Refer to the QuickLIT Web site for the most up-to-date version of this document.
Part No. 24-9890-951, Rev. A
Issued August 17, 2011
Supersedes October 15, 2009
Applications
The T60xDFH-4 and T60xDFH-4+PIR Series
Thermostat Controllers provide control of two- or
four-pipe fan coils, cabinet unit heaters, or other
equipment. These thermostat controllers provide
on/off, floating, or proportional 0 to 10 VDC control
outputs; three speeds of fan control; and
dehumidification capability. The T60xDFH-4+PIR
Series Thermostat Controllers have occupancy
sensing capability built into the device. These are
stand-alone devices that maximize up to 30% energy
savings in high-energy usage light commercial
buildings, such as schools and hotels, during occupied
times by using additional Stand-By setpoints. See the
Occupancy Sensor Operation – T60xDFH-4+PIR
Thermostat Controllers section for more information.
The non-programmable T60x Series Thermostat
Controllers provide the user access to parameters such
as system mode, fan mode, and temperature setpoints.
Additionally, the T60x Series has over 20 configurable
parameters enabling the thermostat controllers to
adapt to a variety of applications.
All T60x Series Thermostat Controllers use an intuitive,
plain text, menu-driven backlit display that makes
setup and operation quick and easy. The T60x Series
also employ a unique, Proportional-Integral (PI)
time-proportioning algorithm that virtually eliminates
temperature offset associated with traditional,
differential-based thermostat controllers.
IMPORTANT: The T60xDFH-4 and
T60xDFH-4+PIR Series Thermostat Controllers are
intended to provide an input to equipment under
normal operating conditions. Where failure or
malfunction of the thermostat controller could lead to
personal injury or property damage to the controlled
equipment or other property, additional precautions
must be designed into the control system.
Incorporate and maintain other devices, such as
supervisory or alarm systems or safety or limit
controls, intended to warn of or protect against
failure or malfunction of the thermostat controller.
North American Emissions Compliance
United States
This equipment has been tested and found to
comply with the limits for a Class A digital device
pursuant to Part 15 of the FCC Rules. These limits
are designed to provide reasonable protection
against harmful interference when this equipment is
operated in a commercial environment. This
equipment generates, uses, and can radiate radio
frequency energy and, if not installed and used in
accordance with the instruction manual, may cause
harmful interference to radio communications.
Operation of this equipment in a residential area is
likely to cause harmful interference, in which case
the user will be required to correct the interference
at his/her own expense.
Canada
This Class (A) digital apparatus meets all the
requirements of the Canadian Interference-Causing
Equipment Regulations.
Cet appareil numérique de la Classe (A) respecte
toutes les exigences du Règlement sur le matériel
brouilleur du Canada.
Installation
Location Considerations
Locate the T60x Series Thermostat Controller:
•on a partitioning wall, approximately 5 ft (1.5 m)
above the floor in a location of average
temperature
•away from direct sunlight, radiant heat, outside
walls, outside doors, air discharge grills, or
stairwells; and from behind doors
•away from steam or water pipes, warm air stacks,
unconditioned areas (not heated or cooled), or
sources of electrical interference
For integrated Passive Infrared (PIR) models, be sure
that the thermostat controller is located centrally , wh ere
occupant movement is abundant.
T60xDFH-4 and T60xDFH-4+PIR Series Thermostat Controllers with Dehumidification
and Occupancy Sensing Capability Installation Instructions
1
Note: Allow for vertical air circulation to the thermostat
Figure 1: Removing the
Thermostat Controller Cover
(T60xDFH-4+PIR Model Shown)
FIG:cvr_ rmvl
Figure 2: Opening the
Thermostat Controller PCB
F
I
G
:
p
r
c
r
c
t
b
r
d
Tabs
Figure 3: Securing the Thermostat Controller
Mounting Base to the Wall
F
I
G
:
m
n
t
b
controller.
To install the thermostat controller:
1. Use a Phillips-head screwdriver to remove the
security screw if it is installed on the bottom of the
thermostat controller cover.
Note: Be sure to position the thermostat controller
mounting base so that the arrow on the base points
upward to indicate the top of the thermostat controller.
Note: Normally, the security screw comes packaged
separately in a plastic bag with the thermostat
controller. Skip this step if the screw is not installed on
the bottom of the cover.
2. Pull the bottom edge of the thermostat controller
cover and open the thermostat controller as
illustrated in Figure 1.
Note: PIR models have a wiring connection between
the cover and the Printed Circuit Board (PCB). This
connection allows for proper wiring of the occupancy
sensor. Carefully remove the wiring connection from
the PCB by pulling up on the connector block. Do not
attempt to remove the connector block by pulling on the
wires.
PCB
Locking
6. Drill a 3/16 in. (5 mm) hole at each of the two
marked locations and tap nylon anchors (included
with the thermostat controller) flush to the wall
surface.
Note: Other means of anchoring the device may be
desired, depending on the wall medium.
7. Position the thermostat controller mounting base
on the wall and use the two mounting screws
(included with the thermostat controller) to secure
the base to the wall surface as illustrated in
Figure 3.
3. Carefully pull the locking tabs on the right side of
the thermostat controller mounting base and
unlock the PCB. Open the PCB to the left as
illustrated in Figure 2.
4. Pull approximately 6 in. (152 mm) of wire from the
wall and insert the wire through the hole in the
thermostat controller mounting base.
5. Align the thermostat controller mounting base on
the wall and use the base as a template to mark
the two mounting hole locations.
Note: Be careful not to overtighten the mounting
screws.
s
8. Swing the PCB back to the right and carefully snap
it into the locking tabs on the thermostat controller
mounting base.
T60xDFH-4 and T60xDFH-4+PIR Series Thermostat Controllers with Dehumidification and Occupancy
2
Sensing Capability Installation Instructions
9. Remove the screw terminal blocks that are
!
Figure 4: Removing the Screw Terminal Blocks
!
attached to a disposable adhesive. Figure 4
illustrates the locations of the screw terminal
blocks on the thermostat controller.
s
k
c
l
b
_
l
n
m
r
t
:
G
I
F
Wiring
When an existing thermostat controller is replaced,
remove and label the wires to identify the terminal
functions. When a T60x Series Thermostat Controller
is replaced, simply remove the old screw terminal
blocks and reinsert them onto the PCB of the
replacement thermostat controller.
CAUTION: Risk of Property Damage.
Do not apply power to the system before
checking all wiring connections. Short
circuited or improperly connected wires
may result in permanent damage to the
equipment.
