Johnson Controls T600HPP-2 Installation Instructions Manual

Page 1
Installation Instructions Issue Date December 1, 2004
T600HPP-2 Programmable Thermostat
IMPORTANT: Use this T600HPP-2
programmable thermostat only as an operating control. Where failure or malfunction of the thermostat could lead to personal injury or property damage to the controlled equipment or other property, additional precautions must be designed into the system. Incorporate and maintain other devices such as supervisory or alarm systems or safety or limit controls intended to warn of, or protect against, failure or malfunction of the thermostat.
The T600HPP-2 is a programmable heat pump thermostat that provides exceptional accuracy through the use of a unique Proportional-Integral (PI) time proportioning algorithm. The algorithm virtually eliminates temperature offset associated with traditional, differential-based on/off thermostats. The T600HPP-2 also uses an adaptive control logic algorithm to control the space temperature during recovery to minimize overshoot while providing maximum comfort. Additionally, the menu driven backlit display, plain text menus, and five keys on the T600HPP-2 make programming the thermostat easy and intuitive.
To install the thermostat:
1. Remove the security screw on the bottom of the thermostat cover using a Phillips-head screwdriver. Open the thermostat by pulling on the bottom side of the thermostat cover (Figure 1).
2. Unlock the Printed Circuit Board (PCB) by carefully pressing the locking tab to the right (Figure 2). Open the thermostat’s PCB to the left.
3. Pull out approximately 6 in. (152 mm) of wires from the wall and insert the cable through the hole in the base.
4. Align the base on the wall, and using the base as a template, mark the location of the two mounting holes on the wall. Confirm the thermostat base is installed with the proper side up.
5. Use the supplied anchors and screws for mounting on drywall or plaster. Drill two 3/16 in. (4.7 mm) holes at the marked locations and tap nylon anchors flush to wall surface (Figure 3).
6. Position base on the wall, insert screws through mounting base, and fasten into wall anchors. Do not overtighten screws.
Installation
7. Swing the thermostat PCB back to the right to close. Gently press on the PCB to secure each of
Location Considerations
Locate the T600HPP-2 thermostat:
on a partitioning interior wall, and approximately 5 ft. (1.5 m) above the floor in a location of average temperature
the locking tabs.
8. Pull out the screw terminal blocks using the pull-tabs on each connector (Figure 4).
Note: The number of terminals on the terminal blocks varies depending on the T600 model.
away from direct sunlight, radiant heat, outside walls, behind doors, air discharge grills, stairwells, or outside doors
away from steam or water pipes, warm air stacks, unheated/uncooled areas, or sources of electrical interference
© 2004 Johnson Controls, Inc. Part No. 24-9889-134, Rev. — www.johnsoncontrols.com
1
Page 2
r e
v o C _ e
v o
m e R _ C E T _
0 0 6 T
Figure 1: Removing the Thermostat Cover
Wiring
s
k
c o
l B _
l a
n
i m
r e
T _ C E T
_ 0 0 6 T
Figure 4: Removing the Terminal Blocks
PCB
LockingTabs
t a
t S _
m
n e p
O _ C E T _
0 0 6 T
Figure 2: Opening the Thermostat PCB
e
s
a B _ g n
i
t n u o
M _ C E T _
0 0 6 T
Figure 3: Mounting the Thermostat Base
!
CAUTION: Risk of Electric Shock. Disconnect power supply before making electrical connections to avoid electric shock.
Note: When replacing an existing thermostat, remove and label wires to identify terminal designations. When replacing a T600HPP thermostat, simply remove the terminal blocks and reinsert on to the new thermostat.
To wire the thermostat:
1. Strip each wire 1/4 in. (6.35 mm) and connect to the appropriate terminal according to the wiring diagram (Figure 5).
2. Gently push excess wire back into wall, plug the wall hole with fireproof material to prevent drafts from affecting ambient temperature readings, and install screw terminal blocks back onto the PCB.
3. Reattach the thermostat cover to the installed base (top side first) and install the security screw on the bottom.
!
CAUTION: Risk of Property Damage.
Do not apply power to the system before checking all wiring connections. Short circuited or improperly connected wires may result in permanent damage to the equipment.
2 T600HPP-2 Programmable Thermostat Installation Instructions
Page 3
V
Terminal
Y1 Y2
G
RC
C RH W1
O/B
AUX
D1 D2
RS
Scom
OS
Y2 Y1
Cool 2
Function
Energizes first stage co m pressor on a call for heating or cool i ng Energizes second st age compressor on a call f or heating or cooling Energizes fan in accordance with the selected fan mode 24 VAC from equipment transformer 24 VAC (comm o n) f ro m eq uipment tra nsformer 24 VAC for auxiliary heat Energizes auxiliary heat Energizes reversing va lv e ( con f ig ur ab le to energiz e va lve on a call for heat or ca ll fo r coo li ng ) Configur able auxiliar y output Configur able digital in put Configur able digital in put Remote roo m sensor Sensor common Outdoor air sensor
GRCC RHW1O/B
Cool 1
Fan
Heat 1
Rev
Valve
5 pole left top connector
Y1 G RC
Y2
6 pole bottom connector
Aux D1 D2 RS
AUX
D1 D2
Aux
3 pole right top connector
C
RH W1 O/B
Scom
OS
Scom
OSRS
24 VAC
Thermostat Power
Y2 Y1
R3
R2
Separate 24 V AC
Transformer
If using the same power source for the ther m ostat and heating loads, in stall a jumper across RC and RH.
DC Switching Application for He at Pumps
GRCC
RH W1 O/B
O/B
R1
R4
R4-1
T o Au xiliary Heat Circuit
Note:
(provided by the user).
Figure 5: T600HPP-2 Thermostat Wiring Schematic
Remote
Room
Sensor
Heat Pump Circuit Car d
RC
GY1Y2
R1-1 R2-1
Use 24 VAC interface relays
Remote Outdoor
Sensor
R3-1
g n
i
r
i W
_
2
­P P H
0 0
6 T
T600HPP-2 Programmable Thermostat Installation Instructions 3
Page 4
Setup and Adjustments
Thermostat Operation Overview
Backlit, plain text, Liquid Crystal Display (LCD) is easy to read in any condition.
Room Temp
75.0ºF
Light Emi t ting Diodes (L E Ds) indicate system activi t y.
Five keys on the T600 make operation easy and intuitive.
Figure 6: T600HPP-2 Thermostat Front Cover
r
e
v
o C _
t n o
r F _ C E T _ 0 0 6 T
Thermostat Interface Keys
The T600HPP-2 interface consists of five keys on the front cover, and one configuration key (Figure 7) that is accessed by removing the front cover. Use the:
YES/SCROLL key to:
confirm menu selections, and to advance to
the next menu item
stop the Status Display Menu from scrolling and to manually scroll to the next parameter on the menu. When left unattended for 45 seconds, the display resumes scrolling.
