Johnson Controls T600xxx-4 Series, T600xxx-4+PIR Series Catalog Page

Page 1
T600xxx-4 and T600xxx-4+PIR Series
T600xxx-4 and T600xxx-4+PIR Series Thermostat Controllers
Thermostat Controllers
Description
The T600xxN-4 and T600xxN-4+PIR Series Non-programmable and T600xxP-4 and T600xxP-4+PIR Series Programmable Thermostat Controllers are specifically designed for control of single-stage, multi-stage, and heat pump commercial heating and cooling equipment. The T600xxP-4 and T600xxP-4+PIR Series Thermostat Controllers are also specifically designed for control of rooftop units (with and without economizers).
The T600xxx-4+PIR Series Thermostat Controllers have occupancy sensing capability built into the device. These are stand-alone devices that maximize up to 30% energy savings in high-energy usage light commercial buildings, such as schools and hotels, during occupied times by using additional setpoint strategies.
The T600xxx-4 and T600xxx-4+PIR Series Thermostat Controllers provide exceptional temperature control in an easy-to-use and flexible package. All models have over 20 configurable parameters, enabling the thermostat controllers to adapt to a variety of applications.
The T600xxx-4 and T600xxx-4+PIR Series Thermostat Controllers include several models: single-stage (T600HCx-4 and T600HCx-4+PIR Series), heat pump (T600HPx-4 and T600HPx-4+PIR Series), multi-stage (T600MSx-4 and T600MSx-4+PIR Series), and economizer (T600MEP-4 and T600MEP-4+PIR). All models employ a unique, Proportional-Integral (PI) time-proportioning algorithm that virtually eliminates temperature offset associated with traditional, differential-based thermostat controllers.
Refer to the T600xxx-4 and T600xxx-4+PIR
Series Thermostat Controllers Product Bulletin (LIT-12011583) for important product
application information.
Features
• onboard occupancy sensor (Passive Infrared [PIR] Models) — provides energy savings without additional installation time/cost
• password protection option — protects against undesired thermostat controller tampering
• backlit Liquid Crystal Display (LCD) — offers real-time control status of the environment in easy-to-read, English plain text messages with constant backlight that brightens during user interaction
• simplified setpoint adjustment — enables the user to change the setpoint by simply pressing the UP/DOWN arrow keys
• five easy-to-use interface keys — allow for easy commissioning and adjustment of the thermostat controller and eliminates the need for DIP switches
• three Light-Emitting Diodes (LEDs) — provide fan, heating, and cooling status at a glance
Code No. LIT-1900616 November 13, 2009
• two configurable digital inputs — provide additional inputs for advanced functions such as remote night setback, occupancy override, and service or filter alarms
• over 20 configurable parameters – enable the thermostat controller to adapt to any application, allowing installer parameter access without opening the cover
• configurable auxiliary output — provides 24 VAC control for exhaust fans, lighting, and other auxiliary functions
• economizer output (T600MEP-4 and T600MEP-4+PIR models) — controls economizer operation for single- and multi-stage unitary rooftop equipment
Repair Information
If either the T600xxx-4 or T600xxx-4+PIR Series Thermostat Controller fails to operate within its specifications, replace the unit. For a replacement thermostat controller, contact the nearest Johnson Controls® representative.
Accessories
Code Number Description
SEN-600-1 Remote Inside Air Temperature Sensor SEN-600-4 Remote Inside Air Temperature Sensor with Occupancy Override and LED
TE-6361M-1 TE-6363P-1 TEC-3-PIR
1. Additional TE-63xx-x Series 10k ohm Johnson Controls Type II Thermistor Sensors are available; refer to the TE-6300 Series Temperature Sensors
2. The TEC-3-PIR Accessory Cover can be used to replace the existing cover on a non-PIR T600xxx-4 Series Th ermost at Con troller to provide occupancy sensing
The performance specifications are nomina l and conf orm to accep table industr y standar ds. For ap plications a t condition s beyond th ese specification s, consult the local Johnson Controls o ffice. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2012 Johnson Controls, Inc.
1
1
2
Product Bulletin (LIT-216320) for more de tails. When a TE-63xx-x Se ries Sensor is installe d according to remote sensing wiring, the thermost at controller controls based off the temperature sensed by the TE-63xx-x Series Sensor.
capability.