IMPORTANT: Make all wiring connections in
accordance with local, national, and regional
regulations. Do not exceed the electrical ratings of
the T60x Series Thermostat Controller.
To wire the thermostat controller:
1. Strip the ends of each wire a 1/4 in. (6 mm) and
connect them to the appropriate screw terminals as
indicated in Table 1 and Figure 5 through Figure 9.
2. Carefully push any excess wire back into the wall.
Note: Seal the hole in the wall with fireproof material
to prevent drafts from affecting the ambient
temperature readings.
3. Reinsert the screw terminal blocks onto the PCB.
Note: If multiple wires are inserted into the terminals,
be sure to properly twist the wires together prior to
inserting them into the terminal connectors.
4. For PIR models, carefully reattach the PIR
connector to the PCB.
CAUTION: Risk of Electric Shock.
Disconnect the power supply before
making electrical connections to avoid
electric shock.
5. Reattach the thermostat controller cover to the
mounting base (top side first).
6. Use a Phillips-head screwdriver to reinstall the
security screw on the bottom of the thermostat
controller cover if desired. The security screw
comes packaged separately in a plastic bag with
the thermostat controller.
T60xDFH-4 and T60xDFH-4+PIR Series Thermostat Controllers with Dehumidification and Occupancy
Sensing Capability Installation Instructions
3
Table 1: Terminal Identification (See Figure 5.)
Terminal
Number
T601DFH-4,
T601DFH-4+PIR
(On/Off Control)
1Fan-HFan-HFan-HFan On – High
2Fan-MFan-MFan-MFan On – Medium
3Fan-LFan-LFan-LFan On – Low
424 V~ Hot24 V~ Hot24 V~ Hot24 VAC from Transformer
524 V~ Com24 V~ Com24 V~ Com24 VAC (Common) from Transformer
6BO5 AuxBO5 AuxBO5 AuxAux BO (Auxiliary Output)
7BO5 AuxBO5 AuxBO5 AuxAux BO (Auxiliary Output)
8BO3BO3BlankOpen Heat
T602DFH-4,
T602DFH-4+PIR,
T603DFH-4,
T603DFH-4+PIR
(On/Off or
Floating Control)
T604DFH-4,
T604DFH-4+PIR,
T605DFH-4,
T605DFH-4+PIR
(Proportional 0 to
10 VDC Control)
T60xDFH-4 and T60xDFH-4+PIR Series Thermostat Controllers with Dehumidification and Occupancy
4
Sensing Capability Installation Instructions
Figure 5: Wiring the T60xDFH-4 or T60xDFH-4+PIR Series Thermostat Controller
(See Table 1.)
FIG:wrng
Contact
• COC/NH
= Cold Water
• COC/NC
Normally C ool
= Hot Water
Voltage-Free
Contact
• Door
• Remote
Override
• Filter Alarm
• Service Alarm
Voltage-Free
Contact
• Remote NSB
• Motion
• Window
- OR Same 24 VAC
(24 VA C Maximum )
(24 VA C Maximum )
BO5
Aux
BO5
Aux
24 VAC
Thermostat Controller
Power
24 V~
Com
24 V~
Hot
Power and Fan
Power and Fan
BO5
Aux
BO5
Aux
Contacts
• Reheat
• Lighting
• Exhaust Fan
Aux
Aux
Fan
-H
Fan
-M
Fan
-L
24 VAC
Thermostat Controller
24 V~
Com
24 V~
Hot
Fan
-H
Fan
-M
Fan
-L
Three-Pole
Right Top
Connector
Eight-Pole Bottom Connector
BO1/
AO1
UI3
BI1
BI2
Hot
Com
BO4/
AO2
Left Top Connector
1 2 3 4 5
Separate 24 VAC
Power Source for Auxiliary Output
Five-Pole
Fan
Fan-MFan
-H
-L
BO5
Aux
BO5
Aux
BO3
24 V~
24 V~
6 7 8
Power Source for Auxiliary Output
9 10 11 12 13 14 15 16
Independent
• On/Off Actuation
BI1
BO2
Remote Inputs
Scom
BI2UI3
- OR -
Supply S ensor
Changeover Sensor
RS
Scom
Voltage-Free
Normally Heat
Closed Contact
Closed Contact
Power
T60xDFH-4 and T60xDFH-4+PIR Series Thermostat Controllers with Dehumidification and Occupancy
Sensing Capability Installation Instructions
5
Figure 6: Wiring T601DFH-4 Thermostat Controllers for On/Off Control
24 V~
Com
24 V~
Hot
BO2
Two -Pip e Applic ations
Four-Pipe Applications
Com
N.O.
Heating
Valve
24 V~
Hot
BO3
N.C.
Cooling
Valve
Figure 7: Wiring T602DFH-4 and T603DFH-4 Thermostat Controllers for On/Off Control
Two -Pip e Applic ations
Four-Pipe Applications
24 V~
Com
24 V~
Hot
or
Com
Hot
Cooling
Valve
or
Heating
Valve
or
Figure 8: Wiring T602DFH-4 and T603DFH-4 Thermostat Controllers for Floating Control
Two -Pip e Applicat ions
Com
Hot
BO1
Cooling
Valve
Heating
Valve
24 V~
Com
24 V~
Hot
BO1
Heating/Cooling
Valve
BO2
Figure 9: Wiring T604DFH-4 and T605DFH-4 Thermostat Controllers for Proportional Control
Two -Pip e Applic ations
Four-Pipe Applications
F
I
G
:
T
6
0
4
5
d
f
h
3
p
r
p
Heating/Cooling
Valve
Com
Hot
Cooling
Valve
Heating
Valve
24 V~
Com
24 V~
Hot
AO1
24 V~
24 V~
24 V~
c
o
o
3
h
f
d
1
0
6
T
:
G
I
F
c
o
o
3
h
f
d
3
2
0
6
T
:
G
I
F
BO2 BO3
BO4
24 V~
c
f
3
h
f
d
3
2
0
6
T
:
G
I
F
24 V~
Four-Pipe Applications
24 V~
24 V~
AO2
AO1
T60xDFH-4 and T60xDFH-4+PIR Series Thermostat Controllers with Dehumidification and Occupancy
6
Sensing Capability Installation Instructions
Setup and Adjustments
Figure 10: Front Cover of Thermostat Controller (T60xDFH-4+PIR Model Shown)
Thermostat Controller Operation Overview
Thermostat Controller User Interface Keys
The T60x Series Thermostat Controller user interface
consists of five keys on the front cover (as illustrated in
Figure 10). The function of each key is as follows:
•Use the MODE key to toggle among the system
modes available, as defined by selecting the
appropriate operation sequence in the Installer
Configuration Menu (for example, Off, Heat, Cool,
Auto).
