Johnson Controls T60xDFH-4 Series, T60xDFH-4+PIR Series Installation Guide

T60xDFH-4 and T60xDFH-4+PIR Series Thermostat Controllers with Dehumidification and Occupancy Sensing Capability
Installation Instructions
T601DFH-4, T602DFH-4, T603DFH-4, T604DFH-4, T605DFH-4, T601DFH-4+PIR, T602DFH-4+PIR, T603DFH-4+PIR, T604DFH-4+PIR, T605DFH-4+PIR
Refer to the QuickLIT Web site for the most up-to-date version of this document.
Part No. 24-9890-951, Rev. A
Issued August 17, 2011
Supersedes October 15, 2009

Applications

The T60xDFH-4 and T60xDFH-4+PIR Series Thermostat Controllers provide control of two- or four-pipe fan coils, cabinet unit heaters, or other equipment. These thermostat controllers provide on/off, floating, or proportional 0 to 10 VDC control outputs; three speeds of fan control; and dehumidification capability. The T60xDFH-4+PIR Series Thermostat Controllers have occupancy sensing capability built into the device. These are stand-alone devices that maximize up to 30% energy savings in high-energy usage light commercial buildings, such as schools and hotels, during occupied times by using additional Stand-By setpoints. See the
Occupancy Sensor Operation – T60xDFH-4+PIR Thermostat Controllers section for more information.
The non-programmable T60x Series Thermostat Controllers provide the user access to parameters such as system mode, fan mode, and temperature setpoints. Additionally, the T60x Series has over 20 configurable parameters enabling the thermostat controllers to adapt to a variety of applications.
All T60x Series Thermostat Controllers use an intuitive, plain text, menu-driven backlit display that makes setup and operation quick and easy. The T60x Series also employ a unique, Proportional-Integral (PI) time-proportioning algorithm that virtually eliminates temperature offset associated with traditional, differential-based thermostat controllers.
IMPORTANT: The T60xDFH-4 and T60xDFH-4+PIR Series Thermostat Controllers are intended to provide an input to equipment under normal operating conditions. Where failure or malfunction of the thermostat controller could lead to personal injury or property damage to the controlled equipment or other property, additional precautions must be designed into the control system. Incorporate and maintain other devices, such as supervisory or alarm systems or safety or limit controls, intended to warn of or protect against failure or malfunction of the thermostat controller.

North American Emissions Compliance

United States

This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when this equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference, in which case the user will be required to correct the interference at his/her own expense.

Canada

This Class (A) digital apparatus meets all the requirements of the Canadian Interference-Causing Equipment Regulations.
Cet appareil numérique de la Classe (A) respecte toutes les exigences du Règlement sur le matériel brouilleur du Canada.

Installation

Location Considerations

Locate the T60x Series Thermostat Controller:
on a partitioning wall, approximately 5 ft (1.5 m) above the floor in a location of average temperature
away from direct sunlight, radiant heat, outside walls, outside doors, air discharge grills, or stairwells; and from behind doors
away from steam or water pipes, warm air stacks, unconditioned areas (not heated or cooled), or sources of electrical interference
For integrated Passive Infrared (PIR) models, be sure that the thermostat controller is located centrally , wh ere occupant movement is abundant.
T60xDFH-4 and T60xDFH-4+PIR Series Thermostat Controllers with Dehumidification
and Occupancy Sensing Capability Installation Instructions
1
Note: Allow for vertical air circulation to the thermostat
Figure 1: Removing the
Thermostat Controller Cover
(T60xDFH-4+PIR Model Shown)
FIG:cvr_ rmvl
Figure 2: Opening the
Thermostat Controller PCB
F
I
G
:
p
r
c
r
c
t
b
r
d
Tabs
Figure 3: Securing the Thermostat Controller
Mounting Base to the Wall
F
I
G
:
m
n
t
b
controller. To install the thermostat controller:
1. Use a Phillips-head screwdriver to remove the security screw if it is installed on the bottom of the thermostat controller cover.
Note: Be sure to position the thermostat controller mounting base so that the arrow on the base points upward to indicate the top of the thermostat controller.
Note: Normally, the security screw comes packaged separately in a plastic bag with the thermostat controller. Skip this step if the screw is not installed on the bottom of the cover.
2. Pull the bottom edge of the thermostat controller cover and open the thermostat controller as illustrated in Figure 1.
Note: PIR models have a wiring connection between the cover and the Printed Circuit Board (PCB). This connection allows for proper wiring of the occupancy sensor. Carefully remove the wiring connection from the PCB by pulling up on the connector block. Do not attempt to remove the connector block by pulling on the wires.
PCB Locking
6. Drill a 3/16 in. (5 mm) hole at each of the two marked locations and tap nylon anchors (included with the thermostat controller) flush to the wall surface.
Note: Other means of anchoring the device may be desired, depending on the wall medium.
7. Position the thermostat controller mounting base on the wall and use the two mounting screws (included with the thermostat controller) to secure the base to the wall surface as illustrated in Figure 3.
3. Carefully pull the locking tabs on the right side of the thermostat controller mounting base and unlock the PCB. Open the PCB to the left as illustrated in Figure 2.
4. Pull approximately 6 in. (152 mm) of wire from the wall and insert the wire through the hole in the thermostat controller mounting base.
5. Align the thermostat controller mounting base on the wall and use the base as a template to mark the two mounting hole locations.
Note: Be careful not to overtighten the mounting screws.
s
8. Swing the PCB back to the right and carefully snap it into the locking tabs on the thermostat controller mounting base.
T60xDFH-4 and T60xDFH-4+PIR Series Thermostat Controllers with Dehumidification and Occupancy
2
Sensing Capability Installation Instructions
9. Remove the screw terminal blocks that are
!
Figure 4: Removing the Screw Terminal Blocks
!
attached to a disposable adhesive. Figure 4 illustrates the locations of the screw terminal blocks on the thermostat controller.
s k
c
l
b
_
l
n m
r
t
: G
I F

