Johnson Controls T7000 Series, T7601-TF20-***JS0, T7600-TF20-***JS0, T7603-T000-***JF0, T7600-TF21-***JS0 Installation Instructions Manual

...
T7000 LCD Digital Thermostat
Installation Instructions
T7600-TF21-...JS0, T7601-TF20-...JS0, T7600-TF20-...JS0, T7603-T000-...JF0, T7600-TB21-...JA0
Refer to the QuickLIT website for the most up-to-date version of this document
Figure 1
Figure 4
1
Figure 2
Figure 3
/
o
F
AUTO
> 50 cm (19.68 inch)
> 150 cm (59.05 inch)
°C
•• Ambient
• Ambiante
• Umgebung
• Ambiente
• Ambiente
• Atmosfeer
• Omgivnin
Prostředí
• Otoczenia
Среда
• Omgivelse
MAX MIN MAX MIN
45 °C 113 °F
-0 °C
-32 °F
60 °C 140 °F
-10 °C
-14 °F
MAX 90% RH
MIN 10% RH
MAX 90% RH
MIN 10% RH
室温
ON / OFF
M
TiO2/ESP
Timer Symbol
ONONOFF
OFF
T7603-T000-...JF0
T7600-TB21-…JA0
Application VAL
Floor heater Floor heater water valve
Application AO AI
2-pipe FCU, AO valve Valve Actuator feedback
GND B AGND NTC OCC COM
LVAL N
T7601-TF20-...JS0
Application AO1 VAL2 VAL1
2-pipe relay valve
N/A
N/A Valve
4-pipe relay valve Heating Cooling
2-pipe 3-wire relay valve Valve off Valve on
2-pipe relay valve with TiO2/ESP
TiO2/ESP Valve
2-pipe relay valve with
oor heating
Floor heating
Valve
Water source heat pump Reversing Compressor
2-pipe AO valve Valve N/A N/A
Notes: F-ON is line voltage relay output, used for enable/ disable ECM fan in some case
FAN AO1
F-ON VAL2 VAL1
GND B AGND NTC OCC COM
L N
T7600-TF21-...JS0
Application AO2 AO1
2-pipe FCU N/A Valve
4-pipe FCU Heating Cooling
AO2GND B AAO1 GND NTC OCC COM
L HI MED LOW N
AIGND B AAO GND NTC OCC COM
L HI MED LOW N
T7600-TF20-...JS0
Application VAL2 VAL1
2-pipe relay valve N/A Valve
4-pipe relay valve Heating Cooling
2-pipe 3-wire relay valve Valve off Valve on
2-pipe relay valve with TiO2/ESP
TiO2/ESP Valve
2-pipe relay valve with
oor heating
Floor heating Valve
Water source heat pump Reversing Compressor
GND B AGND NTC OCC COM
L HI MEDVAL2VAL1 LOW N
3
T7000
INSTALLATION INSTRUCTIONS FOR THE TECHNICIAN/FITTER
READ THIS INSTRUCTION SHEET AND THE SAFETY WARNING CAREFULLY BEFORE INSTALLING AND SAVE IT FOR FUTURE USE
REPAIR AND REPLACEMENT
Do not attempt to repair the T7000 thermostat. In case of improperly functioning control, contact the nearest Johnson Controls® representative, and specify the desired product code number. When con-tacting the supplier for a replacement please state the type/model number of the control located on the data plate or cover label.
IMPORTANT:
• Use this T7000 thermostat only as an operating control. Where failure of malfunction of the T7000 thermostat could lead to personal injury or property damage to the controlled equipment or other property, additional precautions must be designed into the system. Incorporate and maintain other devices such as supervisory or alarm systems or safety or limit controls intended to warn of, or protect against, failure or malfunction of the T7000 thermostat.
• Do not install this thermostat in condensing, wet, or damp environment. Moisture may cause damage to the thermostat.
• Do not remove PCB from the enclosure cover. Removing the PCB from the enclosure cover voids the product warranty.
• Make all wiring connection in accordance with local, nation, and regional regulations. Do not exceed the T7000 thermostat electrical ratings.
• Remove LCD plastic cover before use
WARNING:
Disconnect power supply before making electrical connections. Contact with components carrying hazardous voltages can cause electrical shock and may result in severe personal injury or death.
• Risk of Electrical Shock: Ground the thermostat according to local, national, and regional regulations. Failure to ground the thermostat may result in electrical shock and severe personal injury and death.
• Risk of Electrical Shock and Property Damage: Insulate and secure each unused wire lead before applying power to the thermostat. Failure to insulate and secure each unused wire lead may result property damage, electrical shock, and severe personal injury or death.
Setup and adjustment:
Press and button for 5 seconds at power off mode (only press button for T7603-T000-...JF0), to get in parameter list, press M button (press
button for T7603-T000-...JF0 ) to switch over setting items and use and button to change parameter
value.
Item
T7600-
TF21-
...JS0
T7601-
TF20­...JS0
T7600-
TF20­...JS0
T7603-
T000­...JF0
T7600-
TB21­...JA0
Parameter Function Default
01 Application
T7601-TF20-...JS0 with EC Motor control
00: 2-pipe relay valve; 01: 4-pipe relay valve; 02: 2-pipe 3-wire relay valve; 03: 2-pipe relay valve with TiO2/ESP;
04: 2-pipe relay valve with oor heating;
05: water source heat pump; 06: 2-pipe AO valve
T7600-TF21-...JS0 Proportional Control
00: 2-pipe AO valve; 01: 4-pipe AO valve
T7600-TF20-...JS0 ON/OFF control
00: 2-pipe relay valve; 01: 4-pipe relay valve; 02: 2-pipe 3-wire relay valve; 03: 2-pipe relay valve with TiO2/ESP;
04: 2-pipe relay valve with oor heating;
05: water source heat pump
00
02 Upper set point limit Setting range 2~40℃ (36~99
o
F) 35
03 Lower set point limit Setting range 0~38℃ (32~95
o
F) 5
04 Cooling set point unoccupied Setting range 22~32℃ (72~90
o
F) 26
05
Heating set point unoccupied Setting range 10~21 (50~70
o
F
) 18
06
Frost protection 00: on; 01: off 00
07
Frost protection set point Setting range 0~20 5
08
Fan mode when set point reach
00: off 01: low 00
09
Fan mode when unoccupied 00: low speed; 01: set speed 00
10
ECM Min voltage Min voltage below which the fan output is 0%, range 0-10V. (0.5V) 3V
Loading...