NO key when you do not desire a parameter change, and to advance to the next menu item
MENU key to access the Main User Menu or exit the menu
UP/DOWN arrow keys to:
adjust values
activate a Temporary Setpoint
y e K _ g
i
f n o C _ C E T
Configuration
Key
_ 0 0 6 T
Figure 7: Configuration Key Location
Backlit Liquid Crystal Display (LCD)
The T600HPP-2 uses a two-line, eight-character backlit display. Low level backlighting is present during normal operation and it brightens when any user interface key is pressed. The backlight returns to the lower level when the thermostat is left unattended for 45 seconds.
Light-Emitting Diodes (LED)s
Three LEDs are used to indicate the status of the fan, call for heat, or call for cooling. When:
the fan is on, the FAN LED lights up
auxiliary heat is on, the AUX HEAT LED lights up
4 T600HPP-2 Programmable Thermostat Installation Instructions
the heat pump compressor is on, the HEAT-PUMP LED lights up
Page 5
r
A
Programming Overview
There are three menus used to view, program, and configure the T600HPP-2 thermostat: the Status Display, Main User, and Installer Configuration Menus.
The Status Display Menu is displayed during normal thermostat operation. The menu continually scrolls through the following parameters.
Room Temperature
Day and Time
System Mode
Schedule Status (Occupied/Unoccupied)
Outdoor Temperature (providing sensor is
connected and functional)
Applicable Alarms (the backlight lights up as an alarm condition is displayed)
To temporarily stop the scrolling, press the YES/SCROLL key.
The Main User Menu is used to access and change the thermostat’s basic operating parameters. Access the menu by pressing the MENU key during normal thermostat operation.
The Installer Configuration Menu is used to set up the thermostat for application specific operation. Access the menu by removing the front cover and pressing the configuration key, labeled CONFIG (Figure 7).
Configuring the T600HPP-2
The T600HPP-2 ships from the factory with default settings for all configurable parameters. The default settings are shown in Table 1. To reconfigure the parameters, follow the steps in this section for the corresponding parameters. To set up the parameters, access the Installer Configuration Menu. Access the Installer Configuration Menu by removing the front cover and pressing the configuration key (Figure 7).
Exit the Installer Configuration Menu any time by pressing the MENU key and, at the exit prompt, pressing the YES key. To pass over a parameter without changing it, press the NO key.
When the thermostat is in the Installer Configuration Menu and left unattended for 45 seconds, it reverts to the Status Display Menu.
Table 1: Installer Configuration Menu
RoomTemp
75.0 °F
DI1 set? Y/N
DI2 set? Y/N
Lockout set? Y/N
Pwr del set? Y/N
Frost p set? Y/N
Heat max set? Y/N
Cool min set? Y/N
nticycl
set? Y/N
Heat cph set? Y/N
Cool cph set? Y/N
Continued on the next page . . .
Remove the cover and press the CONFIG key from the Status Display Menu to enter the Installer Configuration Menu.
Configures Digital Input 1 Default: No Function (None) See the Configuring the Digital Inputs (DI1 and DI2) section.
Configures Digital Input 2 Default: No Function (None) See the Configuring the Digital Inputs (DI1 and DI2) section.
Sets Keypad Lockout Level Default: No Lockout (0) See the Enabling Keypad Lockout (Lockout) section.
Sets Power-up Delay Default: Ten Seconds (10.0 sec) See the Setting the Power-up Delay (Pwr del) section.
Enables/Disables Frost Protection Default: Disabled (Off) See the Enabling Frost Protection (Frost pr) section.
Sets the Maximum Heating Setpoint Default: 90.0°F (32.0°C) See the Setting the Maximum Heating Setpoint (Heat max) section.
Sets the Minimum Cooling Setpoint Default: 54.0°F (12.0°C) See the Setting the Minimum Cooling Setpoint (Cool min) section.
Sets the Anti-Short Cycle Timer Default: Two Minutes (2.0 min) See the Setting the Anti-Short Cycle Timer (Anticycl).
Sets the Maximum Heating Cycles per Hour (Auxiliary Heating) Default: Four (4.0) See the Setting the Maximum Heating Cycles per Hour (Heat cph) section.
Sets the Maximum Cooling Cycles per Hour (Compressor Cycles) Default: Four (4.0) See the Setting the Maximum Cooling Cycles per Hour (Cool cph) section.
T600HPP-2 Programmable Thermostat Installation Instructions 5
Page 6
A
Table 1: Installer Configuration Menu (Cont.)
Deadband set? Y/N
Fan cont set? Y/N
Fan del set? Y/N
TOccTime set? Y/N
Cal RS set? Y/N
Cal OS set? Y/N
HP Stage set? Y/N
H lock set? Y/N
C lock set? Y/N
Sets the Minimum Heating/Cooling Deadband Default: 2.0°F (1.1°C) See the Setting the Heating/Cooling Deadband (Deadband) section.
Determines how the Fan Activates in Response to a call for Heat Default: Thermostat Controls Fan (On) See the Setting the Fan Control (Fan cont) section.
Delays Fan Termination at Cycle’s End for 60 Seconds Default: No Delay (Off) See the Setting the Fan Delay (Fan del) section.
Sets the Duration for Temporary Occupancy Time Default: Three Hours (3.0 hrs) See the Establishing the Temporary Occupancy Time (TOccTime) section.
Room Air Sensor Calibration (Offset) Default: 0.0°F (0.0°C) See the Room Air Sensor Calibration (Cal RS) section.
Outdoor Air Sensor Calibration (Offset) Default: 0.0°F (0.0°C) See the Outdoor Air Sensor Calibration (Cal OS) section.
Selects the Number of Compressor Stages Default: Two Stages See the Enable/Disable Heat Pump Stage (HP Stage) section.
Disables Heating Operation based on Outdoor Air Temperature Default: 120°F (49°C) See the Setting the Heating Lockout (H lock) section.
Disables Cooling Operation based on Outdoor Air Temperature Default: -40°F (-40°C) See the Setting the Cooling Lockout (C lock) section.
2/4event set? Y/N
ux cont
set? Y/N
Prog Rec set? Y/N
Hi b.p. set? Y/N
Lo b. p. set? Y/N
Comf/eco set? Y/N
Re valve set? Y/N
Comp/aux set? Y/N
Sets the Number of Events in 24-Hour Period Default: Two Events (2.0) See the Selecting the Number of Events (2/4event) section.
Sets the Auxiliary Contact as Normally Open or Normally Closed Default: Normally Open (N.O.) See the Configuring the Auxiliary Contact (Aux cont) section.
Enable/Disable Progressive Recovery Default: Off See the Enable/Disable Progressive Recovery (Prog Rec) section.
Set the High Balance Point Default: 90°F (32°C) See the Setting the High Balance Point (Hi b.p.) section.
Set the Low Balance Point Default: -12°F (-24°C) See the Setting the Low Balance Point (Lo b.p) section.
