Johnson Controls VB30, VB24, VB36, VM09, VM12 Installation, Operation And Maintenance Manual

...
INDOOR PACKAGED EQUIPMENT
Installation, Operation, and Maintenance Supersedes: 145.18-IOM1 (115) Form 145.18-IOM1 (818)
HIGH EFFICIENCY VSCS SERIES
VERTICAL STACKED WATER SOURCE HEAT PUMP
LD27626
CABINET MODEL VB/VM/VS09–36
AND
R-410A
ISSUE DATE:
August 30, 2018
FORM 145.18-IOM1
ISSUE DATE: 8/30/2018
IMPORTANT!
READ BEFORE PROCEEDING!
GENERAL SAFETY GUIDELINES
This equipment is a relatively complicated apparatus. During rigging, installation, operation, maintenance, or service, individuals may be exposed to certain com­ponents or conditions including, but not limited to: heavy objects, refrigerants, materials under pressure, rotating components, and both high and low voltage. Each of these items has the potential, if misused or handled improperly, to cause bodily injury or death. It is the obligation and responsibility of rigging, instal­lation, and operating/service personnel to identify and recognize these inherent hazards, protect themselves, and proceed safely in completing their tasks. Failure to comply with any of these requirements could result in serious damage to the equipment and the property in
which it is situated, as well as severe personal injury or death to themselves and others at the site.
This document is intended for use by owner-authorized rigging, installation, and operating/service personnel. It is expected that these individuals possess independent training that will enable them to perform their assigned tasks properly and safely. It is essential that, prior to performing any task on this equipment, this individual shall have read and understood the on-product labels, this document and any referenced materials. This in­dividual shall also be familiar with and comply with all applicable industry and governmental standards and regulations pertaining to the task in question.
SAFETY SYMBOLS
The following symbols are used in this document to alert the reader to specific situations:
Indicates a possible hazardous situation which will result in death or serious injury if proper care is not taken.
Identies a hazard which could lead to
damage to the machine, damage to other equipment and/or environmental pollu­tion if proper care is not taken or instruc­tions and are not followed.
Indicates a potentially hazardous situa­tion which will result in possible injuries or damage to equipment if proper care is not taken.
External wiring, unless specied as an optional connection in the manufacturer’s product line, is not
to be connected inside the control cabinet. Devices such as relays, switches, transducers and controls and any external wiring must not be installed inside the micro panel. All wiring must be in accor-
dance with the manufacturer's published specications and must be performed only by a qualied
electrician. The manufacturer will NOT be responsible for damage/problems resulting from improper connections to the controls or application of improper control signals. Failure to follow this warn-
ing will void the manufacturer’s warranty and cause serious damage to property or personal injury.
WARNING: This product can expose you to chemicals including formaldehyde, which is known to the state of California to cause cancer. For more information, go to www.P65Warnings.ca.gov.
2
Highlights additional information useful to the technician in completing the work being performed properly.
FORM 145.18-IOM1 ISSUE DATE: 8/30/2018
CHANGEABILITY OF THIS DOCUMENT
In complying with the manufacturer's’ policy for con­tinuous product improvement, the information con­tained in this document is subject to change without notice. There is no commitment to update or provide
lifting, and operating/service personnel should verify whether the equipment has been modified and if current literature is available from the owner of the equipment
prior to performing any work on the equipment. current information automatically to the manual or product owner. Updated manuals, if applicable, can be
CHANGE BARS
obtained by contacting the nearest service office.
Revisions made to this document are indicated with a It is the responsibility of rigging, lifting, and operating/ service personnel to verify the applicability of these documents to the equipment. If there is any question regarding the applicability of these documents, rigging,
line along the left or right hand column in the area the
revision was made. These revisions are to technical in-
formation and any other changes in spelling, grammar
or formatting are not included.
ASSOCIATED LITERATURE
MANUAL DESCRIPTION FORM NUMBER
Vertical Stacked Heat Pump Start-Up and Performance Checklist 145.18-CL1
Vertical Stacked Water Source Heat Pump Heating and Cooling Data Record Sheet 145.18-CL2
3
FORM 145.18-IOM1
ISSUE DATE: 8/30/2018
CABINET NOMENCLATURE
1, 2 3, 4 5 6 7 8 9 10 11, 12 13 14 15
VB 12 M 1 D E A 2 2T 4 0 C
PRODUCT CATEGORY
VB = Vertical Stacked Heat Pump -
Standard Cabinet Assembly
VM = Vertical Stacked Heat Pump -
Master Cabinet Assembly
VS = Vertical Stacked Heat Pump -
Satellite Cabinet Assembly
UNIT CAPACITY
09 = 0.75 TON 24 = 2 TON
12 = 1 TON 30 = 2.5 TON
15 = 1.25 TON 36 = 3 TON
18 = 1.5 TON
CONTROL OPTIONS
M = Microprocessor (MP) Control with 2-Speed
Unit Mounted Switch
2 = MP Control with 2-Speed Thermostat Control
3 = MP Control with 3-Speed Thermostat Control
P = MP Control with Surface-Mount Thermostat
Connection with Unit Mounted Switch
4 = MP Control with Surface-Mount Thermostat
Connection with 2-Speed Thermostat Control
5 = MP Control with Surface-Mount Thermostat
Connection with 3-Speed Thermostat Control (ECM Only)
VOLTAGE
1 = 208/230-60-1
6 = 265-60-1
ELECTRICAL CONNECTION
0 = None (Terminal Block)
D = Non-Fused Disconnect
F = Disconnect with Fuses
BLOWER OPTIONS
A = PSC Blower
B = Hi-Static PSC Blower
E = ECM Blower
F = Hi-Static ECM Blower
G = ECM with Continuous Low Speed
H = Hi-Static ECM with Continuous Low Speed
DESIGN SERIES
C = Current Generation
MISCELLANEOUS OPTIONS
0 = None
S = Stainless Steel (SST) Drain Pan
F = MERV 8 Filters
C = SST Drain Pan with MERV 8 Filters
HORIZONTAL DISCHARGE OPENING ORIENTATION
00, 0T 1H, 1T 2H, 2T 3H, 3T
X = None B = Back 1 = Left + Front 7 = Front + Left + Right
F = Front 2 = Left + Back 8 = Front + Right + Back
L = Left 3 = Left + Right 9 = Front + Left + Back
R = Right 4 = Right + Back
5 = Right + Front
6 = Back + Front
SUPPLY AIR CONFIGURATION
1H = Single Horizontal Supply 2T = Double Horizontal Supply
2H = Double Horizontal Supply
3H = Triple Horizontal Supply 3T = Triple Horizontal Supply
0T = Top Only
1T = Single Horizontal Supply
+ Top
+ Top
+ Top
00 = Field Cut (No Openings)
RISER ARRANGEMENT
1 = Right Hand Risers
2 = Left Hand Risers
3 = Back Risers
4 = Right Hand Risers with Cover
5 = Left Hand Risers with Cover
6 = Back Risers with Cover
CABINET OPTIONS
Cabinet Height
88 inches A G L R W
80 inches B H M T X
80 inches with 4-inch Stand D K P V Z
80 inches with 8-inch Stand F 2 4 6 8
No OA
Options
Left Top OA Entry
(4-inch Round)
4
Left Top OA Entry (4-inch
Round with Motorized Damper)
Right Top OA Entry
(4-inch Round)
Right Top OA Entry (4-inch
Round with Motorized Damper)
FORM 145.18-IOM1 ISSUE DATE: 8/30/2018
1, 2, 3, 4 5, 6 7 8 9 10 11 12 13
VSCS 12 C 1 0 0 A C 0
PRODUCT CATEGORY
VSCS = Vertical Stacked Heat Pump Chassis
R-410A
UNIT CAPACITY
09 = 0.75 TON
12 = 1 TON
15 = 1.25 TON
18 = 1.5 TON
24 = 2 TON
30 = 2.5 TON
36 = 3 TON
CHASSIS NOMENCLATURE
MISCELLANEOUS OPTIONS
O = None
WATERSIDE OPTIONS
C = Standard Water Coil
B = Standard Water Coil with Low Temperature
Option
N = Cupro-Nickel Water Coil
R = Cupro-Nickel Water Coil with Low Temperature
Option
AIRSIDE OPTIONS
A = Standard Airside Coil
C = Corrosion Protective Coating
DESIGN SERIES
C = Current Generation
VOLTAGE
1 = 208/230-60-1
6 = 265-60-1
WATER VALVE & PUMP OPTIONS
VALVE OPTIONS
No Water Control Valve
Motorized 2-Way Shut-Off Valve
Motorized 3-Way Shut-Off Valve
VALVE
ONLY
Y-STRAINER
O S
M Y
N V
AUTO-FLOW REGULATOR
0 = No Flow Control Valve
B = 1.5 USGPM
C = 2.0 USGPM
D = 2.5 USGPM
E = 3.0 USGPM
F = 3.50 USGPM
H = 4.0 USGPM
J = 4.5 USGPM
K = 5.0 USGPM
L = 6.0 USGPM
M = 7.0 USGPM
N = 8.0 USGPM
P = 9.0 USGPM
R = 10.0 USGPM
5
FORM 145.18-IOM1
ISSUE DATE: 8/30/2018
TABLE OF CONTENTS
SECTION 1 - INSTALLATION ..................................................................................................................................9
Notice and Disclaimer ......................................................................................................................................9
Disclaimer ................................................................................................................................................9
Pre-Installation .................................................................................................................................................9
Literature .................................................................................................................................................9
Shipping ..................................................................................................................................................9
Inspection and Storage .........................................................................................................................10
Preparations for Installing the Unit ........................................................................................................10
Rigging .................................................................................................................................................. 11
Cabinet Riser Installation ............................................................................................................................... 11
Placing the Cabinet ............................................................................................................................... 11
Riser Loop ...................................................................................................................................................... 16
Hoses .............................................................................................................................................................16
Electrical Wiring .............................................................................................................................................. 18
Field-Installed Power Wiring ..................................................................................................................18
Field-Installed Low Voltage Wiring ........................................................................................................18
Optional Surface Mount Thermostat Connection Wiring ....................................................................... 19
Optional Remote Mounted Thermostat Wiring ...................................................................................... 19
Optional ADA Door Mounted Thermostat .............................................................................................. 20
EC Motor (ECM) Continuous Fan .........................................................................................................20
Closet and Drywall Installation .......................................................................................................................20
Acoustic Return Air (RA) Panel ......................................................................................................................20
Supply Air (SA) Ductwork ............................................................................................................................... 24
Horizontal Supply Air ............................................................................................................................. 24
Top Discharge Supply Air ......................................................................................................................24
Top Mounted Fresh Air Intake ........................................................................................................................27
Top Mounted Fresh Air Intake with Motorized Damper .........................................................................27
System Flushing and Cleaning ...................................................................................................................... 28
Flushing the System .............................................................................................................................. 28
Cleaning the System .............................................................................................................................29
Chassis Installation ........................................................................................................................................32
For Units with NPSH Valve Connection and Hose Sets ........................................................................ 32
For Units with NPT Style (Tapered Pipe Thread) Valve Connection and Hoses ...................................32
SECTION 2 - OPERATION .....................................................................................................................................35
Pre-Start-Up Checklist .................................................................................................................................... 35
Initial Unit Start-Up .........................................................................................................................................35
System Loop Temperature .............................................................................................................................36
Fan Speed Adjustment ................................................................................................................................... 36
Unit Controls ................................................................................................................................................... 40
Sequence of Operation .........................................................................................................................40
Continuous Blower ................................................................................................................................40
Safety Control Reset .............................................................................................................................40
Operation Errors .................................................................................................................................... 41
Safety Controls ...................................................................................................................................... 41
Random Start ........................................................................................................................................42
Compressor Protection ..........................................................................................................................42
Microprocessor Control Unit Flash Codes .............................................................................................42
Communication ....................................................................................................................................42
6
FORM 145.18-IOM1 ISSUE DATE: 8/30/2018
TABLE OF CONTENTS (CONT'D)
SECTION 3 - MAINTENANCE ................................................................................................................................ 43
APPENDIX ..............................................................................................................................................................45
Heating and Cooling Data Record Sheet .......................................................................................................49
R-410A Quick Reference Guide ..................................................................................................................... 51
LIST OF FIGURES
FIGURE 1 - Ideal Riser Insertion Depth ..................................................................................................................12
FIGURE 2 - Correct/Incorrect Stub-Out Positions in Cabinet Riser Opening ..........................................................12
FIGURE 3 - Cabinet Unit Dimensions & Floor Sleeve Dimensions .........................................................................14
FIGURE 4 - Cabinet Riser Dimensions ...................................................................................................................15
FIGURE 5 - Standard Factory Supplied NPSH Hose Kits and Risers.....................................................................17
FIGURE 6 - Optional Field Supplied Risers with Factory Supplied NPSH Hose Kits and Shut-Off Valves .............17
FIGURE 7 - Conversion of NPT to NPSH Type Fittings (VB Units with NPT Fittings Only) ....................................18
FIGURE 8 - Field Wiring Diagram ...........................................................................................................................19
FIGURE 9 - Remote Thermostat Wiring ..................................................................................................................19
FIGURE 10 - Unit Switch Plate with ADA Thermostat Connection .......................................................................... 20
FIGURE 11 - Critical Return Air (RA) Panel with Unit Cabinet Installation Dimensions ..........................................21
FIGURE 12 - RA Panel Cross Section Installation at Floor Level ...........................................................................22
FIGURE 13 - RA Panel Dimensions ........................................................................................................................22
FIGURE 14 - Optional RA Panel with ADA Mounted Thermostat ............................................................................23
FIGURE 15 - Supply Grille with Volume Damper and 1/8-inch Neoprene Tape Applied to Perimeter ....................24
FIGURE 16 - Unit Mounted Supply Grille Installation ..............................................................................................25
FIGURE 17 - Damper Plate Fasteners ....................................................................................................................27
FIGURE 18 - Remove the Red Cover .....................................................................................................................27
FIGURE 19 - Position Black Cover..........................................................................................................................28
FIGURE 20 - System Flushing and Cleaning ..........................................................................................................29
FIGURE 21 - Fresh Air Opening without Motorized Damper – Left and Right Hand Unit Shown ...........................30
FIGURE 22 - Fresh Air Opening with Motorized Damper – Left and Right Hand Unit Shown ................................31
FIGURE 23 - Lift the Chassis Front .........................................................................................................................33
FIGURE 24 - Tilt the Chassis ..................................................................................................................................33
FIGURE 25 - Insert the Chassis ..............................................................................................................................33
FIGURE 26 - Pivot the Chassis ...............................................................................................................................34
FIGURE 27 - Slide the Chassis ...............................................................................................................................34
FIGURE 28 - Check the Chassis .............................................................................................................................34
FIGURE 29 - PSC Motor Wiring Diagram ...............................................................................................................45
FIGURE 30 - ECM Wiring Diagram .........................................................................................................................46
FIGURE 31 - Continuous Fan with ECM Wiring Diagram .......................................................................................47
FIGURE 32 - Motorized Damper ECM Wiring Diagram ..........................................................................................48
7
FORM 145.18-IOM1
ISSUE DATE: 8/30/2018
LIST OF TABLES
TABLE 1 - High Series Physical Data .....................................................................................................................13
TABLE 2 - Replacement Hose Gaskets ..................................................................................................................16
TABLE 3 - Chassis Hoses .......................................................................................................................................16
TABLE 4 - Typical Wire Connections ......................................................................................................................19
TABLE 5 - Unit Supply Opening Sizes ....................................................................................................................26
TABLE 6 - Unit Supply Face Velocity (FPM) ...........................................................................................................26
TABLE 7 - Operating Limits ....................................................................................................................................36
TABLE 8 - PSC Standard Blower Performance (CFM) ...........................................................................................37
TABLE 9 - PSC High Static Blower Performance (CFM) ........................................................................................37
TABLE 10 - ECM Standard Blower Performance (CFM) ........................................................................................38
TABLE 11 - ECM High Static Blower Performance (CFM) ......................................................................................38
TABLE 12 - ECM Blower Performance - All Speed Taps (CFM) ............................................................................. 39
TABLE 13 - Flash Codes ........................................................................................................................................42
8
FORM 145.18-IOM1 ISSUE DATE: 8/30/2018
SECTION 1 - INSTALLATION
After installing the unit, show the user how to turn off the electricity to the unit. Point out control and switch locations for turning off the electricity.
