Johnson Controls T600xxx-3 Series, T600HCN-3, T600HPN-3, T600MSN-3, T600HCP-3 Product Bulletin

...
Page 1
T600xxx-3 Series Thermostats
Product Bulletin
The T600xxN-3 Series non-programmable and T600xxP-3 Series programmable thermostats are specifically designed for control of single-stage, multi­stage, and heat pump commercial heating and cooling equipment. The T600xxP-3 Series thermostats are also specifically designed for control of rooftop units (with and without economizers).
The T600xxx-3 Series thermostats include several models: Single-stage (T600HCx-3), Heat Pump (T600HPx-3), Multi-stage (T600MSx-3), and Economizer (T600MEP-3). All thermostats use a unique Proportional-Integral (PI) proportional control algorithm that virtually eliminates temperature offset associated with traditional differential based thermostats.
Code No. LIT-12011193
Issued September 6, 2006
Figure 1: T600xxx-3 Series Thermostat
Table 1: Features and Benefits
Features Benefits
Backlit Liquid Crystal Display (LCD) Offers real-time control status of the environment in easy-to-read,
Simplified Setpoint Adjustment Enables user to change the setpoint by simply pressing the UP/DOWN
Five Easy-to-Use Interface Keys Allow for easy commissioning and adjustment of the thermostat and
Three Light-Emitting Diodes (LEDs) Provide fan, heating, and cooling status at a glance Two Configurable Digital Inputs Provide additional inputs for advanced functions such as remote night
Over 20 Configurable Parameters Enable the thermostat to adapt to any application, allowing installer
Configurable Auxiliary Output Provides 24 VAC control for exhaust fans, lighting, and other auxiliary
Economizer Output (T600MEP-3) Controls economizer operation for single- and multi-stage unitary
English plain text messages with constant backlight that brightens during user interaction.
arrow keys.
eliminates the need for Dual Inline Package (DIP) switches.
setback, occupancy override, and service or filter alarms.
parameter access without opening the thermostat cover.
functions.
rooftop equipment.
T600xxx-3 Series Thermostats Product Bulletin 1
Page 2
Product Overview
The T600xxx-3 Series thermostats are sp ecifically designed for control of the most common commercial heating and cooling equipment. A number of configurable parameters enable the T600xxx-3 Series thermostat to effectively and efficiently control various types of equipment in nearly any application. Configuration, setup, and operation of the T600xxx-3 Series thermostat are extremely intuitive and are accomplished through the user interface.
The T600xxP-3 Series programmable thermostats feature a fully programmable 7-day, 2- or 4-event schedule, along with two programmable digital inputs and one configurable output, enabling effective and efficient control of equipment in nearly any application.
IMPORTANT: Use the T600xxx-3 thermostat only as an operating control. Where failure or malfunction of these thermostats could le ad to p er sonal injury o r property damage to the controlled equipment or other property, additional precautions must be designed into the system. Incorporate and maintain other devices such as supervisory or alarm systems or safety or limit controls intended to warn of, or protect against, failure or malfunction of the thermostats.
Additional Features
The T600xxx-3 Series thermostats also offer many other features:
Adjustable Heating/Cooling Deadband Adjusts the minimum heating/cooling deadband from 2 to 4F° (1 to 2C°).
Adjustable Power Delay on Start-up Enables a delay before any operation is authorized upon power up of the thermostat. Can be used for equipment protection or to sequence start-up of multiple units in one location.
Remote Indoor and Outdoor Sensing Accommodates remote indoor and outdoor sensors. Up to three indoor sensors can be averaged.
Three Levels of Keypad Lockout Provide three different levels of keypad lockout that can be set up through the menu and interface keys.
Adjustable Anti-Short Cycling Timer Adjusts the minimum on and off times for the equipment from 0 to 5 minutes.
Frost Protection Enable/Disable Turns the heat on when the zone temperature drops below 42°F (5.5°C) regardless of the thermostat’s mode.
Adjustable Temporary Occupancy Time Adjusts the occupancy override time from 0to12hours.
High and Low Balance Point Adjustments Enable more precise control of heat pump operation based on outdoor air temperature (T600HPx-3).
System Mode Lockout Allows the heating and cooling modes to be locked out based on outdoor air temperature when an outdoor air sensor is connected.
Adjustable Maximum Heating/Minimum Cooling
Setpoints
Establish the maximum heating setpoint and minimum cooling setpoint that can be entered through the user interface.
Progressive Recovery Ensures the correct temperature is reached at the programmed occupied time.
Adjustable Heating/Cooling Cycles per Hour Configurable for a maximum of 3 to 8 heating cycles and 3 or 4 cooling cycles in a 1-hour period, balancing temperature control and equipment cycling.
