245ALH9A4AGA VG1245ALH9A4IGA VG1245ALH9A4GGA
VG1245BLH9A4AGA VG1245BLH9A4IGA VG1245BLH9A4GGA
VG1245CNH9A4AGA VG1245CNH9A4IGA VG1245CNH9A4GGA
1
On/Off (Floating) with Timeout
0 to 10 VDC Proportional
AC 24 V On/Off (Floating)
without Timeout
M9106-AGA-2 M9109-AGA-2
VG1245DP+906AGA VG1245DP+906IGA VG1245DP+906GGA
VG1245ER+906AGA VG1245ER+906IGA VG1245ER+906GGA
VG1245FS+909AGA VG1245CNH9A4GGA
1
On/Off (Floating)
0 to 10 VDC Proportional
with Timeout
M9106-IGA-2 M9106-GGA-2
M9109-GGA-2
Actuators
Actuators
Actuators
Actuators
Threaded Ball Valves and
Threaded Ball Valves and
Threaded Ball Valves and
Threaded Ball Valves and
The performance specifications are nomina l and con form to accep table ind ustry stand ards. For applicati ons at con ditions be yond these specification s, consult th Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2014 Johnson Controls, Inc.
V–109
Page 3
VG1000 Series Two-Way, Stainless Steel Trim, NPT End Connections Ball Valves with Non-Spring-Return Electric Actuators (Continued)
Two-Way Stainless Steel Trim Ball Valves, Non-Spring Return, M9106 and M9109 Electric Actuators with Switches
Fluid Temperatures: -22 to 284°F (-30 to 140°C) Water and 15 psi Saturated Steam
Valve Size, in. Cv Closeoff
VG1245AD 1/2 1.2 VG1245AE 1.9 VG1245AF 2.9 VG1245AG 4.7 VG1245AL 7.4 VG1245AN 11.7 VG1245AN+906AGC VG1245AN+906IGC VG1245AN+906GGC VG1245BG 3/4 4.7 VG1245BL 7.4 VG1245BN 11.7 VG1245BN+906AGC VG1245BN+906IGC VG1245BN+906GGC VG1245CL 17.4 VG1245CN 11.7 VG1245CP 18.7 VG1245CP+906AGC VG1245CP+906IGC VG1245CP+906GGC VG1245DN 1-1/4 11.7 VG1245DP 18.7 VG1245DR 29.2 VG1245DR+906AGC VG1245DR+906IGC VG1245DR+906GGC VG1245EP 1-1/2 18.7 VG1245ER 29.2 VG1245ES 46.8 VG1245ES+906AGC VG1245ES+906IGC VG1245ES+906GGC VG1245FR 229.2 VG1245FS 46.8
Actuators
Actuators
VG1245FT 73.7 VG1245FT+909AGC VG1245FT+909GGC
1. To avoid excessive wear or drive time on the motor for the AGx models, use a controller or softwa re that provides a timeout function to remove the signal at the
Threaded Ball Valves and
Threaded Ball Valves and
2. Valve has a characterizing disk.
end of rotation (stall).
Threaded Ball Valves and Actuators
AC 24 V On/Off (Floating)
without Timeout
1
M9106-AGC-2
2 2 2 2 2
2 2
2
2
2 2
2 2
2 2
200 VG1245AD+906AGC VG1245AD+906IGC VG1245AD+906GGC
200 VG1245BG+906AGC VG1245BG+906IGC VG1245BG+906GGC
200 VG1245CL+906AGC VG1245CL+906IGC VG1245CL+906GGC
200 VG1245DN+906AGC VG1245DN+906IGC VG1245DN+906GGC
200 VG1245EP+906AGC VG1245EP+906IGC VG1245EP+906GGC
200 VG1245FR+909AGC VG1245FR+909GGC
psig
M9109-AGC-2
VG1245AE+906AGC VG1245AE+906IGC V G1245AE+906GGC VG1245AF+906AGC VG1245AF+906IGC VG1245AF+906GGC VG1245AG+906AGC VG1245AG+906IGC VG1245AG+906GGC VG1245AL+906AGC VG1245AL+906IGC VG1245AL+906GGC
VG1245BL+906AGC VG1245BL+906IGC VG1245BL+906GGC
VG1245CN+906AGC VG1245CN+906IGC VG1245CN+906GGC
VG1245DP+906AGC VG1245DP+906IGC VG1245DP+906GGC
VG1245ER+906AGC VG1245ER+906IGC VG1245ER+906GGC
VG1245FS+909AGC VG1245FS+909GGC
On/Off (Floating)
0 to 10 VDC Proportional
with Timeout M9106-IGC-2 M9106-GGC-2
M9109-GGC-2
The performance specifications are nomina l and con form to accep table ind ustry stand ards. For applicati ons at con ditions be yond these specification s, consult th Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2014 Johnson Controls, Inc.
V–110
Page 4
Threaded Ball Valves and Actuators
VG1000 Series Two-Way, Stainless Steel Trim, NPT End Connections Ball Valves with Non-Spring-Return Electric Actuators (Continued)
Technical Specifications
VG1000 Series Two-Way, Stainless Steel Trim, NPT End Connections Ball Valves with Non-Spring-Return Electric Actuators
1
Service Fluid Temperature Limits Water -22 to 284F (-30 to 140C)
Steam 15 psig (103 kPa) at 250°F (121°C)
Maximum Actuator Fluid Temperature Limits
Valve Body Pressure/ Temperature Rating
Maximum Closeoff Pressure 200 psid (1,378 kPa) Maximum Recommended Operating Pressure Drop 50 psid (340 kPa) Flow Characteristics Two-Way Equal Percentage
Rangeability Minimum Ambient Operating Temperature -4°F (-20°C) Maximum Ambient
Operating Temperature by the Actuator and Linkage)
Leakage 0.01% of Maximum Flow per ANSI/FCI 70-2, Class 4 End Connections National Pipe Thread (NPT) Materials Body Forged Brass
1. Proper water treatment is recommended; refer to the VDI 2035 Guideline.
2. Rangeability is defined as the ratio of maximum controllable flow to minimum controllable f l ow.
3. In steam applications, install the valve with the stem horizontal to the piping and wrap the valve and piping with insulation.
2
3
(Limited
212°F (100°C) VA9104
284°F (140°C) M9106 or M9109 with M9000-520 Linkage, or VA9104 with M9000-561 Thermal Barrier Water 580 psig (3,999 kPa) (PN40) Steam 15 psig (103 kPa) Saturated Steam
M9000-550 Linkage 140°F (60°C): VA9104 and M9104 Series Non-Spring-Return Actuators
M9000-520 Linkage 125°F (52°C): M9106 and M9109 Series Non-Spring-Return Actuators
Ball 300 Series Stainless Steel Blowout-Proof Stem 300 Series Stainless Steel
Seats Graphite-Reinforced Polytetrafluoroethylene (PTFE) with Ethylene Propylene Diene Monomer
Stem Seals EPDM Double O-Rings Characterizing Disk Amodel
Hot Water, Chilled Water, 50/50 Glycol Solutions, and 15 psig (103 kPa) Saturated Steam for HVAC Systems
M9104 with M9000-550 Linkage
Greater than 500:1
(EPDM) O-Ring Backing
® AS-1145HS Po lyphthalamide Resin
Actuators
Actuators
Actuators
Actuators
The performance specifications are nomina l and con form to accep table ind ustry stand ards. For applicati ons at con ditions be yond these specification s, consult th Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2014 Johnson Controls, Inc.
Threaded Ball Valves and
Threaded Ball Valves and
Threaded Ball Valves and
Threaded Ball Valves and
V–111