Ensure the user understands the impor­tance of following all safety precautions.
NOTICE AND DISCLAIMER
This unit contains refrigerant installed by the factory that is approved for use in the unit’s intended country of installation or market. Distributors are only autho­rized to provide refrigerants that have been approved for use in the countries or markets they serve.
The refrigerant used in this unit is identified on the unit's nameplate and in this manual. Any additions of refrigerant into this unit must comply with the coun­try’s requirements with regard to refrigerant use and should be obtained from manufacturer approved dis­tributors. Use of unapproved refrigerant substitutes will void all warranties and can cause injury or death.
1
Modifications may invalidate product certifications or violate country standards. Any person or entity making changes to the product is responsible for obtaining the required engineering review and approval, as well as covering certification and other related costs.
Unauthorized customer modifications to certified products are prohibited for the following reasons:
A. Modications may create hazards that could result
in death, serious injury, or equipment damage.
B. Modications will void product warranties.
C. Modications may invalidate product certica-
tions and may violate country standards. Country
standards may require that only certied products be used in certain applications, and modications that result in the loss of product certication may
violate those standards.
PRE-INSTALLATION
Literature
Disclaimer
Customer modifications to certified products are pro­hibited. If performed without the express written ap­proval of the manufacturer, modifications will void all warranties (expressed or implied) and may result in hazardous situations resulting in equipment damage, serious physical injury or property damage, or death.
The manufacturer has certified the product as being compliant with applicable government and/or industry standards. Product certification is designated either on the product itself or in the product literature. The cer­tification mark identifies the applicable standards as well as the Nationally Recognized Test Lab (NRTL) or other testing facility that conducted the testing, where applicable.
If changes are made to the product, an engineering re­view is required to assess the impact to the product cer­tification. In some instances, the changes may require that the NRTL or testing facility review and re-approve the product by means of a field or site inspection and certification.
Review this Installation, Operation, and Maintenance (IOM) manual prior to installation. After installing the unit, give this IOM to the end user. If help is needed with any of the installation instructions or matters re­lating to the unit, contact the sales office where you bought the unit. You may also refer to the unit rating plate for a contact name.
Shipping
Cabinets and risers ship in one of the following con­figurations:
• Cabinets are stacked on their side with risers at­tached. Chassis ship on separate skids.
• Risers ship loose, packaged in boxes and sorted
by oor. Cabinets ship upright up to four per skid.
Chassis ship on separate skids.
• Risers ship loose, packaged in boxes, and sorted by oor. Cabinets ship upright on skids with chas­sis inside the cabinet. Chassis electrical and water connections are not installed. The chassis is se­cured to the service panel. Remove the screws be­fore removing the service panel and chassis.
The cabinet must remain standing upright. Do not place cabinets on their side with the chassis inside.
9
SECTION 1 - INSTALLATION
FORM 145.18-IOM1
ISSUE DATE: 8/30/2018
Inspection and Storage
Store cabinets, chassis, and risers the same way they were shipped. Ensure the storage area is dry and pro­tected from the environment. Keep the units in their upright position. If the risers are stored at the job site, ensure the pipe ends are capped to prevent foreign ob­ject debris and contamination.
In areas where construction is not complete (including dry wall, plaster, paint, and where any emission of dust particulates or fumes from outgassing are present), all precautions must be taken to protect the cabinet, open­ings, and chassis from contamination or physical damage.
Upon delivery, perform the following inspections:
1. Inspect the unit for shipment damage. Notify the Transportation Company of any damage and note the damage on the shipping receipt.
Rough handling may dislocate and dam­age internal components.
• Remove the inner service panel and manually check the blower wheel for free rotation.
• Match the refrigeration chassis to the proper cabi­nets by referring to the cabinet and chassis name­plate and label information.
• Remove the chassis refrigeration access panel (top cover) and inspect the unit. Ensure that the refrigerant tubing is free from obvious physical damage and kinks, and check that piping does not touch other unit components.
• Ensure the compressor is mounted on neoprene isolators with metal spacing sleeves inside. Se­cured it with nuts that are snug against the metal spacer sleeves.
• Inspect all electrical connections. Connections must be clean and tight at the terminals.
Do NOT use the risers to lift the cabinet assembly.
2. Inspect the riser projections at each end of the cabinet for misalignment or end damage that would prevent making an acceptable connection.
3. Inspect the thermostats and other accessories that have been shipped separately for quantity and transit damage.
Store the refrigeration chassis in the normal upright orientation to maintain oil in the compressor sump.
Preparations for Installing the Unit
Before installing the unit, perform the following prep­arations:
• Verify the model number on the unit nameplate with the ordering and shipping information to en­sure the correct unit has been shipped.
• Carefully inspect each unit before delivery to the installation site. All cabinets may not be equipped with the same size riser or the same air supply grille arrangement. In most cases, each cabinet is
individually tagged for a specic location in the
building.
Do NOT install this unit outdoors.
A compressor/unit comprises a pressur­ized system. Never loosen threaded joints while the system is under pressure, and never open pressurized system parts.
Before servicing, open and tag all discon­nect switches.
Do NOT install units in a flammable environment due to the danger of an explosion.
• Keep the cabinet sealed with the shipping materi­als until all plastering, painting, and construction work is complete.
10
FORM 145.18-IOM1 ISSUE DATE: 8/30/2018
SECTION 1 - INSTALLATION
Safety guards, shields, barriers, cov­ers, and protective devices must not be removed while the compressor/unit is operating.
All safety features, disengagement, and interlocks must be in place and function correctly before the equipment is put into operation. Never bypass or wire around any safety device.
Use gloves and protective goggles where appropriate and have a gas mask close at hand. Use electrical protection equipment and tools suited for electrical operations.
Personnel must be qualied according
to national safety rules and regulations.
CABINET RISER INSTALLATION
Do NOT use the risers to lift or move the cabinets.
Refer to Figure 3 on page 14, which shows the correct location of the cabinet in relation to the floor sleeve and risers.
Risers are not designed to support or lift any part of the cabinet. Do not use them to lift a cabinet. Risers are at­tached using nylon ties to allow for slight adjustments during installation, and expansion of riser column dur­ing operation. Take care during installation to avoid damage to risers and riser stub-outs.
Improper handling and installation of risers could damage riser stub-outs and valves and could result in property dam­age, death, or serious injury.
1
Only manufacturer- qualied personnel
should install this system. If not, it may cause water leakage, electric shock, or
re.
Rigging
Follow all applicable regulations and safety practices during rigging and lifting.
Prepare and follow written rigging and lifting plan. Lifting must be directed by trained, professional rigger.
Spreader bars must be used and be long enough to pre­vent rigging from contacting unit. Use only the desig­nated lift points according to unit's IOM, and use ALL lift points.
Locate the center of gravity through trial lifts to ac­count for possible variations in unit configuration. Use rigging and lifting techniques that keep the unit stable and level. Keep clear of unit when lifted.
Do not allow the risers to bottom out. Riser stub-out should be centrally located with the stub-out opening of the cabinet riser. Do not allow riser stub-outs or risers to contact cabinet sheet metal.
Do not drag risers on the oor while mov­ing the cabinet.
When the risers are shipped loose, riser installation can be completed before cabinet installation. When install­ing risers, ensure the riser stub-outs are centered in the the cabinet openings. Ensure that the risers cannot bot­tom out in swage (see Figure 1 on page 12).
When risers are shipped attached to cabinets, complete the installation of risers and cabinet at the same time. Detaching the riser from the cabinet is unnecessary.
Placing the Cabinet
The correct location of the cabinet in relation to the floor sleeve and risers is shown in Figure 3 on page
14. To place the cabinet correctly, perform the fol­lowing steps:
11
SECTION 1 - INSTALLATION
FORM 145.18-IOM1
ISSUE DATE: 8/30/2018
1. Place the cabinet in a horizontal position on the oor adjacent to its installation location (when ris­ers are attached to cabinet).
The units are designed to accommodate a maxi­mum supply and return riser stub-out movement of 1-1/2 inches due to expansion and contraction (total movement of 3 inches). If the total calcu­lated riser expansion or contraction exceeds 1-1/2 inches, the field must provide expansion compen­sation.
2. Install eld or factory-provided riser extensions, if required, to the unit-mounted risers prior to
moving the cabinet into nal position.
3. Raise the cabinet upright. Lower the risers through
the oor cutout, aligning the risers into the swaged section of the unit on the oor below.
Take extra care not to scrape or dent ris­ers during positioning. The riser tailpiece should insert approximately 2 inches into the 3-inch long swaged section of the unit below.
7. Center the risers’ horizontal stub-outs (complete with factory-installed shut-off valves) in the cabi­net slot openings. Ensure that the stub-outs are perpendicular to the side/back panel.
8. Verify all risers are vertical and that they penetrate the swaged joint at least 1 inch.
Factory provided risers come with a 3-inch deep swage. Do not allow risers to completely bottom out at 3 inches in the swage. The 3-inch swage depth is oversized to allow for adjustments if nec­essary to keep riser stub-outs and valves centered in the cabinet opening.
9. Center the riser stub-out in cabinet opening to allow for expansion and contraction. Riser stub­outs must not contact on any sheet metal opening. Otherwise damage can occur to stub-outs, result­ing in water leaks and property damage.
Top Vertical
Riser
DO NOT allow the riser tailpiece to bottom out into the swaged section. This ensures the correct riser positioning and com-
pensates for variations in oor-to-oor
dimensions.
4. Center the risers in the pipe chase, and level the cabinet using shims as necessary.
5. Plumb risers in two planes to assure proper unit operation and condensate drainage.
6. Anchor the cabinets into place using rubber iso­lated sheet metal angles. Approved and tested sheet metal angles are available from factory.
It is strongly recommended to install vibration isolation pads to reduce noise transmission into the floor. Failure to use isolation kits could result in loud unit operation.
Do not drill or drive screws into the cabi­net in the area of the internal drain pan.