Smart Fan Enables the fan to operate continuously during the occupied times and cycle with the equipment during the unoccupied times.
T600xxx-3 Series Thermostats Product Bulletin2
Non-volatile EEPROM Memory Prevents loss of adjusted parame ters during power failure.
Power Loss Backup for Clock (T600xxP-3) Retains clock setting for up to 6 hours in case of power loss.
Heating and Cooling Stage Enable/Disable (T600MEP-3, T600MSx-3) Allows operation of the second-stage heating and cooling to be disabled, reverting the thermostat to single-stage operation on multi-stage the rmostats.
Heat Pump Compressor Stage Enable/Disable
(T600HPx-3)
Allows operation of the second-stage compressor to be disabled, reverting the thermostat to single­stage compressor operation on heat pump thermostats.
Page 3
Fan Operation Control Enables the user to select how the fan operates on a call for heating and the delay at the end of the heating or cooling cycle.
Backlit plain English text LCD is easy to read in any condi t io n.
LEDs indicate system activity.
Five keys make operation easy and i ntuiti ve.
Room Temp
70.0ºF
3-3/8
(86)
4-15/16
Figure 2: T600 Thermostat
(125)
t
n
r
f _
0
0 6 T
: G
I F
1-1/8
(29)
- access the Installer Configuration Menu or to exit the menu
•Use the UP/DOWN arrow keys to change the configuration parameters and to activate a setpoint adjustment.
Backlit Liquid Crystal Display (LCD)
The T600xxx-3 Series thermostat includes a 2-line, 8-character backlit display. Low-level backlighting is present during normal operation, and it brightens wh en any user interface key is pressed. The backlight returns to low level when the thermostat is left unattended for 45 seconds.
Light-Emitting Diodes (LEDs)
Three LEDs are included to indicate the fan status, call for heat, or call for cooling on the T600HCx-3, T600MSx-3, and T600MEP-3 thermostats:
•The FAN LED is on when the fan is on.
•The HEAT LED is on when heating is on.
•The COOL LED is on when cooling is on.
On the T600HPx-3 thermostats, the three LEDs indicate heat pump operation.
•The FAN LED is on when the fan is on.
•The AUX HEAT LED is on when auxiliary heat is on
Thermostat User Interface Keys
The T600xxx-3 Series thermostat user interface consists of five keys on the front cover (as illustrated in Figure 2). The function of each key is as follows:
•Use the YES/SCROLL key to:
- confirm menu selections and to advance to the next menu item
- stop the Status Display Menu from scrolling and to manually scroll to the next parameter on the menu
Note: When the thermostat is left unattended for 45 seconds, the thermostat display resumes scrolling.
•Use the NO key to decline a parameter change and to advance to the next menu item.
•Use the MENU key to:
- access the Main User Menu or exit the menu
•The HEAT-PUMP LED is on when the heat-pump compressor is on.
Programming Overview
There are three menus used to view, program, and configure the T600xxx-3 Series thermostat:
The Status Display Menu is displayed during normal thermostat operation. This menu continuously scrolls through the following parameters:
Room Temperature
Day and Time (T600xxP-3)
System Mode
Occupancy Status – Occupied/Unoccupied/ Override
Outdoor Temperature – An outdoor air temper ature sensor must be connected.
Applicable Alarms – The backlight lights up as an alarm condition is displayed.
Note: Press the YES/SCROLL key to temporarily stop this menu from scrolling.
T600xxx-3 Series Thermostats Product Bulletin 3
Page 4
The Main User Menu is used to access and change the basic operating parameters of the thermostat. Access this menu by pressing the MENU key during normal thermostat operation.
The Installer Configuration Menu is used to set up the thermostat for application-specific operation. To access this menu, press and hold the MENU key for approximately 8 seconds.
Number of Heat Pump Stages (T600HPx-3)
Heating Operation Lockout Based on Outdoor Air Temperature
Cooling Operation Lockout Based on Outdoor Air Temperature
Two or Four Events per Day Configuration (T600xxP-3)
The Installer Configuration Menu includes the following parameters that are accessed by pressing the same MENU key:
DI1 and DI2 Input Configuration
Three Keypad Lockout Levels
Power Delay on Power up
Frost Protection
Maximum Heating Setpoint/Minimum Cooling Setpoint
Anti-Short Cycle Timer
Heating Stages Cycles per Hour
Cooling Stages Cycles per Hour
Minimum Deadband
Fan Control
End of Cycle Fan Delay
Temporary Occupancy Time
Room Air Sensor Calibration
Outdoor Air Sensor Calibration
Number of Heating S tages (T600MSx-3 and T600MEP-3)
Number of Cooling Stages (T600MSx-3 and T600MEP-3)
Auxiliary Output Configuration
Enable/Disable Progressive Recovery The following parameters are for the T600HPx-3
thermostats:
Low Balance Point
High Balance Point
Comfort/Economy Heat Pump Operation
Reversing Valve Operation
Compressor/Auxiliary Interlock The following parameters are for the T600MEP-3
thermostat:
Economizer Changeover Setpoint
Outdoor Air Minimum Position
Mechanical Cooling Operation w/ Economizer
Mixed Air Temperat ur e Set po in t
Displaying the Mixed Air Temperature
Repair Information
If the T600xxx-3 Series thermostat fails to operate within its specifications, replace the unit. For a replacement T600xxx-3 Series thermostat, contact the nearest Johnson Controls® representative.
