Johnson Controls T600HCN-1 Installation Instructions Manual

Page 1
Installation Instructions Issue Date December 9, 2003
T600HCN-1 Non-Programmable Thermostat
The T600HCN-1 is a single-stage non-programmable thermostat that provides exceptional accuracy through the use of a unique Proportional-Integral (PI) time proportioning algorithm. The thermostat’s proprietary adaptive logic algorithm provides a constant space temperature by controlling the Heating, Ventilating, and Air Conditioning (HVAC) equipment to minimize overshoot and maximize comfort. The algorithm virtually eliminates temperature offset associated with traditional, differential-based on/off thermostats. Additionally, the menu-driven backlit display, plain text menus, and five keys on the T600HCN-1 make operating the thermostat easy and intuitive.
To install the thermostat:
1. Remove the security screw on the bottom of the thermostat cover using a Phillips-head screwdriver. Open the thermostat by pulling on the bottom side of the thermostat cover (see Figure 1).
2. Unlock the Printed Circuit Board (PCB) by carefully pressing the locking tabs to the right (see Figure 2). Open the thermostat’s PCB to the left.
3. Pull out approximately 6 in. (152 mm) of wires from the wall and insert the cable through the hole in the base.
Installation
Location Considerations
Locate the T600HCN-1 thermostat as follows:
on a partitioning interior wall, and approximately 5 ft (1.5 m) above the floor in a location of average temperature
away from direct sunlight, radiant heat, outside walls, behind doors, air discharge grills, stairwells, or outside doors
away from steam or water pipes, warm air stacks, unheated/uncooled areas, or sources of electrical interference
4. Align the base on the wall, and using the base as a template, mark the location of the two mounting holes on the wall. Confirm the thermostat base is installed with the proper side up.
5. Use the supplied anchors and screws for mounting on drywall or plaster. Drill two 3/16 in. (4.7 mm) holes at the marked locations and tap nylon anchors flush to wall surface (see Figure 3).
6. Position base on the wall, insert screws through mounting base, and fasten into wall anchors. Do not overtighten screws.
7. Swing the thermostat PCB back to the right to close. Gently press on the PCB to secure each of the locking tabs.
8. Pull out the screw terminal blocks using the pull tabs on each connector (see Figure 4).
Note: The number of terminals on the terminal blocks varies depending on the T600 model.
IMPORTANT: Use this T600HCN-1 non-programmable thermostat only as an operating control. Where failure or malfunction of the T600HCN-1 could lead to personal injury or property damage to the controlled equipment or other property, additional precautions must be designed into the system. Incorporate and maintain other devices such as supervisory or alarm systems or safety or limit controls intended to warn of, or protect against, failure or malfunction of the T600HCN-1.
© 2003 Johnson Controls, Inc. Part No. 24-9889-10, Rev. A www.johnsoncontrols.com
1
Page 2
Figure 1: Removing the Thermostat Cover
Figure 4: Removing the Terminal Blocks
Wiring
PCB
Lockin g Tabs
Figure 2: Opening the Thermostat PCB
!
CAUTION: Risk of Electrical Shock. Disconnect power supply before making electrical connections to avoid electrical shock.
Note: When replacing an existing thermostat, remove and label wires to identify terminal designations. When replacing a T600HCN-1 thermostat, simply remove the terminal blocks and reinsert onto the new thermostat.
To wire the thermostat:
1. Strip each wire 1/4 in. (6.35 mm) and connect to the appropriate terminal according to the wiring diagram (see Figure 5).
2. Gently push excess wire back into wall, plug the wall hole with fireproof material to prevent drafts from affecting ambient temperature readings, and install screw terminal blocks back onto the PCB.
3. Reattach the thermostat cover to the installed base (top side first) and install the security screw on the bottom.
Figure 3: Mounting the Thermostat Base
2 T600HCN-1 Non-Programmable Thermostat Installation Instructions
!
CAUTION: Risk of Property Damage.
Do not apply power to the system before checking all wiring connections. Short circuited or improperly connected wires may result in permanent damage to the equipment.
Page 3
Terminal
W1
Y1
G
RC
C
RH
D1 D2
RS
Scom
OS
Cool 1
Thermostat Power
Function
Energize s on call for heating Energize s on call for cooling Energize s fa n in accordance with the selected fan m ode 24 VAC from equipment transformer 24 VAC (comm on from equip m ent transformer 24 VAC for heati ng stage Configurable digital input Configurable digital input Remote ro om sensor Sensor com mon Outdoor air sensor
Y1
GRCC
Fan
24 VAC
)
RH W1 D1
Heat 1
If using the same power source for the thermostat and heating loads, ins t all a jumper across RC and RH.
