Johnson Controls T606MSx-4 Series, T606MSx-4+PIR Series Installation Guide

T606MSx-4 and T606MSx-4+PIR Series Multi-Stage Temperature and Humidity Controllers
Installation Instructions
T606MSN-4, T606MSP-4, T606MSN-4+PIR, T606MSP-4+PIR
Refer to the QuickLIT Web site for the most up-to-date version of this document.

Applications

The T606MSN-4 and T606MSN-4+PIR non-programmable and T606MSP-4 and T606MSP-4+PIR programmable temperature and humidity controllers are specifically designed for control of multi-stage commercial heating and cooling equipment with a humidifier and/or dehumidifier.
IMPORTANT: The T606MSx-4 and T606MSx-4+PIR Series Temperature and Humidity Controllers are intended to provide an input to equipment under normal operating conditions. Where failure or malfunction of the controller could lead to personal injury or property damage to the controlled equipment or other property, additional precautions must be designed into the control system. Incorporate and maintain other devices, such as supervisory or alarm systems or safety or limit controls, intended to warn of or protect against failure or malfunction of the controller.

North American Emissions Compliance

United States

This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when this equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference, in which case the user will be required to correct the interference at his/her own expense.
Part No.
Supersedes December 1, 2010
24-9890-1354,
Issued August 16, 2012
Rev. A

Canada

This Class (A) digital apparatus meets all the requirements of the Canadian Interference-Causing Equipment Regulations.
Cet appareil numérique de la Classe (A) respecte toutes les exigences du Règlement sur le matériel brouilleur du Canada.

Installation

Location Considerations

Locate the T606MSx-4 or T606MSx-4+PIR Series Temperature and Humidity Controller:
on a partitioning wall, approximately 5 ft ( 1. 5 m) above the floor in a location of average temperature
away from direct sunlight, radiant heat, outside walls, outside doors, air discharge grills, or stairwells; or from behind doors
away from steam or water pipes, warm air stacks, unconditioned areas (not heated or cooled), or sources of electrical interference
For integrated Passive Infrared (PIR) models, be sure that the controller is located centrally, where occupant movement is abundant.
Note: Allow for vertical air circulation to the controller. To install the controller:
1. Use a Phillips-head screwdriver to remove the security screw if it is installed on the bottom of the controller cover.
Note: Normally, the security screw is packaged separately in a plastic bag with the controller. Skip this step if the screw is not installed on the bottom of the cover.
2. Pull the bottom edge of the controller cover and open the controller as illustrated in Figure 1.
T606MSx-4 and T606MSx-4+PIR Series Multi-Stage Temperature and Humidity
Controllers Installation Instructions
1
Note: PIR models have a wiring connection
Figure 1: Removing the Cover
(T606MSx-4+PIR Model Shown)
FIG:cvr_ rmvl
Figure 2: Opening the PCB
FIG:prntd_ crct_br d
Tabs
Figure 3: Securing the Mounting Base to the Wall
(Example)
FIG:mntng_bs
Figure 4: Removing the Screw Terminal Blocks
F
I
G
:
t
r
m
n
l
_
b
l
c
k
s
between the cover and the Printed Circuit Board (PCB). This connection allows for proper wiring of the occupancy sensor. Carefully remove the wiring connection from the PCB by pulling up on the connector block. Do not attempt to remove the connector block by pulling on the wires.
3. Carefully pull the locking tabs on the right side of the controller mounting base and unlock the PCB. Open the PCB to the left as illustrated in Figure 2.
Note: If you need to install the thermostat on an electrical junction box, use 2-1/2 x 4 in. (63 x 101 mm) square boxes with mud ring covers, and avoid smaller 1-1/2 x 4 in. (38 x 101 mm) square or 3 x 2 in. (76 x 51 mm) boxes. This procedure ensures you have enough space for cabling a nd end- of-line devices, if needed.
Note: For surface-mount applications, use durable mounting hardware such as Molly bolt anchors that cannot be easily pulled out of the mounting surface.
7. Secure the base to the wall surface using two mounting screws as illustrated in Figure 3.
Note: Be careful not to overtighten the mounting screws.
PCB Locking
4. Pull approximately 6 in. (152 mm) of wire from the wall and insert the wire through the hole in the controller mounting base.
5. Align the controller mounting base on the wall and use the base as a template to mark the two mounting hole locations.
6. Position the controller mounting base so that the arrow on the base points upward to indicate the top of the controller.
8. Swing the PCB back to the right and carefully snap it into the locking tabs on the controller mounting base.
9. Remove the screw terminal blocks that are attached to a disposable adhesive. Figure 4 illustrates the locations of the screw terminal blocks on the controller.
T606MSx-4 and T606MSx-4+PIR Series Multi-Stage Temperature and Humidity Controllers
2
Installation Instructions

Wiring

!
!
Figure 5: Terminal Blocks
DE
HUM
DI HS
S
COM
Eight-Pole Bottom Connector
OS
HL
AUX
10 11 12 14
15
1613
FIG:T606MSx_trmblk
Five-Pole Left Top Conn ec tor
Y2 G RC
C
1
34
5
Y1
2
Three-Pole Right Top Connector
RH
W2
6
8
W1
7
HUM
9
When an existing controller is replaced, remove and label the wires to identify the terminal functions. When a T606MSx-4 or T606MSx-4+PIR Series Controller is replaced, simply remove the old screw terminal blocks and reinsert them onto the PCB of the replacement controller.
CAUTION: Risk of Electric Shock.
Disconnect power supply before making electrical connections to avoid electric shock.
CAUTION: Risk of Property Damage.
Do not apply power to the system before checking all wiring connections. Short circuited or improperly connected wires may result in permanent damage to the equipment.
IMPORTANT: Make all wiring connections in accordance with local, national, and regional regulations. Do not exceed the electrical ratings of the T606MSx-4 or T606MSx-4+PIR Series Temperature and Humidity Controller.
To wire the controller:
1. Strip the ends of each wire 1/4 in. (6 mm) and connect them to the appropriate screw terminals as indicated in Figure 5.
2. Carefully push any excess wire back into the wall. Note: Seal the hole in the wall with fireproof
material to prevent drafts from affecting the ambient temperature readings.
3. Reinsert the screw terminal blocks onto the PCB. If multiple wires are inserted into the terminals, be sure to properly twist the wires together prior to inserting them into the terminal connectors.
4. For PIR models, carefully reattach the PIR connector to the PCB.
5. Reattach the controller cover to the mounting base (top side first).
6. Use a Phillips-head screwdriver to install the security screw on the bottom of the controller cover if desired. The security screw comes packaged separately in a plastic bag with the controller.
Table 1: Terminal Ident ification (See Figure 5.)
Number Label Function
1
1
2
3
4 RC 24 VAC from Equipment
5 C 24 VAC (Common) from
6 RH 24 VAC for Heating Stage 7
8
9 HUM Humidity Output
10 11 DEHUM Dehumidificatio n Output
12 DI Configurable Digital Input 13 HS 0–10 VDC Remote Humidity
14 SCOM Sensor Common 15 OS Outside Air Temperature Sensor 16 HL 0–10 VDC High Limit Humidity
1. Provides the voltage from RC through a relay contact.
2. Provides the voltage from RH through a relay contact.
Y2
Y1
G
W1
W2
AUX
1
Energizes on a Call for Second-Stage Cooling
1
Energizes on a Call for First-Stage Cooling
Energizes Fan in Accordance with Selected Fan Mode
Transformer
Equipment Transformer
2
Energizes on a Call for First-Stage Heating
2
Energizes on a Call for Second-Stage Heating
1
Auxiliary Output
Sensor
Sensor
T606MSx-4 and T606MSx-4+PIR Series Multi-Stage Temperature and Humidity Controllers Installation Instructions
3
Figure 6: Wiring the T606MSx-4 or T606MSx-4+PIR Series Cont roller
Cool 2
24 VAC
Thermostat Controller
Power
Y2 Y1
GRCC
Heat 1
Heat 2
RH W1
W2
Fan
Cool 1
Scom
HS
DI
0–10 VDC
Remote
Room
Humidity
Sensor
OS
Outdoor
Air
Temperature
Sensor
HUM
0 to 10
VDC
24 VAC
Common
Aux
AUX
0–10 VDC
High Limit
Humidity
Sensor
Cool 2
FIG:T606MSx_wir
Independent Contact
- Lighting
- On/Off Actuation
- Exhaust Fan
DE
HUM
Dehum
Output
Wiring Note s:
1. If you use t he same powe r source for the heat ing stages, in st all a jumper acr oss RC and RH. M aximum curre nt is 2.0 ampere s.
2. If you use t he auxiliary output to toggle oc cupancy of th e el ectronic cont r ol card inside the equipme nt , configure the r elay parameter (Aux Cont) to the Normally Open (N.O.) setting. A second relay can be added for additional occupancy input functions.
3. The humidifier ou tp ut uses a half-br id ge rectifier. The c ont r ol signal refer ence is the con troller power supply common (terminal C).
4. Electro mechanical contacts are used with the dig it al input. Elect r onic triacs can not be used for in put switchin g. U s e terminal C (common) for the switching leg of the digital input.
5. The unit transformer provides power to the controller and the additional loads that are wired to the controller.
Figure 7: Front Cover of Controller (T606MSx-4+PIR Model Shown)
Backlit, plain text
LCD is easy to read
in any condit io n.
Five keys on the therm ost at controller make ope ra t ion easy and int ui tive.
LEDs indicate system activity.
FIG:frnt _vw
PIR motion detector
saves ener gy.
27.0 %RH
70.0 °F
T606MSx-4 and T606MSx-4+PIR Series Multi-Stage Temperature and Humidity Controllers
4
Installation Instructions