Note: If the automatic changeover function (auto
function) is enabled in the sequence of operation
(SeqOpera), then automatic changeover heating
or cooling demand overrides the mode when
MODE = off.
•Use the FAN key to toggle among the fan modes
available, as defined by selecting the appr op ria te
fan menu options defined in the Installer
Configuration Menu (for example, Low, Med, High,
Auto).
•Use the °C/°F key to change the temperature scale
to either Celsius or Fahrenheit and allow access to
the Installer Configuration Menu. See the
Configuring the T60xDFH-4 and
T60xDFH-4+PIR Series Thermostat Controller
section.
•Use the UP/DOWN arrow keys to change the
configuration parameters and to activate a setpoint
adjustment.
Backlit LCD
The T60x Series Thermostat Controllers include a
2-line, 8-character backlit display. Low-level
backlighting is present during normal operation, and it
brightens when any user interface key is pressed. The
backlight returns to low level when the thermostat
controller is left unattended for 45 seconds.
LEDs
Three LEDs are included to indicate the fan status, call
for heat, or call for cooling:
•The fan LED is on when the fan is on.
•The heat LED is on when heating is on.
•The cool LED is on when cooling is on.
Integrated PIR Sensor – T60xDFH-4+PIR
Thermostat Controllers
The integrated PIR sensor allows for automatic
switching between fully adjustable Occupied and
Stand-By temperature setpoints without user
interaction. This feature generates incremental energy
savings during scheduled occupied periods while the
space is unoccupied.
T60xDFH-4 and T60xDFH-4+PIR Series Thermostat Controllers with Dehumidification and Occupancy
Sensing Capability Installation Instructions
7
Status Display Menu
The Status Display Menu is displayed during normal
thermostat controller operation. This menu
continuously scrolls through the following parameters:
•Room Temperature (All Models) and Humidity
(T603DFH-4 and T605DFH-4 Models)
Note: For models with dehumidification capability, the
default setting is no humidity reading on the display
(%RH disp parameter is set to off). The %RH disp
parameter must be set to on to display the current
humidity reading.
•System Mode
•Schedule Status
(Occupied/Unoccupied/Override/Stand-By
[PIR Models])
•Applicable Alarms – The backlight lights up as an
alarm condition is displayed.
Note: An option is available within the Installer
Configuration Menu to lock out the scrolling display and
show only the Room Temperature paramete r.
Dehumidification Operation – T603DFH-4 and
T605DFH-4 Thermostat Controller Models
Dehumidification activates when th e room humidity is
above the adjustable humidity setpoint as sensed by
the integral humidity sensor.
Note: Dehumidification operation functions only in the
Cooling mode; dehumidification operation does not
function in either the Off or the Heating mode.
The minimum deadband between the Heating and
Cooling setpoints is adjustable from 2.0F°/1.0C° to
5.0F°/2.5C°, as defined by the Deadband parameter in
Table 4. If the room temperature resides in the
deadband between the Heating and Cooling setpoints:
•the thermostat controller forces the fan to low
speed
•the chilled water valve opens to the specified
maximum value set by CoolMax
•the thermostat controller stages Heating to
maintain the room temperature at the Cooling
setpoint, as sensed by the thermostat controller
If the room temperature falls below the result of the
formula 1 + Cooling Setpoint – Deadband, then the
thermostat controller disables dehumidification
operation.
If the thermostat controller is in Cooling demand:
•the chilled water valve opens to 100%
•the thermostat controller stages Heating to
maintain the room temperature at the Cooling
setpoint, as sensed by the thermostat controller
If the thermostat controller is in Cooling demand and
the room temperature rises 2F°/1C° above the Cooling
setpoint, the thermostat controller automatically
disables dehumidification operation. Likewise, if the
thermostat controller is in Cooling demand and the
room temperature falls below the current Heating
setpoint, the thermostat controller disables
dehumidification operation.
A T60xDFH-4+PIR Series Thermostat Controller (or a
T60xDFH-4 Series Thermostat Controller equipped
with a PIR accessory cover) provides advanced
occupancy logic.
Note: The PIR strategy is an occupied strategy. If the
thermostat controller is programmed to be Unoccupied ,
the PIR function does not have an effect on the
occupancy strategy.
The thermostat controller automatically switches
occupancy levels from Occupied to Stand-By and
Unoccupied as required, when local movement is
sensed.
Occupancy sensing is enabled only if a PIR cover is
installed on the thermostat controller (PIR models) or if
a remote input is configured as a remote PIR sensor
(MotionNO or MotionNC).
PIR Warm-Up Period
When a PIR cover is used and a thermostat controller
is powered up, there is a 1-minute warm-up period
before any local movement can be detected and
acknowledged by the PIR sensing device. The local
status LEDs for the PIR function are not active, and the
sensor is in Stand-By mode for the 1-minute period.
The PIR functionality and local movement status LEDs
are activated after the 1-minute warm-up period has
elapsed after the initial powering of the thermostat
controller. If movement is present, the mode changes
to Occupied.
PIR Diagnostic LEDs
The diagnostic LEDs inside the PIR lens brighten when
movement is detected within the first 30 minutes after
powerup. The LEDs do not light up or brighten after the
initial 30-minute period.
T60xDFH-4 and T60xDFH-4+PIR Series Thermostat Controllers with Dehumidification and Occupancy
8
Sensing Capability Installation Instructions
Setpoints
St-By Heat
= 69°F
Occ Heat
= 72°F
Occ Cool
= 75°F
St-By Cool
= 78°F
Unocc Heat
= 65°F
Room Temperature
FIG:rm_tmp
Figure 11: Increa sing Room Temperature Setpoints
Figure 12: Unoccupied Timer Set to 6 Hours and Stand-By Timer Set to 2 Hours
The Stand-By setpoints are under the same limitations
and restrictions as the Occupied and Unoccupied
setpoints. Stand-By setpoints reside between the
corresponding Occupied and Unocc up ie d set po in t
values.
The installer must be certain that the difference
between the Stand-By and Occupied values can be
recovered within a timely fashion to ensure occupancy
comfort. In addition, the difference between the two
values must be large enough to warrant maximum
energy savings.