Figure 5: T600HCN-1 Wiring Schematic
4-pole l ef t to p connector
Y1 G RC
5-pole bo t to m connector
D1 D2 RS
2-pole ri ght top connector
C
RH W1
Scom
OS
RS
Scom
D2
Remote
Room
Sensor
OS
Setup and Adjustments
Thermostat Operation Overview
Backlit, plain text, Liquid Crystal Display (LCD) is easy to read in any condition.
Five keys on the T600 make operation easy and intuitive.
Figure 6: T600HCN-1 Front Cover
Room Temp
75.0ºF
Light Emi t ting Diodes (L E Ds) indicate system activit y.
T600HCN-1 Non-Programmable Thermostat Installation Instructions 3
Page 4
Thermostat Interface Keys
The T600HCN-1 interface consists of five keys on the front cover and one configuration key (see Figure 7) that is accessed by removing the front cover. The functions of the keys are as follows. Use the:
YES key to confirm a selection and move onto the next menu item
NO key when you do not desire a parameter change, and to advance to the next menu item
MENU key to access the Main User Menu or exit the menu
down arrow key to scroll through menu selections or adjust values
up arrow/SCROLL key to:
scroll through menu selections or adjust
values
stop the Status Display Menu from scrolling
and to manually scroll to the next parameter on the menu. When left unattended for 45 seconds, the display resumes scrolling
Programming Overview
There are three menus used to view, program, and configure the T600HCN-1 thermostat.
The Status Display Menu is the menu that displays during normal thermostat operation. The menu continually scrolls through the following parameters (see Figure 6).
Room Temperature
System Mode
Schedule Status (Occupied/Unoccupied
[see Note])
Outdoor Temperature (providing sensor is connected and functional)
Applicable Alarms (the backlight lights up as an alarm condition is displayed)
To temporarily stop the scrolling, press the up arrow/SCROLL key.
Note: Displayed only if Digital Input (DI1 or DI2) is configured for remote Night Setback (NSB).
The Main User Menu is used to access and change the thermostat’s basic operating parameters. Access the menu by pressing the MENU key during normal thermostat operation.
Configuration
Key
Figure 7: Configuration Key Location
Backlit Liquid Crystal Display (LCD)
The T600HCN-1 uses a two-line, eight-character backlit display. Low level backlighting is present during normal operation and it brightens when any user interface key is pressed. The backlight returns to the lower level when the thermostat is left unattended for 45 seconds.
Light-Emitting Diodes (LED)s
Three LEDs are used to indicate the status of the fan, call for heat, or call for cooling. When:
the fan is on, the FAN LED lights up
heating is on, the HEAT LED lights up
cooling is on, the COOL LED lights up
The Installer Configuration Menu is used to set up the thermostat for application specific operation. Access the menu by removing the front cover and pressing the configuration key, labeled CONFIG (see Figure 7).
Configuring the T600HCN-1
The T600HCN-1 ships from the factory with default settings for all configurable parameters. The default settings are shown in Table 1. To reconfigure the parameters, follow the steps in this section for the corresponding parameters. The parameters must be set up by accessing the Installer Configuration Menu. Access the Installer Configuration Menu by removing the front cover and pressing the configuration key (see Figure 7).
Exit the Installer Configuration Menu anytime by pressing the MENU key and, at the exit prompt, pressing the YES key. To pass over a parameter without changing it, press the NO key.
When the thermostat is in the Installer Configuration Menu and left unattended for 45 seconds, it reverts to the Status Display Menu.
4 T600HCN-1 Non-Programmable Thermostat Installation Instructions
Page 5
Table 1: Installer Configuration Menu
RoomTemp
75.0°F
DI1 set? Y/N
DI2 set? Y/N
Lockout set? Y/N
Remove the cover and press the CONFIG key from the Status Display Menu to enter the Installer Configuration Menu.
Configures Digital Input 1 Default: No Function (None) See Configuring the Digital Inputs (DI1 and DI2).
Configures Digital Input 2 Default: No Function (None) See Configuring the Digital Inputs (DI1 and DI2).
Sets Keypad Lockout Level Default: No Lockout (0) See Enabling Keypad Lockout (Lockout).
Cool cph set? Y/N
Deadband set? Y/N
Fan cont set? Y/N
Fan del set? Y/N
Sets the Maximum Cooling Cycles per Hour Default: Four (4.0) See Setting the Maximum Cooling Cycles per Hour (Cool cph).
Sets the Minimum Heating/Cooling Deadband Default: 2.0°F (1.1°C) See Setting the Heating/Cooling Deadband (Deadband).
Determines how the Fan Activates in Response to a call for Heat Default: Thermostat Controls Fan (On) See Setting the Fan Control (Fan cont).
Delays Fan Termination at Cycle’s End for 60 Seconds Default: No Delay (Off) See Setting the Fan Delay (Fan del).
