Johnson Controls T-901, T-905, T-903 User Manual

T-901, T-903 and T-905
Operation
This series of submaster thermostats is so designed that the set point may be remotely readjusted by changing pressure to the readjusting bellows. (See Fig. 2)
A master-submaster system consists of a primary controller (master thermostat) and submaster thermostat so connected that output (master pressure) from the master thermostat readjusts the set point of the submaster thermostat according to a predetermined schedule. A dial on the submaster thermostat also provides manual selection of set point at the instrument. These thermostats are available with liquid filled remote-bulb-and-capillary, insertion and immersion measuring elements.
Pneumatic Control Manual 717.1
Repair Parts for Discontinued Products Section
Instruction Bulletin T-901-A
Issue Date 16B4
Control Action
These thermostats are available in two-position and proportional action models. Both models are furnished either direct or reverse acting. A direct acting thermostat increases control pressure when temperature increases. A reverse acting thermostat decreases control pressure when temperature increases. A simple change of pivots converts the thermostats from one action to the other. See Fig. 1 and Table I.
Readjusting Action
Depending on the pivots used, an increasing master pressure either raises or lowers the set point. When increasing master pressure raises set point, the thermostat has direct readjustment. When increasing master pressure lowers set point, the thermostat has reverse readjustment.
Sensitivity
Sensitivity of a pneumatic thermostat is defined as the change in the control air pressure per unit change in temperature. It is expressed as psi per degree. Sensitivity of this series is adjustable from 1/8 through 5 psi per degree by moving a slider located on the control mechanism channel.
Fig. 1: T-901 Series Submaster
Thermostat Showing Pivot Locations
Differential
Differential of a two-position controller is defined as the degrees temperature change required to actuate the relay. The sensitivity adjustment described above becomes a differential adjustment in two-position action. Differential is adjustable 2 through 30 F degrees.
Operation of Control Mechanism
The liquid in the measuring element expands or contracts with temperature changes. This movement is transmitted to the control port lid through a system of levers as shown in Fig. 2. Output pressure to the controlled device varies with control port lid
© Johnson Controls, Inc.
Code No. LIT-7171715X
1
movement. The amount of movement depends on the location of the sensitivity slider which causes the control port lid to move. Thus, the lid moves with respect to the control port, located directly beneath the lid. This varies the amount of air leaving the control port and results in varying control port pressure. This varying pressure is used to operate a relay of large capacity located in the thermostat.
Operation of Readjusting Mechanism
Set point depends on the position of the control mechanism assembly with respect to the control port. The assembly is so pivoted that turning the set point dial positions the assembly to establish set point. The readjusting bellows contacts the free end of the readjusting mechanism assembly. As master pressure changes, the bellows moves, repositioning the control mechanism. Movement of the control
2 T-901/T-903/T-905 Instruction Bulletin
Loading...
+ 2 hidden pages