Duct Mount Air Temperature Sensor Outside Air Temperature Sensor Cover with Occupancy Sensor
www.johnsoncontrols.com
1 of 3
Page 2
T600xxx-4 and T600xxx-4+PIR Series Thermostat Controllers (Continued)
T600xxx-4 Series Thermostat Controller (Left) and
T600xxx-4+PIR Series Thermostat Controller (Right)
Dimensions, in. (mm)
4-15/16
(125)
3-3/8
(86)
1-1/8
(29)
(125)
(86)
(36)
70.0ºF
Room Temp
Room Temp
4-15/16
70.0ºF
3-3/8
1-3/8
FIG:dmnsns
Selection Chart
Code Number Description Onboard
Occupancy Sensor
Non-programmable T600HCN-4 Single-Stage No Fan Coil Units, Unit Heaters, and Single-Stage Packaged Heating/Cooling Equipment T600HCN-4+PIR Single-Stage Yes Fan Coil Units, Unit Heaters, and Single-Stage Packaged Heating/Cooling Equipment T600HPN-4 Heat Pump No Heat Pump with Up to Three Heating Stages and Two Cooling Stages T600HPN-4+PIR Heat Pump Yes Heat Pump with Up to Three Heating Stages and Two Cooling Stages T600MSN-4 Multi-Stage No Multi-Stage Packaged Heating/Cooling Equipment T600MSN-4+PIR Multi-Stage Yes Multi-Stage Packaged Heating/Cooling Equipment Programmable T600HCP-4 Single-Stage No Fan Coil Units, Unit Heaters, and Single-Stage Packaged Heating/Cooling Equipment T600HCP-4+PIR Single-Stage Yes Fan Coil Units, Unit Heaters, and Single-Stage Packaged Heating/Cooling Equ ipment T600HPP-4 Heat Pump No Heat Pump with Up to Three Heating Stages and Two Cooling Stages T600HPP-4+PIR Heat Pump Yes Heat Pump with Up to Three Heating Stages and Two Cooling Stages T600MEP-4 Economizer No Packaged Rooftop Units with Economizers T600MEP-4+PIR Economizer Yes Packaged Rooftop Units with Economizers T600MSP-4 Multi-Stage No Multi-Stage Packaged Heating/Cooling Equipment T600MSP-4+PIR Multi-Stage Yes Multi-Stage Packaged Heating/Cooling Equipment
Applications
The performance specifications are nomina l and conf orm to accep table industr y standar ds. For ap plications a t condition s beyond th ese specification s, consult the local Johnson Controls o ffice. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2012 Johnson Controls, Inc.
2 of 3
www.johnsoncontrols.com
Page 3
T600xxx-4 and T600xxx-4+PIR Series Thermostat Controllers (Continued)
Technical Specifications
T600xxx-4 and T600xxx-4+PIR Series Thermostat Controllers
Power Requirements 19 to 30 VAC, 50/60 Hz, 2 VA (Terminals RC and C) at 24 VAC Nominal, Class 2 or
Relay Contact Rating 19 to 30 VAC, 1.0 A Maximum, 15 mA Minimum, 3.0 A Inrush, Class 2 or SELV Digital Inputs Voltage-Free Cont acts across Terminal C to Terminals DI1 or DI2 Economizer Output (T600MEP-4 and
T600MEP-4+PIR Models) Wire Size 18 AWG (1.0 mm Diameter) Maximum, 22 AWG (0. 6 mm Diameter) Recommended Temperature Sensor Type Local 10k ohm Johnson Controls Type II Negative Temperature Coefficient (NTC) Thermistor Sensor Temperature Range Backlit Display -40.0°F/-40.0°C to 122.0°F/50.0°C in 0.5° Increments
Heating Control 40.0°F/4.5°C to 90.0°F/32.0°C
Cooling Control 54.0°F/12.0°C to 100.0°F/38.0°C Accuracy Temperature ±0.9F°/±0.5C° at 70.0°F/21.0°C Ty pical Calibrated Minimum Deadband 2F°/1C° between Heating and Cooling Ambient Conditions Operating 32 to 122°F (0 to 50°C); 95% RH Maximum, Noncondensing
Storage -22 to 122°F (-30 to 50°C); 95% RH Maximum, Noncondensing Compliance United States UL Listed, File E27734, CCN XAPX, Under UL 873, Temperature Indicating and Regulating Equipment
Canada UL Listed, File E27734, CCN XAPX7,
Europe CE Mark, EMC Directive 2004/108/EC
Australia and
New Zealand Shipping Weight T600xxx-4 Models 0.75 lb (0.34 kg)
T600xxx-4+PIR
Models
Safety Extra-Low Voltage (SELV)
0 to 10 VDC into 2k ohm Resistance Minimum
FCC Compliant to CFR 47, Part 15, Subpart B, Class A
Under CAN/CSA C22.2 No. 24, TemperatureIndicating and Regulating Equipment Industry Canada, ICES-003
C-Tick Mark, Australia/NZ Emissions Compliant
0.77 lb (0.35 kg)
The performance specifications are nomina l and conf orm to accep table industr y standar ds. For ap plications a t condition s beyond th ese specification s, consult the local Johnson Controls o ffice. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2012 Johnson Controls, Inc.
www.johnsoncontrols.com
3 of 3