Pwr del set? Y/N
Frost pr set? Y/N
Heat max set? Y/N
Cool min set? Y/N
Anticycl set? Y/N
Heat cph set? Y/N
Sets Power-up Delay Default: Ten Seconds (10.0 sec) See Setting the Power-up Delay (Pwr del).
Enables/Disables Frost Protection Default: Disabled (Off) See Enabling Frost Protection (Frost pr).
Sets the Maximum Heating Setpoint Default: 90.0°F (32.0°C) See Setting the Maximum Heating Setpoint (Heat max).
Sets the Minimum Cooling Setpoint Default: 54.0°F (12.0°C) See Setting the Minimum Cooling Setpoint (Cool min).
Sets the Anti-Short Cycle Timer Default: Two Minutes (2.0 min) See Setting the Anti-Short Cycle Timer (Anticycl).
Sets the Maximum Heating Cycles per Hour Default: Four (4.0) See Setting the Maximum Heating Cycles per Hour (Heat cph).
ToccTime set? Y/N
Cal RS set? Y/N
Cal OS set? Y/N
H lock set? Y/N
C lock set? Y/N
Sets the Duration for Temporary Occupancy Time Default: Three Hours (3.0 hrs) See Establishing the Temporary Occupancy Time (ToccTime).
Room Air Sensor Calibration (Offset) Default: 0.0°F (0.0°C) See Room Air Sensor Calibration (Cal RS).
Outdoor Air Sensor Calibration (Offset) Default: 0.0°F (0.0°C) See Outdoor Air Sensor Calibration (Cal OS).
Disables Heating Operation based on Outdoor Air Temperature Default: 120°F (49°C) See Setting the Heating Lockout
(H lock).
Disables Cooling Operation based on Outdoor Air Temperature Default: -40°F (-40°C) See Setting the Cooling Lockout (C lock).
T600HCN-1 Non-Programmable Thermostat Installation Instructions 5
Page 6
Configuring the Digital Inputs (DI1 and DI2)
Press the configuration menu access key. The first prompt is to program Digital Inputs DI1 and DI2.
The digital inputs display an alarm condition when the input is closed. An alarm message is included on the scrolling Status Display Menu and when the message is displayed, the backlight momentarily lights up.
Each digital input can be programmed in one of five conditions.
None – No function is associated with the input.
Service – A Service alarm is displayed.
Filter – A Filter alarm is displayed.
RemNSB – Remote night setback timer clock
input. The scheduling is set per the digital input when this option is selected.
Open Contact = Occupied setpoints
Closed Contacts = Unoccupied setpoints
RemOVR – Remote override contact. This
disables all override menu functions of the thermostat. The override function is controlled manually by a remote, momentarily closed contact. When configured in this mode, the input operates in a toggle mode. With this function enabled, it is now possible to toggle between unoccupied and occupied setpoints for the amount of time set by the temporary occupancy time parameter.
When override is enabled through the digital inputs, an Override message appears in the Status Display Menu.
To configure the digital inputs while in the Installer Configuration Menu:
1. The first prompt is to configure the digital inputs. Press YES to configure Digital Input 1 or NO to advance to Digital Input 2.
2. Use the UP/DOWN arrow keys to locate the desired function for the Digital Input 1. Press YES to select the desired function.
3. Press YES to configure Digital Input 2 or NO to advance to the keypad lockout setup prompt.
4. Use the UP/DOWN arrow keys to locate the desired function for the Digital Input 2. Press YES to select the desired function.
The display now shows the keypad lockout setup prompt. See the Enabling Keypad Lockout (Lockout) section for instructions.
Enabling Keypad Lockout (Lockout)
The T600HCN-1 has three levels of keypad lockout. The levels and degree of lockout are shown in Table 2.
To set the keypad lockout level while in the Installer Configuration Menu:
1. Answer NO to all prompts until the keypad lockout setup prompt appears in the display. Press YES to enter the keypad lockout menu.
2. Use the UP/DOWN arrow keys to locate the desired lockout level. Press YES to select the level.
The display now shows the power delay setup prompt. See the Setting the Power-up Delay (Pwr del) section for instructions.
Table 2: Keypad Lockout Levels
Level 0 Level 1 Level 2
*Resume to Scheduling
Temperature
Setpoints
System
Mode Setting
Fan Mode
Setting
*Permanent
Hold
* Displayed only if digital input DI1 or DI2 is configured
for remote NSB.
Setting the Power-up Delay (Pwr del)
On initial power up of the T600HCN-1 (or each time power is removed and reapplied), there is a delay before any operation is authorized (fan, cooling, and heating). The delay time is adjustable between 10 and 120 seconds. You can also use this parameter to sequence the startup of multiple units in one location.