Hotel and lodging applications can benefit from the
addition of an entry door switch wired to one of the
binary inputs of the thermostat controller. When a door
contact is used and configured, the S t and-By timer a nd
its configuration are no longer active or used. The
occupancy toggle between Occupied and Stand-By is
then dictated by both the door contact and the
PIR sensing device used. If movements are detected
by the PIR sensor and the door is closed, the room is
considered occupied. The thermostat controller
switches back to S tan d-By mode only if the door switch
toggles open/closed. Motion is ignored when the door
switch indicates an open door.
PIR occupancy functionality is dictated by both the
Stand-By timer and Unoccupied timer configuration
value and movements present in the area.
Unoccupied Timer Disable
It might be preferable for the local area to stay out of
Unoccupied mode and always stay at the Stand-By
occupancy level when no activity is present. In
instances when areas always need to be on Stand-By
status, ready to respond to demand at any given point
in time, we recommend disabling the Unoccupied
timer. When the loca l PIR occupancy routine is ru nning
at the thermostat controller, the zone drifts into
Unoccupied mode when the Unoccupied timer is set
above its factory default value of 0.0 hours.
T60xDFH-4 and T60xDFH-4+PIR Series Thermostat Controllers with Dehumidification and Occupancy
Sensing Capability Installation Instructions
9
When the local PIR occupancy routine is running at the
Figure 13: Unoccupied Timer Set to 0 Hours and Stand-By Timer Set to 2 Hours
thermostat controller, the zone never drifts into
Unoccupied mode when the Unoccupied timer is set to
its factory default value of 0.0 hours.
Refer to the T60xDFH-4 and T60xDFH- 4+ PIR Ser ies
Thermostat Controllers with Dehumidification and
Occupancy Sensing Capability Application Note
(LIT-12011569) for additional application scenarios
using various combinations of occupancy levels and
door switches.
Configuring the T60xDFH-4 and
T60xDFH-4+PIR Series Thermostat Controller
The T60x Series Thermostat Controller comes from the
factory with default settings for all configurable
parameters. The default settings are shown in Table 4.
To reconfigure the parameters via the thermostat
controller, follow the steps in this section.
1. To access the Installer Configuration Menu, press
and hold the center key for approximately
8 seconds.
Note: If the Password parameter is configured,
Password 0 appears on the thermostat controller
display indicating that the configured password is
required to proceed. Use the UP/DOWN arrow keys to
indicate the configured password, then press the
MODE key to proceed through the Installer
Configuration Menu parameters.
2. Once the Installer Configuration Menu begins,
press and release the center key to scroll through
the parameters listed in Table 4.
3. When the desired parameter is displayed, use the
UP/DOWN arrow keys to choose the desired
selection option.
4. Press and release the center key to continue
scrolling through the parameters.
Note: Pressing the FAN key during configuration
restarts the list of displayed parameters at the first
parameter listed in Table 4.
When the thermostat controller is in the Installer
Configuration Menu and left unattended for
approximately 8 seconds, the thermostat controller
reverts to the Status Display Menu.
Configuring Inputs BI1, BI2, and UI3
When BI1 and BI2 are configured for an alarm
condition, an alarm condition is displayed locally when
the input is closed. An alarm message is included on
the scrolling Status Display Menu and when the
message is displayed, the backlight momentarily
lights up.
The UI3 input provides changeover of hot/cold water
switching or supply air temperature monitoring at the
thermostat controller.
Each input can be configured to the selection options
included in Table 4.
Configuring the Sequence of Operation
(SeqOpera)
Choose the appropriate sequence of operation using
Table 2 or Table 3. The modes presented are userdependent on the sequence of operation selected. For
two-pipe applications using a changeover sensor,
choose the selection option (0): Cooling Only.
Changeover occurs between Cooling Only and
Heating Only. See Figure 14 through Figure 19 for
sequence of operation examples.
T60xDFH-4 and T60xDFH-4+PIR Series Thermostat Controllers with Dehumidification and Occupancy
10
Sensing Capability Installation Instructions
Table 2: Selection Options for Sequence of Operation in Two-Pipe Applications
Selection
Option
(0): Cooling OnlySee Figure 14.10: Normally Open
(1): Heating OnlySee Figure 15.10: N.O. Heating
(2): Cooling and ReheatSee Figure 16.6 and 7: Reheat
(3): Heating and ReheatSee Figure 17.6 and 7: Reheat
Control
Curve
Terminal Numbers Used (See Table 1 and Figure 5.)
On/Off ControlFloating ControlProportional
(N.O.) Cooling
11: Normally Closed
(N.C.) Cooling
11: N.C. Heating
10: N.O. Cooling
11: N.C. Cooling
10: N.O. Heating
11: N.C. Heating
10: Open Cooling
11: Closed Cooling
10: Open Heating
11: Closed Heating
6 and 7: Reheat
10: Open Cooling
11: Closed Cooling
6 and 7: Reheat
10: Open Heating
11: Closed Heating
Table 3: Selection Options for Sequence of Operation in Four-Pipe Applications
Selection
Option
(0): Cooling OnlySee Figure 14.10: N.O. Cooling
(1): Heating OnlySee Figure 15.8: N.O. Heating
(2): Cooling and ReheatSee Figure 16.6 and 7: Reheat
(3): Heating and ReheatSee Figure 17.6 and 7: Reheat
6 and 7: Reheat
10: Open Cooling
11: Closed Cooling
6 and 7: Reheat
8: Open Heating
9: Closed Heating
8: Open Heating
9: Closed Heating
10: Open Cooling
11: Closed Cooling
6 and 7: Reheat
8: Open Heating
9: Closed Heating
10: Open Cooling
11: Closed Cooling
0to10VDC Control
10: Proportional Cooling
10: Proportional Heating
6 and 7: Reheat
10: Proportional Cooling
6 and 7: Reheat
10: Proportional Heating
0to10VDC Control
10: Proportional Cooling
9: Proportional Heating
6 and 7: Reheat
10: Proportional Cooling
6 and 7: Reheat
9: Proportional Heating
9: Proportional Heating
10: Proportional Cooling
6 and 7: Reheat
9: Proportional Heating
10: Proportional Cooling
T60xDFH-4 and T60xDFH-4+PIR Series Thermostat Controllers with Dehumidification and Occupancy
Sensing Capability Installation Instructions
11
Device Closed
Cooling Setpoint
