Installation Instructions Issue Date December 1, 2004
T600HPP-2 Programmable Thermostat
Application
IMPORTANT: Use this T600HPP-2
programmable thermostat only as an operating
control. Where failure or malfunction of the
thermostat could lead to personal injury or property
damage to the controlled equipment or other
property, additional precautions must be designed
into the system. Incorporate and maintain other
devices such as supervisory or alarm systems or
safety or limit controls intended to warn of, or protect
against, failure or malfunction of the thermostat.
The T600HPP-2 is a programmable heat pump
thermostat that provides exceptional accuracy through
the use of a unique Proportional-Integral (PI) time
proportioning algorithm. The algorithm virtually
eliminates temperature offset associated with
traditional, differential-based on/off thermostats. The
T600HPP-2 also uses an adaptive control logic
algorithm to control the space temperature during
recovery to minimize overshoot while providing
maximum comfort. Additionally, the menu driven
backlit display, plain text menus, and five keys on the
T600HPP-2 make programming the thermostat easy
and intuitive.
To install the thermostat:
1. Remove the security screw on the bottom of the
thermostat cover using a Phillips-head
screwdriver. Open the thermostat by pulling on the
bottom side of the thermostat cover (Figure 1).
2. Unlock the Printed Circuit Board (PCB) by
carefully pressing the locking tab to the right
(Figure 2). Open the thermostat’s PCB to the left.
3. Pull out approximately 6 in. (152 mm) of wires
from the wall and insert the cable through the hole
in the base.
4. Align the base on the wall, and using the base as
a template, mark the location of the two mounting
holes on the wall. Confirm the thermostat base is
installed with the proper side up.
5. Use the supplied anchors and screws for mounting
on drywall or plaster. Drill two 3/16 in. (4.7 mm)
holes at the marked locations and tap nylon
anchors flush to wall surface (Figure 3).
6. Position base on the wall, insert screws through
mounting base, and fasten into wall anchors. Do
not overtighten screws.
Installation
7. Swing the thermostat PCB back to the right to
close. Gently press on the PCB to secure each of
Location Considerations
Locate the T600HPP-2 thermostat:
• on a partitioning interior wall, and approximately
5 ft. (1.5 m) above the floor in a location of
average temperature
the locking tabs.
8. Pull out the screw terminal blocks using the
pull-tabs on each connector (Figure 4).
Note: The number of terminals on the terminal
blocks varies depending on the T600 model.
• away from direct sunlight, radiant heat, outside
walls, behind doors, air discharge grills, stairwells,
or outside doors
• away from steam or water pipes, warm air stacks,
unheated/uncooled areas, or sources of electrical
interference
CAUTION: Risk of Electric Shock.
Disconnect power supply before making electrical
connections to avoid electric shock.
Note: When replacing an existing thermostat,
remove and label wires to identify terminal
designations. When replacing a T600HPP thermostat,
simply remove the terminal blocks and reinsert on to
the new thermostat.
To wire the thermostat:
1. Strip each wire 1/4 in. (6.35 mm) and connect to
the appropriate terminal according to the wiring
diagram (Figure 5).
2. Gently push excess wire back into wall, plug the
wall hole with fireproof material to prevent drafts
from affecting ambient temperature readings, and
install screw terminal blocks back onto the PCB.
3. Reattach the thermostat cover to the installed
base (top side first) and install the security screw
on the bottom.
!
CAUTION: Risk of Property Damage.
Do not apply power to the system before checking
all wiring connections. Short circuited or improperly
connected wires may result in permanent damage to
the equipment.
Energizes first stage co m pressor on a call for heating or cool i ng
Energizes second st age compressor on a call f or heating or cooling
Energizes fan in accordance with the selected fan mode
24 VAC from equipment transformer
24 VAC (comm o n) f ro m eq uipment tra nsformer
24 VAC for auxiliary heat
Energizes auxiliary heat
Energizes reversing va lv e ( con f ig ur ab le to
energiz e va lve on a call for heat or ca ll fo r coo li ng )
Configur able auxiliar y output
Configur able digital in put
Configur able digital in put
Remote roo m sensor
Sensor common
Outdoor air sensor
GRCCRHW1O/B
Cool 1
Fan
Heat 1
Rev
Valve
5 pole left top connector
Y1G RC
Y2
6 pole bottom connector
Aux D1 D2 RS
AUX
D1D2
Aux
3 pole right top connector
C
RH W1 O/B
Scom
OS
Scom
OSRS
24 VAC
Thermostat Power
Y2Y1
R3
R2
Separate 24 V AC
Transformer
If using the same power source
for the ther m ostat and heating
loads, in stall a jumper
across RC and RH.