2-inch Ideal
3-inch Cup
Height
Bottom
Vertical Riser
FIGURE 1 - IDEAL RISER INSERTION DEPTH
Insertion Depth
LD23535
12
LD19017
FIGURE 2 - CORRECT/INCORRECT STUB-OUT POSITIONS IN CABINET RISER OPENING
FORM 145.18-IOM1 ISSUE DATE: 8/30/2018
SECTION 1 - INSTALLATION
10. Braze or solder riser joints with industry accepted solder or brazing rod material.
The riser system must be secured to build­ing structure. Cabinets are not designed to support the riser system.
11. Secure the riser system at a minimum of one point to the building structure. Cabinets are not intend­ed to support the riser system. If the temperature range of the system exceeds the allowed expan­sion and contraction limits (1-1/2 inches maxi­mum), the installing contractor must make riser compensation provisions.
12. Ensure that individual unit shut-off valves remain closed until the circulating loop system is cleaned
and ushed.
TABLE 1 - HIGH SERIES PHYSICAL DATA
HIGH SERIES MODEL 09 12 15 18 24 30 36
Nominal Cooling (ton)
Compressor Type Rotary Scroll
Refrigerant Charge (oz) 21 25 34 38 44 48 50
Air Coil-Type Enhanced Copper Tubes, Enhanced Aluminum Fins
Face Area (sq ft) 1.46 1.56 2.35 2.35 2.63 3.33 3.33
1
0.75 1.0 1.25 1.5 2.0 2.5 3.0
1
Rows/FPI 2/146 3/14 3/14 3/14 3/14 3/14 3/14
Water Coil-Type Enhanced Surface Co-Axial
Standard Blower/Motor
Diameter x Width (inches) 9x4T 9x4T 9x7T 9x7T 9x7 9x8 9x8
Motor HP 0.10 0.10 0.17 0.17 0.25 0.33 0.50
Hi-Static Blower/Motor DWDI Forward-Curved Centrifugal/PSC Direct Drive
Diameter x Width (inches) 9x4T 9x4T 9x7T 9x7T 10x7T 10x8T 10x8T
Motor HP 0.10 0.10 0.17 0.17 0.25 0.33 0.50
EC Motor (ECM) Blower/Motor DWDI Forward-Curved Centrifugal/ECM Direct Drive
Diameter x Width (inches) 9x4T 9x4T 9x7T 9x7T 10x7T 9x8 9x8
Motor HP 0.33 0.33 0.33 0.33 0.33 0.50 0.50
Hi-Static ECM Blower/Motor DWDI Forward-Curved Centrifugal/ECM Direct Drive
Diameter x Width (inches) 9x4T 9x4T 9x7T 9x7T 10x7T 10x8T 10x8T
Motor HP 0.33 0.33 0.33 0.33 0.33 0.50 0.50
Filter Quantity/Size (inches) 1/14x25x1 1/14x25x1 1/16x30x1 1/16x30x1 1/16x30x1 1/20x30x1 1/20x30x1
Cabinet Weight (lb)
2
Double Width Double Inlet (DWDI) Forward-Curved Centrifugal/Permanent Split Capacitor
(PSC) Direct Drive
130 130 145 145 150 175 175
Chassis Weight (lb) 70 75 95 100 140 155 160
NOTE:
1. Nominal capacity is calculated in accordance with ARI/ISO Standard 13256-1 for water loop application.
2. Cabinet weight is approximate and does not include the weight of the risers.
13
SECTION 1 - INSTALLATION
7/8-inch
Control
Entrance
80
inches
or 88
inches
Riser Opening Knock­Outs (All 3 Sides)
3 inches
50 inches
B A
Left View
Optional 24V
Connection for
Surface Mount/
Remote Mounted
Thermostat
Electrical Box
Service
Pass-Thru
48 inches
Return Air Flange Standard 1 inch
6 inches
4.5 inches
Hoses
Front View
Optional Front Supply Opening
7 inches
Switch Plate with 2 Speed Fan Switch (Optional: Disconnect/Fuses, ADA Molex Connector)
Chassis Service Panel
4 inches
4.25 inches
4.25 inches
4.25 inches
R
S
D
FORM 145.18-IOM1
ISSUE DATE: 8/30/2018
CABINET DIMENSIONS (INCHES)
MODEL A B
RA FLANGE
WIDTH (C)
09–18 17 17 16
15–24 20 20 19
30–36 24 24 23
Back
Optional Riser Cover Shown
13.25
inches
Right
A/2
4.25 inches
R
S
D
R
S
D
1-inch
Supply
Duct
Flange
6 in.
50.5 inches
7/8-inch OD Power Entrance 7/8-inch OD Control Entrance
4.25 inches
4.5 inches
Right View
4 in.
Supply Riser Opening
Return Riser Opening
inches
Supply Riser
Opening
36 inches
A/2
Back View
8.5
Return Riser Opening
Condensate Riser Opening
Left
Top View Front
R - Return Riser S - Supply Riser D - Drain Riser
4-5/16 inches
VSHP Cabinet
Drain Pan
Do not penetrate
1.50
this area with drills or screws
4.75
NOTES
1. Supply, return, and condensate riser openings are pre-punched on all sides and eld convertible. Cut tabs to remove the knock-out.
2. Supply and return openings are 4 inches x 2.5 inches. During riser installation, ensure the stub-out is centered in supply and return openings.
3. Condensate P-trap is accessible from the front by removing the bottom cover plate.
4. Riser and shut-off location is measured from base of cabinet and does not include the stand height.
FIGURE 3 - CABINET UNIT DIMENSIONS & FLOOR SLEEVE DIMENSIONS
14
LD27627
FORM 145.18-IOM1 ISSUE DATE: 8/30/2018
SECTION 1 - INSTALLATION
A
Return Air Opening
Optional
Supply
Opening
6 in.
P-Trap
B
Insulation
Shut-Off
Ball Valve
3 in.
Supply
and
Return
Risers
Allow for 2-inch Insertion into Swage End
1
36 inches
Condensate Riser (Max. 120 inches)
Supply and Return Riser (Max. 120 inches)
As Req'd
As Req'd
Reducer
Reducer
Reduce Up Riser (Max. 120 inches)
As Req'd
NOTE
Riser shut-off valve is measured from base of cabinet and does not include the stand height.
As Req'd
Reduce Down Riser (Max. 120 inches)
FIGURE 4 - CABINET RISER DIMENSIONS
Capped Down Riser
Capped Up Riser
As Req'd
LD19330
15
SECTION 1 - INSTALLATION
FORM 145.18-IOM1
ISSUE DATE: 8/30/2018
RISER LOOP
5. Install the following parts at the base of each sup­ply and return riser to enable system ushing, bal­ancing, and servicing:
• Drain valve
• Shut-off/balancing valves
• Flow indicators
• Drain tees
6. Install strainers at the inlet of each circulating pump.
7. Insulate loop water piping that runs through un­conditioned areas of the building or outside the building.
When the loop water temperature is maintained between nominal operating limits of 60.0–90.0°F, piping does not sweat or suffer undue heat loss at conditioned space temperatures.
8. Install vents in piping loop as required to bleed
residual air from the piping system during lling
and servicing.
9. Determine the riser shut-off valves and hose kits
required for job specic site conditions:
a. Factory-supplied risers come with the appro-
priate hose kits with NPSH type fittings (see Figure 5 on page 17). Before attaching NPSH type hoses, check that the female end gasket is not missing and is free of damage or debris. See Table 2 for information on re- placement gaskets for NPSH hose kits.
b. For field-supplied risers, it is recommended
to order the appropriate NPSH type field hose kits from the factory, complete with shut-off valves. Shut-off valves are to be field sweat connected to risers (see Figure 6 on page 17).
c. Legacy chassis with NPT type connections
and matching risers with NPT shut-off valve connections require a special hose kit. The kit comes complete with a NPT to NPSH swiv­el adapter on the shut-off valve and chassis connection to mate with factory hoses (see Figure 7 on page 18.
TABLE 2 - REPLACEMENT HOSE GASKETS
PART NUMBER DESCRIPTION
VSGK-UFHW-050 1/2-inch Rubber Gasket
VSGK-UFHW-075 3/4-inch Rubber Gasket
HOSES
Ensure the correct hose set is matched with the com­patible unit size (see Table 3). Instal the NPSH factory- provided hoses by completing the following steps:
1. Inspect for missing or damaged hose gasket. See Table 2 for replacement gasket part numbers.
2. Tighten by hand the screw connections to the
male NPSH tting on the shut-off valve. Hold the
ferrule stationary when tightening.
3. Tighten using a backup wrench a 1/4 turn further. Do not overtighten.
When installing hoses, do not apply a twist or torque load on the hose.
When tightening hoses, hold the ferrule stationary by hand while tightening the screw connections. Avoid tight bends, or
water ow and high pressure drops may
occur.
Hose gasket does not require extreme tightening to obtain a seal. DO NOT OVERTIGHTEN, or damage to gasket or sealing surface will occur. Do not apply thread sealant.
Hoses must be hand tightened, then fur­ther tightened for roughly another 1/4 turn. Check for leaks before tightening any further. Do not apply excessive force; rubber gaskets might get damaged.
Always use a back-up wrench when tight­ening hoses to valves. Otherwise, valve solder joint may fail, leading to property damage or serious injury.
TABLE 3 - CHASSIS HOSES
CHASSIS MODEL HOSE TYPE
09–18 1/2-inch NPSH Female-Female
24–36 3/4-inch NPSH Female-Female
16
FORM 145.18-IOM1 ISSUE DATE: 8/30/2018
SECTION 1 - INSTALLATION
1
1/2-INCH OR 3/4-INCH MALE NPSH BALL VALVE
1/2-INCH OR 3/4-INCH NPSH THREADS
1/2-INCH OR 3/4-INCH FLEXIBLE CONNECTOR HOSE (24 INCHES LONG)
GASKET
GASKET
1/2-INCH OR 3/4-INCH NPSH THREADS
1/2-INCH OR 3/4-INCH MALE NPSH
NOTE
National Pipe Straight Hose (NPSH) connection
FIGURE 5 - STANDARD FACTORY SUPPLIED NPSH HOSE KITS AND RISERS
1/2-INCH OR 3/4-INCH WATER PIPE STUB-OUT
1/2-INCH OR 3/4-INCH SWEAT TO MALE NPSH BALL VALVE
1/2-INCH OR 3/4-INCH NPSH THREADS
1/2-INCH OR 3/4-INCH FLEXIBLE CONNECTOR HOSE (24 INCHES LONG)
1/2-INCH OR 3/4-INCH NPSH THREADS
1/2-INCH OR 3/4-INCH MALE NPSH
LD18126
FIGURE 6 - OPTIONAL FIELD SUPPLIED RISERS WITH FACTORY SUPPLIED NPSH HOSE KITS AND SHUT-
OFF VALVES
NOTE
National Pipe Straight Hose (NPSH) connection
LD18127
17
SECTION 1 - INSTALLATION
HANDLE MUST BE
FACING THE BOTTOM
1/2-INCH OR 3/4-INCH FPT BALL VALVE (FACTORY OR FIELD PROVIDED)
FEMALE SWIVEL 1/2-INCH OR 3/4-INCH NPSH THREADS
GASKET INCLUDED WITH HOSE
ADAPTER MPT TO NPSH INCLUDED WITH HOSE
GASKET INCLUDED
WITH HOSE
FORM 145.18-IOM1
ISSUE DATE: 8/30/2018
1/2-INCH OR 3/4-INCH FLEXIBLE CONNECTOR HOSE (24 INCHES LONG)
FEMALE SWIVEL 1/2-INCH OR 3/4-INCH NPSH THREADS
ADAPTER MPT TO NPSH INCLUDED WITH HOSE
CHASSIS WATER CONNECTION 1/2-INCH OR 3/4-INCH FPT (FACTORY PROVIDED)
NOTE
National Pipe Straight Hose (NPSH) connection
FIGURE 7 - CONVERSION OF NPT TO NPSH TYPE FITTINGS (VB UNITS WITH NPT FITTINGS ONLY)
ELECTRICAL WIRING
Lock all electrical power supply switches in the OFF position before installing the
Use copper conductors only! Failure to use copper conductors can result in equipment damage.
unit. Failure to disconnect power supply may result in electrical shock or even death.
Verify that the available unit power supply is compat-
Field-Installed Power Wiring
ible with the unit’s nameplate rating. Ensure the break­er is properly sized as per the nameplate. The line volt-
Power wiring to the equipment must conform to Na­tional Electrical Codes (NEC), local electrical codes,
age supply enters through the right side of the cabinet at the 7/8-inch power entrance knock-out.
and must be performed by a licensed electrician.
Connect to the line side of the factory-installed termi-
Provide each unit with its own separate electrical cir­cuit, means of circuit protection, and electrical discon­nect switch. Follow current NEC ANSI/NFPA 70, CSA
nal block. Unit terminals are not designed to accept other types of conductors. Failure to use copper con­ductors may result in equipment damage.
C22.1 C.E.C. Part 1, and state and local codes.
Failure to provide these shut-off means could cause electrical shock or re, re­sulting in damage, injury, or death.
Field-Installed Low Voltage Wiring
Select a location for room thermostat, away from supply air registers, on draft-free interior wall that is far from lights, television, direct sunlight, or other heat sources.