Wiring

When an existing thermostat controller is replaced, remove and label the wires to identify the terminal functions. When a T60x Series Thermostat Controller is replaced, simply remove the old screw terminal blocks and reinsert them onto the PCB of the replacement thermostat controller.
CAUTION: Risk of Property Damage.
Do not apply power to the system before checking all wiring connections. Short circuited or improperly connected wires may result in permanent damage to the equipment.
IMPORTANT: Make all wiring connections in accordance with local, national, and regional regulations. Do not exceed the electrical ratings of the T60x Series Thermostat Controller.
To wire the thermostat controller:
1. Strip the ends of each wire a 1/4 in. (6 mm) and connect them to the appropriate screw terminals as indicated in Table 1 and Figure 5 through Figure 9.
2. Carefully push any excess wire back into the wall.
Note: Seal the hole in the wall with fireproof material to prevent drafts from affecting the ambient temperature readings.
3. Reinsert the screw terminal blocks onto the PCB.
Note: If multiple wires are inserted into the terminals, be sure to properly twist the wires together prior to inserting them into the terminal connectors.
4. For PIR models, carefully reattach the PIR connector to the PCB.
CAUTION: Risk of Electric Shock.
Disconnect the power supply before making electrical connections to avoid electric shock.
5. Reattach the thermostat controller cover to the mounting base (top side first).
6. Use a Phillips-head screwdriver to reinstall the security screw on the bottom of the thermostat controller cover if desired. The security screw comes packaged separately in a plastic bag with the thermostat controller.
T60xDFH-4 and T60xDFH-4+PIR Series Thermostat Controllers with Dehumidification and Occupancy Sensing Capability Installation Instructions
3
Table 1: Terminal Identification (See Figure 5.)
Terminal Number
T601DFH-4, T601DFH-4+PIR (On/Off Control)
1 Fan-H Fan-H Fan-H Fan On – High 2 Fan-M Fan-M Fan-M Fan On – Medium 3 Fan-L Fan-L Fan-L Fan On – Low 4 24 V~ Hot 24 V~ Hot 24 V~ Hot 24 VAC from Transformer 5 24 V~ Com 24 V~ Com 24 V~ Com 24 VAC (Common) from Transformer 6 BO5 Aux BO5 Aux BO5 Aux Aux BO (Auxiliary Output) 7 BO5 Aux BO5 Aux BO5 Aux Aux BO (Auxiliary Output) 8 BO3 BO3 Blank Open Heat
9 Blank BO4 AO2 Close Heat 10 Blank BO1 AO1 Open Cool 11 BO2 BO2 Blank Close Cool 12 BI1 BI1 BI1 Configurable Binary Input 1 13 RS RS RS Remote Room Temperature Sensor 14 Scom Scom Scom Sensor Common 15 BI2 BI2 BI2 Configurable Binary Input 2 16 UI3 UI3 UI3 Configurable Universal Input 3
Terminal Label Function
T602DFH-4, T602DFH-4+PIR, T603DFH-4, T603DFH-4+PIR (On/Off or Floating Control)
T604DFH-4, T604DFH-4+PIR, T605DFH-4, T605DFH-4+PIR (Proportional 0 to 10 VDC Control)
T60xDFH-4 and T60xDFH-4+PIR Series Thermostat Controllers with Dehumidification and Occupancy
4
Sensing Capability Installation Instructions
Figure 5: Wiring the T60xDFH-4 or T60xDFH-4+PIR Series Thermostat Controller
(See Table 1.)
FIG:wrng
Contact
• COC/NH
= Cold Water
• COC/NC Normally C ool
= Hot Water
Voltage-Free Contact
• Door
• Remote Override
• Filter Alarm
• Service Alarm
Voltage-Free Contact
• Remote NSB
• Motion
• Window
- OR ­Same 24 VAC
(24 VA C Maximum )
(24 VA C Maximum )
BO5
Aux
BO5
Aux
24 VAC
Thermostat Controller
Power
24 V~
Com
24 V~
Hot
Power and Fan
Power and Fan
BO5
Aux
BO5
Aux
Contacts
• Reheat
• Lighting
• Exhaust Fan
Aux
Aux
Fan
-H
Fan
-M
Fan
-L
24 VAC
Thermostat Controller
24 V~
Com
24 V~
Hot
Fan
-H
Fan
-M
Fan
-L
Three-Pole Right Top Connector
Eight-Pole Bottom Connector
BO1/ AO1
UI3
BI1
BI2
Hot
Com
BO4/
AO2
Left Top Connector
1 2 3 4 5
Separate 24 VAC
Power Source for Auxiliary Output
Five-Pole
Fan
Fan-MFan
-H
-L BO5
Aux
BO5
Aux
BO3
24 V~
24 V~
6 7 8
Power Source for Auxiliary Output
9 10 11 12 13 14 15 16
Independent
• On/Off Actuation
BI1
BO2
Remote Inputs
Scom
BI2 UI3
- OR -
Supply S ensor Changeover Sensor
RS
Scom
Voltage-Free
Normally Heat Closed Contact
Closed Contact
Power
T60xDFH-4 and T60xDFH-4+PIR Series Thermostat Controllers with Dehumidification and Occupancy Sensing Capability Installation Instructions
5
Figure 6: Wiring T601DFH-4 Thermostat Controllers for On/Off Control
24 V~
Com
24 V~
Hot
BO2
Two -Pip e Applic ations
Four-Pipe Applications
Com
N.O.
Heating
Valve
24 V~
Hot
BO3
N.C.
Cooling
Valve
Figure 7: Wiring T602DFH-4 and T603DFH-4 Thermostat Controllers for On/Off Control
Two -Pip e Applic ations
Four-Pipe Applications
24 V~
Com
24 V~
Hot
or
Com
Hot
Cooling
Valve
or
Heating
Valve
or
Figure 8: Wiring T602DFH-4 and T603DFH-4 Thermostat Controllers for Floating Control
Two -Pip e Applicat ions
Com
Hot
BO1
Cooling
Valve
Heating
Valve
24 V~
Com
24 V~
Hot
BO1
Heating/Cooling
Valve
BO2
Figure 9: Wiring T604DFH-4 and T605DFH-4 Thermostat Controllers for Proportional Control
Two -Pip e Applic ations
Four-Pipe Applications
F
I
G
:
T
6
0
4
5
d
f
h
3
p
r
p
Heating/Cooling
Valve
Com
Hot
Cooling
Valve
Heating
Valve
24 V~
Com
24 V~
Hot
AO1
24 V~
24 V~
24 V~
c
o o
3
h
f
d
1 0
6 T
: G
I F
c
o o
3
h
f
d 3
2
0 6 T
: G
I F
BO2 BO3
BO4
24 V~
c
f
3 h
f
d 3
2
0 6 T
: G
I F
24 V~
Four-Pipe Applications
24 V~
24 V~
AO2
AO1
T60xDFH-4 and T60xDFH-4+PIR Series Thermostat Controllers with Dehumidification and Occupancy
6
Sensing Capability Installation Instructions

Setup and Adjustments

Figure 10: Front Cover of Thermostat Controller (T60xDFH-4+PIR Model Shown)

Thermostat Controller Operation Overview

Thermostat Controller User Interface Keys

The T60x Series Thermostat Controller user interface consists of five keys on the front cover (as illustrated in Figure 10). The function of each key is as follows:
•Use the MODE key to toggle among the system modes available, as defined by selecting the appropriate operation sequence in the Installer Configuration Menu (for example, Off, Heat, Cool, Auto).
Note: If the automatic changeover function (auto function) is enabled in the sequence of operation (SeqOpera), then automatic changeover heating or cooling demand overrides the mode when MODE = off.
•Use the FAN key to toggle among the fan modes available, as defined by selecting the appr op ria te fan menu options defined in the Installer Configuration Menu (for example, Low, Med, High, Auto).
Use the °C/°F key to change the temperature scale to either Celsius or Fahrenheit and allow access to the Installer Configuration Menu. See the
Configuring the T60xDFH-4 and T60xDFH-4+PIR Series Thermostat Controller
section.
•Use the UP/DOWN arrow keys to change the configuration parameters and to activate a setpoint adjustment.