Backlit, plain text, Liquid
Crystal Display (LCD)
is easy to read in any
condition.
Room Temp
75.0ºF
Light Emi t ting Diodes (L E Ds)
indicate system activi t y.
Five keys on the T600
make operation easy
and intuitive.
Figure 6: T600HPP-2 Thermostat Front Cover
r
e
v
o
C
_
t
n
o
r
F
_
C
E
T
_
0
0
6
T
Thermostat Interface Keys
The T600HPP-2 interface consists of five keys on
the front cover, and one configuration key
(Figure 7) that is accessed by removing the front
cover. Use the:
• YES/SCROLL key to:
− confirm menu selections, and to advance to
the next menu item
− stop the Status Display Menu from scrolling
and to manually scroll to the next parameter
on the menu. When left unattended for
45 seconds, the display resumes scrolling.
• NO key when you do not desire a parameter
change, and to advance to the next menu item
• MENU key to access the Main User Menu or exit
the menu
• UP/DOWN arrow keys to:
− adjust values
− activate a Temporary Setpoint
y
e
K
_
g
i
f
n
o
C
_
C
E
T
Configuration
Key
_
0
0
6
T
Figure 7: Configuration Key Location
Backlit Liquid Crystal Display (LCD)
The T600HPP-2 uses a two-line, eight-character
backlit display. Low level backlighting is present during
normal operation and it brightens when any user
interface key is pressed. The backlight returns to the
lower level when the thermostat is left unattended for
45 seconds.
Light-Emitting Diodes (LED)s
Three LEDs are used to indicate the status of the fan,
call for heat, or call for cooling. When:
• the fan is on, the FAN LED lights up
• auxiliary heat is on, the AUX HEAT LED lights up
• the heat pump compressor is on, the HEAT-PUMP
LED lights up
r
A
Programming Overview
There are three menus used to view, program, and
configure the T600HPP-2 thermostat: the Status
Display, Main User, and Installer Configuration Menus.
The Status Display Menu is displayed during normal
thermostat operation. The menu continually scrolls
through the following parameters.
• Room Temperature
• Day and Time
• System Mode
• Schedule Status (Occupied/Unoccupied)
• Outdoor Temperature (providing sensor is
connected and functional)
• Applicable Alarms (the backlight lights up as an
alarm condition is displayed)
To temporarily stop the scrolling, press the
YES/SCROLL key.
The Main User Menu is used to access and change
the thermostat’s basic operating parameters. Access
the menu by pressing the MENU key during normal
thermostat operation.
The Installer Configuration Menu is used to set up
the thermostat for application specific operation.
Access the menu by removing the front cover and
pressing the configuration key, labeled CONFIG
(Figure 7).
Configuring the T600HPP-2
The T600HPP-2 ships from the factory with default
settings for all configurable parameters. The default
settings are shown in Table 1. To reconfigure the
parameters, follow the steps in this section for the
corresponding parameters. To set up the parameters,
access the Installer Configuration Menu. Access the
Installer Configuration Menu by removing the front
cover and pressing the configuration key (Figure 7).
Exit the Installer Configuration Menu any time by
pressing the MENU key and, at the exit prompt,
pressing the YES key. To pass over a parameter
without changing it, press the NO key.
When the thermostat is in the Installer Configuration
Menu and left unattended for 45 seconds, it reverts to
the Status Display Menu.
Table 1: Installer Configuration Menu
RoomTemp
75.0 °F
DI1
set? Y/N
DI2
set? Y/N
Lockout
set? Y/N
Pwr del
set? Y/N
Frost p
set? Y/N
Heat max
set? Y/N
Cool min
set? Y/N
nticycl
set? Y/N
Heat cph
set? Y/N
Cool cph
set? Y/N
Continued on the next page . . .