Setup and Adjustments

Controller User Interface Keys

The T606MSx-4 and T606MSx-4+PIR Series Temperature and Humidity Controller user interface consists of five keys on the front cover (Figure 7). The function of each key is as follows:
•Use the YES key to:

Integrated PIR Sensor – T606MSx-4+PIR Series Controllers

The integrated PIR sensor allows for automatic switching between fully adjustable Occupied and Unoccupied temperature setpoints without user interaction. This feature generates incremental energy savings during scheduled occupied periods while the space is unoccupied.
- confirm menu selections and to advance to the
next menu item.
- stop the Status Display Menu fr om scrolling
and to manually scroll to the next parameter on the menu.
Note: When the controller is left unattended for 45 seconds, the controller display resumes scrolling.
•Use the NO key to decline a parameter change and to advance to the next menu item.
•Use the MENU key to:
- access the Main User Menu or exit the menu.
- access the Installer Configuration Menu or to
exit the menu (See Configuring the
T606MSx-4 or T606MSx-4+PIR Series Controller on page 8.)
•Use the UP/DOWN arrow keys to change the configuration parameters and to activate a setpoint adjustment.

Backlit LCD

The T606MSx-4 and T606MSx-4+PIR Series Temperature and Humidity Controllers include a 2-line, 8-character backlit display. Low-level backlighting is present during normal operation, and it brighten s when any user interface key is pressed. The backlight returns to low level when the controller is left unattended for 45 seconds.

LEDs

Three LEDs are included to indicate the fan status, call for heat, or call for cooling:
The fan LED is on when the fan is on.
The heat LED is on when heating is on.

Programming Overview

Three menus are used to view , progra m, and configure the T606MSx-4 and T606MSx-4+PIR Series Temperature and Humidity Controllers: the Status Display Menu, the Main User Menu, and the Installer Configuration Menu.

Status Display Menu

The Status Display Menu is displayed during normal controller operation, and continuously scrolls through the following parameters:
Room Temperature and Humidity Note: %RH disp must be set to ON to display
humidity.
Day and Time (T606MSP-4 and T606MSP-4+PIR Models)
System Mode
Schedule Status (Occupied/Unoccupied/Override [PIR Models])
Outside Temperature – An outside air temperature sensor must be installed and connected.
Applicable Alarms – The backlight lights up as an alarm condition is displayed.
Note: Press the YES key to temporarily stop this menu from scrolling.
Note: An option is available within the Installer Configuration Menu to lock out the scrolling display and show only the Room Temperature parameter.

Main User Menu

Use the Main User Menu to access and change the basic operating parameters of the controller. Access the menu by pressing the MENU key during normal controller operation.
The cool LED is on when cooling is on.
T606MSx-4 and T606MSx-4+PIR Series Multi-Stage Temperature and Humidity Controllers Installation Instructions

Installer Configuration Menu

Use the Installer Configuration Menu to set up the controller for application-specific operation. To acce ss the menu, press and hold the MENU key for approximately 8 seconds.
5

Humidification Operation

0°F 20°F-20°F-40°F
FIG:RE_sp
20%
25%
30%
35%
40%
45%
RE Sp = 20%
RH HT = 32°F
RH LT = -20°F
RH Set = 45%
%RH Setpoint
Outside Air Temperature
Figure 8: Humidity Setpoint Reset by
Outdoor Air Temperature
85%
FIG:HLH_cntrl
0%
50%
100%
Control Output Level
Maximum S upply Humidity
Figure 9: High Humidity Limit versus
Control Output Level Curve
Humidification operates only when the controller is in heating mode (system mode = Heat, or system mode = Auto and mode at the controller is Heat). If a call for humidification occurs and the fan is off, the fan is first turned on, then the humidifier output is activated.
In addition to reaching the humidity setpoint, the following events can stop humidification operation:
RH sensor is out of range
System mode switches to Off or Cool
System mode is Auto, but the controller mode changes from Heat to Cool

Humidity Setpoint Reset

The humidity setpoint reset function minimizes condensation found on windows and building structures during the colder months. An outdoor air sensor connected at the controller is required for humidity setpoint reset function.
When the outdoor air temperature falls below the selected high temperature setpoint (RH HT), the humidity setpoint decreases. The lowest humidity setpoint is reached at the selected low temperature setpoint (RH LT).

High Limit Humidity Sensor Operation

The T606MSx-4(+PIR) Series Temperature and Humidity Controller includes a high limit sequence. This sequence allows the use of a remote 0 to 10 VDC humidity sensor to keep the humidifier from saturating the supply air. The remote sensor throttles the output of the Proportional plus Integral plus Derivative (PID) loop if the high limit sensor measures humidity in the duct over the high limit value (85%) less the proportional band of the high limit PID loop. If no sensor is detected at the high limit (HL) connector, this sequence is disabled at the controller.
The Reset Humidity Setpoint (RE Sp) determines the difference between the original se tpoin t and the lowe st setpoint. For example, in Figure 8, the reset humidity setpoint is set to 20%; therefore, the humidity setpoint decreased from 45% to 20%.