Note: When adjusting the time with the UP/DOWN arrow keys, holding the keys down changes the time by 10-second intervals.
Yes access Yes access No access
Yes access No access No access
Yes access Yes access No access
Yes access Yes access No access
Yes access Yes access No access
6 T600HCN-1 Non-Programmable Thermostat Installation Instructions
Page 7
To set the delay time while in the Installer Configuration Menu:
1. Answer NO to all prompts until the power delay setup prompt appears in the display. Press YES to enter the power delay setup menu.
2. Use the UP/DOWN arrow keys to adjust the power up delay setting. Press YES to store the setting.
The display now shows the frost protection setup prompt. See the Enabling Frost Protection (Frost pr) section for setup instructions.
Enabling Frost Protection (Frost pr)
Frost protection establishes a minimum heating setpoint of 42°F (5.5°C) to prevent freezing in the zone controlled by the thermostat. If enabled, frost protection is activated even if the thermostat is set to the Off System Mode. If frost protection is active, it is displayed as an alarm (Frost on with the backlight lit) on the Status Display Menu.
To enable frost protection while in the Installer Configuration Menu:
1. Answer NO to all prompts until the frost protection setup prompt appears in the display. Press YES to enter the frost protection menu.
2. Use the UP/DOWN arrow keys to select off or on. Press YES to store the selection.
The display now shows the maximum heating setpoint prompt. See the Setting the Maximum Heating Setpoint (Heat max) section for instructions.
Setting the Minimum Cooling Setpoint (Cool min)
The minimum cooling setpoint establishes the minimum temperature in the cooling setpoint range that can be adjusted from the Main User Menu. The parameter is adjustable from 54 to 100°F (12 to 37.5°C).
Note: When adjusting the temperature, holding the keys down changes the temperature by 5 F/C° increments.
To set the minimum cooling setpoint while in the Installer Configuration Menu:
1. Answer NO to all prompts until the minimum cooling setpoint prompt appears in the display. Press YES to enter the minimum cooling setpoint menu.
2. Use the UP/DOWN arrow keys to adjust the minimum cooling setpoint temperature. Press YES to store the value.
The display now shows the anti-short cycle timer prompt. See the Setting the Anti-Short Cycle Timer (Anticycl) section for instructions.
Setting the Anti-Short Cycle Timer (Anticycl)
The anti-short cycle timer establishes the minimum on/off times for the cooling and heating stages. The timer is adjustable from 0 to 5 minutes in 1-minute increments. Set the anti-short cycling to 0 for equipment that possesses its own anti-short cycling timer.
Setting the Maximum Heating Setpoint (Heat max)
The maximum heating setpoint establishes the maximum temperature in the heating setpoint range that can be adjusted from the Main User Menu. The parameter is adjustable from 40 to 90°F (4.5 to 32°C).
Note: When adjusting the temperature, holding the keys down changes the temperature by 5 F/C° increments.
To set the maximum heating setpoint while in the Installer Configuration Menu:
1. Answer NO to all prompts until the maximum heating setpoint prompt appears in the display. Press YES to enter the maximum heating setpoint menu.
2. Use the UP/DOWN arrow keys to adjust the maximum heating setpoint temperature. Press YES to store the value.
The display now shows the minimum cooling setpoint prompt. See the Setting the Minimum Cooling Setpoint (Cool min) section for instructions.
T600HCN-1 Non-Programmable Thermostat Installation Instructions 7
!
CAUTION: Risk of Property Damage.
Do not set the T600HCN-1 anti-short cycling timer to 0 minutes if the controlled equipment is not protected by its own internal anti-short cycling timer. Setting the T600HCN-1 anti-short cycling timer to 0 minutes can damage controlled equipment that does not have an anti-short cycling timer.
To set the anti-short cycle time while in the Installer Configuration Menu:
1. Answer NO to all prompts until the anti-short cycle timer prompt appears in the display. Press YES to enter the anti-short cycle timer menu.
2. Use the UP/DOWN arrow keys to adjust the minimum on/off times for the heating and cooling stages. Press YES to store the value.
The display now shows the heating cycles per hour setup prompt. See the Setting the Maximum Heating Cycles per Hour (Heat cph) section for instructions.
Page 8
Setting the Maximum Heating Cycles per Hour (Heat cph)
The heating cycles per hour establishes the maximum number of times the equipment is turned on and off in one hour. The selection ranges from three to eight cycles per hour.
Note: A higher number of heating cycles per hour results in more accurate temperature control, but could accelerate the wear of mechanical components in the equipment.
To set the maximum number of heating cycles per hour while in the Installer Configuration Menu:
1. Answer NO to all prompts until the heating cycles per hour prompt appears in the display. Press YES to enter the heating cycles per hour menu.
