Johnson Controls VFD66 Series, VFD66xxx-2 Series, VFD66xxx-1 Series Quick Start Commissioning Manual

Optional
Ground
Connection
Fuses
FIG:trmnl_cnnctns
Ground Connection
Terminals (For Power
and Motor Ground)
Supply Ground
TB2
L3/T
L2/S
L1/R
T1/U
T2/V
T3/W
Mains Supply
A: Alarm
B: Alarm
1: +5V Output
2: Analog Input 1
3: Analog Input 2
FIG:cntrl_cnnctns
TB1
4: 0V Common
Quick Start Commissioning Guide VFD66xxx-2 Series Issue Date July 15, 2011
Electrical Connections
Figure 1: VFD66xxx-2
Power Terminal Connections
Manual Operation
Operating the VFD66 Control from the Keypad
VFD66xxx-1 Setup
The speed is controlled with P1 (P2 is not used).  J2 = On, J3 = On, and J7 = On or Off.
Figure 2: VFD66xxx-2
Control Connections
VFD66xxx-2 Setup
Set parameter 05 to PAd (manual input mode).  Press the green button on the keyboard to run;
press the red button to stop.
Use the up arrow key to increase the speed; use
the down arrow key to decrease the speed.
Note: If you cycle the power, the VFD66xxx-2 stops and you must press the green button again.
© 2011 Johnson Controls, Inc. 1
Part No. 24-10511-112, Rev. www.johnsoncontrols.com
)
Max. Pressure Rating of Sensor
(
10 + 80 x
Desired Pressure Setpoint
]
Max. Pressure Rating of Sensor
[
80 x
(Pressure Setpoint – Min. Req. Pressure)
Operating the VFD66 Control with a P35 Pressure Transducer or Any 0 to 5 VDC Signal
VFD66xxx-1 Setup
J2 = On, J3 = Off, and J7 = On.  P1 = minimum speed.  P2 = minimum speed maintain (stop or hold).
Operating the VFD66 Control with a C450 Control Module or Any 0 to 10 VDC Signal
VFD66xxx-1 Setup
J2 = On, J3 = Off, and J7 = Off.
VFD66xxx-2 Setup
Set parameter 05 to Std (standard input mode;
factory default setting).
Set parameter 65 to 5V (factory default setting).  Set parameter 67 for the desired minimum speed
(factory default setting is 0 Hz).
Set parameter 64 for either stop (factory default
setting; motor stops below the minimum speed setting) or HOLd (motor idles), to obtain the desired action at the minimum speed point.
VFD66xxx-2 Setup
Set parameter 05 to Std (factory default setting).  Set parameter 65 to 10V.  Set parameter 67 for the desired minimum speed
(factory default setting is 0 Hz).
Set parameter 64 for either stop (factory default
setting) or HOLd, to obtain the desired action at the minimum speed point.
Operating the VFD66 Control with a Ratiometric P499 Series Electronic Pressure Transducer
VFD66xxx-1 Setup
J2 = Off, J3 = On or Off, and J7 = On or Off.  P1 = setpoint.  P2 = proportional band.
VFD66xxx-2 Setup
Set parameter 05 to EPt (electronic pressure
transducer input mode).
Set parameter 65 to 5V (factory default setting) for
ratiometric sensors; set parameter 65 to 10V for 0 to 10 VDC sensors.
Set parameter 61 for the desired setpoint. This
setting is calculated using the following equation:
Example: If a 0 to 500 psig sensor is used and the desired setpoint is 275 psig, then the setting for parameter 61 is 10 + (80 x 275/500) or 54.
Set parameter 62 for the desired proportional band
of the control. This setting is calculated using the following equation:
Example: If a 0 to 750 psig sensor with a setpoint of 500 psig and a minimum required pressure of 410 psig is used, then the setting for parameter 62 is 80 x [(500 – 410)/750] or 9.6.
2 VFD66 Series Condenser Fan Speed Controls Quick Start Commissioning Guide
Loading...
+ 1 hidden pages