Backlit LCD

The T60x Series Thermostat Controllers include a 2-line, 8-character backlit display. Low-level backlighting is present during normal operation, and it brightens when any user interface key is pressed. The backlight returns to low level when the thermostat controller is left unattended for 45 seconds.

LEDs

Three LEDs are included to indicate the fan status, call for heat, or call for cooling:
The fan LED is on when the fan is on.
The heat LED is on when heating is on.
The cool LED is on when cooling is on.

Integrated PIR Sensor – T60xDFH-4+PIR Thermostat Controllers

The integrated PIR sensor allows for automatic switching between fully adjustable Occupied and Stand-By temperature setpoints without user interaction. This feature generates incremental energy savings during scheduled occupied periods while the space is unoccupied.
T60xDFH-4 and T60xDFH-4+PIR Series Thermostat Controllers with Dehumidification and Occupancy Sensing Capability Installation Instructions
7

Status Display Menu

The Status Display Menu is displayed during normal thermostat controller operation. This menu continuously scrolls through the following parameters:
Room Temperature (All Models) and Humidity (T603DFH-4 and T605DFH-4 Models)
Note: For models with dehumidification capability, the default setting is no humidity reading on the display (%RH disp parameter is set to off). The %RH disp parameter must be set to on to display the current humidity reading.
System Mode
Schedule Status (Occupied/Unoccupied/Override/Stand-By [PIR Models])
Applicable Alarms – The backlight lights up as an alarm condition is displayed.
Note: An option is available within the Installer Configuration Menu to lock out the scrolling display and show only the Room Temperature paramete r.

Dehumidification Operation – T603DFH-4 and T605DFH-4 Thermostat Controller Models

Dehumidification activates when th e room humidity is above the adjustable humidity setpoint as sensed by the integral humidity sensor.
Note: Dehumidification operation functions only in the Cooling mode; dehumidification operation does not function in either the Off or the Heating mode.
The minimum deadband between the Heating and Cooling setpoints is adjustable from 2.0F°/1.0C° to
5.0F°/2.5C°, as defined by the Deadband parameter in
Table 4. If the room temperature resides in the deadband between the Heating and Cooling setpoints:
the thermostat controller forces the fan to low speed
the chilled water valve opens to the specified maximum value set by CoolMax
the thermostat controller stages Heating to maintain the room temperature at the Cooling setpoint, as sensed by the thermostat controller
If the room temperature falls below the result of the formula 1 + Cooling Setpoint – Deadband, then the thermostat controller disables dehumidification operation.
If the thermostat controller is in Cooling demand:
the chilled water valve opens to 100%
the thermostat controller stages Heating to maintain the room temperature at the Cooling setpoint, as sensed by the thermostat controller
If the thermostat controller is in Cooling demand and the room temperature rises 2F°/1C° above the Cooling setpoint, the thermostat controller automatically disables dehumidification operation. Likewise, if the thermostat controller is in Cooling demand and the room temperature falls below the current Heating setpoint, the thermostat controller disables dehumidification operation.

Occupancy Sensor Operation – T60xDFH-4+PIR Thermostat Controllers

A T60xDFH-4+PIR Series Thermostat Controller (or a T60xDFH-4 Series Thermostat Controller equipped with a PIR accessory cover) provides advanced occupancy logic.
Note: The PIR strategy is an occupied strategy. If the thermostat controller is programmed to be Unoccupied , the PIR function does not have an effect on the occupancy strategy.
The thermostat controller automatically switches occupancy levels from Occupied to Stand-By and Unoccupied as required, when local movement is sensed.
Occupancy sensing is enabled only if a PIR cover is installed on the thermostat controller (PIR models) or if a remote input is configured as a remote PIR sensor (MotionNO or MotionNC).

PIR Warm-Up Period

When a PIR cover is used and a thermostat controller is powered up, there is a 1-minute warm-up period before any local movement can be detected and acknowledged by the PIR sensing device. The local status LEDs for the PIR function are not active, and the sensor is in Stand-By mode for the 1-minute period. The PIR functionality and local movement status LEDs are activated after the 1-minute warm-up period has elapsed after the initial powering of the thermostat controller. If movement is present, the mode changes to Occupied.

PIR Diagnostic LEDs

The diagnostic LEDs inside the PIR lens brighten when movement is detected within the first 30 minutes after powerup. The LEDs do not light up or brighten after the initial 30-minute period.
T60xDFH-4 and T60xDFH-4+PIR Series Thermostat Controllers with Dehumidification and Occupancy
8
Sensing Capability Installation Instructions

Setpoints

St-By Heat
= 69°F
Occ Heat
= 72°F
Occ Cool
= 75°F
St-By Cool
= 78°F
Unocc Heat
= 65°F
Room Temperature
FIG:rm_tmp
Figure 11: Increa sing Room Temperature Setpoints
Figure 12: Unoccupied Timer Set to 6 Hours and Stand-By Timer Set to 2 Hours
The Stand-By setpoints are under the same limitations and restrictions as the Occupied and Unoccupied setpoints. Stand-By setpoints reside between the corresponding Occupied and Unocc up ie d set po in t values.
The installer must be certain that the difference between the Stand-By and Occupied values can be recovered within a timely fashion to ensure occupancy comfort. In addition, the difference between the two values must be large enough to warrant maximum energy savings.
Hotel and lodging applications can benefit from the addition of an entry door switch wired to one of the binary inputs of the thermostat controller. When a door contact is used and configured, the S t and-By timer a nd its configuration are no longer active or used. The occupancy toggle between Occupied and Stand-By is then dictated by both the door contact and the PIR sensing device used. If movements are detected by the PIR sensor and the door is closed, the room is considered occupied. The thermostat controller switches back to S tan d-By mode only if the door switch toggles open/closed. Motion is ignored when the door switch indicates an open door.
PIR occupancy functionality is dictated by both the Stand-By timer and Unoccupied timer configuration value and movements present in the area.