2. Use the UP/DOWN arrow keys to adjust the maximum number of heating cycles per hour. Press YES to store the value.
The display now shows the cooling cycles per hour setup prompt. See the Setting the Maximum Cooling Cycles per Hour (Cool cph) section for instructions.
Setting the Maximum Cooling Cycles per Hour (Cool cph)
The cooling cycles per hour establishes the maximum number of times the equipment is turned on and off in one hour. The selection ranges from three to four cycles per hour.
Note: A higher number of cooling cycles per hour results in more accurate temperature control, but could accelerate the wear of mechanical components in the equipment.
To set the maximum number of cooling cycles per hour while in the Installer Configuration Menu:
1. Answer NO to all prompts until the cooling cycles per hour prompt appears in the display. Press YES to enter the cooling cycles per hour menu.
2. Use the UP/DOWN arrow keys to adjust the maximum number of cooling cycles per hour. Press YES to store the value.
The display now shows the minimum heating/cooling deadband prompt. See the Setting the Heating/Cooling Deadband (Deadband) section for instruction s.
Setting the Heating/Cooling Deadband (Deadband)
The heating/cooling deadband setting establishes the minimum difference between the heating and cooling setpoints. The range is adjustable from 2 to 4 F° (1 to 2 C°).
To change the minimum deadband between the heating and cooling setpoints while in the Installer Configuration Menu:
1. Answer NO to all prompts until the deadband setpoint prompt appears in the display. Press YES to enter the deadband setpoint menu.
2. Use the UP/DOWN arrow keys to adjust the minimum deadband between the heating and cooling setpoints. Press YES to store the value.
The display now shows the fan control prompt. See the Setting the Fan Control (Fan cont) section for instructions.
Setting the Fan Control (Fan cont)
This parameter controls how the fan activates in response to a call for heating.
When the fan is in Auto Mode (as selected on the Main User Menu):
Selecting on enables the thermostat to control the fan on a call for heating or cooling.
When selecting off, the fan energizes by the thermostat on a call for cooling only. On a call for heating, the fan is controlled by the equipment fan limit control.
To set the fan control while in the Installer Configuration Menu:
1. Answer NO to all prompts until the fan control prompt appears in the display. Press YES to enter the fan control menu.
2. Using the UP/DOWN arrow keys, select on or off
.
Press YES to store the selection.
The display now shows the fan delay prompt. See the Setting the Setting the Fan Delay (Fan del) section for instructions.
Setting the Fan Delay (Fan del)
The fan delay extends the fan operation by 60 seconds after the call for heating or cooling has ended. This feature is only active when the fan is in the Auto mode.
To enable the fan delay while in the Installer Configuration Menu:
1. Answer NO to all prompts until the fan delay prompt appears in the display. Press YES to enter the fan delay menu.
2. Using the UP/DOWN arrow keys, select on or off. Press YES to store the selection.
The display now shows the occupancy override prompt. See the Establishing the Temporary Occupancy Time (ToccTime) section for inst ructions.
8 T600HCN-1 Non-Programmable Thermostat Installation Instructions
Page 9
Establishing the Temporary Occupancy Time (ToccTime)
The temporary occupancy time is the length of time the occupied mode setpoints are used when the override function is enabled (the override function can be enabled from the Main User Menu or from one of the digital inputs) or a temporary setpoint is entered. The range is adjustable from 0 to 12 hours.
To change the temporary occupancy time while in the Installer Configuration Menu:
1. Answer NO to all prompts until the temporary occupancy time prompt appears in the display. Press YES to enter the temporary occupancy time menu.
2. Use the UP/DOWN arrow keys to adjust the length of time the temporary occupancy setpoint should be in effect. Press YES to store the time.
The display now shows the room sensor calibration prompt. See the Room Air Sensor Calibration (Cal RS) section for instructions.
Room Air Sensor Calibration (Cal RS)
An offset can be added or subtracted to the actual displayed room temperature as needed. The range is ±5.0 F° (±2.5 C°), adjustable in increments of 1 F° (0.5 C°).
To change the room sensor calibration/offset while in the Installer Configuration Menu:
1. Answer NO to all prompts until the room sensor calibration prompt appears in the display. Press YES to enter the room sensor calibration menu.
2. Use the UP/DOWN arrow keys to adjust the correction that should be applied to the sensor reading. Press YES to store the offset.
The display now shows the outdoor air sensor calibration prompt. See the Outdoor Air Sensor Calibration (Cal OS) section for instructions.
Outdoor Air Sensor Calibration (Cal OS)
An offset can be added or subtracted to the actual displayed outdoor air temperature as needed. The range is ±5.0 F° (±2.5 C°), adjustable in increments of 1 F° (0.5 C°).
To change the outdoor air sensor calibration/offset while in the Installer Configuration Menu:
1. Answer NO to all prompts until the outdoor sensor calibration prompt appears in the display. Press YES to enter the outdoor sensor calibration menu.
