The T600xxN-3 Series non-programmable and
T600xxP-3 Series programmable thermostats are
specifically designed for control of single-stage, multistage, and heat pump commercial heating and cooling
equipment. The T600xxP-3 Series thermostats are
also specifically designed for control of rooftop units
(with and without economizers).
The T600xxx-3 Series thermostats p rovide exceptional
temperature control in an easy-to-use, yet flexible,
package. The T600xxx-3 Series thermostat s have over
20 configurable parameters, enabling the thermo stats
to adapt to a variety of applications.
The T600xxx-3 Series thermostats include several
models: Single-stage (T600HCx-3), Heat Pump
(T600HPx-3), Multi-stage (T600MSx-3), and
Economizer (T600MEP-3). All thermostats use a
unique Proportional-Integral (PI) proportional control
algorithm that virtually eliminates temperature offset
associated with traditional differential based
thermostats.
Code No. LIT-12011193
Issued September 6, 2006
Figure 1: T600xxx-3 Series Thermostat
Table 1: Features and Benefits
FeaturesBenefits
Backlit Liquid Crystal Display (LCD)Offers real-time control status of the environment in easy-to-read,
Simplified Setpoint AdjustmentEnables user to change the setpoint by simply pressing the UP/DOWN
Five Easy-to-Use Interface KeysAllow for easy commissioning and adjustment of the thermostat and
Three Light-Emitting Diodes (LEDs) Provide fan, heating, and cooling status at a glance
Two Configurable Digital InputsProvide additional inputs for advanced functions such as remote night
Over 20 Configurable ParametersEnable the thermostat to adapt to any application, allowing installer
Configurable Auxiliary OutputProvides 24 VAC control for exhaust fans, lighting, and other auxiliary
Economizer Output (T600MEP-3)Controls economizer operation for single- and multi-stage unitary
English plain text messages with constant backlight that brightens
during user interaction.
arrow keys.
eliminates the need for Dual Inline Package (DIP) switches.
setback, occupancy override, and service or filter alarms.
parameter access without opening the thermostat cover.
functions.
rooftop equipment.
T600xxx-3 Series Thermostats Product Bulletin1
Page 2
Product Overview
The T600xxx-3 Series thermostats are sp ecifically
designed for control of the most common commercial
heating and cooling equipment. A number of
configurable parameters enable the
T600xxx-3 Series thermostat to effectively and
efficiently control various types of equipment in nearly
any application. Configuration, setup, and operation of
the T600xxx-3 Series thermostat are extremely intuitive
and are accomplished through the user interface.
The T600xxP-3 Series programmable thermostats
feature a fully programmable 7-day, 2- or 4-event
schedule, along with two programmable digital inputs
and one configurable output, enabling effective and
efficient control of equipment in nearly any application.
IMPORTANT: Use the T600xxx-3 thermostat only
as an operating control. Where failure or malfunction
of these thermostats could le ad to p er sonal injury o r
property damage to the controlled equipment or
other property, additional precautions must be
designed into the system. Incorporate and maintain
other devices such as supervisory or alarm systems
or safety or limit controls intended to warn of, or
protect against, failure or malfunction of the
thermostats.
Additional Features
The T600xxx-3 Series thermostats also offer many
other features:
•Adjustable Heating/Cooling Deadband
Adjusts the minimum heating/cooling deadband
from 2 to 4F° (1 to 2C°).
•Adjustable Power Delay on Start-up
Enables a delay before any operation is authorized
upon power up of the thermostat. Can be used for
equipment protection or to sequence start-up of
multiple units in one location.
•Remote Indoor and Outdoor Sensing
Accommodates remote indoor and outdoor
sensors. Up to three indoor sensors can be
averaged.
•Three Levels of Keypad Lockout
Provide three different levels of keypad lockout that
can be set up through the menu and interface
keys.
•Adjustable Anti-Short Cycling Timer
Adjusts the minimum on and off times for the
equipment from 0 to 5 minutes.
•Frost Protection Enable/Disable
Turns the heat on when the zone temperature
drops below 42°F (5.5°C) regardless of the
thermostat’s mode.
•Adjustable Temporary Occupancy Time
Adjusts the occupancy override time from
0to12hours.
•High and Low Balance Point Adjustments
Enable more precise control of heat pump
operation based on outdoor air temperature
(T600HPx-3).
•System Mode Lockout
Allows the heating and cooling modes to be locked
out based on outdoor air temperature when an
outdoor air sensor is connected.
•Adjustable Maximum Heating/Minimum Cooling
Setpoints
Establish the maximum heating setpoint and
minimum cooling setpoint that can be entered
through the user interface.
•Progressive Recovery
Ensures the correct temperature is reached at the
programmed occupied time.