Dehumidification Operation

Dehumidification operation depends upon the dehumidification lockout setting.
If Dehumidification Lockout (Dhu LCK) is set to On:
Dehumidification operates when the controller is in cooling mode (system mode = Cool, or system mode = Auto and the mode at the controller is Cool). If a dehumidification demand exists and the fan is off, the fan is first turned on, then the dehumidification output is activated.
In addition to reaching the dehumidification setpoint, the following events can stop dehumidification operation:
RH sensor is out of range
System mode is switched to Off or Heat
System mode is Auto but controller mode is Heat
Room temperature falls below the cooling setpoint less the deadband value
Outside air temperature falls below the dehumidification outside air temperature lockout value
6
T606MSx-4 and T606MSx-4+PIR Series Multi-Stage Temperature and Humidity Controllers Installation Instructions
If Dehumidification Lockout (Dhu LCK) is set to Off:
Figure 10: Increasing Room Temperature Setpoints
Occ Heat
= 72°F
Occ Cool
= 75°F
Unocc Heat
= 65°F
Room Temperature
FIG:rm_tmp
Dehumidification operates when the controller is in any mode except Off. If a dehumidification demand exists and the fan is off, the fan is first turned on, then the dehumidification output is activated.
In addition to reaching the dehumidification setpoint, the following events can stop dehumidification operation at any time:
RH sensor is out of range
The controller automatically switches the occupancy level between Occupied and Unoccupied as req uired , when local movement is sensed. In the Occupied mode, if no movement is detected beyond the Unocc TM parameter setting, the mode changes to Unoccupied. Once movement is detected, the mode changes back to Occupied.
Occupancy sensing is enabled only if a PIR cover is installed. The PIR cover, when installed, is auto detected.
System mode is switched to Off
Outside air temperature falls below the dehumidification outside air temperature lockout value
No active temperature lockout protection is available while the system is in dehumidification mode. If dehumidification operation causes the room temperature to fluctuate, the controller reacts by either activating the cooling or heating outputs based on the current system mode setting.

Occupancy Sensor Operation – T606MSx-4+PIR Series Controllers

A T606MSx-4+PIR Series Controller (or a T606MSx-4 Series Controller equipped with a PIR accessory cover) provides advanced occupancy logic.
Note: The PIR strategy is an occupied strategy. If the controller is programmed to be Unoccupied, the PIR function does not have an effect on the occupancy strategy.

PIR Diagnostic LEDs

The diagnostic LEDs inside the PIR lens brighten when movement is detected within the first 30 minutes after powerup. The LEDs do not light up or brighten after the initial 30-minute period.

Setpoints

The installer must be certain that the difference between the Occupied and Unoccupied setpoints can be recovered within a timely fashion to ensure occupancy comfort. In addition, the difference between the two setpoints must be large enough to warrant maximum energy savings.
These setpoints and Unoccupied timers are adjust able to allow for customization, as dictated by the individual space requirements. See Figure 10 for an example of increasing room temperature setpoints.
T606MSx-4 and T606MSx-4+PIR Series Multi-Stage Temperature and Humidity Controllers Installation Instructions
7

Configuring the T606MSx-4 or T606MSx-4+PIR Series Controller

The T606MSx-4 and T606MSx-4+PIR Series Controllers ship from the factory with default settings for all configurable parameters. The default settings are shown in T able 2. T o reconfigure the parameters via the controller, follow the steps in this section.
1. To access the Installer Configuration Menu, press and hold the MENU key fo r ap pr ox ima te l y 8 seconds.
Note: If the Password parameter is configured, Password 0 appears on the controller display indicating that the configured password is required to proceed. Use the UP/DOWN arrow keys to indicate the configured password, then press the YES key to proceed through the Installer Configuration Menu parameters.
2. Once the Installer Configuration Menu begins, press the NO key to scroll through the parameters listed in Table 2.
Table 2: Installer Configuration Menu (Part 1 of 6)
Parameter Appearing on Display
Pswrd Sets the protective access
%RH disp Enables the display of humidity
1
DI
Description and Default Selection Options
Range: 0 to 1,000 password to prevent unauthorized access to the Installer Configuration Menu.
Default: 0 Note: The default setting does not
lock out access to the Installer Configuration Menu.
(On): Display %RH. (%RH) below the room temperature on the controller display.
Default: Off Configures digital input.
Open Contact Input = function not energized.
Closed Contact Input = function energized.
Default: None
(Off): No %RH display.
(None): No function is associated with an input.
(Service): A Service alarm is displayed on the controller when the
input is energized. Tie this input into the air conditioni n g un i t control
card, which provides an alarm if a malfunction occurs.
(Filter): A Filter alarm is displayed. This alarm can be connected to
a differential pressure switch that monitors a filter.
(RemOVR): Temporary occupancy request via a remote input. This
override function is controlled by a manual remote occupancy
override. When enabled, this condition disables the override
capability of the controller.
(RemNSB): Remote Night Setback (NSB) via a time clock input, an
occupancy sensor, or from a voltage-free contact.
Contact open = Occupied; contact closed = Unoccupied.
(Fan lock): A backlit flashing Fan lock alarm is displayed on the
controller when the input is not energized. This alarm is used in
conjunction with a local airflow sensor connected to the input. The
controller heating or cooling act i on is locked out if no airflow is
detected 10 seconds after the fan (T erminal G) is energized. Contact
open = no airflow; contact closed = airflow present.
3. When the desired parameter is displayed, use the YES key to choose the desired selection option.
4. Press the YES key and then the NO key to continue scrolling through the parameters.
To exit the Installer Configuration Menu at any time, press the MENU key, then at the exit prompt, press the YES key. To pass over a parameter without chan ging it, press the NO key.
When the controller is in the Installer Configuration Menu and left unattended for approximately 8 seconds, the controller reverts to the Status Display Menu.