Unoccupied Timer Disable

It might be preferable for the local area to stay out of Unoccupied mode and always stay at the Stand-By occupancy level when no activity is present. In instances when areas always need to be on Stand-By status, ready to respond to demand at any given point in time, we recommend disabling the Unoccupied timer. When the loca l PIR occupancy routine is ru nning at the thermostat controller, the zone drifts into Unoccupied mode when the Unoccupied timer is set above its factory default value of 0.0 hours.
T60xDFH-4 and T60xDFH-4+PIR Series Thermostat Controllers with Dehumidification and Occupancy Sensing Capability Installation Instructions
9
When the local PIR occupancy routine is running at the
Figure 13: Unoccupied Timer Set to 0 Hours and Stand-By Timer Set to 2 Hours
thermostat controller, the zone never drifts into Unoccupied mode when the Unoccupied timer is set to its factory default value of 0.0 hours.
Refer to the T60xDFH-4 and T60xDFH- 4+ PIR Ser ies
Thermostat Controllers with Dehumidification and Occupancy Sensing Capability Application Note (LIT-12011569) for additional application scenarios
using various combinations of occupancy levels and door switches.

Configuring the T60xDFH-4 and T60xDFH-4+PIR Series Thermostat Controller

The T60x Series Thermostat Controller comes from the factory with default settings for all configurable parameters. The default settings are shown in Table 4. To reconfigure the parameters via the thermostat controller, follow the steps in this section.
1. To access the Installer Configuration Menu, press and hold the center key for approximately 8 seconds.
Note: If the Password parameter is configured, Password 0 appears on the thermostat controller display indicating that the configured password is required to proceed. Use the UP/DOWN arrow keys to indicate the configured password, then press the MODE key to proceed through the Installer Configuration Menu parameters.
2. Once the Installer Configuration Menu begins, press and release the center key to scroll through the parameters listed in Table 4.
3. When the desired parameter is displayed, use the UP/DOWN arrow keys to choose the desired selection option.
4. Press and release the center key to continue scrolling through the parameters.
Note: Pressing the FAN key during configuration restarts the list of displayed parameters at the first parameter listed in Table 4.
When the thermostat controller is in the Installer Configuration Menu and left unattended for approximately 8 seconds, the thermostat controller reverts to the Status Display Menu.

Configuring Inputs BI1, BI2, and UI3

When BI1 and BI2 are configured for an alarm condition, an alarm condition is displayed locally when the input is closed. An alarm message is included on the scrolling Status Display Menu and when the message is displayed, the backlight momentarily lights up.
The UI3 input provides changeover of hot/cold water switching or supply air temperature monitoring at the thermostat controller.
Each input can be configured to the selection options included in Table 4.

Configuring the Sequence of Operation (SeqOpera)

Choose the appropriate sequence of operation using Table 2 or Table 3. The modes presented are user­dependent on the sequence of operation selected. For two-pipe applications using a changeover sensor, choose the selection option (0): Cooling Only. Changeover occurs between Cooling Only and Heating Only. See Figure 14 through Figure 19 for sequence of operation examples.
T60xDFH-4 and T60xDFH-4+PIR Series Thermostat Controllers with Dehumidification and Occupancy
10
Sensing Capability Installation Instructions
Table 2: Selection Options for Sequence of Operation in Two-Pipe Applications
Selection Option
(0): Cooling Only See Figure 14. 10: Normally Open
(1): Heating Only See Figure 15. 10: N.O. Heating
(2): Cooling and Reheat See Figure 16. 6 and 7: Reheat
(3): Heating and Reheat See Figure 17. 6 and 7: Reheat
Control Curve
Terminal Numbers Used (See Table 1 and Figure 5.)
On/Off Control Floating Control Proportional
(N.O.) Cooling 11: Normally Closed (N.C.) Cooling
11: N.C. Heating
10: N.O. Cooling 11: N.C. Cooling
10: N.O. Heating 11: N.C. Heating
10: Open Cooling 11: Closed Cooling
10: Open Heating 11: Closed Heating
6 and 7: Reheat 10: Open Cooling 11: Closed Cooling
6 and 7: Reheat 10: Open Heating 11: Closed Heating
Table 3: Selection Options for Sequence of Operation in Four-Pipe Applications
Selection Option
(0): Cooling Only See Figure 14. 10: N.O. Cooling
(1): Heating Only See Figure 15. 8: N.O. Heating
(2): Cooling and Reheat See Figure 16. 6 and 7: Reheat
(3): Heating and Reheat See Figure 17. 6 and 7: Reheat
(4): Cool/Heat Four-Pipe See Figure 18. 8: N.O. Heating
(5): Cool/Heat Four-Pipe and Reheat
Control Curve
See Figure 19. 6 and 7: Reheat
Terminal Numbers Used (See Table 1 and Figure 5.)
On/Off Control Floating Control Proportional
11: N.C. Cooling
9: N.C. Heating
10: N.O. Cooling 11: N.C. Cooling
8: N.O. Heating 9: N.C. Heating
9: N.C. Heating 10: N.O. Cooling 11: N.C. Cooling
8: N.O. Heating 9: N.C. Heating 10: N.O. Cooling 11: N.C. Cooling
10: Open Cooling 11: Closed Cooling
8: Open Heating 9: Closed Heating
6 and 7: Reheat 10: Open Cooling 11: Closed Cooling
6 and 7: Reheat 8: Open Heating 9: Closed Heating
8: Open Heating 9: Closed Heating 10: Open Cooling 11: Closed Cooling
6 and 7: Reheat 8: Open Heating 9: Closed Heating 10: Open Cooling 11: Closed Cooling
0to10VDC Control
10: Proportional Cooling
10: Proportional Heating
6 and 7: Reheat 10: Proportional Cooling
6 and 7: Reheat 10: Proportional Heating
0to10VDC Control
10: Proportional Cooling
9: Proportional Heating
6 and 7: Reheat 10: Proportional Cooling
6 and 7: Reheat 9: Proportional Heating
9: Proportional Heating 10: Proportional Cooling
6 and 7: Reheat 9: Proportional Heating 10: Proportional Cooling
T60xDFH-4 and T60xDFH-4+PIR Series Thermostat Controllers with Dehumidification and Occupancy Sensing Capability Installation Instructions
11
Device Closed
Cooling Setpoint
Device Opened
On/Off, Floating,
or Propor t ional
Output
F
I
G
:
c
l
n
g
_
n
l
y
Figure 14: Cooling Only,
Two- or Four-Pipe Applications
Device Closed
Device Opened
On/Off, Floating,
or Propor t ional
Output
F
I
G
:
h
t
n
g
_
n
l
y
Figure 15: Heating Only,
Two- or Four-Pipe Applications
Figure 16: Cooling with Reheat, Two- or Four-Pipe Applications
Heating Setpoint
Closed
Cooling Setpoint
Device
Opened
F
I
G
:
c
l
n
g
_
w
t
h
_
r
h
t
Deadband
Reheat
Outputs
Cooling Output
Off
Off
On
On
F
I
G
:
h
t
g
_
w
t
h
_
Reheat
On/Off, Floating,
or Propor t io nal
Output
Off
Off
On
Figure 17: Heating with Reheat, Two- or Four-Pipe Applications
Figure 18: Heating/Cooling,
Four-Pipe Applications
Heating Setpoint
Closed
Cooling Setpoint
Device
Opened
F
I
G
:
h
t
n
g
_
c
l
n
g
Deadband
Cooling Output
Device
Closed
Device
Opened
On/Off, Floating, or Proport ional Outputs
Tempe r at ur e Increase
(Increments of 1F°/0.5C°)
Heating Setpoint
Temperature Increase
(Increments of 1F°/0.5C°)
On
Temperature Increase
(Increments of 1F°/0.5C°)
Heating Output
100%
0%
t
h
r
12
Heating Output
Device
Temperature Increase
(Increments of 1F°/0.5C°)
On/Off, Floating,
Device
or Propor tional
Temperature Increase
(Increments of 1F°/0.5C°)
T60xDFH-4 and T60xDFH-4+PIR Series Thermostat Controllers with Dehumidification and Occupancy Sensing Capability Installation Instructions
Figure 19: Heating/Cooling with Reheat,
Four-Pipe Applications
Heating Setpoint
Device
Closed
Device Closed
Device
Opened
Cooling Setpoint
Device
Opened
F
I
G
:
h
t
n
g
_
c
l
n
g
_
r
h
t
Deadband
Reheat Output
On/Off, Floating,
or Propor t ional
Outputs
Heatin g O ut put Cooling Output
Off
Off
On
On
Figure 20: Low-Med-High-Auto and Low-High-Auto Fan Operation
Temperature Deviation from Setpoint, °F
2.0F°/1. 0C° to
5.0F°/2.5C° Deadband
100%
0%
2.5
2.5
2.0 2.0
1.5
1.50.5 0.5
Heating
Valve
Cooling
Valve
On
On
On
On
Off
Off
Off
Off
Low
Medium
between the
heating and
cooling se t points
if the
parameter is
set to .
Auto Fan
AS AD
Setpoint
High
FIG:fn_opr tn
Fan
Speed
Heating
Setpoint
Tempe r at ur e Increase
(Increments of 1F°/0.5C°)