LD27628
18
Locate thermostat away from supply drafts. Ensure the back of the thermostat is sealed and protected from air drafts. Short cycling can result in damage to the unit.
FORM 145.18-IOM1 ISSUE DATE: 8/30/2018
SECTION 1 - INSTALLATION
Install the thermostat by connecting the remote ther­mostat wiring to microprocessor board low voltage terminal strip. See Figure 8 for typical wiring connec­tions.
Ensure that the control wiring between the thermostat and the unit’s terminations does not exceed 1 ohm.
Resistance in excess of 1 ohm may cause
component damage due to insufcient AC
voltage supply.
Check all loads and conductors for grounds, shorts, or miswiring. Do not run the low voltage wiring in the same conduit with the high voltage power wiring.
TABLE 4 - TYPICAL WIRE CONNECTIONS
RECOMMENDED WIRE
SIZE (GAUGE)
20 50
18 75
16 125
MAXIMUM LOW VOLTAGE
WIRE LENGTH (FEET)
Optional Surface Mount Thermostat Connection Wiring
For applications where the thermostat is mounted di­rectly above the return air (RA) panel, select cabinet control option P (for example, VB12P). The thermostat Molex pigtail harness (shipped loose) is field wired to thermostat terminals. The Molex connector clips to the panel-mounted, mating Molex connector on unit cabi­net that is located 7 inches above the electrical box. See optional 24V surface mount connection in Figure 3 on page 14.
Optional Remote Mounted Thermostat Wiring
For units ordered with an extended thermostat harness option, the thermostat is remote mounted. A specific, plenum rated extended harness length can be ordered.
Use low voltage 7/8-inch knock-out on the side of the unit at the electrical box to field wire the low voltage thermostat wiring. Using a plastic bushing to pass the harness inside electrical box to the factory wired mat­ing Molex harness (see Figure 9). The thermostat pig­tail Molex harness ships loose for field wiring to the thermostat terminals.
1
FIGURE 8 - FIELD WIRING DIAGRAM
LD27629 LD27630
FIGURE 9 - REMOTE THERMOSTAT WIRING
LD19520
19
SECTION 1 - INSTALLATION
Optional Disconnect
FORM 145.18-IOM1
ISSUE DATE: 8/30/2018
CLOSET AND DRYWALL INSTALLATION
To avoid potential vibration and noise is­sues, the RA panel should not contact any part of the unit cabinet or sleeve. Maintain
a sufcient gap between RA panel frame
and cabinet.
Optional ADA Molex Connection
LD27631
FIGURE 10 - UNIT SWITCH PLATE WITH ADA THERMOSTAT CONNECTION
Optional ADA Door Mounted Thermostat
For units ordered with the Americans with Disabilities Act (ADA) thermostat option to meet ADA require­ments, the thermostat is located on the RA panel door at a height of 48 inches from the base of the cabinet. Unit is supplied with a custom RA door panel with thermostat mounting holes, unit switch plate with a Molex connector, and an ADA Molex pigtail harness. See Acoustic Return Air (RA) Panel on page 20 and Figure 14 on page 23.
Wire leads from the ADA thermostat harness are field wired to thermostat terminals. The Molex end of the ADA thermostat harness is field connected to the sur­face mounted Molex connector at unit switch plate.
Mount the thermostat using the factory provided 1/4­inch number 8 screws. The ADA thermostat harness is plenum rated. It hangs behind the RA door. For chassis servicing, unclip harness from unit switch plate.
EC Motor (ECM) Continuous Fan
This option features a factory wired continuous low speed fan circuit. Because of the five available motor speed taps, the EC motor (ECM) offers an ideal range for supporting continuous low speed fan.
Build a closet enclosure for the cabinet that incorpo­rates the RA panel size while maintaining a sufficient gap between the closet and cabinet. This prevents the cabinet from contacting the RA panel and closet enclo­sure. Refer to Acoustic Return Air (RA) Panel on page
20, Figure 11 on page 21, and Figure 12 on page
22.
1. Cover the supply and return openings with plas­tic or cardboard before installing drywall around cabinet. This prevents dust or debris from entering the unit components.
2. Install the drywall using conventional construc­tion methods. Do not fasten studs or drywall di­rectly to the cabinet surface. Space the framing members according to the RA access and the type/ quantity of supply air (SA) outlets. See Figure 11 on page 21 and Figure 12 on page 22.
3. Install sheetrock around unit cabinet by securing the drywall to the building construction studs.
4. Cut holes around the SA and RA openings to al­low access to the unit chassis, unit controls, and the SA connection.
5. Vacuum all dust and construction debris from the unit drain pan, electrical box, and discharge ple­num after cutting out the supply/returns openings.
To prevent electrical shorts and drain pan leaks, DO NOT penetrate unit compo­nents when driving screws near the unit control box or drain pan. Do not allow screws or nails to penetrate chassis, risers, electrical junction boxes, conduits, or to interfere with chassis removal.
ACOUSTIC RETURN AIR (RA) PANEL
The fan runs continuously on the low fan speed setting even if there is no demand for cooling or heating. The continuous fan is controlled by a dry contact to provide interlocking to energy recovery ventilator (ERV) or room occupancy control. See Figure 28 on page 46 for electrical schematics.
20
RA panels are painted standard appliance white. Care­fully unpack RA panels from their shipping box. RA panels with optional key locks require the key locks to be field installed to the slot in the panel door. ADA RA door panels come with an opening and pilot holes mounting a thermostat. The ADA harness for wiring the thermostat and connecting to the unit is shipped loose with the thermostats.
FORM 145.18-IOM1 ISSUE DATE: 8/30/2018
SECTION 1 - INSTALLATION
1. Locate the drywall opening at a distance from the unit so that it prevents the RA panel from contacting the unit sleeve. See Figure 11 on page 21 and Figure 12 on page 22.
2. Center the RA panel throat opening to the unit
cabinet RA ange opening.
3. Fasten the RA panel to frame opening using the screws provided. See Figure 11 on page 21.
D
E
Vertical Stack Cabinet
Top View
B
0.5-inch Drywall
6 x Fasteners
C
Figure 14 on page 23 shows the opening for mount­ing an ADA compliant thermostat at 48 inches above floor. Note that location of the opening on the door changes if the cabinet is ordered with a stand. A left hand opening door is shown. The RA panel with ADA is not reversible. It must be ordered in either a left or right-hand opening configuration, determined by the location of the door hinge.
Return Air Flange Standard = 1 inch Optional OA Fresh Air = 4.25 inches
Wall Stud
1-3/16 inch
(Drywall to Fastener Based on 0.5-inch Drywall
1
F
Vertical Stack Cabinet Top View
G
Min. 1/8-inch, Max. 3/8-inch Gap (RA Flange Must Not Contact Acoustic Door Frame)
A
UNIT SIZE
09/12/15/18 25 3/4 19 19 1/4 23 3/4 ± 1/8 20 20
24/30/36 29 3/4 23 23 1/4 27 3/4 ± 1/8 24 24
NOTE
All dimensions are in inches.
A (PANEL WIDTH)
B
(SLEEVE
WIDTH)
C
(R/A PANEL
OPENING)
D
(ROUGH IN
WIDTH)
E
(UNIT
WIDTH)
DEPTH)
H
Rear Closet to Cabinet Back: No Risers = 0.5-inch Minimum With Risers = 5-inch Minimum
2.25-inch Minimum (Unit Sleeve to Drywall)
F
(UNIT
G
(NO OA
OPTION)
23 1/4 MIN
23 1/2 MAX
27 1/4 MIN
27 1/2 MAX
G
(OA OPTION)
27 1/4 MIN
27 1/2 MAX
31 1/4 MIN
31 1/2 MAX
FIGURE 11 - CRITICAL RETURN AIR (RA) PANEL WITH UNIT CABINET INSTALLATION DIMENSIONS
LD19500
21
SECTION 1 - INSTALLATION
FORM 145.18-IOM1
ISSUE DATE: 8/30/2018
RA flange must not contact door frame
Acoustical
1-inch RA flange
Panel Door
Frame
2.5 inches
6 inches
3.75 inches
Cabinet
Floor
Closet Drywall
FIGURE 12 - RA PANEL CROSS SECTION
INSTALLATION AT FLOOR LEVEL
B
B
C
C
1.92
1.92
0.28
0.28 inches
inches
Figure 12 on page 22 shows a cutaway view for a standard cabinet with no stand. Add the stand height to the cabinet to obtain the correct dimension of the RA panel from floor.
For maximum return airow, the ush
mounted acoustic panel must be centered vertically and horizontally over the RA opening of the cabinet. SA duct collar extensions may be required to prevent short cycling.
LD27621
ALL DIMENSIONS ARE IN INCHES
MODEL A B C D
VSCS09–12 22.75 20.50 16.25 18.50 20.75 52.75
VSCS15–24 25.75 23.50 19.25 21.50 23.75 52.75
VSCS30–36 29.75 27.50 23.25 25.50 27.75 52.75
ROUGH-IN
WIDTH
ROUGH-IN
HEIGHT
Mounting Holes x 6
Mounting Holes x 6
52.50
50.5 inches
56.75
54.75 inches
D
D
50.25
54.50
(54 3/4" ROUGH-IN
48.25 inches
52.5 inches
WALL OPENING)
(52.75-inch Rough-In Wall Opening)
A
A
NOTES:
1. Acoustic panel is powder coated in appliance white
2. Acoustic panel can be installed on the right hand side or left hand side.
3. See Figure 11 on page 21 for additional RA panel and cabinet installation information.
FIGURE 13 - RA PANEL DIMENSIONS
A
Magnetic Catches x 2
Magnetic
Catches x 2
54.75 inches
LD19319C
22
FORM 145.18-IOM1 ISSUE DATE: 8/30/2018
1.5 inches
1.50
1.25 inches
1.25
Left Hand Opening Shown
LEFT HAND OPENING SHOWN
SECTION 1 - INSTALLATION
1
Thermostat mounting location,
Thermostat mounting location,
Cut-out for routing
cut-out for routing ADA thermostat
ADA thermostat harness
harness
0.5-inch Insulation
1/2" Insulation
Magnetic Catches x 2
Magnetic Catches x 2
Notes:
- Powder coated in 'Appliance White'
NOTES:
- Inside panel lined with 1/2" acoustical insulation
1. Powder coated in appliance white
- Hinged panel complete with magnetic latches
2. Inside panel lined with 0.5-inch acoustical insulation
- Panel comes either Left or Right hand opening
3. Hinged panel complete with magnetic latches
4. Panel comes either left or right hand opening
LD19320
FIGURE 14 - OPTIONAL RA PANEL WITH ADA MOUNTED THERMOSTAT
LD19320
23
SECTION 1 - INSTALLATION
FORM 145.18-IOM1
ISSUE DATE: 8/30/2018
SUPPLY AIR (SA) DUCTWORK
Ensure there is no direct contact between cabinet sheet metal parts and drywall en-
closure. This includes RA and SA anges.
Failure to follow these instructions will negatively affect unit sound performance.
Horizontal Supply Air
A 2-inch duct flange (field provided) may be required to eliminate supply air recirculation when shallow pro­file, single deflection supply grilles are installed at the cabinet discharge openings. If the discharge from the cabinet is not ducted completely into the conditioned space, air can recirculate into the RA opening from the space inside the drywall enclosure.
Manufacturer supplied grilles have a clearance of a 1/4 inch around the perimeter to fit inside the unit supply flange. Other grille manufacturers could have different clearances that should be verified.
Field supplied gasket must be applied in order to pre­vent air recirculation and vibration transfer when sup­ply grilles are mounted to unit supply opening. When mounting supply grilles with optional volume damper directly to cabinet supply flange, the volume damper fits inside the cabinet supply flange. It is recommended to apply 1/8-inch neoprene tape (field supplied) around the perimeter of the volume damper prior to inserting it into the supply opening. See Figure 15 on page 24 for an example. This assists in reducing noise transmis­sion and air recirculation into the unit closet.
For ducted openings, connect the unit supply opening to the supply ductwork using a watertight flexible duct connector. This minimizes the transmission of operat­ing sounds through the supply ductwork. Elbows with turning vanes or splitters are recommended to mini­mize air noise due to turbulence and to help reduce static pressure.
Top Discharge Supply Air
Units that are installed with a top discharge should be connected to the supply ductwork with a watertight flexible connector. This minimizes the transmission of operating sounds through the supply ductwork. El­bows with turning vanes or splitters are recommended to minimize air noise due to turbulence and to help re­duce static pressure.
For information on available unit horizontal and top supply openings see Table 5 and Table 6 on page 26. Recommended face velocity at the outlet supply grille is 300–500 FPM. Table 6 gives face velocity at the unit supply openings in relation to Table 5. To calculate the face velocity at the supply grille, take the FPM from Table 6 and divide by the supply grille area factor.