Remove the cover and press the
CONFIG key from the Status Display
Menu to enter the Installer
Configuration Menu.
Configures Digital Input 1
Default: No Function (None)
See the Configuring the Digital Inputs (DI1 and DI2) section.
Configures Digital Input 2
Default: No Function (None)
See the Configuring the Digital Inputs (DI1 and DI2) section.
Sets Keypad Lockout Level
Default: No Lockout (0)
See the Enabling Keypad Lockout (Lockout) section.
Sets Power-up Delay
Default: Ten Seconds (10.0 sec)
See the Setting the Power-up Delay (Pwr del) section.
Enables/Disables Frost Protection
Default: Disabled (Off)
See the Enabling Frost Protection (Frost pr) section.
Sets the Maximum Heating Setpoint
Default: 90.0°F (32.0°C)
See the Setting the Maximum Heating Setpoint (Heat max) section.
Sets the Minimum Cooling Setpoint
Default: 54.0°F (12.0°C)
See the Setting the Minimum Cooling Setpoint (Cool min) section.
Sets the Anti-Short Cycle Timer
Default: Two Minutes (2.0 min)
See the Setting the Anti-Short Cycle Timer (Anticycl).
Sets the Maximum Heating Cycles per
Hour (Auxiliary Heating)
Default: Four (4.0)
See the Setting the Maximum Heating Cycles per Hour (Heat cph) section.
Sets the Maximum Cooling Cycles per
Hour (Compressor Cycles)
Default: Four (4.0)
See the Setting the Maximum Cooling Cycles per Hour (Cool cph) section.
Sets the Minimum Heating/Cooling
Deadband
Default: 2.0°F (1.1°C)
See the Setting the Heating/Cooling Deadband (Deadband) section.
Determines how the Fan Activates in
Response to a call for Heat
Default: Thermostat Controls Fan (On)
See the Setting the Fan Control (Fan cont) section.
Delays Fan Termination at Cycle’s End
for 60 Seconds
Default: No Delay (Off)
See the Setting the Fan Delay (Fan del) section.
Sets the Duration for Temporary
Occupancy Time
Default: Three Hours (3.0 hrs)
See the Establishing the Temporary Occupancy Time (TOccTime) section.
Room Air Sensor Calibration (Offset)
Default: 0.0°F (0.0°C)
See the Room Air Sensor Calibration (Cal RS) section.
Outdoor Air Sensor Calibration (Offset)
Default: 0.0°F (0.0°C)
See the Outdoor Air Sensor Calibration (Cal OS) section.
Selects the Number of Compressor
Stages
Default: Two Stages
See the Enable/Disable Heat Pump Stage (HP Stage) section.
Disables Heating Operation based on
Outdoor Air Temperature
Default: 120°F (49°C)
See the Setting the Heating Lockout (H lock) section.
Disables Cooling Operation based on
Outdoor Air Temperature
Default: -40°F (-40°C)
See the Setting the Cooling Lockout (C lock) section.
2/4event
set? Y/N
ux cont
set? Y/N
Prog Rec
set? Y/N
Hi b.p.
set? Y/N
Lo b. p.
set? Y/N
Comf/eco
set? Y/N
Re valve
set? Y/N
Comp/aux
set? Y/N
Sets the Number of Events in 24-Hour
Period
Default: Two Events (2.0)
See the Selecting the Number of Events (2/4event) section.
Sets the Auxiliary Contact as Normally
Open or Normally Closed
Default: Normally Open (N.O.)
See the Configuring the Auxiliary Contact (Aux cont) section.
Enable/Disable Progressive Recovery
Default: Off
See the Enable/Disable Progressive Recovery (Prog Rec) section.
Set the High Balance Point
Default: 90°F (32°C)
See the Setting the High Balance Point (Hi b.p.) section.
Set the Low Balance Point
Default: -12°F (-24°C)
See the Setting the Low Balance Point (Lo b.p) section.
Set the Comfort or Economy Mode
Default: Comfort
See the Selecting Comfort or Economy Mode (Comf/eco) section.
Sets the Reversing Valve Operation
Default: O
See the Selecting the Reversing Valve Operation (Re valve) section.
Sets the Compressor/Auxiliary Heat
Interlock
Default: Off
See the Compressor/Auxiliary Interlock (Comp/aux) section.