Set the Comfort or Economy Mode Default: Comfort See the Selecting Comfort or Economy Mode (Comf/eco) section.
Sets the Reversing Valve Operation Default: O See the Selecting the Reversing Valve Operation (Re valve) section.
Sets the Compressor/Auxiliary Heat Interlock Default: Off See the Compressor/Auxiliary Interlock (Comp/aux) section.
6 T600HPP-2 Programmable Thermostat Installation Instructions
Page 7
Configuring the Digital Inputs (DI1 and DI2)
Press the configuration menu access key. The first prompt is to program Digital Inputs DI1 and DI2.
The digital inputs display an alarm condition when the input is closed. An alarm message is included on the scrolling Status Display Menu, and when the message displays, the backlight momentarily lights up.
Each digital input can be programmed in one of five conditions:
None – No function is associated with the input.
Service – A Service alarm is displayed.
Filter – A Filter alarm is displayed.
RemNSB – Remote Night Setback (NSB) timer
clock input. The scheduling is set per the digital input when this option is selected. The time continues to be displayed, but the menu related to scheduling is disabled and no longer accessible.
Open Contact = Occupied setpoints
Closed Contacts = Unoccupied setpoints
RemOVR – Remote override contact. This
disables all override menu functions of the thermostat. The override function is controlled manually by a remote, momentarily closed contact. When configured in this mode, the input operates in a toggle mode. With this function enabled, it is now possible to toggle between unoccupied and occupied setpoints for the amount of time set by the temporary occupancy time parameter.
When override is enabled through the digital inputs, an Override message appears in the Status Display Menu.
To configure the digital inputs while in the Installer Configuration Menu:
1. The first prompt is to configure the digital inputs. Press YES to configure Digital Input 1 or NO to advance to Digital Input 2.
2. Use the UP/DOWN arrow keys to locate the desired function for the Digital Input 1. Press YES to select the desired function.
3. Press YES to configure Digital Input 2 or NO to advance to the keypad lockout setup prompt.
4. Use the UP/DOWN arrow keys to locate the desired function for the Digital Input 2. Press YES to select the desired function.
The display now shows the keypad lockout setup prompt. See the Enabling Keypad Lockout (Lockout) section for instructions.
Enabling Keypad Lockout (Lockout)
The T600HPP-2 has three levels of keypad lockout. The levels and degree of lockout are shown in Table 2.
To set the keypad lockout level while in the Installer Configuration Menu:
1. Answer NO to all prompts until the keypad lockout setup prompt appears in the display. Press YES to enter the keypad lockout menu.
2. Use the UP/DOWN arrow keys to locate the desired lockout level. Press YES to select the level.
The display now shows the power delay setup prompt. See the Setting the Power-up Delay (Pwr del) section for instructions.
Table 2: Keypad Lockout Levels
Level 0 Level 1 Level 2
Resume to
Scheduling
Temperature
Setpoints
System Mode
Setting
Fan Mode
Setting
Schedules
Setting
Clock Setting
Permanent
Hold
Yes access Yes access No access
Yes access No access No access
Yes access Yes access No access
Yes access Yes access No access
Yes access No access No access
Yes access Yes access
Yes access Yes access No access
Yes
access
Setting the Power-up Delay (Pwr del)
On initial power-up of the T600HPP-2 (or each time power is removed and reapplied), there is a delay before any operation is authorized (fan, cooling, and heating). The delay time is adjustable between 10 and 120 seconds. This parameter can also be used to sequence the start-up of multiple units in one location.
Note: When adjusting the time with the UP/DOWN arrow keys, holding the keys changes the time by 10-second intervals.
To set the delay time while in the Installer Configuration Menu:
1. Answer NO to all prompts until the power delay setup prompt appears in the display. Press YES to enter the power delay setup menu.
2. Use the UP/DOWN arrow keys to adjust the power-up delay setting. Press YES to store the setting.
T600HPP-2 Programmable Thermostat Installation Instructions 7
Page 8
The display now shows the frost protection setup prompt. See the Enabling Frost Protection (Frost pr) section for setup instructions.
Enabling Frost Protection (Frost pr)
Frost protection establishes a minimum heating setpoint of 42°F (5.5°C) to prevent freezing in the zone controlled by the thermostat. If enabled, frost protection is activated even if the thermostat is set to the Off System Mode. If frost protection is active, it is displayed as an alarm (Frost on with the backlight lit) on the Status Display Menu.
To enable frost protection while in the Installer Configuration Menu:
1. Answer NO to all prompts until the frost protection setup prompt appears in the display. Press YES to enter the frost protection menu.
2. Use the UP/DOWN arrow keys to select off or on. Press YES to store the selection.
The display now shows the maximum heating setpoint prompt. See the Setting the Maximum Heating Setpoint (Heat max) section for instructions.
Setting the Maximum Heating Setpoint (Heat max)
The maximum heating setpoint establishes the maximum temperature in the heating setpoint range that can be adjusted from the Main User Menu for both occupied and unoccupied periods. The parameter is adjustable from 40 to 90°F (4.5 to 32°C).
Note: When adjusting the temperature, holding the keys down changes the temperature by 5 F/C° increments.
To set the maximum heating setpoint while in the Installer Configuration Menu:
1. Answer NO to all prompts until the maximum heating setpoint prompt appears in the display. Press YES to enter the maximum heating setpoint menu.
2. Use the UP/DOWN arrow keys to adjust the maximum heating setpoint temperature. Press YES to store the value.
The display now shows the minimum cooling setpoint prompt. See the Setting the Minimum Cooling Setpoint (Cool min) section for instructions.
Setting the Minimum Cooling Setpoint (Cool min)
The minimum cooling setpoint establishes the minimum temperature in the cooling setpoint range that can be adjusted from the Main User Menu for both occupied and unoccupied periods. The parameter is adjustable from 54 to 100°F (12 to 37.5°C).
Note: When adjusting the temperature, holding the keys down changes the temperature by 5 F/C° increments.
To set the minimum cooling setpoint while in the Installer Configuration Menu:
1. Answer NO to all prompts until the minimum cooling setpoint prompt appears in the display. Press YES to enter the minimum cooling setpoint menu.
2. Use the UP/DOWN arrow keys to adjust the minimum cooling setpoint temperature. Press YES to store the value.
The display now shows the anti-short cycle timer prompt. See the Setting the Anti-Short Cycle Timer (Anticycl) section for instructions.
Setting the Anti-Short Cycle Timer (Anticycl)
The anti-short cycle timer establishes the minimum on/off times for the cooling and heating stages. The timer is adjustable from 0 to 5 minutes in 1-minute increments. Set the anti-short cycle to 0 for equipment that possesses its own anti-short cycle timer.
!
CAUTION: Risk of Property Damage.
Do not set the T600HPP-2 anti-short cycling timer to 0 minutes, if the controlled equipment is not protected by its own internal anti-short cycling timer. Setting the anti-short cycling timer to 0 minutes may result in damage to the controller.