Ordering Information
Table 2: T600xxx-3 Series Thermostats (Part 1 of 2)
Code Number Description Applications
Non-Programmable T600HCN-3 Single-stage Fan Coil Units, Unit Heaters, and Single-stage Packaged Heating/Cooling Equipment T600HPN-3 Heat Pump Heat Pump with up to 3 Heating/2 Cooling Stages
T600MSN-3 Multi-stage Multi-stage Packaged Heating/Cooling Equipment
T600xxx-3 Series Thermostats Product Bulletin4
Page 5
Table 2: T600xxx-3 Series Thermostats (Part 2 of 2)
Programmable T600HCP-3 Single-stage Fan Coil Units, Unit Heaters, and Single-stage Packaged Heating/Cooling Equipment
T600HPP-3 Heat Pump Heat Pump with up to 3 Heating/2 Cooling Stages T600MEP-3 Economizer Packaged Rooftop Units with Economizers T600MSP-3 Multi-stage Multi-stage Packaged Heating/Cooling Equipment
Table 3: Accessories (Order Separately)
Code Number Description
SEN-600-1 Remote Indoor Air Temperature Sensor SEN-600-4 Remote Indoor Air Temperature Sensor with Occupancy Override and LED
1
TE-6361P-1 8 in. (203 mm) TE-6363P-1 Outdoor Air Temperature Sensor
1. Other probe lengths available.
Duct Mount Air Temperature Sensor
T600xxx-3 Series Thermostats Product Bulletin 5
Page 6
Technical Specifications
T600xxx-3 Series Thermostats
Power Requirements 19 to 30 VAC, 50/60 Hz, 2 VA (Terminals 4 and 5) at 24 VAC Nominal, Class 2 or
Safety Extra-Low Voltage (SELV)
Relay Contact Rating Maximum Inductive
Digital Input s Voltage-Free Contacts across Terminal C to Terminals DI1 or DI2 Economizer Output 0 to 10 VDC into 2k ohm resistance minimum (T600MEP-3 only) Recommended Wire Size 18 AWG (1.0 mm Diameter) Maximum, 22 AWG (0.6 mm Diameter) Recommended Sensor Type Local 10k ohm NTC thermistor Temperature Range Backlit
Display Heating
Control Cooling
Control
Accuracy T emperature ±0.9F°/±0.5C° at 70.0°F/21.0°C Typical Calibrated Minimum Deadband 2F°/1C° between Heating and Cooling Ambient Conditions Operating 32 to 122°F (0 to 50°C); 95% RH Maximum, Noncondensing
Storage -22 to 122°F (-30 to 50°C); 95% RH Maximum, Noncondensing Dimensions (H x W x D) 4.94 x 3.38 x 1.13 in. (125 x 86 x 29 mm) Compliance United States UL Listed, File E27734, CCN XAPX,
Canada UL Listed, File E27734, CCN XAPX7,
Europe CE Mark, EMC Directive 89/336/EEC
Australia and
New Zealand Shipping Weight 0.75 lb (0.34 kg)
30 VAC, 1.0 A Maximum, 3.0 A In-Rush
-40.0°F/-40.0°C to 122.0°F/ 50.0°C in 0.5° Increments
40.0°F/4.5°C to 90.0°F/32.0°C
54.0°F/12.0°C to 100.0°F/38.0°C
Under UL 873, Temperature Indicating and Regulating Equipment FCC Compliant to CFR 47, Part 15, Subpart B, Class A
Under CAN/CSA C22.2 No. 24, Temperature Indicating and Regulating Equipment Industry Canada, ICES-003
C-Tick Mark, Australia/NZ Emissions Compliant
The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products.
United States Emissions Compliance:
This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when this equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference, in which case the user will be required to correct the interference at his/her own expense.
Canadian Emissions Compliance:
This Class (A) digital apparatus meets all requirements of the Canadian Interference-Causing Equipment Regulations. Cet appareil numérique de la Classe (A) respecte toutes les exigences du Règlement sur le matériel brouiller du Canada.