LD27622
FIGURE 15 - SUPPLY GRILLE WITH VOLUME DAMPER AND 1/8-INCH NEOPRENE TAPE APPLIED TO PERIMETER
24
FORM 145.18-IOM1 ISSUE DATE: 8/30/2018
WALL STUD
Wall Stud
D E
VERTICAL STACK CABINET
Vertical Stack Cabinet
Top View
TOP VIEW
Optional Opposed Blade Damper
A
Louvered Supply Grille
Detail A
DETAIL A
SECTION 1 - INSTALLATION
1
0.5-inch Drywall
1/2”
DRYWALL
B
MOUNTING SCREWS
Mounting Screws
VERTICAL STACK CABINET
Vertical Stack Cabinet
Optional Framing Studs
for Supply Opening
FOR SUPPLY OPENING
UNIT
15–24 X B=X - 0.5 C=X + 1.75 23 3/4 ± 1/8 20
30–36 X B=X - 0.5 C=X + 1.75 27 3/4 ± 1/8 24
NOTES:
(SUPPLY GRILLE
SIZE
NOMINAL WIDTH)
9–18 X B=X - 0.5 C=X + 1.75 20 3/4 ± 1/8 17
1. All dimensions are in inches and typical for factory supplied grilles only.
2. Check dimensions for eld-supplied grilles because dimensions can be different.
OPTIONAL
FRAMING STUDS
A
B
(GRILLE
WIDTH)
(UNIT SUPPLY DUCT FLANGE
(Unit Supply Duct Flange
TO 1/2” DRYWALL FACE)
to 0.5-inch Drywall Face)
C
(GRILLE
FLANGE WIDTH)
C
Top View
TOP VIEW
2.25-inch Minimum
2-1/4” MIN.
D
(ROUGH IN
WIDTH)
(UNIT
WIDTH)
E
1/8” THICK FIELD SUPPLIED
1/8-inch Thick Field Supplied
GASKET TAPE
Gasket Tape Applied Around
APPLIED AROUND
Full Perimeter of Supply
FULL PERIMETER OF
Grilled with Volume Damper
SUPPLY GRILLE WITH
VOLUME DAMPER
FACTORY SUPPLIED
Factory Supplied
1” DUCT FLANGE
1-inch Duct Flange
DETAIL A
Detail A
FIGURE 16 - UNIT MOUNTED SUPPLY GRILLE INSTALLATION
LD19321
25
SECTION 1 - INSTALLATION
FORM 145.18-IOM1
ISSUE DATE: 8/30/2018
TABLE 5 - UNIT SUPPLY OPENING SIZES
HORIZONTAL OPENINGS
SINGLE HORIZONTAL DOUBLE HORIZONTAL
MODEL
NO TOP
OPENING
TOP OPENING
NO TOP
OPENING
TOP OPENING
9 14W x 12H 14W x 6H 14W x 8H Not Available Not Available 12 x 8
12 14W x 14H 14W x 6H 14W x 10H Not Available Not Available 12 x 8
15 16W x 14H 14W x 6H 14W x 10H Not Available 14W x 8H 14 x 12
18 Not Available 14W x 6H 14W x 12H 14W x 6H 14W x 10H 14 x 12
24 Not Available 14W x 10H 16W x 14H 14W x 6H 14W x 10H 14 x 12
30 Not Available 14W x 6H 20W x 14H 14W x 6H 16W x 12H 18 x 16
36 Not Available 14W x 10H Not Available 14W x 6H 16W x 14H 18 x 16
NOTES:
1. Unit mounted supply grilles are supplied as double-deection type.
2. Grilles for unequal airow applications (for example, unit mounted plus ducted supply) are provided with integral opposed blade dampers.
3. All grilles are supplied in standard appliance white painted nish.
4. Grilles are shipped loose for eld installation upon completion of cabinet/ductwork/drywall installation.
5. Top opening size does not change. When combined with any other discharge arrangement, it is included in determining horizontal opening grille size.
6. Openings marked Not Available result in face velocities outside the recommended 300–500 FPM range.
7. Hi-static blower option or single horizontal discharge openings with unit mounted supply grille are not recommended.
TRIPLE
HORIZONTAL
NO TOP
OPENING
TOP OPENING
TABLE 6 - UNIT SUPPLY FACE VELOCITY (FPM)
HORIZONTAL OPENINGS
MODEL
SINGLE HORIZONTAL DOUBLE HORIZONTAL
NO TOP
OPENING
TOP OPENING
NO TOP
OPENING
TOP OPENING
9 291 272 219 Not Available Not Available 510
12 316 344 221 Not Available Not Available 645
15 354 314 283 Not Available 236 471
18 Not Available 391 294 294 235 587
24 Not Available 397 273 364 291 729
30 Not Available 416 276 339 269 538
36 Not Available 410 Not Available 385 261 610
NOTES:
1. Tabulated face velocities do not account for supply grille free area factor. Face velocities at supply grille are higher depending on grille type.
2. Face velocities are based on the nominal rated CFM and feet per minute (FPM).
3. Face velocities are calculated by taking the average across all openings. Tabulated top opening face velocity is only for units with single top opening and no horizontal openings.
TRIPLE
HORIZONTAL
NO TOP
OPENING
TOP OPENING
26
FORM 145.18-IOM1 ISSUE DATE: 8/30/2018
SECTION 1 - INSTALLATION
TOP MOUNTED FRESH AIR INTAKE
The optional fresh air intake provides a 4-inch round duct connection on top of the unit (see Figure 23 on page 31 for right and left hand version). The fresh air is discharged upstream of the direct expansion (DX) coil through the discharge collector box.
Do not allow incoming air to bypass the DX coil, otherwise, damage to the unit may occur.
Units can be selected with the fresh air opening located on the top left or right hand side for ease of installation.
It is recommended that applications requiring 10% or more outdoor air utilize a pressurized fresh air system. Unit cabinet static pressure at the RA opening is not designed to draw 10% or more in passive fresh air sys­tems.
The fresh air duct inside the unit is insulated to protect the unit from condensation in the event of high humid­ity air. However excessively moist fresh air over pro­longed periods can result in condensate inside unit or closet.
During transportation, handling or instal­lation of the cabinet, excessive handling can cause an inner black plastic cover to come loose and jam the actuator, prevent­ing the damper from opening.
During start-up, check that the damper is opening when the unit fan is running. It can take 20 seconds to fully open. If the damper opens, the unit is operating as in­tended. If the damper fails to open, the cause is likely a loose cover preventing actuator from rotating. Remove the actuator to service the damper.
Removing the Actuator
1. Remove the damper plate:
a. Look underneath the top of the RA flange to
notice the damper assembly.
b. Remove the seven fasteners holding the
damper plate (see Figure 19 on page 28).
c. Drop the plate and disconnect the quick-con-
nect terminals from the harness.
2. Remove the red cover from the actuator body (see Figure 18 on page 27).
1
To avoid condensate developing inside ducts and equipment, it is recommended to pretreat fresh air with a high humidity ratio before it enters the unit assembly through ERVs or make-up air units.
The unit comes with a 4-1/4 inch RA sleeve. Front supply openings come with a 4-1/4 inch supply plaster flange.
Top Mounted Fresh Air Intake with Motorized Damper
This include the same features as the top mounted fresh air intake option with the addition of a motorized damp­er assembly inside the discharge collector box similar (see Figure 23 on page 31).
The damper assembly can be easily removed for ser­vicing (see Removing the Actuator on page 27). The motorized damper assembly opens during FAN ON op­eration. See Figure 28 on page 46 for the electrical schematic. For other control options, please contact the factory.
LD23557
FIGURE 17 - DAMPER PLATE FASTENERS
LD23558
FIGURE 18 - REMOVE THE RED COVER
27
SECTION 1 - INSTALLATION
LD23559
FORM 145.18-IOM1
ISSUE DATE: 8/30/2018
SYSTEM FLUSHING AND CLEANING
After the piping system is complete, and before con­necting the refrigeration chassis, flush and clean the risers This ensures a proper start-up and continued ef­ficient operation of the system (see Figure 20 on page
29).
Flushing the System
1. Ensure the supply and return riser shut-off valves are closed at each unit.
2. Using exible hoses or piping, connect the supply and return stub-outs in the unit located at the end of the riser run(s).
If the building has more than ten floors, connect the supply and return stub-outs in the last two units to divide the water flow and reduce pressure drop at the pump (see Figure 20 on page 29).
LD23560
FIGURE 19 - POSITION BLACK COVER
3. If the black cover is loose, position it in place and slide it back onto the actuator (see Figure 19 on page 28).
4. Secure the red cover back over the actuator as­sembly.
5. Ensure the plastic tabs are secured to the metal body bracket.
6. Connect the quick-connect terminals, and insert the damper assembly into the discharge collector box.
7. Fasten the assembly using the seven fasteners.
3. Open the shut-off valves in the units that have had the supply and return risers interconnected.
4. Fill the water circulation system with clean wa­ter from the make-up water supply. Ensure the air
vents are open during initial lling. Do not allow the system to overow.
5. Close the air vents, and start the circulating pump.
6. Ensure that all air is bled from the system by cracking each air vent.
Make-up water must be available in suf­cient volume to replace the volume oc­cupied by the air that is bled off.
7. When all the air is vented and the water is circu­lating under pressure, check the entire system for leaks. Repair any leaks as required.
8. Raise the temperature to approximately 85.0°F by setting the loop temperature controls. Visually check for any leaks that may have occurred due to the increased heat. Repair any leaks as required.
9. Open the drain at the lowest point in the system.
The make-up water ow rate must be
equal to the rate of the drain bleed.
28
FORM 145.18-IOM1
to chassis
Hose or piping
Riser
Return
Riser
ISSUE DATE: 8/30/2018
SECTION 1 - INSTALLATION
10. Continue to bleed the system until the water leav­ing the drain is clear, no less than 2 hours.
11. Completely drain the piping system.
Cleaning the System
1. After the initial ushing, chemically clean the system. Repeat the method in Flushing the System
on page 28 to rell the system and circulate the
cleaning solution.
It is recommended to use the services of a pro­fessional water treatment company for the type of solution to be used and the duration of the clean­ing application.
2. Once the cleaning process is complete, shut off the circulating pump and completely drain the system.
3. Rell the system with clean water to prepare for refrigeration chassis connection and system start­up.
It is recommended that a professional wa­ter treatment company perform ongoing maintenance of the water loop including chemical analysis and ushing, if neces­sary. The water loop testing should be per­formed at intervals recommended by the professional water treatment consultant.
Stub-outs to
Stub-outs
chassis
Hose or piping
connecting
supply & return
connecting supply
runouts
and return runouts
1
It is recommended that the water loop testing be performed at least once a year. Standard practice is once a month or quarterly.
The customer is responsible for complet­ing adequate water loop maintenance over the lifespan of the units. Otherwise, damage to the units may occur.
Supply
Supply
Riser
Return
Riser
LD19685
FIGURE 20 - SYSTEM FLUSHING AND CLEANING
29
SECTION 1 - INSTALLATION
CABINET DIMENSIONS (INCHES)
MODEL A B C
09–12 17 8 12
15–24 20 12 14
30–36 24 16 18
1. Optional fresh air option comes with 2.5-inch RA ange.
2. Optional front supply opening comes with 2.5-inch duct ange.
3. All other openings come with standard 1-inch duct ange.
4. Left and right hand versions shown.
A
4-inch Ø Fresh Air Take-Off Intake
A
Left Hand Shown (Right Hand Opposite Side)
FORM 145.18-IOM1
ISSUE DATE: 8/30/2018
Front Supply Flange
(Optional)
Fresh Air Discharge
Collector Box
2.5-inch Return Air Flange
C
2.5 inches
Front Supply
(Optional)
Optional 24V Molex Connection for Surface Mount/ Remote Mounted Thermostat
Unit Switch Plate
B
3 inches
Ø 7/8-inch Power Entrance
Ø 7/8-inch Control Entrance (Knock-Out, Both Sides)
Riser Opening Knock-Outs (All Three Sides)
FIGURE 21 - FRESH AIR OPENING WITHOUT MOTORIZED DAMPER – LEFT AND RIGHT HAND UNIT SHOWN
30
LD27632
FORM 145.18-IOM1 ISSUE DATE: 8/30/2018
SECTION 1 - INSTALLATION
CABINET DIMENSIONS (INCHES)
MODEL A B C
09–12 17 8 12
15–24 20 12 14
30–36 24 16 18
1. Optional fresh air option comes with 4.25-inch RA ange.
2. Optional front supply opening comes with 4.25-inch duct ange.
3. All other openings come with standard 1-inch duct ange.
4. Left and right hand versions shown.
A
4-inch Ø Left Hand Fresh Air Take-Off Intake
Optional Front Supply
(4.25-inch Flange)
Fresh Air Discharge
Collector Box
4.25-inch Return Air Flange
4-inch Ø Fresh Air
Take-Off Intake
1
4.25 inches
A
C
C
B
Optional Front Supply (4.25-in. Flange)
Fresh Air Discharge Collector Box
Optional 24V Molex Connection for Surface Mount/ Remote Mounted Thermostat
Unit Switch Plate
3 inches
Ø 7/8-inch Power Entrance
Ø 7/8-inch Control Entrance (Knock-Out, Both Sides)
Riser Opening
61-7/8 inches
Knock-Outs (All Three Sides)
FIGURE 22 - FRESH AIR OPENING WITH MOTORIZED DAMPER – LEFT AND RIGHT HAND UNIT SHOWN
LD27634
31
SECTION 1 - INSTALLATION
FORM 145.18-IOM1
ISSUE DATE: 8/30/2018
CHASSIS INSTALLATION
Prior to installation of the refrigeration chassis and connection to the supply and return risers, the entire water loop system must be ushed and cleaned. See System Flushing and Cleaning on page 28.