To set the anti-short cycle time while in the Installer Configuration Menu:
1. Answer NO to all prompts until the anti-short cycle timer prompt appears in the display. Press YES to enter the anti-short cycle timer menu.
2. Use the UP/DOWN arrow keys to adjust the minimum on/off times for the heating and cooling stages. Press YES to store the value.
8 T600HPP-2 Programmable Thermostat Installation Instructions
The display now shows the heating cycles per hour setup prompt. See the Setting the Maximum Heating Cycles per Hour (Heat cph) section for instructions.
Page 9
Setting the Maximum Heating Cycles per Hour (Heat cph)
The heating cycles per hour establishes the maximum number of times the auxiliary heat is turned on and off in one hour. The selection ranges from three to eight cycles per hour.
Note: A higher number of heating cycles per hour results in more accurate temperature control, but could accelerate the wear of mechanical components in the equipment.
To set the maximum number of heating cycles per hour while in the Installer Configuration Menu:
1. Answer NO to all prompts until the heating cycles per hour prompt appears in the display. Press YES to enter the heating cycles per hour menu.
2. Use the UP/DOWN arrow keys to adjust the maximum number of heating cycles per hour. Press YES to store the value.
The display now shows the cooling cycles per hour setup prompt. See the Setting the Maximum Cooling Cycles per Hour (Cool cph) section for instructions.
Setting the Maximum Cooling Cycles per Hour (Cool cph)
The cooling cycles per hour establishes the maximum number of times the compressor stages (independent of heating or cooling mode) is turned on and off in one hour. The selection ranges from three to four cycles per hour.
Note: A higher number of cooling cycles per hour results in more accurate temperature control, but could accelerate the wear of mechanical components in the equipment.
To set the maximum number of cooling cycles per hour while in the Installer Configuration Menu:
1. Answer NO to all prompts until the cooling cycles per hour prompt appears in the display. Press YES to enter the cooling cycles per hour menu.
2. Use the UP/DOWN arrow keys to adjust the maximum number of compressor cycles per hour. Press YES to store the value.
The display now shows the minimum heating/cooling deadband prompt. See the Setting the Heating/Cooling Deadband (Deadband) section for instructions.
Setting the Heating/Cooling Deadband (Deadband)
The heating/cooling deadband setting establishes the minimum difference between the heating and cooling setpoints. The range is adjustable from 2 to 4 F° (1 to 2 C°).
To change the minimum deadband between the heating and cooling setpoints while in the Installer Configuration Menu:
1. Answer NO to all prompts until the deadband setpoint prompt appears in the display. Press YES to enter the deadband setpoint menu.
2. Use the UP/DOWN arrow keys to adjust the minimum deadband between the heating and cooling setpoints. Press YES to store the value.
The display now shows the fan control prompt. See the Setting the Fan Control (Fan cont) section for instructions.
Setting the Fan Control (Fan cont)
This parameter controls how the fan activates in response to a call for auxiliary heating.
When the fan is in Auto Mode (as selected on the Main User Menu):
Selecting on enables the thermostat to control the fan on a call for heating or cooling.
Selecting off enables the thermostat to energize the fan on a call for cooling only. On a call for auxiliary heating, the fan is controlled by the equipment fan limit control.
To set the fan control while in the Installer Configuration Menu:
1. Answer NO to all prompts until the fan control prompt appears in the display. Press YES to enter the fan control menu.
2. Using the UP/DOWN arrow keys, select on or off. Press YES to store the selection.
The display now shows the fan delay prompt. See the Setting the Setting the Fan Delay (Fan del) section for instructions.
Setting the Fan Delay (Fan del)
The fan delay extends the fan operation by 60 seconds after the call for heating or cooling has ended. This feature is only active when the fan is in the Auto mode.
To enable the fan delay while in the Installer Configuration Menu:
1. Answer NO to all prompts until the fan delay prompt appears in the display. Press YES to enter the fan delay menu.
2. Using the UP/DOWN arrow keys, select on or off. Press YES to store the selection.
T600HPP-2 Programmable Thermostat Installation Instructions 9
Page 10
The display now shows the occupancy override prompt. See the Establishing the Temporary Occupancy Time (TOccTime) section for instructions.
Establishing the Temporary Occupancy Time (TOccTime)
The temporary occupancy time is the length of time the occupied mode setpoints are used when the override function is enabled (the override function can be enabled from the Main User Menu or from one of the digital inputs) or a temporary setpoint is entered. The range is adjustable from 0 to 12 hours.
To change the temporary occupancy time while in the Installer Configuration Menu:
1. Answer NO to all prompts until the temporary occupancy time prompt appears in the display. Press YES to enter the temporary occupancy time menu.
2. Use the UP/DOWN arrow keys to adjust the length of time the temporary occupancy setpoint should be in effect. Press YES to store the time.
The display now shows the room sensor calibration prompt. See the Room Air Sensor Calibration (Cal RS) section for instructions.
To change the outdoor air sensor calibration/offset while in the Installer Configuration Menu:
1. Answer NO to all prompts until the outdoor sensor calibration prompt appears in the display. Press YES to enter the outdoor sensor calibration menu.
2. Use the UP/DOWN arrow keys to adjust the correction that should be applied to the sensor reading. Press YES to store the offset.
The display now shows the heat pump stage setting prompt. See the Enable/Disable Heat Pump Stage (HP Stage) section for instructions.
Enable/Disable Heat Pump Stage (HP Stage)
This parameter reverts the operation of two-stage heat pump thermostat to a single stage when the second compressor stage is not needed.
To change the second stage operation while in the Installer Configuration Menu:
1. Answer NO to all prompts until the setting the
heat pump stages prompt appears in the display. Press YES to enter the setting the heat pump stages menu.
2. Use the UP/DOWN arrow keys to select 1.0 or
2.0 stages. Press YES to store the selection.
Room Air Sensor Calibration (Cal RS)
An offset can be added or subtracted to the actual displayed room temperature as needed. The range is ±5.0 F° (±2.5 C°), adjustable in increments of 1 F° (0.5 C°).
To change the room sensor calibration/offset while in the Installer Configuration Menu:
1. Answer NO to all prompts until the room sensor calibration prompt appears in the display. Press YES to enter the room sensor calibration menu.
2. Use the UP/DOWN arrow keys to adjust the correction that should be applied to the sensor reading. Press YES to store the offset.
The display now shows the outdoor air sensor calibration prompt. See the Outdoor Air Sensor Calibration (Cal OS) section for instructions.
Outdoor Air Sensor Calibration (Cal OS)
An offset can be added or subtracted to the actual displayed outdoor air temperature as needed. The range is ±5.0 F° (±2.5 C°), adjustable in increments of 1 F° (0.5 C°).
The display now shows the heating lockout prompt. See the Setting the Heating Lockout (H lock)
section
for instructions.
Setting the Heating Lockout (H lock)
This feature disables heating operation based on outdoor air temperature (requires outdoor air temperature sensor to be connected for the function to be enabled). If the outdoor air temperature is above the heating lockout temperature, heating operation is disabled.