Device Opened
On/Off, Floating,
or Propor t ional
Output
F
I
G
:
c
l
n
g
_
n
l
y
Figure 14: Cooling Only,
Two- or Four-Pipe Applications
Device Closed
Device Opened
On/Off, Floating,
or Propor t ional
Output
F
I
G
:
h
t
n
g
_
n
l
y
Figure 15: Heating Only,
Two- or Four-Pipe Applications
Figure 16: Cooling with Reheat,
Two- or Four-Pipe Applications
Heating Setpoint
Closed
Cooling Setpoint
Device
Opened
F
I
G
:
c
l
n
g
_
w
t
h
_
r
h
t
Deadband
Reheat
Outputs
Cooling Output
Off
Off
On
On
F
I
G
:
h
t
g
_
w
t
h
_
Reheat
On/Off, Floating,
or Propor t io nal
Output
Off
Off
On
Figure 17: Heating with Reheat,
Two- or Four-Pipe Applications
Figure 18: Heating/Cooling,
Four-Pipe Applications
Heating Setpoint
Closed
Cooling Setpoint
Device
Opened
F
I
G
:
h
t
n
g
_
c
l
n
g
Deadband
Cooling Output
Device
Closed
Device
Opened
On/Off, Floating, or
Proport ional Outputs
Tempe r at ur e Increase
(Increments of 1F°/0.5C°)
Heating Setpoint
Temperature Increase
(Increments of 1F°/0.5C°)
On
Temperature Increase
(Increments of 1F°/0.5C°)
Heating Output
100%
0%
t
h
r
12
Heating Output
Device
Temperature Increase
(Increments of 1F°/0.5C°)
On/Off, Floating,
Device
or Propor tional
Temperature Increase
(Increments of 1F°/0.5C°)
T60xDFH-4 and T60xDFH-4+PIR Series Thermostat Controllers with Dehumidification and Occupancy
Sensing Capability Installation Instructions
Figure 19: Heating/Cooling with Reheat,
Four-Pipe Applications
Heating Setpoint
Device
Closed
Device
Closed
Device
Opened
Cooling Setpoint
Device
Opened
F
I
G
:
h
t
n
g
_
c
l
n
g
_
r
h
t
Deadband
Reheat
Output
On/Off, Floating,
or Propor t ional
Outputs
Heatin g O ut put
Cooling Output
Off
Off
On
On
Figure 20: Low-Med-High-Auto and Low-High-Auto Fan Operation
Temperature Deviation from Setpoint, °F
2.0F°/1. 0C° to
5.0F°/2.5C°
Deadband
100%
0%
2.5
2.5
2.02.0
1.5
1.50.50.5
Heating
Valve
Cooling
Valve
On
On
On
On
Off
Off
Off
Off
Low
Medium
between the
heating and
cooling se t points
if the
parameter is
set to .
Auto Fan
AS AD
Setpoint
High
FIG:fn_opr tn
Fan
Speed
Heating
Setpoint
Tempe r at ur e Increase
(Increments of 1F°/0.5C°)
Configuring Automatic Fan Speed
Use the Fan Menu parameter in the Installer
Configuration Menu to set the available fan mode
options. Use the FAN key to select the desired fan
mode option.
When selection option (2): Low-Med-High-Auto is
chosen in the Fan Menu parameter, the fan operates
as shown in Figure 20. When selection option
(3): Low-High-Auto is chosen in the Fan Menu
parameter, the fan operates at only the low and high
settings and ignores the medium setting (Figure 20).
This operation applies to the Occupied mode when the
fan is set to Auto.
Cooling
The fan is of f
T60xDFH-4 and T60xDFH-4+PIR Series Thermostat Controllers with Dehumidification and Occupancy
Sensing Capability Installation Instructions
13
Table 4: Installer Configuration Menu (Part 1 of 7)
Parameter
Description and DefaultSelection Options
Appearing
on Display
PswrdSets the protective access
password to prevent unauthorized
access to the Installer Configuration
Menu.
Default: 0
Note: The default setting does not
lock out access to the Installer
Configuration Menu.
BI1Configuration of Binary Input 1.
Default: None
Range: 0 to 1,000
(None): No function is associated with an input.
(Rem NSB): Remote Night Setback (NSB) via a time clock input, an
occupancy sensor, or from a voltage-free contact.
Contact open = Occupied; contact closed = Unoccupied.
(MotionNO*): Temporary occupancy request via a motion detector
input. Contact open = Unoccupied. When the contact closes, the
thermostat controller goes into the Occupied mode for a specified
TOccTime. Once the TOccTime begins, the thermostat controller
remains in the Occupied mode if the contact is open, until the
TOccTime expires. Advanced PIR occupancy functions using a
Normally Open (N.O.) or Normally Closed (N.C.) remote PIR motion
sensor.
(MotionNC*): Temporary occupancy request via a motion detector
input. Contact closed = Unoccupied. When the contact opens, the
thermostat controller goes into the Occupied mode for a specified
TOccTime. Once the TOccTime begins, the thermostat controller
remains in the Occupied mode if the contact is closed, until the
TOccTime expires. Advanced PIR occupancy functions using a
Normally Open (N.O.) or Normally Closed (N.C.) remote PIR motion
sensor.
(Window): Cancels the thermostat controller heating or cooling
action when a window is open. The fan operation is only affected if
the Fan Menu parameter is set to (4): On-Auto, and Auto is the
selected fan mode. A Window alarm is displayed indicating that the
window needs to be closed to resume heating or cooling. The
heating and/or cooling outputs are enabled only when the contact is
closed.
* These settings disable any local override function. For PIR
models, see the Occupancy Sensor Operation – T60xDFH-4+PIR Thermostat Controllers section.
T60xDFH-4 and T60xDFH-4+PIR Series Thermostat Controllers with Dehumidification and Occupancy
14
Sensing Capability Installation Instructions
Table 4: Installer Configuration Menu (Part 2 of 7)
Parameter
Description and DefaultSelection Options
Appearing
on Display
BI2Configuration of Binary Input 2.
Default: None
UI3Configuration of Universal Input 3.
Default: None
MenuScroGives the option of having the
AutoModeEnables the auto function to be
%RH dispDisplays the current humidity
display continuously scroll the
parameters.
Default: on
visible within the MODE key menu.
(The
MODE key is the key at the far
left of the thermostat controller
cover.)
Default: off
reading (T603 and T605 models).
Default: off
(None): No function is associated with an input.
(Door Dry): Door contact only has an effect if BI1 is set to
MotionNO or MotionNC or if a PIR accessory cover is used. (See
the BI1 parameter earlier in this table.) The occupancy is now
dictated via BI1, BI2, or PIR. Any motion detected sets the zone to
Occupied status. The thermostat controller remains in the Occupied
mode until the door contact switch opens momentarily, at which
point the thermostat controller goes into Stand-By mode. If more
movements are detected, the Occupied mode resumes. While the
door is open, any movements detected by the PIR sensor are
ignored. Use a Normally Closed (N.C.) switching device. (Contact
open = door open; contact closed = door closed.)