Do not apply sealing tape or pipe dope on NPSH style ttings.
Check that the female end gasket from the hose is not missing, has no visible damage, and is free of debris.
Always use a backup wrench when install­ing hoses.
Remove the inner service panel from the cabinet, and inspect the interior compartment for debris. Clear all debris and vacuum construction dust from the cabinet.
Locate the supply and return shut-off valves. Verify the following:
• The valves are closed.
The type of hose kit ttings provided with the unit. Units shipped after June 2013 feature NPSH ttings (straight thread), while previous genera­tion hose kits are NPT type (tapered thread). Refer to Riser Loop on page 16 for more information.
For Units with NPSH Valve Connection and Hose Sets
NPSH flexible connection hoses do not require any pipe dope or sealant tape. DO NOT ADD THREAD SEALANT OR PIPE DOPE TO NPSH FITTINGS. Connect the hoses to the NPSH fitting on the shut-off valves. Always use a backup wrench when tightening the hose to the valve fitting. Allow the hoses to hang free inside the cabinet.
Protect the chassis from physical dam­age, drywall dust, paint fumes, and any other construction contamination during installation.
Hoses must be hand tightened then fur­ther tightened no more than 1/4 turn. Do not apply excessive force.
Always use a backup wrench when tight­ening hoses to valves. Otherwise, damage to the valve solder joint can lead to prop­erty damage or serious injury.
Slide the chassis into place using the following steps:
1. Attach the NPSH hoses to the NPSHttings on the chassis stub-outs by projecting through the top of the compressor compartment access cover.
2. Use a backup wrench to prevent twisting of the copper water piping within the chassis assembly.
3. For chassis installation, see For Units with NPT
Style (Tapered Pipe Thread) Valve Connection and Hoses on page 32 .
For Units with NPT Style (Tapered Pipe Thread) Valve Connection and Hoses
Factory supplied NPT flexible connection hoses come with thread sealing compound pre-applied. NO AD­DITIONAL THREAD SEALING TAPE SHOULD BE REQUIRED. Connect the hoses to the female pip thread fitting on the shut-off valves. Always use a backup wrench when tightening the hose to the valve fitting. Allow the hoses to hang free inside the cabinet.
Slide chassis into place using the following steps. A J-swivel adapter (supplied with the hose kit) comes with thread sealing compound pre-applied. NO AD­DITIONAL THREAD SEALANT SHOULD BE RE­QUIRED.
32
FORM 145.18-IOM1 ISSUE DATE: 8/30/2018
SECTION 1 - INSTALLATION
1. Thread the swivel adapters into the female pipe
thread ttings projecting through the top of the
compressor compartment access cover. To prevent twisting of the copper water piping in the chassis assembly, always use a backup wrench.
To minimize the possibility of damage to the chassis or cabinet and for maximum ease of installation, the use of a two­wheeled dolly is strongly recommended.
Do not contact the nned coil face. Dam­age to the ns will result.
2. Lift chassis from the front of chassis (see Figure 22 on page 33).
3. Align chassis with the opening of the cabinet. Tilt
the chassis sufciently for the base of the chassis
to clear the mounting rails on the cabinet drain pan (see Figure 23 on page 33).
1
LD23565
FIGURE 24 - TILT THE CHASSIS
4. Insert the chassis midway into the opening of the cabinet. Lower the rear of the chassis until the base of the chassis touches the formed mounting rails in the cabinet drain pan (see Figure 24 on page 33).
LD23564
FIGURE 23 - LIFT THE CHASSIS FRONT
LD23566
FIGURE 25 - INSERT THE CHASSIS
Before fully inserting chassis, ensure wiring harness and or water hoses will not be pinched.
5. Pivot the chassis base on the front edge of the drain pan rails. Before fully inserting the chassis, ensure the wiring harness and water hoses cannot be pinched between the chassis and cabinet (see Figure 25 on page 34).
33
SECTION 1 - INSTALLATION
FIGURE 26 - PIVOT THE CHASSIS
LD23567
FORM 145.18-IOM1
ISSUE DATE: 8/30/2018
Do not apply excessive force when sliding chassis into cabinet.
6. Slide the chassis into the cabinet until at least 3/4 of the depth of the chassis is supported. The chas­sis should slide easily on the drain pan rails. DO NOT APPLY EXCESSIVE FORCE. Ensure that the chassis will not tip forward before removing dolly (see Figure 26 on page 34).
To avoid damage from clogged coil sur­faces, plugged motor ventilation open­ings, and potential unit failure, DO NOT operate unit without compete enclosure,
supply grille, RA panel, and lter in place.
7. Connect the hoses to the chassis. Ensure that the hoses cannot be pinched once the chassis is slid into place.
FIGURE 27 - SLIDE THE CHASSIS
8. Without touching the anges on either side, en­sure the chassis' alignment in the cabinet is cen­tered in the cabinet opening (see Figure 27 on page 34).
9. Complete the electrical connections to the chas­sis using the two quick-connect mating plugs. The unit-mounted plug ends are located on the bottom of the control box.
LD23568
10. Remove the shipping cover from the face of the air-to-refrigerant coil.
11. Install the inner service panel and check that the foam gasket seal between the panel and the chas­sis is slightly compressed.
If necessary, pull the chassis forward slightly to ensure an adequate seal between the chassis and the service panel.
12. Install the air lter onto the face of the service
panel. Slide the lter upward into the top-re­taining clip until the bottom of the lter can be
dropped onto the lower clip.
FIGURE 28 - CHECK THE CHASSIS
34
LD23569
13. Install service panel.
14. Install the RA panel into the drywall opening if not already installed. Refer to Acoustic Return Air (RA) Panel on page 20. Secure the panel into the drywall with six screws.
FORM 145.18-IOM1 ISSUE DATE: 8/30/2018
SECTION 2 - OPERATION
Once the installation is complete and the system is cleaned and flushed, begin unit start-up. Open the sup­ply and return shut-off valves at each unit, refill the system, and bleed off all air.
PRE-START-UP CHECKLIST
Before energizing the unit, perform the following checks and complete the Vertical Stacked Heat Pump Start-Up and Performance Checklist (Form 145.18- CL1) in compliance with warranty requirements.
The high voltage power supply is correct and in
accordance with the nameplate ratings.
The field wiring and circuit protection are the cor-
rect size.
The unit is electrically grounded.
The low voltage control wiring is correct per the
unit wiring diagram.
There is vibration isolation (for example, unit iso-
lation pad, flexible hoses).
The low-side or high-side pressure temperature
caps are secure and in place.
All the unit access panels are secure and in place.
The thermostat is in the OFF position.
INITIAL UNIT START-UP
During installation, testing, servicing, and troubleshooting of this product, it may be necessary to work with live electri­cal components. Failure to follow all elec­trical safety precautions when exposed to live electrical components could result in serious injury or death.
1. Close the disconnect switches on all units to pro­vide line power.
2. Set the thermostat to the highest temperature set­ting.
3. Set the thermostat system switch to COOL and the fan control switch to AUTO. The compressor should NOT run.
4. Reduce the temperature control setting until the compressor and supply fan energize, with the following results:
• Water temperature leaving the heat exchang­er is warmer than the entering water temper­ature (EWT) (approximately 9.0–12.0°F).
• The blower operation is smooth.
• The compressor and blower amps are within the nameplate data values.
2
The water flow is established and circulating
through all the units.
The ductwork (if required) is correctly sized, run,
taped, and insulated.
The indoor blower turns freely without rubbing.
If applicable, glycol fluid was added in the proper
mix to prevent freezing in closed system applica­tion.
Clean, properly sized air filters are in place.
The condensate drain pipe is firmly secured to
both the drain riser and the drain pan stub.
• The suction line is cool with no frost ob­served in the refrigerant circuit.
5. Turn the thermostat switch to the OFF position. The compressor and fan stop running and the re­versing valve de-energizes.
6. To allow for pressure equalization, leave the unit off for approximately 5 minutes.
7. Turn the thermostat to the lowest setting.
8. Set the thermostat system switch to the HEAT po­sition. The compressor should NOT run.
9. Adjust the temperature setting upward until the compressor and supply fan energize, with the fol­lowing results after several minutes:
• Warm air is detected at the supply register.
• The water temperature decreases approxi­mately 5.0–9.0°F across the heat exchanger.
35
SECTION 2 - OPERATION
FORM 145.18-IOM1
ISSUE DATE: 8/30/2018
• The blower and compressor operation are smooth with no frost observed in the refrig­erant circuit.
10. Set the thermostat to maintain the desired space temperature.
11. Check all water connections for any leaks, includ­ing condensate drain hose connections.
SYSTEM LOOP TEMPERATURE
Loop temperatures affect unit performance, power consumption (efficiency), maintenance and reliability, and noise levels. High EWT in cooling mode above rated conditions of 86.0°F EWT increases power con­sumption and compressor noise levels. Sustained op­eration above 100°F EWT can increase maintenance costs, and increased compressor noise can affect oc­cupancy comfort. The unit is designed to operate up to
110.0°F EWT for intermittent periods when high load conditions elevate system loop temperatures.
It is not recommended to set system loop temperatures at 110.0°F in case high load conditions cause supply loop temperatures to exceed 110.0°F EWT. Unit sound performance can be negatively impacted at high EWT.
During heating season, the maximum operating loop temperature is 90.0°F EWT. For optimal unit perfor­mance, it is recommended to maintain system loop temperatures at or above the rated conditions of 68.0°F EWT. If system loop temperatures are low and freezing the coaxial is possible, the system loop must contain a glycol fluid mixture that is adequate to prevent freez­ing. The minimum loop temperature with glycol mix­ture is 20.0°F EWT. Lower loop temperatures result in lower efficiency and heating capacity.
High system loop temperatures may nega-
tively affect unit performance, efciency,
maintenance and reliability, and noise levels.
FAN SPEED ADJUSTMENT
Multi-speed direct drive motors are used in all units as standard. Permanent split capacitor (PSC) fan motors have a minimum of three selectable speeds. EC motors (ECMs) have five speeds, however only two speeds are recommended and available for selection.
Optional ECMs increase operating efficiency by con­suming fewer watts than standard PSC motors. Motors are factory programmed and cannot be re-programmed in the field. Each motor contains five low voltage speed taps. Two speed taps are used as standard.
Blower speed taps are factory set for optimum heating and cooling airflow ranges. See Table 8 on page 37 for factory blower speed settings and minimum operat­ing airflow.
Operating the unit below the minimum
airow may result poor heating/cooling
performance and periodic unit lockout.
A unit mounted two-speed fan switch located on the electrical box cover allows the fan speed to switch from LOW and HIGH. This enables the fan speed to meet site conditions such as increased ductwork static pressure or the use of higher efficient filters.
Perform a test run on the installed system to ensure op­eration with sufficient heating and cooling airflow. Ex­cessive ductwork static pressure results in an improper volume of airflow. High airflow volumes result in el­evated noise levels and can affect occupancy comfort.
Lock all electrical power supply switches in the OFF position before servicing the unit. Failure to disconnect power supply may result in electrical shock or even death.
TABLE 7 - OPERATING LIMITS
COOLING HEATING
MINIMUM EWT 30.0°F 20.0°F
MAXIMUM EWT 110.0°F 90.0°F
36
FORM 145.18-IOM1 ISSUE DATE: 8/30/2018
SECTION 2 - OPERATION
2
EXTERNAL STATIC PRESSURE (IN W.G.)
MIN.
RATED
MOTOR
0.0 0.05 0.1 0.15 0.2 0.25 0.3 0.35 0.4 0.45 0.5
340 330 320 310 300 285 270 255 240 225 -
CFM
CFM
HIGH
SPEED
340 220
LOW 255 250 240 230 220 210 - - - - -
445 435 425 415 400 385 370 355 340 320 295
430 290
LOW 350 345 335 325 315 305 290 - - - -
HIGH
580 570 560 550 535 520 505 485 465 445 425
550 335
LOW 385 380 375 370 365 355 345 335 - - -
HIGH
700 690 675 660 635 615 595 575 550 525 495
685 430
LOW 450 445 440 435 430 425 - - - - -
HIGH
880 855 835 815 795 770 740 710 680 650 615
850 575
HIGH
LOW 715 710 705 690 670 650 630 605 580 - -
1115 1100 1075 1050 1020 990 960 930 895 850 800
1075 700
LOW 965 960 950 935 915 895 870 840 810 780 745
HIGH
1230 1200 1170 1140 111 0 1075 1040 1000 960 915 870
1220 840
LOW 1115 1100 1075 1050 1020 990 960 930 895 855 805
HIGH
EXTERNAL STATIC PRESSURE (IN W.G.)
MIN.