•Adjustable Heating/Cooling Cycles per Hour
Configurable for a maximum of 3 to 8 heating
cycles and 3 or 4 cooling cycles in a 1-hour period,
balancing temperature control and equipment
cycling.
•Smart Fan
Enables the fan to operate continuously during the
occupied times and cycle with the equipment
during the unoccupied times.
T600xxx-3 Series Thermostats Product Bulletin2
•Non-volatile EEPROM Memory
Prevents loss of adjusted parame ters during power
failure.
•Power Loss Backup for Clock (T600xxP-3)
Retains clock setting for up to 6 hours in case of
power loss.
•Heating and Cooling Stage Enable/Disable (T600MEP-3, T600MSx-3)
Allows operation of the second-stage heating and
cooling to be disabled, reverting the thermostat to
single-stage operation on multi-stage the rmostats.
•Heat Pump Compressor Stage Enable/Disable
(T600HPx-3)
Allows operation of the second-stage compressor
to be disabled, reverting the thermostat to singlestage compressor operation on heat pump
thermostats.
Page 3
•Fan Operation Control
Enables the user to select how the fan operates on
a call for heating and the delay at the end of the
heating or cooling cycle.
Backlit
plain English text
LCD is
easy to read
in any condi t io n.
LEDs indicate
system activity.
Five keys
make operation
easy and i ntuiti ve.
Room Temp
70.0ºF
3-3/8
(86)
4-15/16
Figure 2: T600 Thermostat
(125)
t
n
r
f
_
0
0
6
T
:
G
I
F
1-1/8
(29)
-access the Installer Configuration Menu or to
exit the menu
•Use the UP/DOWN arrow keys to change the
configuration parameters and to activate a setpoint
adjustment.
Backlit Liquid Crystal Display (LCD)
The T600xxx-3 Series thermostat includes a 2-line,
8-character backlit display. Low-level backlighting is
present during normal operation, and it brightens wh en
any user interface key is pressed. The backlight returns
to low level when the thermostat is left unattended for
45 seconds.
Light-Emitting Diodes (LEDs)
Three LEDs are included to indicate the fan status, call
for heat, or call for cooling on the T600HCx-3,
T600MSx-3, and T600MEP-3 thermostats:
•The FAN LED is on when the fan is on.
•The HEAT LED is on when heating is on.
•The COOL LED is on when cooling is on.
On the T600HPx-3 thermostats, the three LEDs
indicate heat pump operation.
•The FAN LED is on when the fan is on.
•The AUX HEAT LED is on when auxiliary heat is
on
Thermostat User Interface Keys
The T600xxx-3 Series thermostat user interface
consists of five keys on the front cover (as illustrated in
Figure 2). The function of each key is as follows:
•Use the YES/SCROLL key to:
-confirm menu selections and to advance to the
next menu item
-stop the Status Display Menu from scrolling
and to manually scroll to the next parameter on
the menu
Note: When the thermostat is left unattended for
45 seconds, the thermostat display resumes
scrolling.
•Use the NO key to decline a parameter change and
to advance to the next menu item.
•Use the MENU key to:
-access the Main User Menu or exit the menu
•The HEAT-PUMP LED is on when the heat-pump
compressor is on.
Programming Overview
There are three menus used to view, program, and
configure the T600xxx-3 Series thermostat:
The Status Display Menu is displayed during normal
thermostat operation. This menu continuously scrolls
through the following parameters:
•Room Temperature
•Day and Time (T600xxP-3)
•System Mode
•Occupancy Status – Occupied/Unoccupied/
Override
•Outdoor Temperature – An outdoor air temper ature
sensor must be connected.
•Applicable Alarms – The backlight lights up as an
alarm condition is displayed.
Note: Press the YES/SCROLL key to temporarily stop
this menu from scrolling.
T600xxx-3 Series Thermostats Product Bulletin 3
Page 4
The Main User Menu is used to access and change
the basic operating parameters of the thermostat.
Access this menu by pressing the MENU key during
normal thermostat operation.
The Installer Configuration Menu is used to set up
the thermostat for application-specific operation. To
access this menu, press and hold the MENU key for
approximately 8 seconds.