Configuring Automatic Fan Speed

Use the Fan Menu parameter in the Installer Configuration Menu to set the available fan mode options. Use the FAN key to select the desired fan mode option.
When selection option (2): Low-Med-High-Auto is chosen in the Fan Menu parameter, the fan operates as shown in Figure 20. When selection option (3): Low-High-Auto is chosen in the Fan Menu parameter, the fan operates at only the low and high settings and ignores the medium setting (Figure 20). This operation applies to the Occupied mode when the fan is set to Auto.
Cooling
The fan is of f
T60xDFH-4 and T60xDFH-4+PIR Series Thermostat Controllers with Dehumidification and Occupancy Sensing Capability Installation Instructions
13
Table 4: Installer Configuration Menu (Part 1 of 7)
Parameter
Description and Default Selection Options Appearing on Display
Pswrd Sets the protective access
password to prevent unauthorized
access to the Installer Configuration
Menu.
Default: 0
Note: The default setting does not
lock out access to the Installer
Configuration Menu. BI1 Configuration of Binary Input 1.
Default: None
Range: 0 to 1,000
(None): No function is associated with an input. (Rem NSB): Remote Night Setback (NSB) via a time clock input, an
occupancy sensor, or from a voltage-free contact. Contact open = Occupied; contact closed = Unoccupied.
(MotionNO*): Temporary occupancy request via a motion detector input. Contact open = Unoccupied. When the contact closes, the thermostat controller goes into the Occupied mode for a specified TOccTime. Once the TOccTime begins, the thermostat controller remains in the Occupied mode if the contact is open, until the TOccTime expires. Advanced PIR occupancy functions using a Normally Open (N.O.) or Normally Closed (N.C.) remote PIR motion sensor.
(MotionNC*): Temporary occupancy request via a motion detector input. Contact closed = Unoccupied. When the contact opens, the thermostat controller goes into the Occupied mode for a specified TOccTime. Once the TOccTime begins, the thermostat controller remains in the Occupied mode if the contact is closed, until the TOccTime expires. Advanced PIR occupancy functions using a Normally Open (N.O.) or Normally Closed (N.C.) remote PIR motion sensor.
(Window): Cancels the thermostat controller heating or cooling action when a window is open. The fan operation is only affected if the Fan Menu parameter is set to (4): On-Auto, and Auto is the selected fan mode. A Window alarm is displayed indicating that the window needs to be closed to resume heating or cooling. The heating and/or cooling outputs are enabled only when the contact is closed.
* These settings disable any local override function. For PIR models, see the Occupancy Sensor Operation – T60xDFH-4+PIR Thermostat Controllers section.
T60xDFH-4 and T60xDFH-4+PIR Series Thermostat Controllers with Dehumidification and Occupancy
14
Sensing Capability Installation Instructions
Table 4: Installer Configuration Menu (Part 2 of 7)
Parameter
Description and Default Selection Options Appearing on Display
BI2 Configuration of Binary Input 2.
Default: None
UI3 Configuration of Universal Input 3.
Default: None
MenuScro Gives the option of having the
AutoMode Enables the auto function to be
%RH disp Displays the current humidity
display continuously scroll the
parameters.
Default: on
visible within the MODE key menu.
(The
MODE key is the key at the far left of the thermostat controller cover.)
Default: off
reading (T603 and T605 models). Default: off
(None): No function is associated with an input. (Door Dry): Door contact only has an effect if BI1 is set to
MotionNO or MotionNC or if a PIR accessory cover is used. (See
the BI1 parameter earlier in this table.) The occupancy is now dictated via BI1, BI2, or PIR. Any motion detected sets the zone to Occupied status. The thermostat controller remains in the Occupied mode until the door contact switch opens momentarily, at which point the thermostat controller goes into Stand-By mode. If more movements are detected, the Occupied mode resumes. While the door is open, any movements detected by the PIR sensor are ignored. Use a Normally Closed (N.C.) switching device. (Contact open = door open; contact closed = door closed.)
(RemOVR): Temporary occupancy request via a remote input. This override function is controlled by a manual remote occupancy override. When enabled, this condition disables the override capability of the thermostat controller.
(Filter): A Filter alarm is displayed. This alarm can be connected to a differential pressure switch that monitors a filter.
(Service): A Service alarm is displayed on the thermostat controller when the input is energized. This input can be tied into the air conditioning unit control card, which provides an alarm should there be a malfunction.
(None): No function is associated with an input. (COC/NH): Changeover Contact/Normally Heat: A dry contact input
is used to signal seasonal hot/cold water changeover. The contact closes when cold water is present. Valid only for two-pipe systems.
(COC/NC): Changeover Contact/Normally Cool: A dry contact input is used to signal seasonal hot/cold water changeover. The contact closes when hot water is present. Valid only for two-pipe systems.
(COS): Changeover Analog Sensor: Used for hot/cold water changeover switching. Valid only for two-pipe systems. (Parameter Pipe No is set to 2.0.) If the water temperature is greater than 75°F/ 24°C, hot water is present. If the water temperature is less than 75°F/24°C, cold water is present.
Note: Choose the selection option (0): Cooling Only for the SeqOpera parameter to allow changeover to occur between Cooling Only and Heating Only. The changeover sensor does not operate in Cooling and Reheat, Heating and Reheat, or Cool/ Heat Four-Pipe and Reheat applications.
(SS): Supply Air Sensor Monitoring (off): The scroll is inactive.
(on): The scroll is active.
(on): The auto function is active (Off-Auto-Heat-Cool). Provides
automatic changeover between heating and cooling.
(off): The auto function is inactive (Off-Heat-Cool).
(on): Displays the current humidity reading in % RH. (off): Does not display the current humidity reading.
T60xDFH-4 and T60xDFH-4+PIR Series Thermostat Controllers with Dehumidification and Occupancy Sensing Capability Installation Instructions