2. Use the UP/DOWN arrow keys to adjust the correction that should be applied to the sensor reading. Press YES to store the offset.
The display now shows the heating lockout prompt. See the Setting the Heating Lockout (H lock) section for instructions.
Setting the Heating Lockout (H lock)
This feature disables heating operation based on outdoor air temperature (requires outdoor air temperature sensor to be connected for the function to be enabled). If the outdoor air temperature is above the heating lockout temperature, heating operation is disabled.
The heating lockout temperature parameter is adjustable from -15 to 120°F (-26 to 49°C) in increments of 5 F/C°.
To change the outdoor air temperature heating lockout while in the Installer Configuration Menu:
1. Answer NO to all prompts until the heating lockout prompt appears in the display. Press YES to enter the heating lockout menu.
2. Use the UP/DOWN arrow keys to adjust the lockout temperature. Press YES to store the value.
The display now shows the cooling lockout prompt. See the Setting the Cooling Lockout (C lock) section for instructions.
Setting the Cooling Lockout (C lock)
This feature disables cooling operation based on outdoor air temperature (requires outdoor air temperature sensor to be connected for the function to be enabled). If the outdoor air temperature is below the cooling lockout temperature, cooling operation is disabled.
The cooling lockout temperature parameter is adjustable from -40 to 95°F (-40 to 35°C) in increments of 5 F/C°.
To change the outdoor air temperature cooling lockout while in the Installer Configuration Menu:
1. Answer NO to all prompts until the cooling lockout prompt appears in the display. Press YES to enter the cooling lockout menu.
2. Use the UP/DOWN arrow keys to adjust the lockout temperature. Press YES to store the value.
3. The exit menu is displayed. Press YES to exit the Installer Configuration Menu or press NO to return to the beginning of the menu (digital input configuration).
T600HCN-1 Non-Programmable Thermostat Installation Instructions 9
Page 10
Operation
Operating the T600HCN-1
Once the T600HCN-1 is configured through the Installer Configuration Menu, the thermostat’s operating parameters can be entered through the Main User Menu (access the Main User Menu by pressing the MENU key during normal thermostat operation). The Main User Menu contains the basic operating features of the T600HCN-1 (see Table 3).
The Main User Menu uses Auto Help. Auto Help is displayed automatically in the Main User Menu when there is a pause in programming activity. To exit Auto Help, continue with the programming selection.
When the thermostat is in the Main User Menu and is left unattended for 45 seconds, it reverts to the Status Display Menu.
Table 3: T600HCN-1 Parameter Selection
RoomTemp
75.0°F
Override schd Y/N
*Resumes Regular Programmed
Resume schd Y/N
Temperat set? Y/N
Sys mode set? Y/N
Fan mode set? Y/N
Press the MENU key while in the Status Display Menu to enter the Main User Menu.
*Overrides Unoccupied Setpoints
Only Appears if Thermostat is in Unoccupied State See Enabling Occupancy Schedule.
Schedule and Setpoints Only Appears if Thermostat is in Override Mode See Resuming the Programmed Schedule.
Sets the Temperature Setpoints See Entering Temperature Setpoints.
Selects the System Mode Default: Automatic Mode (auto) See Selecting the System Mode.
Selects the Fan Mode Default: Automatic (auto) See Selecting the Fan Mode.
Enabling Override Schedule (only appears when in Unoccupied Mode) *See note in Table 3
The override schedule prompt only appears when the thermostat is in the unoccupied state. This menu selection gives the user the option of overriding the unoccupied setpoints with the occupied setpoints for the amount of time specified under the Establishing the Temporary Occupancy Time (ToccTime) parameter (see the Configuring the T600HCN-1 section). If one of the digital inputs is configured to operate as a remote override contact, this menu is disabled.
To override the unoccupied state while in the Main User Menu:
1. Answer NO to all prompts until the Override Schedule prompt appears. If the thermostat is in the unoccupied state, this is the first prompt.
2. Press YES to enable the temporary override. The T600HCN-1 returns to the Status Display Menu.
When scrolling through the Status Display Menu, Override now appears for the schedule status parameter.
Resuming the Programmed Schedule (only appears when in the Override Mode) See * in Table 3.
This menu only appears when the T600HCN-1 is in the:
unoccupied override mode
permanent occupied hold mode
permanent unoccupied hold mode
Note: (If the T600HCN-1 is not in one of these modes, this prompt does not appear). Answering yes to this prompt enables the T600HCN-1 to resume the regular scheduled program and setpoints.
To resume the schedule while in the Main User Menu:
1. Answer NO to all prompts until the Resume Schedule prompt appears. If the thermostat is in the override state, this is the first prompt.