Configuring the Digital Input

When DI is configured for an alarm condition, an alarm condition is displayed locally when the input is closed. An alarm message is included on the scrolling Status Display Menu and when the message is displayed, the backlight momentarily lights up.
The input can be configured to the Selection Options included in Table 2.
T606MSx-4 and T606MSx-4+PIR Series Multi-Stage Temperature and Humidity Controllers
8
Installation Instructions
Table 2: Installer Configuration Menu (Part 2 of 6)
Parameter
Description and Default Selection Options Appearing on Display
MenuScro Gives the option of having the
display continuously scroll the
parameters.
Default: on Lockout Selectable Lockout Levels for
limiting end-user keypad interaction.
Default: 0
Pwr del
3
Sets the delay time period at
controller powerup, or each time
power is removed and reapplied,
before any operation (fan, heating,
or cooling) is authorized. Also can
be used to sequence the startup of
multiple units in one location.
Default: 10.0 sec Frost pr Provides a minimum heating
setpoint of 42.0°F/5.5°C to prevent
freezing in the zone controlled by
the controller.
Default: off
Heat max
4
Sets the Occupied and Unoccupied
maximum Heating setpoint values.
Default: 90.0°F/32.0°C
Cool min
4
Sets the Occupied and Unoccupied
minimum Cooling setpoint values.
Default: 54.0°F/12.2°C
(off): The scroll is inactive. (on): The scroll is active.
Function Lockout Level
Occupancy Override
Permanent T emperature Setpoints
T emporary T emperature Setpoints
Humidity Setpoints
System Mode Setting
Fan Mode Setting Access No Access No Access Schedules
Setting Clock Setting Permanent Hold
Range: 10.0 to 120.0 sec
(on): Enabled (off): Disabled
Range: 40.0°F/4.5°C to 90.0°F/32.0°C
Range: 54.0°F/12.2°C to 100.0°F/37.7°C
(0) (1) (2)
Access Access No Access
Access No Access No Access
Access Access No Access
Access No Access No Access
Access No Access No Access
Access No Access No Access
2
2
Access Access Access
2
Access No Access No Access
T606MSx-4 and T606MSx-4+PIR Series Multi-Stage Temperature and Humidity Controllers Installation Instructions
9
Table 2: Installer Configuration Menu (Part 3 of 6)
Parameter
Description and Default Selection Options Appearing on Display
Pband Sets the proportional band used by
the controller Proportional-Integral
(PI) control loop.
Default: 2.0F°/1.1C°
Note: The proportional band
default setting of 2.0F°/1.1C°
provides satisfactory controller
operation in most instances. A
proportional band setting other than
the default is normally used in
installations where the location of
the controller is problematic, leading
to unwanted cycling. An example of
a problematic installation is a
wall-mounted controller installed
between the return and supply air
feeds, that is directly influenced by
the supply air stream. Anticycl Anti-Short Cycle timer sets the
minimum on/off times for heating
and cooling.
Default: 2.0 min
Note: Set the anti-short cycle timer
to 0.0 min for equipment that
already has its own anti-short cycle
timer. Heat cph Sets the maximum number of
Heating cycles per hour.
Default: 4.0 Cool cph Sets the maximum number of
Cooling cycles per hour.
Default: 4.0 Deadband Sets the minimum deadband
between the heating and cooling
setpoints.
Default: 2.0F°/1.0C° Fan cont Determines how the fan is activated
in response to a call for heating.
Default: on
Note: The Fan cont parameter
applies to W1 and W2 when the fan
is in the Auto mode only. The Fan
cont parameter does not affect fan
operation on a call for cooling
(Y1 and Y2). Fan del Fan delay extends fan operation
after a heating or cooling cycle has
ended.
Default off
Note: The fan delay is only active
when the fan is in the Auto mode.
(2): 2.0F°/1.1C° (3): 3.0F°/1.7C° (4): 4.0F°/2.2C° (5): 5.0F°/2.8C° (6): 6.0F°/3.3C° (7): 7.0F°/3.9C° (8): 8.0F°/4.4C°
Range: 0.0 to 5.0 min adjustable in 1-minute increments
Range: 3.0 to 8.0 cycles per hour
Range: 3.0 or 4.0 cycles per hour
Range: 2.0F°/1.0C° to 4.0F°/2.0C° adjustable in 1.0F°/0.5C° increments
(off): The controller does not activate the fan in response to a call for heating. The fan is activated by the equipment fan and limit control.
(on): Enables the controller to activate the fan in response to a call for heating.
(on): Extends fan operation by 60 seconds after a heating or cooling cycle has ended.
(off): No extension of fan operation after a heating or cooling cycle has ended.
T606MSx-4 and T606MSx-4+PIR Series Multi-Stage Temperature and Humidity Controllers
10
Installation Instructions
Table 2: Installer Configuration Menu (Part 4 of 6)
Parameter
Description and Default Selection Options Appearing on Display
TOccTime Sets the duration of the Tempo rary
Occupancy Time (when the
controller is in the Unoccupied
mode) when a Schedule Override
Function is enabled using either the
Main User Menu or DI1 or DI2
configured as a temporary override
remote contact (RemOVR).
Sets the effective duration of the
Temporary heating or cooling
setpoints set using the
UP/DOWN arrow keys.
Default: 3.0 hrs Cal RS Sets the desired room air
temperature sensor calibration
(offset). The offset can be added to
or subtracted from the actual
displayed room temperature.
Default: 0.0F°/0.0C°C Cal OS Sets the desired outside air
temperature sensor calibration
(offset). The offset can be added to
or subtracted from the actual
displayed room temperature.
Default: 0.0F°/0.0C° H stage Reverts the operation of a two-stage
controller to a single-stage controller
when the second heating stage is
not needed.
Default: 2.0 C stage Reverts the operation of a two-stage
controller to a single-stage controller
when the second cooling stage is
not needed.
Default: 2.0 H lock Disables heating stage(s) operation
when the outside air temperature is
greater than the configured value. If
the fan mode is set to Auto or
Smart, the fan output is also
disabled. Requires that an outside
air temperature sensor be installed
and connected.
Default: 120°F/49°C C lock Disables cooling stage(s) operation
when the outside air temperature is
less than the configured value. If the
fan mode is set to Auto or Smart,
the fan output is also disabled.
Requires that an outside air
temperature sensor be installed and
connected.
Default: -40°F/-40°C
Range: 0.0 to 12.0 hrs adjustable in 1-hour increments
Range: -5.0F°/-2.5C° to 5.0F°/2.5C° adjustable in 1.0F°/0.5C° increments
Range: -5.0F°/-2.5C° to 5.0F°2.5C° adjustable in 1.0F°/0.5C° increments
(1.0): One Stage (2.0): Two Stages
(1.0): One Stage (2.0): Two Stages
Range: -15°F/-26°C to 120°F/49°C adjustable in 5F°/5C° increments
Range: -40°F/-40°C to 95°F/35°C adjustable in 5F°/5C° increments
T606MSx-4 and T606MSx-4+PIR Series Multi-Stage Temperature and Humidity Controllers Installation Instructions
11
Table 2: Installer Configuration Menu (Part 5 of 6)
Parameter
Description and Default Selection Options Appearing on Display
Unocc TM Sets the time delay between the
moment when the controller toggles
from the Occupied mode to the
Unoccupied mode after the last
motion is detected by the
occupancy sensor.
Default: 0.5 hours
2/4event
Aux cont Energizes peripheral devices
Prog rec
RH LT
RH HT Sets maximum outside air
HL Sp Sets high humidity level setpoint
Dhu OALK
Dhu LCK Enables or disables
DehuHyst Controls dehumidification hysteresis
2
2
5
Sets the number of events within a
24-hour period.
Default: 2.0
(lighting equipment and exhaust
fans).
Default: n.o.
Note: The contact toggles with the
internal Occupied/Unoccupied
schedule (or the NSB contact on
one of the digital inputs, if used).
Provides the desired occupied
temperature either at the start of the
Occupied schedule or after the
Occupied schedule begins.
Default: off
Note: Progressive recovery is
disabled if DI is configured as
remote NSB.
Sets minimum outside air
temperature for RH setpoint reset.
Default: -20°F/-29°C
temperature for RH setpoint reset.
Default: 32°F/0°C
when 0 to 10 VDC sensor is
connected at the controller.
Default: 85% RH
5
Sets outside air temperature under
which dehumidification operation is
disabled.
Default: 32°F/0°C
dehumidification lockout control.
Default: On
when dehumidification sequence is
enabled.
Default: 5% RH
Range: 0.5 hours to 24.0 hours adjustable in 0.5 hour increments
(4.0): Four events (two Occupied and two Unoccupied) within a 24-hour period
(2.0): Two events (one Occupied and one Unoccupied) within a 24-hour period
(n.c.): Contact open = Occupied; contact closed = Unoccupied (n.o.): Contact closed = Occupied; contact open = Unoccupied
(on): Enabled (provides the desired occupied temperature at the
start of the Occupied schedule) (off): Disabled (provides the desired occupied temperature after the
Occupied schedule begins)
Range: -40°F/-40°C to 15°F/-9.5°C
Range: 20°F/-6.5°C to 55°F/13°C
Range: 50 to 90% RH Note: Feature is automatically disabled if no sensor is connected to
the controller
Range: -40°F/-40°C to 122°F/50°C
(On): Dehumidification operation is restricted based on the following conditions:
• System mode must be Cool or Auto
• Low ambient room temperature protection is enabled (Off): Dehumidification process not restricted, the following
conditions are present:
• System mode must be Cool, Heat or Auto
• Ambient room temperature protection is not enabled Range: 2 to 20% RH
T606MSx-4 and T606MSx-4+PIR Series Multi-Stage Temperature and Humidity Controllers
12
Installation Instructions
Table 2: Installer Configuration Menu (Part 6 of 6)
75.0 °F
schd Y/N
ovrd Y/N
set? Y/N
Parameter
Description and Default Selection Options Appearing on Display
5
RE Sp
6
RH Cal
Display HL Displays the high limit sensor value
1. Setting DI to RemNSB disables schedules and stops the Schedule menu display . Any other setting enables schedules and the Schedule menu (T606MSP-4 and T606MSP-4+PIR models).
2. T606MSP-4 and T606MSP-4+PIR models.
3. When adjusting the numeric value, press the UP/DOWN arrow key to change the value by single increments; press and hold the UP/DOWN arrow key to change the numeric value in increments of ten.
4. When adjusting the temperature, press the UP/DOWN arrow key to change the value in 0.5F°/0.5C° increments; press and hold the UP/DOWN arrow key to change the value in 5.0F°/5.0C° increments.
5. This value is valid only when an outdoor air sensor is connected at the controller or a network value is transmitted to the controller.
6. Calibration applies to the internal humidity sensor if no remote humidity sensor is connected. If a remote humidity sensor is connected, calibration applies to that sensor.
Provides RH setpoint when the RH LT outside air temperature value is reached.
Default: 20% RH Sets humidity offset from actual
displayed humidity. Default: 0% RH
and helps troubleshoot and diagnose sensor/humidifier operation.
Default (when no sensor present):
0% RH
Range: 10 to 90% RH
Range: -15% to 15% RH
Range: 0 to 100% RH