The heating lockout temperature parameter is adjustable from -15 to 120°F (-26 to 49°C) in increments of 5 F/C°.
To change the outdoor air temperature heating lockout while in the Installer Configuration Menu:
1. Answer NO to all prompts until the heating lockout prompt appears in the display. Press YES to enter the heating lockout menu.
2. Use the UP/DOWN arrow keys to adjust the lockout temperature. Press YES to store the value.
The display now shows the cooling lockout prompt. See the Setting the Cooling Lockout (C lock) section for instructions.
10 T600HPP-2 Programmable Thermostat Installation Instructions
Page 11
Setting the Cooling Lockout (C lock)
This feature disables cooling operation based on outdoor air temperature (requires outdoor air temperature sensor to be connected for the function to be enabled). If the outdoor air temperature is below the cooling lockout temperature, cooling operation is disabled.
The cooling lockout temperature parameter is adjustable from -40 to 95°F (-40 to 35°C) in increments of 5 F/C°.
To change the outdoor air temperature cooling lockout while in the Installer Configuration Menu:
1. Answer NO to all prompts until the cooling lockout prompt appears in the display. Press YES to enter the cooling lockout menu.
2. Use the UP/DOWN arrow keys to adjust the lockout temperature. Press YES to store the value.
The display now shows the number of events prompt. See the Selecting the Number of Events (2/4event) section for instructions.
Selecting the Number of Events (2/4event)
This feature sets the number of events per 24-hour period that can be programmed into the daily schedule.
Two events selects one occupied and one unoccupied period per 24 hours and four events selects two occupied and two unoccupied periods per 24 hours.
To change the number of events in a 24-hour period while in the Installer Configuration Menu:
1. Answer NO to all prompts until the number of events prompt appears in the display. Press YES to enter the number of events menu.
2. Use the UP/DOWN arrow keys to select 2 or 4 events. Press YES to store the value.
The display now shows the auxiliary contact configuration prompt. See the Configuring the Auxiliary Contact (Aux cont) section for instructions.
Configuring the Auxiliary Contact (Aux cont)
The auxiliary contact is an output that can be used to energize peripheral devices (for example, lighting equipment, exhaust fans, and economizers). The contact can be configured as normally open or normally closed and toggles with the internal occupied/unoccupied schedule (or the remote NSB contact on one of the digital inputs, if used).
Table 3: Operation of Auxiliary Contact
Configuration
Setup
Normally Opened
Normally Closed
Contact
Occupied
Status
Closed Opened
Opened Closed
Contact
Unoccupied
Status
To configure the auxiliary contact while in the Installer Configuration Menu:
1. Answer NO to all prompts until the auxiliary contact prompt appears in the display. Press YES to enter the auxiliary contact menu.
2. Use the UP/DOWN arrow keys to select Normally Open (N.O.) or Normally Closed (N.C.). Press YES to store the selection.
The display now shows the progressive recovery prompt. See the Enable/Disable Progressive Recovery (Prog Rec) section for instructions.
Enable/Disable Progressive Recovery (Prog Rec)
When progressive recovery is enabled, the desired occupied temperature is attained by the time the occupied schedule starts.
When progressive recovery is disabled, the system restarts at the programmed occupied time.
Note: Programming one of the digital inputs to remote NSB disables the progressive recovery function.
To enable/disable the progressive recovery feature while in the Installer Configuration Menu:
1. Answer NO to all prompts until the progressive recovery prompt appears in the display. Press YES to enter the progressive recovery menu.
2. Use the UP/DOWN arrow keys to select on or off. Press YES to store the selection.
The display now shows the high balance point prompt. See the Setting the High Balance Point (Hi b.p.) section for instructions.
T600HPP-2 Programmable Thermostat Installation Instructions 11
Page 12
Setting the High Balance Point (Hi b.p.)
The high balance point is the outdoor temperature at which the auxiliary heat is not used. Above the high balance point, only the heat pump is used to maintain the heating setpoint. If no outdoor air sensor is connected, auxiliary heat pump operation may still be used above the high balance point.
The high balance point is adjustable from 34 to 90°F (1 to 32°C) in increments of 0.5 F/C°. Holding the keys down changes the temperature by intervals of 5 F/C°.
To set the high balance point while in the Installer Configuration Menu.
1. Answer NO to all prompts until the set high balance point prompt appears in the display. Press YES to enter the high balance point menu.
2. Use the UP/DOWN arrow keys to adjust the high balance point. Press YES to enter the value.
The display now shows the low balance point prompt. See the Setting the Low Balance Point (Lo b.p.) section for instructions.
Setting the Low Balance Point (Lo b.p.)
The low balance point is the outdoor temperature at which the heat pump operation is terminated when the heat pump is in the heating mode. Below the low balance point, only the auxiliary heat is used to maintain the heating setpoint. If no outdoor air sensor is connected, heat pump operation may still be used below the low balance point.
The low balance point is adjustable from -40 to 34°F (-40 to 1°C) in increments of 0.5 F/C°. Holding the keys down changes the temperature by intervals of 5 F/C°.
To set the low balance point while in the Installer Configuration Menu:
1. Answer NO to all prompts until the set low balance point prompt appears in the display. Press YES to enter the low balance point menu.
2. Use the UP/DOWN arrow keys to adjust the low balance point. Press YES to enter the value.
The display now shows the comfort/economy selection prompt. See the Selecting Comfort or Economy Mode (Comf/eco) section for instructions.
Selecting Comfort or Economy Mode (Comf/eco)
This feature selects how the auxiliary heat is used on heat pump models. The selections are Comfort or Economy mode.
Comfort Mode (in heating mode) If the heat pump is not able to satisfy the heating setpoint, the auxiliary heat is energized to satisfy the same heating setpoint.
Economy Mode (in heating mode) If the heat pump is not able to satisfy the heating setpoint, the auxiliary heat is energized to satisfy the setpoint only when the temperature has dropped 2.0°F (1.1°C) below the heating setpoint.
Note: Selecting Economy Mode adds a deadband between the heat pump and auxiliary heat in heating mode. The actual temperature maintained is lower than the true heating setpoint to maximize the heat pump operation. When the outdoor temperature drops below the Low Balance Point, the deadband is eliminated.
Economy Mode (in emergency heat mode) If emergency heat mode is selected, the setpoint maintained is the heating setpoint.
To select the heat pump mode while in the Installer Configuration Menu:
1. Answer NO to all prompts until the comfort or
economy mode prompt appears in the display. Press YES to enter the mode selection menu.
2. Use the UP/DOWN arrow keys to select comfort
or economy mode. Press YES to enter the value.
The display now shows the reversing valve operation prompt. See the Selecting the Reversing Valve Operation (Re valve) section for instructions.
Selecting the Reversing Valve Operation (Re valve)
This parameter governs the reversing valve operation. When selecting O, the valve energizes in cooling operation (valve is normally heat). When selecting B, the valve energizes in the heating operation (valve is normally cool).