2. Press YES to resume the programmed schedule.
Schedule hold Y/N
* Displayed only if Digital Input DI1or DI2 is configured
for remote NSB.
*Sets a Permanent Hold on the
Schedule or Resumes the Schedule See Setting Permanent Hold.
10 T600HCN-1 Non-Programmable Thermostat Installation Instructions
The T600HCN-1 returns to the Status Display Menu.
Page 11
Entering Temperature Setpoints
When the T600HCN-1 is in the occupied state, the first prompt appearing in the Main User Menu is to set the temperature setpoints. This prompt is where the heating and cooling setpoints for the occupied and unoccupied (see * in Table 3) states are entered. It is also where any temporary setpoints are entered.
To enter the heating and cooling setpoints for the occupied and unoccupied (see * in Table 3) modes (permanent or temporary), follow the steps in Table 4. When changing the temperatures, pressing the keys once changes the temperature 0.5 F/C° and holding down the keys changes the temperature by 5 F/C° increments.
Table 4: Entering Temperature Setpoints
RoomTemp
75.0°F
Temperat set? Y/N
Cooling set? Y/N
Press MENU from the Status Display Menu to enter the Main User Menu.
Answer NO to all prompts until the temperature set prompt appears in the display (it may be the first prompt). Press YES to enter temperature setting menu.
Press YES to change occupied cooling setpoint. Press NO to advance to occupied heating setpoint menu.
Setpoint Type Permanent Setpoints are permanently stored in the
schedule. This is the default setpoint type. Temporary Setpoints are changed, but are in effect
only for the time specified in the Establishing the Temporary Occupancy Time (ToccTime) parameter (see the Configuring the T600HCN-1 section).
Note: There is no indication that a temporary setpoint is enabled or active.
After the specified time, the temporary setpoint reverts to the permanent setpoint.
The temporary setpoint can be cancelled at any time by using the Permanent Setpoint option in this menu. When permanent modifications of the setpoints are required, this parameter needs to be set to permanent.
Unocc CL
80.0°F
Unocc HT set? Y/N
*Use the UP/DOWN arrow keys to
set temperature. Press YES to store value and advance to next menu.
*Press YES to change the
unoccupied heating setpoint. Press NO to advance to temperature display units.
Unocc HT
62.0°F
*Use the UP/DOWN arrow keys to
set temperature. Press YES to store value and advance to next menu.
Cooling
75.0°F
Heating set? Y/N
Heating
68.0°F
Unocc CL set? Y/N
Use the UP/DOWN arrow keys to set temperature. Press YES to store value and advance to next menu.
Press YES to change the occupied heating setpoint. Press NO to advance to unoccupied cooling setpoint menu.
Use the UP/DOWN arrow keys to set temperature. Press YES to store value and advance to next menu.
*Press YES to change the
unoccupied cooling setpoint. Press NO to advance to the unoccupied heating setpoint.
* Displayed only if Digital Input DI1 or DI2 is configured
°F/°C set? Y/N
Setpoint type Y/N
Setpoint permnent
Exit? Y/N
for remote NSB.
Press YES to set the display units to °F or °C. Press NO to advance to temperature setpoint type menu.
Press YES to select the setpoint type (permanent or temporary).
Using the UP/DOWN arrow keys, select the setpoint type (see Setpoint Type section for a description of choices). Press YES to enter the choice.
Press YES to return to the Status Display Menu or NO to re-enter the temperature setting menu.
T600HCN-1 Non-Programmable Thermostat Installation Instructions 11
Page 12
Selecting the System Mode
The T600HCN-1 has four system modes.
Automatic Mode (auto)
Automatic changeover between heating and cooling. This is the default setting.
Cooling Mode (cool)
Cooling operation only.
Heating Mode (heat)
Heating operation only.
Off Mode (off)
The T600HCN-1 is off. However, when frost protection is on (see the Enabling Frost Protection [Frost pr] section) the thermostat still calls for heat, if required.
To set the system mode while in the Main User Menu:
1. Answer NO to all prompts until the system mode prompt appears in the display. Press YES to set the system mode.
2. Use the UP/DOWN arrow keys to locate the desired system mode. Press YES to select the desired system mode.
3. Press YES to return to the Status Display Menu or NO to return to the system mode selection menu.
Selecting the Fan Mode
The T600HCN-1 has three fan mode settings.
On Fan Mode (on)
Energizes the fan all the time for both occupied and unoccupied periods (even if the system mode is set to off).
Automatic Fan Mode (auto)
Operates the fan only on a call for heating or cooling for both occupied and unoccupied periods. This is the default setting.
Smart Fan Mode (smart)
Energizes the fan all the time for occupied periods and only on a call for heat and cooling in unoccupied periods.