Operation

Setup/Operation of the T606MSx-4 or T606MSx-4+PIR Series Controller

Once the controller is configured via the Installer Configuration Menu, set up its operating parameters via the Main User Menu. Access this menu by pressing the MENU key during normal controller operation. The Main User Menu contains the basic operating features of the controller.
The Main User Menu also uses Auto Help, which is displayed automatically in the menu when there is a pause in setup activity . To exit Auto Help, continue with the setup selection. When the controller is in the Main User Menu and is left unattended for 45 seconds, the menu reverts to the Status Display Menu.
Follow the steps in Table 3 to set up the controller.
Table 3: Setting Up the T606MSx-4 or
T606MSx-4+PIR Series Controller (Part 1 of 2)
Controller
Description
Display
Press the MENU key while in the
RoomTemp
Override
Cancel
Temperat
Status Display Menu to enter the Main User Menu.
Overrides Unoccupied Setpoints Only Appears if Controller is in
Unoccupied State See Enabling Temporary Override
Schedule on page 14. Cancels Override Mode
Sets the Temperature Setpoints See Entering Permanent
Temperature Setpoints on page 14.
T606MSx-4 and T606MSx-4+PIR Series Multi-Stage Temperature and Humidity Controllers Installation Instructions
13
Table 3: Setting Up the T606MSx-4 or
Humidity set? Y/N
set? Y/N
set? Y/N
set? Y/N
set? Y/N
hold? Y/N
T606MSx-4+PIR Series Controller (Part 2 of 2)
Controller
Description
Display
Sets the Humidity Setpoints. See
Entering Humidity Setpoints on page
16.
The override schedule prompt only appears when the controller is in the Unoccupied state. This menu selection gives the user the option of overridin g the Unoccupied setpoints with the Occupied setpoints for the amount of time specified under the TOccTime parameter. See Configuring the
T606MSx-4 or
T606MSx-4+PIR Series Controller on page 8.
Note: If DI is configured to operate as a remote override contact, this menu is disabled.
Sys mode
Fan mode
Schedule
Clock
Schedule
Selects the System Mode Default: Automatic (auto)
Entering Humidity Setpoints on
See page 16.
Selects the Fan Mode Default: Automatic (auto) for
T606MSN-4 and T606MSN-4+PIR Models
Smart (smart) for T606MSP-4 and T606MSP-4+PIR Models
Selecting the Fan Mode on page
See
16. Sets the Occupied and Unoccupied
Time Periods
Programming the Daily
See
Schedule – Two-Event (T606MSP-4 and T606MSP-4+PIR Models) on
page 17 and
Schedule – Four-Event (T606MSP-4 and T606MSP-4+PIR Models) on
page 18. Sets the Day and Time
Setting the Day and Time
See
(T606MSP-4 and T606MSP-4+PIR Models) on page 19.
Sets a Permanent Hold on the Schedule or Resumes the Schedule
Setting Schedule Hold on page
See
20.
Programming the Daily
To override the Unoccupied state while in the Main User Menu:
1. Press the NO key for all prompts until the Override Schedule prompt appears. If the controller is in the Unoccupied state, this is the first prompt.
2. Press the YES key to enable the temporary override. The controller returns to the Status Display Menu.
When scrolling through the Status Display Menu, Override now appears for the schedule status parameter.

Canceling the Temporary Override

The Cancel Override (Cancel ovrd) prompt only appears when the controller is in the Unoccupied override mode.
To resume the schedule while in the Main User Menu:
1. Press the NO key for all prompts until the Cancel ovrd prompt appears. If the controller is in the override state, this is the first prompt.
2. Press the YES key to resume the programmed schedule.
The controller returns to the Status Display Menu.

Entering Permanent Temperature Setpoints

The first prompt appearing in the Main User Menu of the controller when in the Occupied state set s the permanent temperature setpoint.
Note: Schedule Set and Clock Set are available on the T606MSP-4 and T606MSP-4+PIR models only.