15
Table 4: Installer Configuration Menu (Part 3 of 7)
Parameter
Description and Default Selection Options Appearing on Display
Lockout Selectable Lockout Levels for
limiting end-user keypad interaction.
Default: 0
Pipe No Selectable number of pipes in the
system.
Default: 4.0 Pipes
CntrlTyp Defines the control output for the
type of valves used in the
installation (T602 and T603
models).
Default: Floating SeqOpera Determines the sequence of
operation.
Default: 1
Fan Menu Sets the fan mode options.
Default: 4
Lockout Level
(2.0 Pipes): Limits the number of sequences of operation available
from 0 to 3, and enables heat/cool operation from the same output. (4.0 Pipes): Allows access to all sequences of operation from 0 to 5,
and enables heat/cool operation from different outputs. (On/Off): For Normally Open (N.O.) or Normally Closed (N.C.)
24 VAC two-position valves.
(Floating): For three-wire control of 24 VAC floating valves.
Sequence of Operation Default Based on
(0): Cooling Only (Off-Cool) Cool Cool (1): Heating Only (Off-Heat) Heat Heat (2): Cooling and Reheat (Off-Auto*-
Heat-Cool)
(3): Heating and Reheat (Off-Heat) Heat Heat (4):Cool/Heat Four-Pipe (Off-Auto*-
Heat-Cool) (5): Cool/Heat Four-Pipe and Reheat
(Off-Auto*-Heat-Cool) * Auto can be disabled with the AutoMode param eter.
Note: Choose the selection option (0): Cooling Only when using a changeover sensor to allow changeover to occur between Cooling
Only and Heating Only. Note: Default parameter settings are always equal to off when the
mode is equal to off. (0): Low-Med-High: Three-speed configuration using three fan
relays (L-M-H). The default is High. (1): Low-High: Two-speed configuration using two fan relays (L-H).
The default is High. (2): Low-Med-High-Auto: Three-speed configuration with Auto Fan
speed mode using three fan relays (L-M-H). The default is High. (3): Low-High-Auto: Two-speed configuration with Auto Fan speed
mode using two fan relays (L-H). The default is High. (4): On-Auto: One-speed configuration, (H) Auto is for Fan on
demand and On is for Fan on all the time. The default is Auto.
Function
Mode Setting
(0) Access Access Access Access (1) Access Access No Access Access (2) No Access No Access Access Access (3) No Access No Access No Access Access (4) No Access No Access Access No Access (5) No Access No Access No Access No Access
Fan Setting
Local Override
AutoMode Parameter Setting
On Off
Auto Heat
Auto Heat
Auto Heat
Occupied Temperature Setpoints
T60xDFH-4 and T60xDFH-4+PIR Series Thermostat Controllers with Dehumidification and Occupancy
16
Sensing Capability Installation Instructions
Table 4: Installer Configuration Menu (Part 4 of 7)
Parameter
Description and Default Selection Options Appearing on Display
DHumiLCK Locks out the dehumidification
capability (T603 and T605 models).
Default: on
%RH set
DehuHyst
DehuCool
St-By TM Sets the Stand-By timer value
Unocc TM Sets the Unoccupied timer value
St-By HT Sets the Stand-By heating setpoint
St-By CL Sets the Stand-By cooling setpoint
1
Sets the dehumidification setpoints
(T603 and T605 models). This
parameter can be used only if the
dehumidification sequence is
enabled.
Default: 50.0% RH
1
Sets the dehumidification hysteresis
(T603 and T605 models). This
parameter can be used only if the
dehumidification sequence is
enabled.
Default: 5.0% RH
1
Sets the maximum dehumidification
cooling output (T603 and T605
models). This parameter can be
used only if the dehumidification
sequence is enabled.
Default: 100%
(PIR models).
Default: 0.5 hours
(PIR models).
Default: 0.0 hours
(PIR models).
Default: 69.0°F/20.5°C
(PIR models).
Default: 78.0°F/25.5°C
(off): Dehumidification is locked out. (on): Dehumidification is allowed.
Range: 30.0 to 95.0% RH
Range: 2.0 to 20.0% RH
Range: 20.0 to 100.0% Note: This parameter can be used to balance smaller reheat loads
installed with regard to the capacity of the cooling coil.
Time delay between the moment the PIR cover detected the last movement in the area and the time at which the thermostat controller Stand-By mode and setpoints become active.
Range: 0.5 to 24.0 hrs adjustable in 0.5-hour increments Time delay between the moment the thermostat controller toggled to
Stand-By mode and the time at which the thermostat controller Unoccupied mode and setpoints become active. Setting this parameter to the factory value (0.0 hours) disables the Unoccupied timer. This prevents the thermostat controller from switching from Stand-By mode to Unoccupied mode when PIR functions are used.
Range: 0.0 to 24.0 hrs adjustable in 0.5-hour increments The value of this parameter should reside between the Occupied
and Unoccupied heating setpoints, and ensure that the difference between the Stand-By and Occupied value can be recovered in a timely fashion when movement is detected in the zone.
Range: 40.0°F/4.5°C to 90.0°F/32.0°C The value of this parameter should reside between the Occupied
and Unoccupied cooling setpoints, and ensure that the difference between the Stand-By and Occupied value can be recovered in a timely fashion when movement is detected in the zone.
Range: 54.0°F/12.0°C to 100.0°F/37.5°C
T60xDFH-4 and T60xDFH-4+PIR Series Thermostat Controllers with Dehumidification and Occupancy Sensing Capability Installation Instructions
17
Table 4: Installer Configuration Menu (Part 5 of 7)
Parameter
Description and Default Selection Options Appearing on Display
Unocc HT Sets the Unoccupied heating
setpoint value.
Default: 62.0°F/16.5°C Unocc CL Sets the Unoccupied cooling
setpoint value.
Default: 80.0°F/26.5°C Heat max Sets the Occupied and Unoccupied
maximum heating setpoint values.
Default: 90.0°F/32.0°C Cool min Sets the Occupied and Unoccupied
minimum cooling setpoint values.
Default: 54.0°F/12.0°C Pband Sets the proportional band used by
the thermostat controller
Proportional-Integral (PI) control
loop.
Default: 3.0F°/1.7C°
Note: The proportional band
default setting of 3.0F°/1.7C°
provides satisfactory thermostat
controller operation in most
instances. A proportional band
setting other than the default is
normally used in installations where
the location of the thermostat
controller is problematic, leading to
unwanted cycling. An example of a