Note: Displayed only if Digital Input DI1 or DI2 is configured for remote NSB.
To select the fan mode while in the Main User Menu:
1. Answer NO to all prompts until the fan mode prompt appears in the display. Press YES to set the fan mode.
2. Use the UP/DOWN arrow keys to locate the desired fan mode. Press YES to select the desired fan mode.
3. Press YES to return to the Status Display Menu or NO to return to the fan mode selection menu.
Setting Permanent Hold Note: Displayed only if Digital Input DI1 or DI2 is
configured for remote NSB. This menu is used to set a permanent hold on the
internal scheduling or resume the schedule. The permanent hold is typically used for nonscheduled events that extend for long periods of time.
There are three selections for this menu:
Permanent Occupied Hold (occ hold) This selection puts the thermostat into a permanent occupied mode using the occupied setpoints. Occupied hold appears in the Status Display Menu when this selection is active.
Permanent Unoccupied Hold
This selection puts the T600HCN-1 into a permanent unoccupied mode using the unoccupied setpoints. Unoccup hold appears in the Status Display Menu when this selection is active.
Resume
This selection cancels the permanent hold and enables the regular program schedule.
To enable the permanent hold feature while in the Main User Menu:
1. Answer NO to all prompts until the schedule hold prompt appears in the display. Press YES to set the schedule hold type.
2. Use the UP/DOWN arrow keys to locate the desired permanent hold type (or resume schedule). Press YES to enter the choice.
3. Press YES to return to the Status Display Menu or NO to change the schedule hold selection again.
Accessories
Using the information in Table 5, contact the nearest Johnson Controls branch office or wholesale distributor to order these accessories.
Table 5: Optional Accessories (Includes Mounting Hardware)
Item
Remote Indoor Temperature Sensor Outdoor Air Temperature Sensor Duct Mount Temperature Sensor Remote Indoor Temperature Sensor
with Occupancy Override and LED
Product Code
Number
SEN-600-1 SEN-600-2 SEN-600-3
SEN-600-4
12 T600HCN-1 Non-Programmable Thermostat Installation Instructions
Page 13
Technical Specifications
Product Power Requirements Relay Contact Rating
Maximum Inductive
Digital Inputs
Recommended Wire Size
Thermostat Measurement
Range
Sensor Type:
Resolution:
Control Accuracy:
Outdoor Air Temperature
Indication Range
Setpoint Control Range
Minimum Deadband
Ambient Operating
Conditions
Ambient Storage
Conditions
Dimensions (H x W x D)
Shipping Weight
UL and cUL Listing
CE Compliance
FCC Compliance
The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products.
T600HCN-1 Non-Programmable Thermostat 20-30 VAC, 50/60 Hz, 24 VAC nominal, Class 2
1 ampere with in-rush surges up to 3 amperes, 30 VAC maximum Relay dry contact only across the C terminal to DI1 or DI2
18 gauge maximum, 22 gauge recommended
-40 to 122°F (-40 to 50°C) Local 10 K ohm NTC thermistor
±0.2 F° (±0.1 C°) ±0.9 F° (±0.5 C°) @ 70°F (21°C) typical calibrated
-40 to 122°F (-40 to 50°C) Cooling: 54 to 100°F (12 to 37.5°C) in 1/2 degree increments
Heating: 40 to 90°F (4.5 to 32°C) in 1/2 degree increments (Between heating and cooling) 2 F° or 1 C°
32 to 122°F (0 to 50°C); 0 to 95% RH noncondensing
-22 to 122°F (-30 to 50°C); 0% to 95% RH noncondensing
4.94 x 3.38 x 1.13 in. (125 x 86 x 29 mm)
0.75 lb (0.34 kg) File E27734 with CCN’s XAPX (US, UL 873) and XAPX7 (Canada, CSA C22.2 No. 24) CE Directives EN50081-1: 1992 EMC Emission; EN50082-2 EMC Immunity (Pending) This equipment has been tested and found to comply with the limits for a Class A digital
device and verified to Class B pursuant to Part 15 of FCC Rules. These limits are designed to provide reasonable protection against harmful interference when this equi pment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications.
This device complies with Class A Part 15 of the FCC rules. It was also verified to Class B. Operation is subject to the following two conditions: (1) This device may not cause harmful interference. (2) This device must accept any interference received, including interference that may cause undesired operation.
This Class A digital apparatus meets all of the requirements of the Canadian Interf erence-Causing Equipment Regulations. Cet appareil numérique de la Classe A respecte toutes les exigences du Règlement sur le materiél brouilleur du Canada.
Controls Group
507 E. Michigan Street P.O. Box 423 Printed in U.S.A. Milwaukee, WI 53201
www.johnsoncontrols.com
T600HCN-1 Non-Programmable Thermostat Installation Instructions 13
Loading...