CFM
CFM
RATED
SPEED
MOTOR
0.0 0.05 0.1 0.15 0.2 0.25 0.3 0.35 0.4 0.45 0.5 0.55 0.6 0.65 0.7 0.75 0.8
375 370 360 350 340 330 315 300 285 265 245 220 - - - - -
340 220
HIGH
LOW 330 320 310 300 290 280 270 255 240 225 - - - - - - -
485 475 465 455 440 425 410 395 380 360 340 315 - - - - -
430 290
HIGH
665 650 635 615 595 575 555 540 520 500 475 450 420 395 370 340 -
750 735 715 695 675 655 630 605 580 555 525 495 465 435 - - -
990 970 950 930 910 890 865 845 820 795 770 740 710 680 650 615 575
1180 1170 1160 1145 1130 111 0 1090 1070 1050 1025 1000 970 940 910 875 840 800
1340 1320 1295 1270 1245 1220 1190 1160 1130 1100 1070 1040 1010 980 945 910 870
550 335
685 430
850 575
1075 700
1220 840
LOW 390 385 380 370 360 350 335 320 305 - - - - - - - -
LOW 580 570 560 550 535 520 505 485 465 445 425 400 375 350 - - -
LOW 670 655 640 625 605 585 560 535 510 485 460 435 - - - - -
LOW 795 785 775 760 745 730 715 695 675 655 630 605 580 - - - -
LOW 985 980 975 970 960 950 940 935 920 905 895 875 850 825 795 765 730
HIGH
HIGH
HIGH
HIGH
HIGH
LOW 1180 1170 1160 1145 1130 111 0 1090 1070 1050 1025 1000 970 940 910 875 840 800
12
09
SIZE
UNIT
TABLE 8 - PSC STANDARD BLOWER PERFORMANCE (CFM)
15
18
24
30
36
09
12
15
SIZE
UNIT
TABLE 9 - PSC HIGH STATIC BLOWER PERFORMANCE (CFM)
18
24
30
36
37
SECTION 2 - OPERATION
FORM 145.18-IOM1
ISSUE DATE: 8/30/2018
EXTERNAL STATIC PRESSURE (IN W.G.)
MIN.
RATED
MOTOR
0.0 0.05 0.1 0.15 0.2 0.25 0.3 0.35 0.4 0.45 0.5
342 317 292 276 259 247 236 228 220 214 207
CFM
340 220
CFM
HIGH
SPEED
EXTERNAL STATIC PRESSURE (IN W.G.)
463 431 399 378 356 340 324 317 310 299 289
600 567 534 500 466 445 424 396 367 340 312
760 726 693 667 642 615 587 574 561 529 497
891 863 835 809 784 757 730 689 648 601 554
1131 1105 1079 1058 1037 1016 994 972 949 934 918
1265 1235 1206 1184 1163 1141 111 8 1085 1051 1008 965
430 290
550 335
685 430
850 575
1075 700
1220 840
LOW 278 252 226 212 198 189 180 - - - -
LOW 342 317 292 276 259 247 236 - - - -
LOW 495 447 399 372 346 307 268 - - - -
LOW 600 567 534 500 466 445 424 396 - - -
LOW 760 726 693 667 642 615 587 574 - - -
LOW 918 894 870 852 835 808 781 762 743 718 -
HIGH
HIGH
HIGH
HIGH
HIGH
HIGH
LOW 1065 1037 1009 987 965 949 934 910 886 874 861
0.0 0.05 0.1 0.15 0.2 0.25 0.3 0.35 0.4 0.45 0.5 0.55 0.6 0.65 0.7 0.75
MIN.
CFM
CFM
RATED
SPEED
MOTOR
411 382 354 334 315 300 286 279 272 263 254 242 231 220 - -
340 220
LOW 342 317 292 276 259 247 236 228 220 - - - - - - -
HIGH
554 529 504 477 451 430 408 393 378 360 341 330 319 300 - -
430 290
LOW 463 431 399 378 356 340 324 317 310 299 290 - - - - -
HIGH
659 623 587 564 541 5 11 482 462 441 419 397 372 346 320 - -
550 335
HIGH
891 863 835 809 784 757 730 689 648 601 554 518 482 446 408 -
1002 971 940 912 883 854 826 800 774 749 724 698 671 643 615 586
1265 1235 1206 1184 1163 1141 1118 1085 1051 1008 965 913 861 808 756 701
1462 1418 1375 1331 1287 1241 1194 1153 111 2 1053 994 964 934 903 872 840
685 430
850 575
1075 700
1220 840
LOW 600 567 534 500 466 445 424 396 367 340 312 - - - - -
LOW 760 726 693 667 642 615 587 574 561 529 497 469 441 412 - -
LOW 866 827 789 762 735 708 682 659 636 612 587 571 - - - -
LOW 1065 1037 1009 987 965 949 934 910 886 874 861 839 818 - - -
HIGH
HIGH
HIGH
HIGH
LOW 1265 1235 1206 1184 1163 1141 1118 1085 1051 1008 965 913 861 - - -
09
12
15
SIZE
UNIT
TABLE 10 - ECM STANDARD BLOWER PERFORMANCE (CFM)
18
38
24
30
36
09
12
15
18
SIZE
UNIT
TABLE 11 - ECM HIGH STATIC BLOWER PERFORMANCE (CFM)
24
30
36
FORM 145.18-IOM1 ISSUE DATE: 8/30/2018
SECTION 2 - OPERATION
2
EXTERNAL STATIC PRESSURE (IN W.G.)
MIN.
RATED
MOTOR
0.0 0.05 0.1 0.15 0.2 0.25 0.3 0.35 0.4 0.45 0.5 0.55 0.6 0.65 0.7 0.75
278 252 226 212 198 189 180 - - - - - - - - -
CFM
CFM
1
SPEED
278 252 226 212 198 189 180 - - - - - - - - -
340 180
2 342 317 292 276 259 247 236 228 220 214 207 - - - - -
3 411 382 354 334 315 300 286 279 272 263 254 242 231 220 - -
4 463 431 399 378 356 340 324 317 310 299 290 - - - - -
5 554 529 504 477 451 430 408 393 378 360 341 330 319 300 - -121
430 236
2 342 317 292 276 259 247 236 - - - - - - - - -
3 411 382 354 334 315 300 286 279 272 263 254 242 231 220 - -
495 447 399 372 346 307 268 - - - - - - - - -
550 268
4 463 431 399 378 356 340 324 317 310 299 289 - - - - -
5 554 529 504 477 451 430 408 393 378 360 341 330 319 300 - -151
2 600 567 534 500 466 445 424 396 367 340 312 - - - - -
3 659 623 587 564 541 511 482 462 441 419 397 372 346 320 - -
495 447 399 372 346 307 268 - - - - - - - - -
685 396
4 760 726 693 667 642 615 587 574 561 529 497 469 441 412 - -
5 891 863 835 809 784 757 730 689 648 601 554 518 482 446 408 -181
2 600 567 534 500 466 445 424 396 367 340 312 - - - - -
3 659 623 587 564 541 511 482 462 441 419 397 372 346 320 - -
659 623 587 564 541 511 482 462 441 419 397 372 346 320 - -
850 574
4 760 726 693 667 642 615 587 574 561 529 497 469 441 412 - -
5 891 863 835 809 784 757 730 689 648 601 554 518 482 446 408 -241
2 760 726 693 667 642 615 587 574 - - - - - - - -
3 866 827 789 762 735 708 682 659 636 612 587 571 - - - -
918 894 870 852 835 808 781 762 743 718 - - - - - -
1075 718
4 891 863 835 809 784 757 730 689 648 601 554 - - - - -
5 1002 971 940 912 883 854 826 800 774 749 724 698 671 643 615 586301
2 1065 1037 1009 987 965 949 934 910 886 874 861 - - - - -
3 1131 1105 1079 1058 1037 1016 994 972 949 934 918 - - - - -
4 1265 1235 1206 1184 1163 1141 1118 1085 1051 1008 965 913 861 808 756 701
5 1462 1418 1375 1331 1287 1241 1194 1153 1112 1053 994 964 934 903 872 840361
918 894 870 852 835 808 781 762 743 718 - - - - - -
1220 861
2 1065 1037 1009 987 965 949 934 910 886 874 861 - - - - -
3 1131 1105 1079 1058 1037 1016 994 972 949 934 918 - - - - -
4 1265 1235 1206 1184 1163 1141 1118 1085 1051 1008 965 913 861 808 756 701
5 1462 1418 1375 1331 1287 1241 1194 1153 1112 1053 994 964 934 903 872 840
SIZE
UNIT
TABLE 12 - ECM BLOWER PERFORMANCE - ALL SPEED TAPS (CFM)
09
1. All airow ratings are at lowest voltage rating of dual rating (for example, 208 volt).
2. Airow ratings include resistance of wet coil and clean air lters.
NOTES
39
SECTION 2 - OPERATION
FORM 145.18-IOM1
ISSUE DATE: 8/30/2018
UNIT CONTROLS
The control system microprocessor board is specifi­cally designed for water source heat pump operation. The control system interfaces with a conventional type thermostat.
• The unit is complete with a self-contained low­voltage control circuit.
• The unit incorporates a lockout circuit that pro­vides reset capability from a hard lockout at the space thermostat or base unit if any of the follow­ing standard safety devices trip and shut off the compressor:
• Low pressure limit switch (loss of charge)
• High pressure limit switch
• Freeze protection switch (unit shutdown on low water temperature)
• Condensate overflow switch
• The unit operates with conventional thermostat designs and has a low voltage terminal strip for easy hook-up.
• Unit control board has on-board diagnostics and fault code display.
• Standard controls include anti-short cycle and low voltage protection.
• The control board monitors each refrigerant safe­ty switch independently.
• The control board has a random start feature.
The control board retains the last ve fault codes in nonvolatile memory that cannot be lost in the event of a power loss.
Sequence of Operation
The room thermostat makes a circuit between R and Y1 for cooling.
The call passes to the unit microprocessor control that determines whether the requested operation is avail­able and if so, which components to energize.
If at any time there is a call for both heating and cool­ing, the heating operation is performed. Heating always takes priority. If cooling mode is operating, it halts and ends the call for cooling.
Continuous Blower
With the room thermostat fan switch set to AUTO and the system switch set to either AUTO or HEAT, the blower energizes whenever a cooling or heating opera­tion is requested. The blower energizes after any speci­fied delay associated with the operation.
The indoor blower energizes for a minimum runtime of 30 seconds. Additionally, the indoor blower delays for 10 seconds between operations.
When the room thermostat calls for cooling, the low­voltage control circuit completes from R to Y1 and G. The compressor and fan motor energize. After com­pleting the specified fan on delay for cooling, the mi­croprocessor control energizes the blower motor.
Once the room thermostat has been satisfied, it de­energizes Y1. If the compressor satisfies its minimum runtime, the compressor and fan de-energize. Oth­erwise, the unit operates the cooling system until the minimum runtime for the compressor completes. After the compressor de-energizes and the fan off delay for cooling elapses, the blower stops.
To be available, a compressor must not be locked-out because of a high pressure limit switch, low pressure limit switch, condensate overflow switch, or a freeze­stat trip. The anti-short cycle delay (ASCD) must elapse.
Safety Control Reset
All VPCS heat pumps are furnished with a high pres­sure limit switch, a low pressure limit switch, low wa­ter temperature freeze protection switch, and conden­sate overflow switch to prevent compressor operation during abnormal conditions.
If any of these safety devices activate, a lockout relay circuit engages. The circuit interrupts heating and cool­ing operation even if the control contacts automatically re-close.
For heating, the room thermostat makes a circuit be­tween R and W1. The microprocessor control energiz­es the compressor and fan, enabling the unit to run in heating mode.
40
This microprocessor driven lockout circuit must be manually reset. Reset by momentarily moving the ther­mostat control (system) switch to OFF, then back to HEAT or COOL (or AUTO).
The lockout circuit can also be reset by opening and closing the unit mounted disconnect switch.
FORM 145.18-IOM1 ISSUE DATE: 8/30/2018
SECTION 2 - OPERATION
If the unit must be reset more than twice on consecutive operating cycles, check
the unit for a dirty lter, abnormal EWT, inadequate or excessive water ow, or
refrigerant circuit malfunction. If the unit continues to cutout, contact a trained service technician.
Operation Errors
Each refrigerant system is monitored for operation out­side of the intended parameters. Errors are handled as described below. All system errors override minimum runtimes for compressors.
High Pressure Limit Switch
If a high pressure limit switch opens, the microproces­sor control de-energizes the compressor, initiates the ASCD, and stops the unit fans (soft lockout). If a call for cooling or heating is still present at the conclusion of the ASCD, the microprocessor control re-energizes the compressor and unit fan.
If a high pressure limit switch opens three times within 2 hours of operation, the microprocessor control per­manently locks out the system compressor, requiring a manual reset of the system (a hard lockout). To manu­ally reset, either de-energize the 24-volt power to the unit or turn the room thermostat to OFF, then back to either HEAT or COOL as required. The microproces­sor control flashes a fault code indicating the high pres­sure lockout (see Table 13 on page 42).
Low Pressure Limit Switch
The microprocessor does not monitor the low pressure limit switch during the initial 30 seconds of compressor operation. For the following 30 seconds, the micropro­cessor control monitors the low pressure limit switch to ensure it closes. If the low pressure limit switch fails to close after the 30 second monitoring phase, the mi­croprocessor control de-energizes the compressor, ini­tiates the ASCD, and stops the fan (a soft lockout).