Enabling Temporary Override Schedule

Note: The Override Schedule function is available on the T606MSN-4 and T606MSN-4+PIR models only when DI is configured as a remote NSB.
Note: The Override Schedule prompt only appears when in the Unoccupied (Unoccup) or Unoccupied Hold (Unoccup hold) mode.
14
To enter the permanent heating and cooling setpoints for the Occupied and Unoccupied modes, follow the steps in Table 4. When changing the temperatures, press and release the keys to change the temperature in 0.5F°/0.5C° increments; press and hold down the keys to change the temperature in 5.0F°/5.0C° increments.
T606MSx-4 and T606MSx-4+PIR Series Multi-Stage Temperature and Humidity Controllers Installation Instructions
Table 4: Entering Permanent Temperature
75.0°F
set? Y/N
set? Y/N
75.0°F
set? Y/N
68.0°F
set? Y/N
80.0°F
set? Y/N
62.0°F
C
set? Y/N
Y/N
Setpoints (Part 1 of 2)
Controller
Description
Display
Press the MENU key while in the
RoomTemp
Sta tus Disp la y Me nu to ent er th e Main User Menu.
Table 4: Entering Permanent Temperature
Setpoints (Part 2 of 2)
Controller
Description
Display
Press the UP/DOWN arrow keys to
Unocc HT
set the temperature. Press the
YES key to store the value and
advance to the next menu.
Temperat
Cooling
Cooling
Heating
Heating
Unocc CL
Unocc CL
Unocc HT
Press the the temperature setpoint prompt appears on the display (it may be the first prompt). Press the enter the temperature setting menu.
Press the Occupied cooling setpoint. Press the
NO key to advance to the Occupied
heating setpoint menu.
Press the set the temperature. Press the
YES key to store the value and
advance to the next menu.
Press the Occupied heating setpoint. Press the
NO key to advance to the
Unoccupied cooling setpoint menu.
Press the set the temperature. Press the
YES key to store the value and
advance to the next menu.
Press the Unoccupied cooling setpoint. Press the Unoccupied heating setpoint.
Press the set the temperature. Press the
YES key to store the value and
advance to the next menu.
Press the Unoccupied heating setpoint. Press the temperature display units.
NO key for all prompts until
YES key to
YES key to change the
UP/DOWN arrow keys to
YES key to change the
UP/DOWN arrow keys to
YES key to change the
NO key to advance to the
UP/DOWN arrow keys to
YES key to change the
NO key to advance to the
YES key to set the display
NO key to
YES key to return to the
°F/°
Exit?
Press the units to °F or °C. Press the advance to the temperature setp oin t type menu.
Press the Status Display Menu or press the
NO key to re-enter the temperature
setting menu.

Entering Temporary Temperature Setpoints

The user can temporarily change the temperature setpoints for the Occupied and Unoccupied heating and cooling modes. To temporarily change the setpoint, press the UP/DOWN arrow keys to change the temporary setpoint for the current mode of operation.
Note: Whether the controller is heating or cooling, the respective setpoint is temporarily adjusted. To toggle between the temporary heating and cooling setpoints, press the NO key while changing the temporary setpoints.

Ending Temporary Temperature Setpoints

The temporary setpoints remain in effect for the duration set in the TOccTime parameter or until manually released.
Note: Setting the TOccTime parameter to 0.0 hrs prevents the temporary setpoints from taking effect.
To manually release the temporary setpoint, while in the Main User Menu:
1. Press the NO key for all prompts until the Temperat set prompt appears. If the controller is in the Occupied state, this is the first prompt.
2. Press the YES key to cancel all temporary setpoints.
3. Press the MENU key again and press the YES key to exit the Main User Menu.
The setpoint reverts to the Permanent Temperature Setpoint.
T606MSx-4 and T606MSx-4+PIR Series Multi-Stage Temperature and Humidity Controllers Installation Instructions
15

Entering Humidity Setpoints

75.0°F
Humidity set? Y/N
Dehumidi set? Y/N
Dehumidi 70 %
Humidifi set? Y/N
Humidifi 50 %
Y/N
75.0 °F
set? Y/N
Sys mode auto
Y/N
You can enter setpoints for humidification and dehumidification after configuring the temperature setpoints. A fixed 5% RH deadband is present between the humidification and dehumidification to prevent overlap in these humidity setpoints. For exampl e, if the humidification setpoint is 50% RH and the dehumidification setpoint is changed from 70% RH to 45% RH, the humidification setpoint is automatically changed to 40% RH by the controller.
To enter humidity setpoints, follow the steps in Table 5.
Table 5: Entering Humidity Setpoints
Controller Display
RoomTemp
Description
Press the MENU key while in the Status Display Menu to enter the Main User Menu.
Press the the humidity setpoint prompt appears on the display. Press the enter the humidity setting menu.
Press the dehumidification setpoint. Press the
NO key to advance to the
humidification setpoint menu.
Press the set the dehumidification setpoint. Press the and advance to the next menu.
Press the humidification setpoint. Press the key to advance to the next menu.
NO key for all prompts until
YES key to
YES key to change the
UP/DOWN arrow keys to
YES key to store the value
YES key to change the
NO

Selecting the System Mode

The controller has four system modes:
Automatic Mode (auto): Automatic changeover between heating and cooling. This is the default setting.
Cooling Mode (cool): Cooling operation only.
Heating Mode (heat): Heating operation only.
Off Mode (off): The controller is off; however, when the frost protection (Frost pr parameter) is enabled, the controller still calls for heat if the temperature falls below 42°F/5.5°C.
To set the system mode, follow the steps in Table 6:
Table 6: Selecting the System Mode
Controller Display
RoomTemp
Sys mode
Exit?
Description
Press the MENU key while in the Status Display Menu to enter the Main User Menu.
Press the until the system mode prompt appears on the display. Press the
YES key to enter the system mode
setting menu. Press the
locate the desired system mode. Press the desired system mode (example for auto mode shown)
NO key for all prompts
UP/DOWN arrow keys to YES key to select the
Press the YES key to return to the Status Displa y Menu or press the NO key to return to the system mode selection menu.
Exit?
16

Selecting the Fan Mode

Press the set the humidification setpoint. Press the advance to the next menu.
Press the Status Display Menu or press the
NO key to re-enter the humidity
setting menu.
T606MSx-4 and T606MSx-4+PIR Series Multi-Stage Temperature and Humidity Controllers Installation Instructions
UP/DOWN arrow keys to
YES key to store the value and
YES key to return to the
The controller has three fan mode settings:
On Fan Mode (on): Energizes the fan all the time for both Occupied and Unoccupied states, even if the system mode is set to off.
Automatic Fan Mode (auto): Energizes the fan only on a call for heating or cooling, for both Occupied and Unoccupied states. This is the default setting for the T606MSN-4 and T606MSN-4+PIR models.
Note: The setting for the Fan cont parameter may affect the fan operation on a call for heating.
Smart Fan Mode (smart): Energizes the fan all
75.0 °F
set? Y/N
Fan mode Smart
Y/N
75.0°F
set? Y/N
y
set? Y/N
day? Y/N
12:00 AM
12:00 AM
y
set? Y/N
previous
set? Y/N
the time for Occupied states, and only on a call for heating or cooling in Unoccupied states. This is the default setting for the T606MSP-4 and T606MSP-4+PIR models.
To select the fan mode, follow the steps in Table 7:
Table 7: Selecting the Fan Mode
Controller
Description
Display
Press the MENU key while in the
RoomTemp
Fan mode
Status Display Menu to enter the Main User Menu.
Press the until the fan mode prompt appears on the display. Press the enter the fan mode setting menu.
Press the locate the desired fan mode. Press the system mode (example for smart mode shown)
NO key for all prompts
YES key to
UP/DOWN arrow keys to
YES key to select the desired
Press the YES key to return to
Exit?
the Status Display Menu or press the NO key to return to the system mode selection menu.
To set the tim e sch ed ul e for a two- ev en t sch ed u le, follow the steps in Table 8. See Table 10, Events 1 and 2, for an example of a two-event office schedule.
Table 8: Programming the Daily Schedule –
Two-Event (Part 1 of 2)
Controller
Description
Display
Press the MENU key while in the
RoomTemp
Schedule
Monda
Occupied
Occupied
Status Display Menu to enter the Main User Menu.
Press the the schedule set prompt appears on the display. Press the enter the scheduling menu.
Press the schedule for Monday or press the
NO key to advance to Tuesday.
Press the Occupied start time for Monday or press the Tuesday. Selecting controller in the Unoccupied state for the entire day.
Press the set the Occupied start time. Press the
YES key to enter the time.
NO key for all prompts until
YES key to
YES key to set the
YES key to set the
NO key to advance to
NO leaves the
UP/DOWN arrow keys to