(RemOVR): Temporary occupancy request via a remote input. This
override function is controlled by a manual remote occupancy
override. When enabled, this condition disables the override
capability of the thermostat controller.
(Filter): A Filter alarm is displayed. This alarm can be connected to
a differential pressure switch that monitors a filter.
(Service): A Service alarm is displayed on the thermostat controller
when the input is energized. This input can be tied into the air
conditioning unit control card, which provides an alarm should there
be a malfunction.
(None): No function is associated with an input.
(COC/NH): Changeover Contact/Normally Heat: A dry contact input
is used to signal seasonal hot/cold water changeover. The contact
closes when cold water is present. Valid only for two-pipe systems.
(COC/NC): Changeover Contact/Normally Cool: A dry contact input
is used to signal seasonal hot/cold water changeover. The contact
closes when hot water is present. Valid only for two-pipe systems.
(COS): Changeover Analog Sensor: Used for hot/cold water
changeover switching. Valid only for two-pipe systems. (Parameter
Pipe No is set to 2.0.) If the water temperature is greater than 75°F/
24°C, hot water is present. If the water temperature is less than
75°F/24°C, cold water is present.
Note: Choose the selection option (0): Cooling Only for the
SeqOpera parameter to allow changeover to occur between
Cooling Only and Heating Only. The changeover sensor does not operate in Cooling and Reheat, Heating and Reheat, or Cool/
Heat Four-Pipe and Reheat applications.
(SS): Supply Air Sensor Monitoring
(off): The scroll is inactive.
(on): The scroll is active.
(on): The auto function is active (Off-Auto-Heat-Cool). Provides
automatic changeover between heating and cooling.
(off): The auto function is inactive (Off-Heat-Cool).
(on): Displays the current humidity reading in % RH.
(off): Does not display the current humidity reading.
T60xDFH-4 and T60xDFH-4+PIR Series Thermostat Controllers with Dehumidification and Occupancy
Sensing Capability Installation Instructions
15
Table 4: Installer Configuration Menu (Part 3 of 7)
Parameter
Description and DefaultSelection Options
Appearing
on Display
LockoutSelectable Lockout Levels for
limiting end-user keypad interaction.
Default: 0
Pipe NoSelectable number of pipes in the
system.
Default: 4.0 Pipes
CntrlTypDefines the control output for the
type of valves used in the
installation (T602 and T603
models).
Default: FloatingSeqOperaDetermines the sequence of
operation.
Default: 1
Fan MenuSets the fan mode options.
Default: 4
Lockout
Level
(2.0 Pipes): Limits the number of sequences of operation available
from 0 to 3, and enables heat/cool operation from the same output.
(4.0 Pipes): Allows access to all sequences of operation from 0 to 5,
and enables heat/cool operation from different outputs.
(On/Off): For Normally Open (N.O.) or Normally Closed (N.C.)
24 VAC two-position valves.
(Floating): For three-wire control of 24 VAC floating valves.
Sequence of OperationDefault Based on
(0): Cooling Only (Off-Cool)CoolCool
(1): Heating Only (Off-Heat)HeatHeat
(2): Cooling and Reheat (Off-Auto*-
Heat-Cool)
(3): Heating and Reheat (Off-Heat)HeatHeat
(4):Cool/Heat Four-Pipe (Off-Auto*-
Heat-Cool)
(5): Cool/Heat Four-Pipe and Reheat
(Off-Auto*-Heat-Cool)
* Auto can be disabled with the AutoMode param eter.
Note: Choose the selection option (0): Cooling Only when using a
changeover sensor to allow changeover to occur between Cooling
Only and Heating Only.
Note: Default parameter settings are always equal to off when the
mode is equal to off.
(0): Low-Med-High: Three-speed configuration using three fan
relays (L-M-H). The default is High.(1): Low-High: Two-speed configuration using two fan relays (L-H).
The default is High.(2): Low-Med-High-Auto: Three-speed configuration with Auto Fan
speed mode using three fan relays (L-M-H). The default is High.(3): Low-High-Auto: Two-speed configuration with Auto Fan speed
mode using two fan relays (L-H). The default is High.(4): On-Auto: One-speed configuration, (H) Auto is for Fan on
demand and On is for Fan on all the time. The default is Auto.
T60xDFH-4 and T60xDFH-4+PIR Series Thermostat Controllers with Dehumidification and Occupancy
16
Sensing Capability Installation Instructions
Table 4: Installer Configuration Menu (Part 4 of 7)
Parameter
Description and DefaultSelection Options
Appearing
on Display
DHumiLCKLocks out the dehumidification
capability (T603 and T605 models).
Default: on
%RH set
DehuHyst
DehuCool
St-By TMSets the Stand-By timer value
Unocc TMSets the Unoccupied timer value
St-By HTSets the Stand-By heating setpoint
St-By CLSets the Stand-By cooling setpoint
1
Sets the dehumidification setpoints
(T603 and T605 models). This
parameter can be used only if the
dehumidification sequence is
enabled.
Default: 50.0% RH
1
Sets the dehumidification hysteresis
(T603 and T605 models). This
parameter can be used only if the
dehumidification sequence is
enabled.
Default: 5.0% RH
1
Sets the maximum dehumidification
cooling output (T603 and T605
models). This parameter can be
used only if the dehumidification
sequence is enabled.
Default: 100%
(PIR models).
Default: 0.5 hours
(PIR models).
Default: 0.0 hours
(PIR models).
Default: 69.0°F/20.5°C
(PIR models).
Default: 78.0°F/25.5°C
(off): Dehumidification is locked out.
(on): Dehumidification is allowed.
Range: 30.0 to 95.0% RH
Range: 2.0 to 20.0% RH
Range: 20.0 to 100.0%Note: This parameter can be used to balance smaller reheat loads
installed with regard to the capacity of the cooling coil.
Time delay between the moment the PIR cover detected the last
movement in the area and the time at which the thermostat
controller Stand-By mode and setpoints become active.
Range: 0.5 to 24.0 hrs adjustable in 0.5-hour increments
Time delay between the moment the thermostat controller toggled to
Stand-By mode and the time at which the thermostat controller
Unoccupied mode and setpoints become active. Setting this
parameter to the factory value (0.0 hours) disables the Unoccupied
timer. This prevents the thermostat controller from switching from
Stand-By mode to Unoccupied mode when PIR functions are used.