If a low pressure limit switch opens three times within 1 hour of operation, the microprocessor control board locks out the compressor (a hard lockout) and flashes a fault code (see Table 13 on page 42).
Freeze-Stat
If a freeze-stat opens, the microprocessor control de­energizes the compressor and initiates the ASCD. If a call for cooling or heating is still present after the ASCD, the microprocessor control re-energizes the halted compressor.
Condensate Overow Switch
A condensate overflow fault occurs if the condensate overflow switch opens continuously for 30 seconds. The compressor shuts down regardless of the mini­mum runtime, and alarm 15 sets. The fan continues operating in its current state.
The microprocessor control logs the first incident per compressor request. Lockout occurs on the second fault occurrence within a request cycle, requiring reset or power cycling. If the compressor request is removed, the fault occurrence counter resets to zero. When lock­outs are removed, the alarm resets.
Safety Controls
The microprocessor control monitors the following in­puts:
1. A suction line freeze-stat to protect against low leaving water temperatures (LWTs) (opens at
34.0°F and resets at 48.0°F).
2. A high pressure limit switch to protect against ex­cessive discharge pressures (opens at 600 psig ± 25 psig).
3. A low pressure limit switch to protect against loss of refrigerant charge (opens at 55 psig ± 5 psig).
4. A condensate overow switch to protect against
condensate overow.
2
Once the low pressure limit switch is proven (closes during the 30 second monitor period), the microproces­sor control monitors the low pressure limit switch for any openings. If the low pressure limit switch opens for more than 5 seconds, the microprocessor control de-energizes the compressor, initiates the ASCD, and stops the compressor (a soft lockout).
If the call for cooling is still present after the ASCD, the microprocessor control re-energizes the compres­sor.
Coaxial Freeze Protection Setpoint
The field can select the coaxial freeze protection setpoint. The unit uses a suction line freeze-stat factory setpoint for compressor lockout when the LWT drops below 35.0°F (resets at 48.0°F). To lower the setpoint for low temperature heating applications with an ad­equate water-antifreeze solution, unplug the freeze­stat sensor located at P6 on the microprocessor control board, and plug in the (pink) jumper attached to the existing harness.
41
SECTION 2 - OPERATION
FORM 145.18-IOM1
ISSUE DATE: 8/30/2018
Installing the jumper bypasses the freeze-stat, enabling heating operation with a leaving glycol fluid mixture temperature below 35.0°F. Use the jumper only in low water applications with adequate antifreeze protection, otherwise damage can occur.
Random Start
The random start function upon power up imposes time delay of 4 minutes plus a random delay of 1–64 seconds. A combination of the following determine the random number generator seed:
A xed seed programmed at the factory
• The serial number
• The model number
• The hours of the unit's compressor runtime
Compressor Protection
In addition to the external pressure switches, the com­pressor also has inherent internal protection. If there is an abnormal temperature rise in a compressor, the protector opens to shut down the compressor. The mi­croprocessor control incorporates features to minimize compressor wear and damage. The control uses an ASCD to prevent compressor operation too soon af­ter its previous run. Additionally, a minimum runtime is imposed any time a compressor is energized. The ASCD initiates on unit start-up and on any compressor reset or lockout.
Microprocessor Control Unit Flash Codes
The microprocessor control uses various flash codes to aid in troubleshooting. The flash codes are distin­guished by a short on and off cycle (approximately 200ms on and 200ms off).
During normal operation, to show that the micropro­cessor correctly functions, the control boards flash for 1 second on, 1 second off, also known as a heart beat. Do not confuse this with an error flash code. To pre­vent confusion, a 1-flash fault code is not used. For a list of all flash codes, see Table 13 on page 42.
Last Error
When this button is pressed and released one time within 5 seconds, it flashes the last five fault codes on the board’s LED. The most recent alarm is shown first and the oldest alarm is shown last.
Test Reset
When this button is pressed and released one time within 5 seconds, any ASCD is bypassed for one cycle.
Comm Setup
If the board is to be networked with other units, this button is used to set the network address.
The first time the button is pressed within 5 seconds, it scans the bus, assigns itself the first available address (starts at 2), and then flashes that address once.
Pressing the button two times within 5 seconds causes the control to flash the address.
TABLE 13 - FLASH CODES
FLASH CODES DESCRIPTION
On Steady Control failure – replace control
Heart Beat Normal operation
2 Flashes Control waiting on ASCD
3 Flashes HPS1 - Compressor lockout
5 Flashes LPS1 - Compressor lockout
13 Flashes Compressor held off due to low voltage
14 Flashes
15 Flashes
16 Flashes
NOTES
1. These ash codes do not represent alarms.
EEPROM storage failure (control failure)
Condensate overow switch -
compressor lockout
Coaxial freeze thermostat ­compressor lockout
1
1
Communication
The communication protocol is Modbus™ using the RTU method of packet framing at 19200-baud rate.
Current alarms or active restrictions are flashed on the microprocessor control LED.
42
FORM 145.18-IOM1 ISSUE DATE: 8/30/2018
SECTION 3 - MAINTENANCE
Unit maintenance is simplified by the following pre­ventive suggestions:
1. At least once a month, visually inspect the unit. Pay special attention to hose assemblies. Note any signs of hose deterioration or cracking. Immedi­ately attend to any sign of minor leakage.
2. At least once every three months, perform lter maintenance to ensure proper operation of the
equipment. Inspect the lters and replace when
visible dirt buildup is evident.
To avoid fouled machinery and extensive unit clean up, DO NOT operate units
without lters in place or use the unit as a
temporary cooling/heating source during construction.
3. Every three months, inspect the condensate drain pan for algae growth and mineral buildup. Exces­sive algae or mineral deposits in the drain pan or
drain line can result in condensate overow and
unpleasant mildew odors.
4. Annually check the fan motor and blower assem­bly. All units employ permanently lubricated fan motors. DO NOT OIL FAN MOTORS. Vacuum any accumulation of dirt from the motor ventila­tion slots and the blower wheel.
5. Annually check the contactors and relays within the control panel. Inspect the panel for any signs of damage caused by overheated contacts or tem­perature change to the wiring. Check the termi­nals for tightness.
6. Annually conduct an amperage check on the com­pressor and fan motor. An amperage draw more than 10% higher than the nameplate values can
indicate heat exchanger fouling, low water ow,
or premature physical motor failure.
7. At least once a year, inspect the air-to-refriger­ant heat exchanger surface. A dirty or partially clogged coil can signicantly reduce operat­ing capacity and can result in serious equipment problems. If the coils appear dirty, clean them us­ing mild detergent or a commercial coil-cleaning agent.
3
8. Inspect hoses, valves, and connections for water leaks. For hose connection leaks, inspect rubber hose gaskets and replace them as required.
43
SECTION 3 - MAINTENANCE
FORM 145.18-IOM1
ISSUE DATE: 8/30/2018
THIS PAGE INTENTIONALLY LEFT BLANK.
44
FORM 145.18-IOM1 ISSUE DATE: 8/30/2018
APPENDIX
FIGURE 29 - PSC MOTOR WIRING DIAGRAM
LD23571
45
APPENDIX
FORM 145.18-IOM1
ISSUE DATE: 8/30/2018
FIGURE 30 - ECM WIRING DIAGRAM
46
LD23572
FORM 145.18-IOM1 ISSUE DATE: 8/30/2018
APPENDIX
FIGURE 31 - CONTINUOUS FAN WITH ECM WIRING DIAGRAM
LD27633
47
APPENDIX
FORM 145.18-IOM1
ISSUE DATE: 8/30/2018
FIGURE 32 - MOTORIZED DAMPER ECM WIRING DIAGRAM
48
LD23574
FORM 145.18-IOM1
_
_
_
Please attach a sketch of the duct(s) run with this form when
VERTICAL STACKED WATER SOURCE HEAT PUMP
HEATING AND COOLING DATA RECORD SHEET
INDOOR PACKAGED EQUIPMENT
Form 145.18-CL2
ISSUE DATE: 8/30/2018
APPENDIX
HEATING AND COOLING DATA RECORD SHEET
JOB NAME: _____________________________________
JOB ADDRESS: _________________________________
______________________________________________
INSTALLER: ____________________________________
SPECIAL QUOTES/OPTIONS (YES/NO): _____________
CABINET MODEL #: _____________________________
CHASSIS MODEL #: _____________________________
OPERATING MODE (HEATING/COOLING): ___________
DUCTED/FREE DISCHARGE: ______________________
LENGTH, WIDTH, HEIGHT OF DUCT(S): _____________
SUPPLY DUCT EXTERNAL STATIC PRESSURE (iwg):
______________________________________________
______________________________________________
UNIT INFORMATION
JOB #: _________________________________________
DATE: _________________________________________
INSTALLER'S ADDRESS: _________________________
_______________________________________________
SERVICE TECHNICIAN: __________________________
CABINET SERIAL #: _____________________________
CHASSIS SERIAL #: _____________________________
LOCATION / ROOM # OF HEAT PUMP: ______________
FLASH CODES OR FAULTS FROM CONTROL BOARD:
_______________________________________________
DOES UNIT HAVE AN INTERNAL PUMP: (YES/NO): ____
SUPPLY AIRFLOW MEASUREMENT (CFM): _________
returned to the Applied Ducted Systems PTS team.
Air Coil
Airflow Airflow
Coil Inlet (Dry Bulb)
Coil Outlet (Dry Bulb) Coil Inlet (Wet Bulb) Coil Outlet (Wet Bulb) Air Relative Humidity (%)
Reversing Valve
°F °F
°F
Coaxial
Coil
°F °F
Expansion Valve
L3
L2
L2
L3
°F
Liquid Line
Water In
°F
psi
Water Flow:
Water Out
°F
psi
GPM
Compressor Amp Draw: L1
Compressor Voltage: L1
*May only need L1 and L2 lines
Internal Pump Voltage: L1 Internal Pump Amp Draw: L1
*If installed
Fan Motor Speed:
Fan Amp Draw: L1
Fan Voltage: L1
L2
L2
*May only need L1 and L2 lines
°F
psi = SAT °F
Compressor
Suction
Discharge
°F
psi = SAT °F
Superheat
Sub-cooling
L2
L2
L3
L3
49
APPENDIX
NOTES
Air Coil
Airflow Airflow
Coil Inlet (Dry Bulb)
Coil Outlet (Dry Bulb) Coil Inlet (Wet Bulb) Coil Outlet (Wet Bulb) Air Relative Humidity (%)
°F °F
°F °F
°F
Expansion Valve
Coaxial
Coil
Reversing Valve
Internal Pump Voltage: L1
L2
Internal Pump Amp Draw: L1
L2
*If installed
Fan Amp Draw: L1
L2
*May only need L1 and L2 lines
L3
Fan Voltage: L1
L2
L3
Fan Motor Speed:
°F
Liquid Line
°F
Water In
psi
°F
Water Out
psi
Water Flow:
GPM
Compressor Amp Draw: L1
L2
*May only need L1 and L2 lines
L3
Compressor Voltage: L1
L2
L3
°F
psi = SAT °F
Superheat Sub-cooling
Suction
Discharge
Compressor
°F
psi = SAT °F
FORM 145.18-IOM1
ISSUE DATE: 8/30/2018
50
FORM 145.18-IOM1 ISSUE DATE: 8/30/2018
R-410A QUICK REFERENCE GUIDE
See Section 1 - Installation for specific installation re­quirements.
• R-410A refrigerant operates at 50–70% higher pressures than R-22 refrigerant. Ensure that ser­vicing equipment and replacement components are designed to operate with R-410A refrigerant.
• R-410A refrigerant cylinders are rose colored.
• Recovery cylinder service pressure rating must be 400 psig (DOT 4BA400 or DOT BW400).
• Recovery equipment must be rated for R-410A refrigerant.
• Do not use R-410A service equipment on R-22 systems. All hoses, gauges, recovery cylinders, charging cylinders, and recovery equipment must be dedicated for use on R-410A systems only.
• Manifold sets must be at least 700 psig high side and 180 psig low side with a 550 psig retard.
• All hoses must have a service pressure rating of 800 psig.
• Leak detectors, must be designed to detect HFC refrigerants.
• Systems must be charged with refrigerant. Use a commercial type metering device in the manifold hose.
• R-410A refrigerant can only be used with polyes­ter (POE) type oils.
• POE type oils rapidly absorb moisture from the atmosphere.
• Vacuum pumps cannot remove moisture from POE type oils.
• Do not use liquid line driers with a working pres­sure rating less than 600 psig.
• Do not install suction line driers in the liquid line.
• A liquid line drier is required on every unit.
• Do not use an R-22 TXV. If a TXV is necessary, it must be an R-410A TXV.
• Never open the system to atmosphere when under vacuum.
• If the system must be opened for service, evacuate the system, then break the vacuum with dry nitro-
gen and replace the lter driers.
51
100 JCI Way, York, Pennsylvania USA 17406-8469 800-861-1001 Subject to change without notice. Printed in USA Copyright © by Johnson Controls 2018 www.johnsoncontrols.com ALL RIGHTS RESERVED
Form 145.18-IOM1 (818) Issue Date: August 30, 2018 Supersedes: 145.18-IOM1 (115)
Loading...