Programming the Daily Schedule – Two-Event (T606MSP-4 and T606MSP-4+PIR Models)

The schedule-setting menu is used to enter the Occupied or Unoccupied states for each day of the week. The schedule-setting menu reflects either a two- or a four-event schedule per day, based on what was selected in the 2/4event parameter during the configuration process. If the schedule-setting menu does not reflect a two-event schedule, select two events in the 2/4event parameter of the Installer Configuration Menu.
When changing the time, press and release the UP/DOWN arrow keys to change the time in 1-minute increments; press and hold down the keys to change the time in 30-minute increments.
Note: Programming one of the digit al input s to remo te NSB disables the menu.
Unoccup
Tuesda
CopyY/N
Wednesda
Press the set the Unoccupied start time. Press the
Press the schedule for Tuesday or press the
NO key to advance to Wednesday.
Press the schedule from the previous day. Press the schedule.
If the prompt is for Wednesday. Repeat the procedure for the rest of the days of the week.
UP/DOWN arrow keys to
YES key to enter the time.
YES key to set the
YES key to copy the NO key to set a different
YES key was pressed, the next
T606MSx-4 and T606MSx-4+PIR Series Multi-Stage Temperature and Humidity Controllers Installation Instructions
17
Table 8: Programming the Daily Schedule –
Y/N
75.0°F
set? Y/N
set? Y/N
day? Y/N
12:00 AM
12:00 AM
12:00 AM
12:00 AM
y
set? Y/N
previous
set? Y/N
Y/N
Two-Event (Part 2 of 2)
Controller
Description
Display
After setting the schedule for all the
Exit?
days of the week, following the last entry for Sunday, press the to return to the Status Display Menu or press the Monday.
NO key to start again at
YES key

Programming the Daily Schedule – Four-Event (T606MSP-4 and T606MSP-4+PIR Models)

The schedule-setting menu is used to enter the Occupied and Unoccupied states for each day of the week. The schedule-setting menu reflects either a two- or four-event schedule per day, based on what was selected in the 2/4event parameter during the configuration process. If the schedule-setting menu does not reflect a four-event schedule, select four events in the 2/4event parameter of the Installer Configuration Menu.
When changing the time, press and release the UP/DOWN arrow keys once to change the time in 1-minute increments; press and hold down the keys to change the time in 30-minute increments.
Note: Programming one of the digital in puts to remote NSB disables the menu.
Table 9: Programming the Daily Schedule –
Four-Event (Part 2 of 2)
Controller
Description
Display
Press the YES key to set the
Occupied
Occupied
Unoccup
Occupie2
Unoccup2
Occupied start time for Monday or press the Tuesday. Selecting controller in the Unoccupied state for the entire day.
Press the set the first Occupied start time. Press the
Press the set the first Unoccupied start time. Press the
Press the set the second Occupied start time. Press the
Press the set the second Unoccupied start time. Press the time.
NO key to advance to
NO leaves the
UP/DOWN arrow keys to YES key to enter the time.
UP/DOWN arrow keys to YES key to enter the time.
UP/DOWN arrow keys to YES key to enter the time.
UP/DOWN arrow keys to
YES key to enter the
To set the time schedule for a four-event schedule, follow the steps in Table 9. See Table 10 for an example of a four-event office schedule.
Table 9: Programming the Daily Schedule –
Four-Event (Part 1 of 2)
Controller
Description
Display
Press the MENU key from the Status
RoomTemp
Schedule
Monday
Display Menu to enter the Main User Menu.
Press the the schedule set prompt appears on the display. Press the enter the scheduling menu.
Press the schedule for Monday or press the
NO key to advance to Tuesday .
NO key for all prompts until
YES key to
YES key to set the
Tuesda
CopyY/N
Wednesda
Exit?
Press the schedule for Tuesday or press the
NO key to advance to Wednesday.
Press the schedule from the previous day. Press the schedule.
If the prompt is for Wednesday. Repeat the procedure for all days of the week.
After setting the schedule for all the days of the week, following the last entry for Sunday, press the to return to the Status Display Menu or press the Monday.
YES key to set the
YES key to copy the NO key to set a different
YES key was pressed, the next
YES key
NO key to start again at
18
T606MSx-4 and T606MSx-4+PIR Series Multi-Stage Temperature and Humidity Controllers Installation Instructions
75.0°F
set? Y/N
Time set? Y/N
Time 0:00
Day set? Y/N
Day Monday
12/24hrs set? Y/N
12/24hrs 12 hrs
Y/N
Table 10: Four-Event Office Schedule
Event 1 Event 2 Event 3 Event 4
Occupied Unoccupied Occupied 2 Unoccupied 2
Event
Monday 7:00 A.M. 5:00 P.M. Tuesday 7:00 A.M. 5:00 P.M. Wednesday 7:00 A.M. 5:00 P.M. Thursday 7:00 A.M. 5:00 P.M. 7:00 P.M. 10:30 P.M.
Friday 7:00 A.M. 5:00 P.M. 7:00 P.M. 10:30 P.M. Saturday
Sunday
1. Programming different events to the same time for that day cancels those events and leaves the controller in the Unoccupied state.
Cool Heat Cool Heat Cool Heat Cool Heat 72°F
(22°C)
12:00 P.M. 12:00 P.M.
70°F
(21°C)
1 1
80°F
(27°C)
12:00 P.M. 12:00 P.M.
62°F
(17°C)
1 1
72°F
(22°C)
12:00 P.M. 12:00 P.M. 12:00 P.M.
12:00 P.M. 12:00 P.M.
70°F
(21°C)
1 1 1
1 1
80°F
(27°C)
12:00 P.M. 12:00 P.M. 12:00 P.M.
12:00 P.M. 12:00 P.M.
62°F
(17°C)
1 1 1
1 1

Setting the Day and Time (T606MSP-4 and T606MSP-4+PIR Models)

Upon initial powerup (or after a power loss of greater than 6 hours), a SetClock alarm appears on the controller display. As the controller scrolls through the Status Display Menu, the SetClock alarm message causes the backlight to light up until the clock is set.
When changing the time, press and release the UP/DOWN arrow keys once to change the time in 1-minute increments; press and hold down the keys to change the time in 30-minute increments.
To set the day and time, follow the steps in Table 11:
Table 11: Setting the Day and Time (Part 1 of 2)
Controller Display
RoomTemp
Clock
Description
Press the MENU key while in the Status Display Menu to enter the Main User Menu.
Press the NO key for all prompts unt il the clock set prompt appears on the display. Press the YES key to enter the clock set menu.
Table 11: Setting the Day and Time (Part 2 of 2)
Controller
Description
Display
Press the UP/DOWN arrow keys to adjust the time. When the correct time is displayed, press the YES key to store the time.
Press the YES key to enter the day set menu or press the NO key to enter the clock format menu.
Press the UP/DOWN arrow keys to adjust the day. When the correct day is displayed, press the YES key to store the day.
Press the YES key to choose the time format or press the NO key to access the Main User Menu exit prompt.
Press the UP/DOWN arrow keys to select the desired time format. Press the YES key to enter the format.
Press the YES key to set the time or press the NO key to advance to the day set menu.
Exit?
Press the YES key to return to the Status Display Menu or press the NO key to return to the time set menu.
T606MSx-4 and T606MSx-4+PIR Series Multi-Stage Temperature and Humidity Controllers Installation Instructions
19
When the controller scrolls through the day and time, the new day and time should show on the display and no alarm or backlight should be present. If the day or time is incorrect, repeat the Setting the Day and Time (T606MSP-4 and T606MSP-4+PIR Models) procedure.