To select the reversing valve mode while in the Installer Configuration Menu:
1. Answer NO to all prompts until the reversing
valve operation prompt appears in the display. Press YES to enter the reversing valve operation menu.
2. Use the UP/DOWN arrow keys to select O or B.
Press YES to enter the selection.
The display now shows the compressor/auxiliary interlock prompt. See the Compressor/Auxiliary Interlock (Comp/aux) section for instructions.
12 T600HPP-2 Programmable Thermostat Installation Instructions
Page 13
Compressor/Auxiliary Interlock (Comp/aux)
This parameter sets the sequence of operation of the heat pump compressor and auxiliary heat. The choices are off and on.
Interlock Off (in heating mode only)
If the heat pump is not able to satisfy the heating setpoint, the auxiliary heat is energized at the same time as the heat pump stage. This typically applies when the air handler heat pump coil is installed before the auxiliary heat (all electric systems).
Interlock On (in heating mode only)
If the heat pump is not able to satisfy the heating setpoint, the auxiliary heat is energized and the heat pump is shut off. This typically applies when the air handler heat pump coil is installed after the auxiliary heat. There is a 2-minute delay to restart the heat pump after the auxiliary heat is shut down.
To select the compressor/auxiliary interlock mode while in the Installer Configuration Menu:
1. Answer NO to all prompts until the compressor/auxiliary interlock prompt appears in the display. Press YES to enter the compressor auxiliary interlock menu.
2. Use the UP/DOWN arrow keys to select on or off. Press YES to enter the selection. The exit menu is displayed.
3. Press YES to exit the Installer Configuration Menu or NO to return to the beginning of the menu (digital input configuration).
Operation
Programming/Operating the T600HPP-2
Once the T600HPP-2 is configured through the Installer Configuration Menu, the thermostat’s operating parameters can be programmed through the Main User Menu (access the Main User Menu by pressing the MENU key during normal thermostat operation). The Main User Menu contains the basic operating features of the T600HPP-2.
The Main User Menu uses Auto Help. Auto Help is displayed automatically in the Main User Menu when there is a pause in programming activity. To exit Auto Help, continue with the programming selection.
When the thermostat is in the Main User Menu and is left unattended for 45 seconds, it reverts to the Status Display Menu.
Follow the steps in Table 4 to program the T600HPP-2 thermostat.
Table 4: Programming the T600HPP-2 Thermostat
RoomTemp
75.0 °F
Override schd Y/N
Resume schd Y/N
Temperat set? Y/N
Sys mode set? Y/N
Fan mode set? Y/N
Schedule set? Y/N
Clock set? Y/N
Schedule hold? Y/N
Press the MENU key while in the Status Display Menu to enter the Main User Menu.
Overrides Unoccupied Setpoints Only Appears if Thermostat is in Unoccupied State See the Enabling Override Schedule section.
Resumes Regular Programmed Schedule and Setpoints Only Appears if Thermostat is in Override Mode See the Resuming the Programmed Schedule section.
Sets the Temperature Setpoints See the Entering Temperature Setpoints section.
Selects the System Mode Default: Automatic Mode (auto) See the Selecting the System Mode section.
Selects the Fan Mode Default: Automatic (auto) See the Selecting the Fan Mode section.
Sets the Occupied and Unoccupied Time Periods See the Programming the Daily
Schedule – Two-Event and Programming the Daily Schedule – Four-Event section.
Sets the Day and Time See the Setting the Day and Time section.
Sets a Permanent Hold on the Schedule or Resumes the Schedule See the Setting Permanent Hold section.
T600HPP-2 Programmable Thermostat Installation Instructions 13
Page 14
Enabling Override Schedule Note: The Enabling Override Schedule only appears
when in the Unoccupied Mode. The override schedule prompt only appears when the
thermostat is in the unoccupied state. This menu selection gives the user the option of overriding the unoccupied setpoints with the occupied setpoints for the amount of time specified under the Establishing the Temporary Occupancy Time (TOccTime) parameter (see Configuring the T600HPP-2 section). If one of the digital inputs is configured to operate as a remote override contact, this menu is disabled.
To override the unoccupied state while in the Main User Menu.
1. Answer NO to all prompts until the Override Schedule prompt appears. If the thermostat is in the unoccupied state, this is the first prompt.
2. Press YES to enable the temporary override. The T600HPP-2 returns to the Status Display Menu.
When scrolling through the Status Display Menu, Override now appears for the schedule status parameter.
Resuming the Programmed Schedule
This menu only appears when the T600HPP-2 is in the:
unoccupied override mode
permanent occupied hold mode
permanent unoccupied hold mode
Entering Permanent Temperature Setpoints
The first prompt appearing in the Main User Menu of the T600HPP-2 thermostat is to set the permanent temperature setpoints. Permanent setpoints are stored in the programmed schedule.
To enter the permanent heating and cooling setpoints for the occupied and unoccupied modes, follow the steps in Table 5. When changing the temperatures, pressing the keys once changes the temperature
0.5 F/C° and holding down the keys changes the temperature by 5 F/C° increments.
Table 5: Entering Permanent Temperature Setpoints
RoomTemp
75.0°F
Temperat set? Y/N
Cooling set? Y/N
Press MENU from the Status Display Menu to enter the Main User Menu.
Answer NO to all prompts until the temperature set prompt appears in the display (it may be the first prompt). Press YES to enter temperature setting menu.
Press YES to change occupied cooling setpoint. Press NO to advance to occupied heating setpoint menu.
Cooling
75.0°F
Use the UP/DOWN arrow keys to set temperature. Press YES to store value and advance to next menu.
Note: If the T600HPP-2 is not in one of these modes, this prompt does not appear. Answering YES to this prompt enables the T600HPP-2 to resume the regular scheduled program and setpoints.
Heating set? Y/N
To resume the schedule while in the Main User Menu:
1. Answer NO to all prompts until the Resume Schedule prompt appears. If the thermostat is in
Heating
68.0°F
the override state, this is the first prompt.
2. Press YES to resume the programmed schedule.
The T600HPP-2 thermostat returns to the Status Display Menu.
Unocc CL set? Y/N
Unocc CL
80.0°F
14 T600HPP-2 Programmable Thermostat Installation Instructions
Press YES to change the occupied heating setpoint. Press NO to advance to unoccupied cooling setpoint menu.
Use the UP/DOWN arrow keys to set temperature. Press YES to store value and advance to next menu.
Press YES to change the unoccupied cooling setpoint. Press NO to advance to the unoccupied heating setpoint.
Use the UP/DOWN arrow keys to set temperature. Press YES to store value and advance to next menu.
Continued on Next Page. . .
Page 15
Table 5: Entering Permanent Temperature Setpoints (Cont.)
Unocc HT set? Y/N
Press YES to change the unoccupied heating setpoint. Press NO to advance to temperature display units.