Range: 0.0 to 24.0hrs adjustable in 0.5-hour increments
The value of this parameter should reside between the Occupied
and Unoccupied heating setpoints, and ensure that the difference
between the Stand-By and Occupied value can be recovered in a
timely fashion when movement is detected in the zone.
Range: 40.0°F/4.5°C to 90.0°F/32.0°C
The value of this parameter should reside between the Occupied
and Unoccupied cooling setpoints, and ensure that the difference
between the Stand-By and Occupied value can be recovered in a
timely fashion when movement is detected in the zone.
Range: 54.0°F/12.0°C to 100.0°F/37.5°C
T60xDFH-4 and T60xDFH-4+PIR Series Thermostat Controllers with Dehumidification and Occupancy
Sensing Capability Installation Instructions
17
Table 4: Installer Configuration Menu (Part 5 of 7)
Parameter
Description and DefaultSelection Options
Appearing
on Display
Unocc HTSets the Unoccupied heating
setpoint value.
Default: 62.0°F/16.5°CUnocc CLSets the Unoccupied cooling
setpoint value.
Default: 80.0°F/26.5°CHeat maxSets the Occupied and Unoccupied
maximum heating setpoint values.
Default: 90.0°F/32.0°CCool minSets the Occupied and Unoccupied
minimum cooling setpoint values.
Default: 54.0°F/12.0°CPbandSets the proportional band used by
the thermostat controller
Proportional-Integral (PI) control
loop.
Default: 3.0F°/1.7C°
Note: The proportional band
default setting of 3.0F°/1.7C°
provides satisfactory thermostat
controller operation in most
instances. A proportional band
setting other than the default is
normally used in installations where
the location of the thermostat
controller is problematic, leading to
unwanted cycling. An example of a
problematic installation is a wall-
mounted thermostat controller
installed between the return and
supply air feeds, that is directly
influenced by the supply air stream.
Set typeProvides the option of temporarily
changing the heating or cooling
setpoint by pressing the UP/DOWN
arrow keys.
Default: permnentSpt FuncDetermines the operation and
(temporar): Local changes to the heating or cooling setpoints are
temporary, and remain effective for the specified TOccTime.
(permnent): Local changes to the heating or cooling setpoints are
permanently stored in the thermostat memory.
(Attch Stp):
setpoint is the setpoint from the last action taken by the thermostat
controller, or the setpoint currently in use. Both the heating and
cooling setpoints are changed simultaneously, while respecting the
minimum configured deadband. If one setpoint is desired over the
other, use the MODE key to toggle between the two setpoints.
(Dual Stp): Dual Occupied Setpoint Adjustment. The displayed
setpoint is the setpoint from the last action taken by the thermostat
controller, or the setpoint currently in use. The heating and cooling
setpoints can be separated individually, allowing the minimum
configured deadband to expand. If one setpoint is desired over the
other, use the MODE key to toggle between the two setpoints.
Note: When adjusting the
temperature, press the UP/DOWN arrow keys to
change the temperature in
0.5F°/0.5C° increments;
press and hold the
UP/DOWN arrow keys
to change the temperature
in 5.0F°/5.0C° increments.
Single Occupied Setpoint Adjustment. The displayed
T60xDFH-4 and T60xDFH-4+PIR Series Thermostat Controllers with Dehumidification and Occupancy
18
Sensing Capability Installation Instructions
Table 4: Installer Configuration Menu (Part 6 of 7)
Parameter
Description and DefaultSelection Options
Appearing
on Display
TOccTimeSets the duration of the Temporary
Occupancy Time when the heating
or cooling setpoints in the Occupied
mode are established by:
• an override function enabled
from a remote override (when
the thermostat controller is in the
Unoccupied mode)
• a temporary heating or cooling
setpoint
Default: 2.0 hrs
DeadbandSets the minimum deadband
between the heating and cooling
setpoints.
Default: 2.0F°/1.0C°
Cal RSSets the desired room air
temperature sensor calibration
(offset). The offset can be added to
or subtracted from the actual
displayed room temperature.
Default: 0.0F°/0.0C°
Cal RHSets the desired humidity sensor
calibration (offset). The offset can
be added to or subtracted from the
actual displayed room humidity
(T603 and T605 models). This
parameter can be used only if the
dehumidification sequence is
enabled.
Default: 0.0% RH
Aux contDetermines the auxiliary contact
function and configuration.
Default: 0
Range: 0.0 to 24.0 hrs adjustable in 1-hour increments
Range: 2.0F°/1.0C° to 5.0F°/2.5C° adjustable in 1.0F°/0.5C°
increments
Range: -5.0F°/-2.5C° to 5.0F°/2.5C° adjustable in 1.0F°/0.5C°
increments
Range: -15.0% RH to 15.0% RH adjustable in 1% RH increments
Note: The contact toggles with the Occupied/Unoccupied schedule
of the NSB contact on BI1, if used.
(0)Not used,
or used for
reheat
(1)Auxiliary
N.O.
(2)Auxiliary
N.C.
(3)Auxiliary
N.O.
(4)Auxiliary
N.C.
If the sequence of operation is set to
reheat (2, 3, or 5), ignore this parameter.
Occupied = contact
closed
Unoccupied = contact
open
Occupied = contact open
Unoccupied = contact
closed
Occupied and fan On =
contact closed
Unoccupied and fan On
or Off = contact open
Occupied and fan On =
contact open
Unoccupied and fan On
or Off = contact closed
The output
aligns with
occupancy.
The output
aligns with
occupancy
and the
fan on
command.
T60xDFH-4 and T60xDFH-4+PIR Series Thermostat Controllers with Dehumidification and Occupancy
Sensing Capability Installation Instructions
19
Table 4: Installer Configuration Menu (Part 7 of 7)
Parameter
Description and DefaultSelection Options
Appearing
on Display
Auto FanAffects the auto mode of operation
for the following Fan Menu
parameter selection options only:
• (2): Low-Med-High-Auto
• (3): Low-High-Auto
Default: AS
FL timeSets the maximum actuator stroke
timing (floating CntrlTyp T602 and
T603 models).
Default: 1.5 minCphSets the maximum number of cycles
per hour (T601 and on/off CntrlTyp
T602 and T603 models).
Default: 4.0RA/DAChoice of reverse or direct acting
analog output signal (T604 and
T605 models)
Default: DAReheatSets the duty cycle time for reheat
output (if Option 2, 3, or 5 is chosen
in the SeqOpera parameter).