•Number of Heat Pump Stages (T600HPx-3)
•Heating Operation Lockout Based on Outdoor Air
Temperature
•Cooling Operation Lockout Based on Outdoor Air
Temperature
•Two or Four Events per Day Configuration
(T600xxP-3)
The Installer Configuration Menu includes the following
parameters that are accessed by pressing the same
MENU key:
•Number of Heating S tages (T600MSx-3 and
T600MEP-3)
•Number of Cooling Stages (T600MSx-3 and
T600MEP-3)
•Auxiliary Output Configuration
•Enable/Disable Progressive Recovery
The following parameters are for the T600HPx-3
thermostats:
•Low Balance Point
•High Balance Point
•Comfort/Economy Heat Pump Operation
•Reversing Valve Operation
•Compressor/Auxiliary Interlock
The following parameters are for the T600MEP-3
thermostat:
•Economizer Changeover Setpoint
•Outdoor Air Minimum Position
•Mechanical Cooling Operation w/ Economizer
•Mixed Air Temperat ur e Set po in t
•Displaying the Mixed Air Temperature
Repair Information
If the T600xxx-3 Series thermostat fails to operate
within its specifications, replace the unit. For a
replacement T600xxx-3 Series thermostat, contact the
nearest Johnson Controls® representative.
Ordering Information
Table 2: T600xxx-3 Series Thermostats (Part 1 of 2)
Code NumberDescriptionApplications
Non-Programmable
T600HCN-3Single-stageFan Coil Units, Unit Heaters, and Single-stage Packaged Heating/Cooling Equipment
T600HPN-3Heat PumpHeat Pump with up to 3 Heating/2 Cooling Stages
Table 2: T600xxx-3 Series Thermostats (Part 2 of 2)
Programmable
T600HCP-3Single-stageFan Coil Units, Unit Heaters, and Single-stage Packaged Heating/Cooling Equipment
T600HPP-3Heat PumpHeat Pump with up to 3 Heating/2 Cooling Stages
T600MEP-3 EconomizerPackaged Rooftop Units with Economizers
T600MSP-3Multi-stageMulti-stage Packaged Heating/Cooling Equipment
Table 3: Accessories (Order Separately)
Code NumberDescription
SEN-600-1Remote Indoor Air Temperature Sensor
SEN-600-4Remote Indoor Air Temperature Sensor with Occupancy Override and LED
1
TE-6361P-18 in. (203 mm)
TE-6363P-1Outdoor Air Temperature Sensor
1.Other probe lengths available.
Duct Mount Air Temperature Sensor
T600xxx-3 Series Thermostats Product Bulletin 5
Page 6
Technical Specifications
T600xxx-3 Series Thermostats
Power Requirements19 to 30 VAC, 50/60 Hz, 2 VA (Terminals 4 and 5) at 24 VAC Nominal, Class 2 or
Safety Extra-Low Voltage (SELV)
Relay Contact Rating Maximum
Inductive
Digital Input sVoltage-Free Contacts across Terminal C to Terminals DI1 or DI2
Economizer Output0 to 10 VDC into 2k ohm resistance minimum (T600MEP-3 only)
Recommended Wire Size18 AWG (1.0 mm Diameter) Maximum, 22 AWG (0.6 mm Diameter) Recommended
Sensor TypeLocal 10k ohm NTC thermistor
Temperature RangeBacklit
Display
Heating
Control
Cooling
Control
AccuracyT emperature±0.9F°/±0.5C° at 70.0°F/21.0°C Typical Calibrated
Minimum Deadband2F°/1C° between Heating and Cooling
Ambient ConditionsOperating32 to 122°F (0 to 50°C); 95% RH Maximum, Noncondensing
Storage-22 to 122°F (-30 to 50°C); 95% RH Maximum, Noncondensing
Dimensions (H x W x D)4.94 x 3.38 x 1.13 in. (125 x 86 x 29 mm)
ComplianceUnited States UL Listed, File E27734, CCN XAPX,
CanadaUL Listed, File E27734, CCN XAPX7,
EuropeCE Mark, EMC Directive 89/336/EEC
Australia and
New Zealand
Shipping Weight0.75 lb (0.34 kg)
30 VAC, 1.0 A Maximum, 3.0 A In-Rush
-40.0°F/-40.0°C to 122.0°F/ 50.0°C in 0.5° Increments
40.0°F/4.5°C to 90.0°F/32.0°C
54.0°F/12.0°C to 100.0°F/38.0°C
Under UL 873, Temperature Indicating and Regulating Equipment
FCC Compliant to CFR 47, Part 15, Subpart B, Class A
Under CAN/CSA C22.2 No. 24, Temperature Indicating and Regulating Equipment
Industry Canada, ICES-003
C-Tick Mark, Australia/NZ Emissions Compliant
The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these
specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or
misuse of its products.
United States Emissions Compliance:
This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of the FCC Rules. These
limits are designed to provide reasonable protection against harmful interference when this equipment is operated in a commercial
environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the
instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause
harmful interference, in which case the user will be required to correct the interference at his/her own expense.
Canadian Emissions Compliance:
This Class (A) digital apparatus meets all requirements of the Canadian Interference-Causing Equipment Regulations.
Cet appareil numérique de la Classe (A) respecte toutes les exigences du Règlement sur le matériel brouiller du Canada.