Unocc HT
62.0°F
Use the UP/DOWN arrow keys to set temperature. Press YES to store value and advance to next menu.
°F/°C set? Y/N
Press YES to set the display units to °F or °C. Press NO to advance to temperature setpoint type menu.
Exit? Y/N
Press YES to return to the Status Display Menu or NO to re-enter the temperature setting menu.
Entering Temporary Temperature Setpoints
To temporarily change the setpoint, press the UP/DOWN arrow keys to change the temporary setpoint for the current mode of operation.
Note: Whether the thermostat is heating or cooling, the respective setpoint will be temporarily adjusted.
Note: To toggle between the temporary heating and cooling setpoints, press the NO key while changing the temporary setpoints.
Ending Temporary Temperature Setpoints
The temporary setpoints remain in effect for the duration set in the Temporary Occupancy Time parameter (TOccTime) or until manually released.
To release the temporary setpoint sooner, while in the main User Menu:
1. Answer YES to the first prompt to appear.
2. If the thermostat does not immediately return to the Status Display Menu, press MENU again and YES to exit the Main User Menu.
The setpoint reverts to the Permanent Temperature Setpoint.
Selecting the System Mode
The T600HPP-2 has five system modes:
Automatic Mode (auto)
Automatic changeover between heating and cooling. This is the default setting.
Cooling Mode (cool)
Cooling operation only.
Heating Mode (heat)
Heating operation only.
Off Mode (off)
The T600HPP-2 is off. However, when frost protection is on (see the Enabling Frost Protection [Frost pr] section) the thermostat still calls for heat, if required.
Emergency Heat Mode (emergenc) Forced auxiliary heat operation mode only
To set the system mode while in the Main User Menu:
1. Answer NO to all prompts until the system mode prompt appears in the display. Press YES to set the system mode.
2. Use the UP/DOWN arrow keys to locate the desired system mode. Press YES to select the desired system mode.
3. Press YES to return to the Status Display Menu or NO to return to the system mode selection menu.
Selecting the Fan Mode
The T600HPP-2 has three fan mode settings:
On Fan Mode (on)
Energizes the fan all the time for both occupied and unoccupied periods (even if the system mode is set to off).
Automatic Fan Mode (auto)
Operates the fan only on a call for heating or cooling for both occupied and unoccupied periods. This is the default setting.
Smart Fan Mode (smart)
Energizes the fan all the time for occupied periods and only on a call for heating and cooling in unoccupied periods.
To select the fan mode while in the Main User Menu:
1. Answer NO to all prompts until the fan mode prompt appears in the display. Press YES to set the fan mode
2. Use the UP/DOWN arrow keys to locate the desired fan mode. Press YES to select the desired fan mode.
3. Press YES to return to the Status Display Menu or NO to return to the fan mode selection menu.
T600HPP-2 Programmable Thermostat Installation Instructions 15
Page 16
Programming the Daily Schedule – Two-Event
The schedule setting menu is used to enter the occupied and unoccupied time periods for each day of the week. The schedule-setting menu reflects either a two- or four-event schedule per day based on what was selected in the Selecting the Number of Events (2/4event) menu during the configuring process. If the schedule-setting menu does not reflect a two-event schedule, return to the Selecting the Number of Events (2/4event) menu in the configuration process and select two events.
When changing the time, pressing the UP/DOWN arrow keys changes the time in 1-minute increments. Holding the keys down changes the time in 30-minute increments.
Note: Programming one of the digital inputs to remote NSB disables the menu.
Refer to Table 8 events 1 and 2 for an example of a two-event office schedule.
To set the time schedule for two-event schedule, follow the steps in Table 6.
Table 6: Programming the Daily Schedule – Two-Event
RoomTemp
75.0°F
Press MENU from the Status Display Menu to enter the Main User Menu.
Unoccup 12:00 AM
Tuesday set? Y/N
Copy Y/N previous
Wednesda set? N/A
Exit? Y/N
Use the UP/DOWN arrow keys to set the unoccupied start time. Press YES to enter the time.
Press YES to set the schedule for Tuesday or NO to advance to Wednesday.
Press YES to copy the schedule from the previous day. Press NO to set a different schedule.
If YES is pressed, the next prompt is for Wednesday. Repeat procedure for all days of the week.
After setting the schedule for all days of the week, following the last entry for Sunday, press YES to return to the Status Display Menu or NO to start again at Monday.
Schedule set? Y/N
Monday set? Y/N
Occupied day? Y/N
Occupied 12:00 AM
Answer NO to all prompts until the schedule set prompt appears in the display. Press YES to enter the scheduling menu.
Press YES to set the schedule for Monday or NO to advance to Tuesday.
Press YES to set the occupied start time for Monday or NO to advance to Tuesday.
Use the UP/DOWN arrow keys to set the occupied start time. Press YES to enter the time.
16 T600HPP-2 Programmable Thermostat Installation Instructions
Page 17
Programming the Daily Schedule – Four-Event
The schedule setting menu is used to enter the occupied and unoccupied time periods for each day of the week. The schedule-setting menu reflects either a two- or four-event schedule per day based on what was selected in the Selecting the Number of Events (2/4event) menu during the configuring process. If the schedule-setting menu does not reflect a four-event schedule, return to the Selecting the Number of Events (2/4event) menu in the configuration process and select four events.
Table 7: Programming the Daily Schedule – Four-Event
RoomTemp
75.0°F
Press MENU from the Status Display Menu to enter the Main User Menu.
When changing the time, pressing the UP/DOWN arrow keys changes the time in 1-minute increments. Holding the keys down changes the time in 30-minute increments.
Note: Programming one of the digital inputs to remote NSB disables the menu.
Follow the steps in Table 7 to set the time schedule for a four-event schedule.
Refer to Table 8 for an example of a four-event office schedule.
Occupie2 12:00 AM
Use the UP/DOWN arrow keys to set the second occupied start time. Press YES to enter the time.
Schedule set? Y/N
Monday set? Y/N
Occupied day? Y/N
Occupied 12:00 AM
Unoccup 12:00 AM
Answer NO to all prompts until the schedule set prompt appears in the display. Press YES to enter the scheduling menu.
Press YES to set the schedule for Monday or NO to advance to Tuesday.
Press YES to set the occupied start time for Monday or NO to advance to Tuesday.
Use the UP/DOWN arrow keys to set the first occupied start time. Press YES to enter the time.
Use the UP/DOWN arrow keys to set the first unoccupied start time. Press YES to enter the time.
Unoccup2 12:00 AM
Tuesday set? Y/N
Copy Y/N previous
Wednesda set? N/A
Exit? Y/N
Use the UP/DOWN arrow keys to set the second unoccupied start time. Press YES to enter the time.
Press YES to set the schedule for Tuesday or NO to advance to Wednesday.
Press YES to copy the schedule from the previous day. Press NO to set a different schedule.
If YES is pressed, the next prompt is for Wednesday. Repeat procedure for all days of the week.