Default: 0
UI3 disDisplays the supply or changeover
temperature when UI3 is configured
as an analog input (supply sensor or
changeover sensor).
Default: -40°F/-40°C
(AS AD): The fan is on Auto during occupied periods. The Med and
High speeds operate automatically on a temperature error from the
setpoint. The Low speed operates Auto on demand. When there is
no demand, the Low speed shuts down. The Low speed is only reactivated when there is a heating or cooling demand.
(AS): The fan is always on during occupied periods. The fan is on
Auto during unoccupied periods. The Low, Med, and High speeds
operate automatically on a temperature error from the setpoint.
Range: 0.5 to 9.0 min adjustable in 0.5-minute increments
Range: 3.0 to 8.0 cycles per hour
(RA): Reverse acting, 0 to 100% = 10 to 0 VDC
(DA): Direct acting, 0 to 100% = 0 to 10 VDC
(1): 10 seconds (six cycles per minute), for various equipment with
solid-state relays that withstand short duty cycles such as electric
heat.
(0): 15 minutes (four cycles per hour), for various equipment with
mechanical relays or contactors controlling mechanical reheat
systems.
Used as a diagnostic/service help, to troubleshoot and diagnose
sensor operation.
1.When adjusting the numeric value, press the UP/DOWN arrow key to change the value by single increments; press and
hold the UP/DOWN arrow key to change the numeric value in increments of ten.
Accessories
All the accessories in Table 5 include mounting
hardware; contact the nearest Johnson Controls®
representative to order any of these parts.
Note: Review the technical specifications of the
accessories prior to their use in an application.
T60xDFH-4 and T60xDFH-4+PIR Series Thermostat Controllers with Dehumidification and Occupancy
20
Repair Information
If the T60xDFH-4 or T60xDFH-4+PIR Series
Thermostat Controller fails to operate within its
specifications, replace the unit. For a replacement
thermostat controller, contact the nearest
Johnson Controls representative.
Sensing Capability Installation Instructions
Table 5: Accessories (Order Separately)
Code NumberDescription
SEN-600-1Remote Inside Air Temperature Sensor
1
TE-6361M-1
TE-636S-1
TEC-6H-PIR
1.Additional TE-636xx-x Series 10k ohm Johnson Controls Type II Thermistor Sensors are available; refer to the
TE-6300 Series Temperature Sensors Product Bulletin (LIT-216320) for more details.
2.The TEC-6H-PIR Accessory Cover can be used to replace the existing cover on a non-PIR T60xDFH-4 Series Thermostat
Controller to provide occupancy sensing capability.
1
Duct Mount Air Temperature Sensor
Strap-Mount Temperature Sensor
2
Cover with Occupancy Sensor
Table 6: Display Messages
DisplayFunction
ServiceIndicates that there is a service alarm in accordance with the programmable Binary Input (BI2).
FilterIndicates that the filter(s) is dirty in accordance with the programmable Binary Input (BI2).
WindowIndicates that an outside window or door is open and has cancelled the thermostat controller heating
or cooling action in accordance with the programmable Binary Input (BI1).
Technical Specifications
T60xDFH-4 and T60xDFH-4+PIR Series Thermostat Controllers with Dehumidification and
Occupancy Sensing Capability (Part 1 of 2)
Power Requirements19 to 30 VAC, 50/60 Hz, 2 VA (Terminals 4 and 5) at 24 VAC Nominal, Class 2 or
Safety Extra-Low Voltage (SELV)
Relay/Triac
Contact
Rating
Analog
Output Rating
Fan Relay Output Rating19 to 30 VAC, 1.0 A Maximum, 3.0 A Inrush
Auxiliary
Output Rating
Digital Input sVoltage-Free Contacts across Terminal Scom to Terminals BI1, BI2, or UI3
Analog InputsResistive Inputs (RS and UI3) for 10k ohm Johnson Controls Type II Negative
Temperature Sensor TypeLocal 10k ohm John son Controls Type II NTC Thermistor Sensor
Wire Size18 AWG (1.0 mm Diameter) Maximum, 22 AWG (0.6 mm Diameter) Recommended
Temperature
Range
AccuracyTemperature±0.9F°/±0.5C° at 70.0°F/21.0°C Typical Calibrated
Minimum Deadband2F°/1C° between Heating and Cooling
Ambient
Conditions
On/Off and
Floating
Control
Proportional
Control
Triac Output19 to 30 VAC, 1.0 A Maximum, 3.0 A Inrush
Backlit Display-40.0°F/-40.0°C to 122.0°F/50.0°C in 0.5° Increments
Heating Control 40.0 °F/4.5°C to 90.0°F/32.0°C
Cooling
Control
Humidity±5% RH from 20 to 80% RH at 50 to 90°F (10 to 32°C)
Operating32 to 122°F (0 to 50°C); 95% RH Maximum, Noncondensing
Storage-22 to 122°F (-30 to 50°C); 95% RH Maximum, Noncondensing
30 VAC, 1.0 A Maximum, 15 mA Minimum, 3.0 A Inrush, Class 2 or SELV
0 to 10 VDC into 2k ohm Resistance (Minimum)
Temperature Coefficient (NTC) Thermistor Sensors
54.0°F/12.0°C to 100.0°F/38.0°C
T60xDFH-4 and T60xDFH-4+PIR Series Thermostat Controllers with Dehumidification and Occupancy
Sensing Capability Installation Instructions
21
Metasys® and Johnson Controls® are registered trademarks of Johnson Controls, Inc.
EuropeCE Mark - Johnson Controls, Inc., declares that this product is in compliance
Australia and
New Zealand
Shipping
Weight
The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these
specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or
misuse of its products.
T60xDFH-4
Models
T60xDFH-4+PIR
Models
Under UL 873, Temperature Indicating and Regulating Equipment
FCC Compliant to CFR 47, Part 15, Subpart B, Class A
Under CAN/CSA C22.2 No. 24, Temperature Indicating and Regulating Equipment
Industry Canada, ICES-003
with the essential requirements and other relevant provisions of the
EMC Directive 2004/108/EC.
C-Tick Mark, Australia/NZ Emissions Compliant
0.75 lb (0.34 kg)
0.77 lb (0.35 kg)
T60xDFH-4 and T60xDFH-4+PIR Series Thermostat Controllers with Dehumidification and Occupancy
22
Sensing Capability Installation Instructions
Published in U.S.A.www.johnsoncontrols.com
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.