problematic installation is a wall-
mounted thermostat controller
installed between the return and
supply air feeds, that is directly
influenced by the supply air stream. Set type Provides the option of temporarily
changing the heating or cooling
setpoint by pressing the UP/DOWN
arrow keys.
Default: permnent Spt Func Determines the operation and
usage of the local setpoint interface
by the user.
Default: Dual Stp
Range: 40.0°F/4.5°C to
90.0°F/32.0°C
Range: 54.0°F/12.0°C to
100.0°F/37.5°C
Range: 40.0°F/4.5°C to
90.0°F/32.0°C
Range: 54.0°F/12.0°C to
100.0°F/37.5°C
(3): 3.0F°/1.7C° (4): 4.0F°/2.2C° (5): 5.0F°/2.8C° (6): 6.0F°/3.3C° (7): 7.0F°/3.9C° (8): 8.0F°/4.4C° (9): 9.0F°/5.0C° (10): 10.0F°/5.6C°
(temporar): Local changes to the heating or cooling setpoints are
temporary, and remain effective for the specified TOccTime. (permnent): Local changes to the heating or cooling setpoints are
permanently stored in the thermostat memory.
(Attch Stp):
setpoint is the setpoint from the last action taken by the thermostat controller, or the setpoint currently in use. Both the heating and cooling setpoints are changed simultaneously, while respecting the minimum configured deadband. If one setpoint is desired over the other, use the MODE key to toggle between the two setpoints.
(Dual Stp): Dual Occupied Setpoint Adjustment. The displayed setpoint is the setpoint from the last action taken by the thermostat controller, or the setpoint currently in use. The heating and cooling setpoints can be separated individually, allowing the minimum configured deadband to expand. If one setpoint is desired over the other, use the MODE key to toggle between the two setpoints.
Note: When adjusting the temperature, press the UP/ DOWN arrow keys to change the temperature in
0.5F°/0.5C° increments; press and hold the UP/DOWN arrow keys to change the temperature in 5.0F°/5.0C° increments.
Single Occupied Setpoint Adjustment. The displayed
T60xDFH-4 and T60xDFH-4+PIR Series Thermostat Controllers with Dehumidification and Occupancy
18
Sensing Capability Installation Instructions
Table 4: Installer Configuration Menu (Part 6 of 7)
Parameter
Description and Default Selection Options Appearing on Display
TOccTime Sets the duration of the Temporary
Occupancy Time when the heating
or cooling setpoints in the Occupied
mode are established by:
• an override function enabled from a remote override (when the thermostat controller is in the Unoccupied mode)
• a temporary heating or cooling setpoint
Default: 2.0 hrs
Deadband Sets the minimum deadband
between the heating and cooling setpoints.
Default: 2.0F°/1.0C°
Cal RS Sets the desired room air
temperature sensor calibration (offset). The offset can be added to or subtracted from the actual displayed room temperature.
Default: 0.0F°/0.0C°
Cal RH Sets the desired humidity sensor
calibration (offset). The offset can be added to or subtracted from the actual displayed room humidity (T603 and T605 models). This parameter can be used only if the dehumidification sequence is enabled.
Default: 0.0% RH
Aux cont Determines the auxiliary contact
function and configuration. Default: 0
Range: 0.0 to 24.0 hrs adjustable in 1-hour increments
Range: 2.0F°/1.0C° to 5.0F°/2.5C° adjustable in 1.0F°/0.5C° increments
Range: -5.0F°/-2.5C° to 5.0F°/2.5C° adjustable in 1.0F°/0.5C° increments
Range: -15.0% RH to 15.0% RH adjustable in 1% RH increments
Note: The contact toggles with the Occupied/Unoccupied schedule of the NSB contact on BI1, if used.
(0) Not used,
or used for reheat
(1) Auxiliary
N.O.
(2) Auxiliary
N.C.
(3) Auxiliary
N.O.
(4) Auxiliary
N.C.
If the sequence of operation is set to reheat (2, 3, or 5), ignore this parameter.
Occupied = contact closed
Unoccupied = contact open
Occupied = contact open Unoccupied = contact
closed Occupied and fan On =
contact closed Unoccupied and fan On
or Off = contact open Occupied and fan On =
contact open Unoccupied and fan On
or Off = contact closed
The output aligns with occupancy.
The output aligns with occupancy and the fan on command.
T60xDFH-4 and T60xDFH-4+PIR Series Thermostat Controllers with Dehumidification and Occupancy Sensing Capability Installation Instructions
19
Table 4: Installer Configuration Menu (Part 7 of 7)
Parameter
Description and Default Selection Options Appearing on Display
Auto Fan Affects the auto mode of operation
for the following Fan Menu
parameter selection options only:
(2): Low-Med-High-Auto
(3): Low-High-Auto
Default: AS
FL time Sets the maximum actuator stroke
timing (floating CntrlTyp T602 and
T603 models).
Default: 1.5 min Cph Sets the maximum number of cycles
per hour (T601 and on/off CntrlTyp
T602 and T603 models).
Default: 4.0 RA/DA Choice of reverse or direct acting
analog output signal (T604 and
T605 models)
Default: DA Reheat Sets the duty cycle time for reheat
output (if Option 2, 3, or 5 is chosen
in the SeqOpera parameter).
Default: 0
UI3 dis Displays the supply or changeover
temperature when UI3 is configured
as an analog input (supply sensor or
changeover sensor).
Default: -40°F/-40°C
(AS AD): The fan is on Auto during occupied periods. The Med and High speeds operate automatically on a temperature error from the setpoint. The Low speed operates Auto on demand. When there is no demand, the Low speed shuts down. The Low speed is only re­activated when there is a heating or cooling demand.
(AS): The fan is always on during occupied periods. The fan is on Auto during unoccupied periods. The Low, Med, and High speeds operate automatically on a temperature error from the setpoint.
Range: 0.5 to 9.0 min adjustable in 0.5-minute increments
Range: 3.0 to 8.0 cycles per hour
(RA): Reverse acting, 0 to 100% = 10 to 0 VDC (DA): Direct acting, 0 to 100% = 0 to 10 VDC
(1): 10 seconds (six cycles per minute), for various equipment with
solid-state relays that withstand short duty cycles such as electric heat.
(0): 15 minutes (four cycles per hour), for various equipment with mechanical relays or contactors controlling mechanical reheat systems.
Used as a diagnostic/service help, to troubleshoot and diagnose sensor operation.
1. When adjusting the numeric value, press the UP/DOWN arrow key to change the value by single increments; press and hold the UP/DOWN arrow key to change the numeric value in increments of ten.

