Johnson Controls T-5500 Series Catalog Page

T-5500 Series
T-5500-1053
Pneumatic Temperature Indicator
Pneumatic Temperature Indicators
Description
The T-5500 Series Pneumatic Temperature Indicator provides continuous indication of the temperature measurement of a transmitter in a 3 to 15 psig (21 to 105 kPa) pneumatic transmission system.
Refer to T-5500 Pneumatic Temperature
Indicator Product Bulletin (LIT-7171350) and T-5502 Pneumatic Temperature Indicator Product Bulletin (LIT-7171355) for important
product information.
Repair Information
If the T-5500 Pneumatic Temperature Indicator fails to operate within its specifications, replace the unit. For a replacement indicator, contact the nearest Johnson Controls® representative.
Technical Specifications
T-5500 Series
Pneumatic Temperature Indicator
Accuracy T-5500: ±1/2% of Full Range
Pressure Range 3 to 15 psig (21 to 105 kPa) Ambient Temp.
Limits Air Connection 1/8 in. NPT Mounting Flush or Surface
per ANSI Spec. B40.1M T-5502: ±3-2-3% of Full Range per ANSI Spec. B40.1M
-20 to 150°F (-29 to 66°C)
Features
• available in two models T-5500: 3-1/2 in. dial size, ± 1/2% accuracy T-5502: 2-1/2 in. dial size, ± 3-2-3% accuracy
• equivalent Fahrenheit and metric scale printed on dial face. The dial range must match the range of the transmitter which is being used.
• easy readability
• removable clear plastic lens cover for cleaning and recalibration
• equipped to be flush or surface mounted
• notched U-clamps for flush-mounting break off to accommodate panel thicknesses of 1/16 to 3/4 in. (2 to 19 mm)
Selection Charts
T-5500 Series - T-5500 Range
Code Number Description
T-5500-1058 40 to 65°F (4.6 to 18.2°C) T-5500-1059 60 to 85°F (15.6 to 29.4°C) T-5500-1051 50 to 100°F (10 to 37.5°C) T-5500-1056 -20 to 80°F (-29 to 27°C) T-5500-1052 0 to 100°F (-17 to 37°C) T-5500-1057 20 to 120°F (-6 to 48°C) T-5500-1053 50 to 150°F (10 to 65°C) T-5500-1054 -40 to 160°F (-40 to 70°C) T-5500-1055 40 to 240°F (6 to 114°C)
Code No. LIT-1921245 Issued January 15, 2008
T-5500 Series - T-5502 Range
Code Number Description
T-5502-1133 40 to 65°F (4.6 to 18.2°C) T-5502-1134 60 to 85°F (15.6 to 29.4°C) T-5502-1001 50 to 100°F (10 to 37.5°C) T-5502-1006 -20 to 80°F (-29 to 27°C) T-5502-1002 0 to 100°F (-17.8 to 37°C) T-5502-1169 20 to 120°F (-6 to 48°C) T-5502-1003 50 to 150°F (10 to 65°C) T-5502-1004 -40 to 160°F (-40 to 70°C) T-5502-1005 40 to 240°F (6 to 114°C)
The performance specifications are nomina l and conf orm to accep table industr y standar ds. For ap plications a t condition s beyond th ese specification s, consult the local Johnson Controls o ffice. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2011 Johnson Controls, Inc.
www.johnsoncontrols.com