Setting Schedule Hold

The schedule hold menu sets a permanent hold on the internal scheduling or resumes the schedule. The permanent hold is typically used for non-scheduled events that extend for long periods of time.
Note: The Override Schedule function is available on the T606MSN-4 and T606MSN-4+PIR models only if DI is configured for remote NSB.
Note: The Schedule Hold menu is also displayed if DI is configured for remote NSB.
The schedule hold menu has the following selections:
Permanent Occupied Hold (occ hold): This selection puts the controller into a permanent Occupied state via the Occupied setpoints. Occupied hold appears in the S t atus Display Menu when this selection is active.
Permanent Unoccupied Hold: This selection puts the controller into a permanent Unoccupied state via the Unoccupied setpoints. Unoccup hold appears in the Status Display Menu when this selection is active.
Resume: This selection cancels the permanent hold and enables the regular program schedule.
T o e nable or cancel the permanent h old feature while in the Main User Menu:
1. Press the NO key for all prompts until the schedule hold prompt appears on the display. Press the YES key to set the schedule hold type.
2. Press the UP/DOWN arrow keys to locate the desired permanent hold type (or resume schedule). Press the YES key to enter the selection.
3. Press the YES key to return to the Status Display Menu or press the NO key to change the schedule hold selection again.
T606MSx-4 and T606MSx-4+PIR Series Multi-Stage Temperature and Humidity Controllers
20
Installation Instructions

Accessories

All the accessories in Table 12 include mounting hardware; contact the nearest Johnson Controls® representative to order any of these parts.
Note: Review the technical specifications of the

Repair Information

If the T606MSx-4 or T606MSx-4+PIR Series Controller fails to operate within its specifications, replace the unit. For a replacement controller, contact the nearest Johnson Controls representative.
accessories prior to their use in an application.
Table 12: Accessories (Order Separately)
Code Number Description
Hx-67 Series TE-6361M-1 TE-636S-1 TE-6363P-1 TEC-3-PIR
1. The humidity sensor must have a 0 to 10 VDC output. Remote wall-mounted versions may be used for remote return or room air humidity sensing with the sensor mounted on the wall. Remote duct-mounted humidity sensor may be used for remote return air humidity sensing with the sensor mounted on the return air duct or as a supply air humidity sensor used as a high limit protection.
2. Additional TE-636xx-x Series 10k ohm Johnson Controls Type II Thermistor Sensors are available; refer to the
TE-6300 Series Temperature Sensors Product Bulletin (LIT-216320) for more details.
3. The TEC-3-PIR Accessory Cover can be used to replace the existing cover on a non-PIR T606MSx-4 Series Controller to provide occupancy sensing capability.
1
2
2
2
3
Duct- or Wall-mount Humidity Sensor Duct Mount Air Temperature Sensor Strap-Mount Temperature Sensor Outside Air Temperature Sensor Cover with Occupancy Sensor
Table 13: Display Messages
Display Function
Service Indicates that there is a service alarm in accordance with the programmable Digital Input (DI). Filter Indicates that the filter(s) is dirty in accordance with the programmable Digital Input (DI). Frost on Indicates that the heating is energized by the low limit frost protection room temperature setpoint. SetClock Indicates that there has been a power failure greater than 6 hours and the clock needs to be reset
(T606MSP-4 and T606MSP-4+PIR models).
Fan lock Indicates that the controller heating or cooling action is locked out because no airflow was detected 10
seconds after the fan (Terminal G) was energized.
T606MSx-4 and T606MSx-4+PIR Series Multi-Stage Temperature and Humidity Controllers Installation Instructions
21
Metasys® and Johnson Controls® are registered trademarks of Johnson Controls, Inc.
All other marks herein are the marks of their respective owners. © 2012 Johnson Controls, Inc.
Building Efficiency
507 E. Michigan Street, Milwaukee, WI 53202

Technical Specifications

T606MSx-4 and T606MSx-4+PIR Series Temperature and Humidity Controllers

Power Requirements 19 to 30 VAC, 50/60 Hz, 2 V A (Terminals RC and C) at 24 VAC Nominal, Class 2 or
Safety Extra-Low Voltage (SELV)
Relay Contact Rating (Y2, Y1, G , W1, W2, and AUX)
Digital Inputs Voltage-Free Contacts across Terminal C to Terminal DI Humidification Analog Output
Rating Wire Size 18 AWG (1.0 mm Diameter) Maximum, 22 AWG (0.6 mm Diameter) Recommended Temperature Sensor Type Local 10k ohm Johnson Controls Type II Negative Temperature Coefficient (NTC)
Temperature Range Backlit
Display Heating
Control Cooling
Control
Accuracy T emperature ±0.9F°/±0.5C° at 70.0°F/21.0°C Typical Calibrated
Humidity ±5% RH from 30 to 70% RH at 50 to 90°F (10 to 32°C) Minimum Deadband 2F°/1C° between Heating and Cooling Ambient Conditions Operating 32 to 122°F (0 to 50°C); 95% RH Maximum, Noncondensing
Storage -22 to 122°F (-30 to 50°C); 95% RH Maximum, Noncondensing Compliance United States UL Listed, File E27734, CCN XAPX,
Canada UL Listed, File E27734, CCN XAPX7,
Europe CE Mark – Johnson Controls, Inc., declares that this product is in compliance with
Australia and
New Zealand Shipping Weight T606MSx-4 Models: 0.75 lb (0.34 kg)
19 to 30 VAC, 1.0 A Maximum, 15 mA Minimum 3.0 A Inrush, Class 2 or SELV
0 to 10 VDC into 2k ohm Resistance Minimum
Thermistor Sensor
-40.0°F/-40.0°C to 122.0°F/ 50.0°C in 0.5° Increments
40.0°F/4.5°C to 90.0°F/32.0°C
54.0°F/12.0°C to 100.0°F/38.0°C
Under UL 873, Temperature Indicating and Regulating Equipment FCC Compliant to CFR 47, Part 15, Subpart B, Class A
Under CAN/CSA C22.2 No. 24, Temperature Indicating and Regulating Equipment Industry Canada, ICES-003
the essential requirements and other relevant provisions of the EMC Directive 2004/108/EC.
C-Tick Mark, Australia/NZ Emissions Compliant
T606MSx-4+PIR Models: 0.77 lb (0.35 kg)
The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products.
T606MSx-4 and T606MSx-4+PIR Series Multi-Stage Temperature and Humidity Controllers
22
Installation Instructions
Published in U.S.A. www.johnsoncontrols.com
Loading...