Accessories

All the accessories in Table 5 include mounting hardware; contact the nearest Johnson Controls® representative to order any of these parts.
Note: Review the technical specifications of the accessories prior to their use in an application.
T60xDFH-4 and T60xDFH-4+PIR Series Thermostat Controllers with Dehumidification and Occupancy
20

Repair Information

If the T60xDFH-4 or T60xDFH-4+PIR Series Thermostat Controller fails to operate within its specifications, replace the unit. For a replacement thermostat controller, contact the nearest Johnson Controls representative.
Sensing Capability Installation Instructions
Table 5: Accessories (Order Separately)
Code Number Description
SEN-600-1 Remote Inside Air Temperature Sensor
1
TE-6361M-1 TE-636S-1 TEC-6H-PIR
1. Additional TE-636xx-x Series 10k ohm Johnson Controls Type II Thermistor Sensors are available; refer to the TE-6300 Series Temperature Sensors Product Bulletin (LIT-216320) for more details.
2. The TEC-6H-PIR Accessory Cover can be used to replace the existing cover on a non-PIR T60xDFH-4 Series Thermostat Controller to provide occupancy sensing capability.
1
Duct Mount Air Temperature Sensor Strap-Mount Temperature Sensor
2
Cover with Occupancy Sensor
Table 6: Display Messages
Display Function
Service Indicates that there is a service alarm in accordance with the programmable Binary Input (BI2). Filter Indicates that the filter(s) is dirty in accordance with the programmable Binary Input (BI2). Window Indicates that an outside window or door is open and has cancelled the thermostat controller heating
or cooling action in accordance with the programmable Binary Input (BI1).

Technical Specifications

T60xDFH-4 and T60xDFH-4+PIR Series Thermostat Controllers with Dehumidification and Occupancy Sensing Capability (Part 1 of 2)

Power Requirements 19 to 30 VAC, 50/60 Hz, 2 VA (Terminals 4 and 5) at 24 VAC Nominal, Class 2 or
Safety Extra-Low Voltage (SELV)
Relay/Triac Contact Rating
Analog Output Rating
Fan Relay Output Rating 19 to 30 VAC, 1.0 A Maximum, 3.0 A Inrush Auxiliary
Output Rating Digital Input s Voltage-Free Contacts across Terminal Scom to Terminals BI1, BI2, or UI3 Analog Inputs Resistive Inputs (RS and UI3) for 10k ohm Johnson Controls Type II Negative
Temperature Sensor Type Local 10k ohm John son Controls Type II NTC Thermistor Sensor Wire Size 18 AWG (1.0 mm Diameter) Maximum, 22 AWG (0.6 mm Diameter) Recommended Temperature
Range
Accuracy Temperature ±0.9F°/±0.5C° at 70.0°F/21.0°C Typical Calibrated
Minimum Deadband 2F°/1C° between Heating and Cooling Ambient
Conditions
On/Off and Floating Control
Proportional Control
Triac Output 19 to 30 VAC, 1.0 A Maximum, 3.0 A Inrush
Backlit Display -40.0°F/-40.0°C to 122.0°F/50.0°C in 0.5° Increments Heating Control 40.0 °F/4.5°C to 90.0°F/32.0°C Cooling
Control
Humidity ±5% RH from 20 to 80% RH at 50 to 90°F (10 to 32°C)
Operating 32 to 122°F (0 to 50°C); 95% RH Maximum, Noncondensing Storage -22 to 122°F (-30 to 50°C); 95% RH Maximum, Noncondensing
30 VAC, 1.0 A Maximum, 15 mA Minimum, 3.0 A Inrush, Class 2 or SELV
0 to 10 VDC into 2k ohm Resistance (Minimum)
Temperature Coefficient (NTC) Thermistor Sensors
54.0°F/12.0°C to 100.0°F/38.0°C
T60xDFH-4 and T60xDFH-4+PIR Series Thermostat Controllers with Dehumidification and Occupancy Sensing Capability Installation Instructions
21
Metasys® and Johnson Controls® are registered trademarks of Johnson Controls, Inc.
All other marks herein are the marks of their respective owners. © 2011 Johnson Controls, Inc.
Building Efficiency
507 E. Michigan Street, Milwaukee, WI 53202
T60xDFH-4 and T60xDFH-4+PIR Series Thermostat Controllers with Dehumidification and Occupancy Sensing Capability (Part 2 of 2)
Compliance United States UL Listed, File E27734, CCN XAPX,
Canada UL Listed, File E27734, CCN XAPX7,
Europe CE Mark - Johnson Controls, Inc., declares that this product is in compliance
Australia and New Zealand
Shipping Weight
The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products.
T60xDFH-4 Models
T60xDFH-4+PIR Models
Under UL 873, Temperature Indicating and Regulating Equipment FCC Compliant to CFR 47, Part 15, Subpart B, Class A
Under CAN/CSA C22.2 No. 24, Temperature Indicating and Regulating Equipment Industry Canada, ICES-003
with the essential requirements and other relevant provisions of the EMC Directive 2004/108/EC.
C-Tick Mark, Australia/NZ Emissions Compliant
0.75 lb (0.34 kg)
0.77 lb (0.35 kg)
T60xDFH-4 and T60xDFH-4+PIR Series Thermostat Controllers with Dehumidification and Occupancy
22
Sensing Capability Installation Instructions
Published in U.S.A. www.johnsoncontrols.com
Loading...