After setting the schedule for all days of the week, following the last entry for Sunday, press YES to return to the Status Display Menu or NO to start again at Monday.
T600HPP-2 Programmable Thermostat Installation Instructions 17
Page 18
Table 8: Example of a Four-Event Office Schedule
Event #1 Event #2 Event #3 Event #4
Event
Occupied Unoccupied Occupied 2 Unoccupied 2
Cool Heat Cool Heat Cool Heat Cool Heat
Monday
Tuesday
Wednesday
Thursday
Friday
Saturday
Sunday
* Programming events to the same time cancels the last period and leaves the thermostat in unoccupied mode
Setting the Day and Time
Upon initial power-up (or after a power loss of greater than 6 hours), the T600HPP-2 shows a SetClock alarm. As the thermostat scrolls through the Status Display Menu, the SetClock message causes the backlight to light up until the clock is set.
When adjusting the time with the UP/DOWN arrow
72°F
(22°C)
7:00 A.M. 5:00 P.M. 12:00 P.M.* 12:00 P.M.* 7:00 A.M. 5:00 P.M. 12:00 P.M.* 12:00 P.M.* 7:00 A.M. 5:00 P.M. 12:00 P.M.* 12:00 P.M.* 7:00 A.M. 5:00 P.M. 7:00 P.M. 10:30 P.M.
7:00 A.M. 5:00 P.M. 7:00 P.M. 10:30 P.M. 12:00 P.M.* 12:00 P.M.* 12:00 P.M.* 12:00 P.M.* 12:00 P.M.* 12:00 P.M.* 12:00 P.M.* 12:00 P.M.*
70°F
(21°C)
80°F
(27°C)
62°F
(17°C)
72°F
(22°C)
70°F
(21°C)
80°F
(27°C)
Setting Schedule Hold Note: Displayed only if Digital Input DI1 or DI2 is
configured for remote NSB. This menu is used to set a permanent hold on the
internal scheduling or resume the schedule. The permanent hold typically is used for non-scheduled events that extend for long periods of time.
keys, holding the keys down changes the time in 30-minute increments.
To set the clock while in the Main User Menu:
1. Answer NO to all prompts until the clock set prompt appears in the display. Press YES to enter the clock set menu.
2. Press YES to set the time or NO to advance to the day set menu.
3. Use the UP/DOWN arrow keys to adjust the time. When the correct time is displayed, press YES to store the time.
4. Press YES to enter the day set menu or NO to enter the clock format menu.
5. Use the UP/DOWN arrow keys to adjust the day. When the correct day is displayed, press YES to store the day.
6. Press YES to choose the time format or NO to access the Main User Menu exit prompt.
7. Use the UP/DOWN arrow keys to select the desired time format. Press YES to enter format.
8. Press YES to return to the Status Display Menu or NO to return to the time set menu.
When the thermostat scrolls through the day and time, the new day and time should be displayed (and no alarm/backlit should be present). If the day and time is
There are three selections for this menu:
Permanent Occupied Hold (occ hold) This selection puts the thermostat into a permanent occupied mode using the occupied setpoints. Occupied hold appears in the Status Display Menu when this selection is active.
Permanent Unoccupied Hold
This selection puts the T600HPP-2 into a permanent unoccupied mode using the unoccupied setpoints. Unoccup hold appears in the Status Display Menu when this selection is active.
Resume
This selection cancels the permanent hold and enables the regular program schedule.
To enable the permanent hold feature while in the Main User Menu:
1. Answer NO to all prompts until the schedule hold prompt appears in the display. Press YES to set the schedule hold type.
2. Use the UP/DOWN arrow keys to locate the desired permanent hold type (or resume schedule). Press YES to enter the choice.
3. Press YES to return to the Status Display Menu or NO to change the schedule hold selection again.
incorrect, repeat the Setting the Day and Time procedure.
62°F
(17°C)
18 T600HPP-2 Programmable Thermostat Installation Instructions
Page 19
Accessories
Using the information in Table 9, contact the nearest Johnson Controls® branch office or wholesale distributor to order these accessories.
Table 9: Optional Accessories (Includes Mounting Hardware)
Description
Remote Indoor Temperature Sensor Outdoor Air Temperature Sensor Duct Mount Temperature Sensor Remote Indoor Temperature Sensor
with Occupancy Override and LED
Product Code
Number
SEN-600-1 SEN-600-2 SEN-600-3
SEN-600-4
T600HPP-2 Programmable Thermostat Installation Instructions 19
Page 20
Technical Specifications
Product
Power Requirements
Relay Contact Rating
Maximum Inductive
Digital Inputs
Recommended Wire Size
Thermostat Measurement
Range
Sensor Type:
Resolution:
Control Accuracy
Outdoor Air Temperature
Indication Range
Setpoint Control Range
Minimum Deadband
Ambient Operating
Conditions
Ambient Storage
Conditions
Dimensions (H x W x D)
Shipping Weight
UL and cUL Listing
FCC Compliance
Industry Canada
The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products.
T600HPP-2 Programmable Thermostat 20-30 VAC, 50/60 Hz, 24 VAC nominal, Class 2 or Safety Extra Low Voltage (SELV)
1 ampere with in-rush surges up to 3 amperes, 30 VAC maximum, Class 2 Relay dry contact only across the C terminal to DI1 or DI2
18 gauge maximum, 22 gauge recommended
-40 to 122°F (-40 to 50°C) Local 10k ohm NTC thermistor
±0.2 F° (±0.1 C°) ±0.9 F° (±0.5 C°) @ 70°F (21°C) typical calibrated
-40 to 50°C (-40 to 122°F) Cooling: 54 to 100°F (12 to 37.5°C) in 1/2 degree increments
Heating: 40 to 90°F (4.5 to 32°C) in 1/2 degree increments (Between heating and cooling) 2 F° or 1 C°
32 to 122°F (0 to 50°C); 0 to 95% RH noncondensing
-22 to 122°F (-30 to 50°C); 0% to 95% RH noncondensing
4.94 x 3.38 x 1.13 in. (125 x 86 x 29 mm)
0.75 lb (0.34 kg) File E27734 with CCN’s XAPX (US, UL 873) and XAPX7 (Canada, CSA C22.2 No. 24) This equipment has been tested and found to comply with the limits for a Class A digital
device and verified to Class B pursuant to Part 15 of FCC Rules. These limits are designed to provide reasonable protection against harmful interference when this equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference, in which case the user will be required to correct the interference at his/her own expense.
This Class A digital apparatus meets all of the requirements of the Canadian Interference-Causing Equipment Regulations. Cet appareil numérique de la Classe A respecte toutes les exigences du Règlement sur le materiél brouilleur du Canada.
Controls Group
507 E. Michigan Street P.O. Box 423 Printed in U.S.A. Milwaukee, WI 53201
20 T600HPP-2 Programmable Thermostat Installation Instructions
www.johnsoncontrols.com
Loading...