Johnson Controls T500HCP-1, T500HPP-1, T500HPP-2, T500MSP-1 User Manual

T500 Series Programmable Thermostats
T500 Series Thermostats provide an economical control solution for single-stage, multi-stage, or heat pump systems. Up to four event setpoints can be selected, as well as heat, cool, automatic changeover, and off modes.
Thermostats are available in the following types: T500HCP-1 (1 heat/1 cool), T500HPP-1 (heat pump, 3 heat/2 cool), T500HPP-2 (heat pump, 1 heat/1 cool), T500MSP-1 (2 heat/2 cool). Each thermostat is packaged with the necessary mounting hardware, and installation is simple and fast for reduced cost.
FANs 216, 1628.3
Product/Technical Bulletin T500
Issue Date 0899
Features and Benefits
!!!! Low-Profile Design
!!!! No Batteries Required
!!!! Lockable Access Cover and
Keypad Lockout
!!!! Full Function Liquid Crystal
Display (LCD)
!!!! Remote Sensor Terminals
!!!! Auxiliary Output
!!!! Fuzzy Logic Control
!!!! Smart Fan Option
Figure 1: T500 Series Programmable Thermostats
Complements any decor
Retains scheduled events and temperatures upon loss of power
Prevents unauthorized changes
Makes controls easy to read, easy to use
Allows the T500 thermostat to be mounted up to 300 m (1,000 ft) away from the controlled space using a SEN-500-1 (sold separately)
Energizes for auxiliary equipment operation
Optimizes control performance
Provides continous fan operation in the occupied mode and intermittent operation at night
© 1999 Johnson Controls, Inc.
Part No. 24-8347-35, Rev. E www.johnsoncontrols.com Code No. LIT-216173
1
ntroduction
I
ocation Considerations
L
The T500 thermostats use an adaptive control routine, based on fuzzy logic, to determine the heating or cooling load of the controlled space. The routine calculates load by evaluating recent room conditions and room reactions to heating and cooling. This load is used to determine the cycle rate of the equipment, giving optimal control of the space.
upplies Needed
S
drill
4.7 mm (3/16 in.) drill bit
3 mm (1/8 in.) flat-blade screwdriver
hammer
marking pencil
wire stripper
114. 3 (4-1/2)
Locate T500 thermostat as follows:
on a partitioning interior wall, and approximately
1.5 m (5 ft) above the floor in a location of average temperature
away from direct sunlight or radiant heat, outside
walls or behind doors, air discharge grills, stairwells, or outside doors
away from steam or water pipes, warm air stacks,
unheated/uncooled areas, or sources of electrical interference
!
CAUTION:
nstallation and Wiring
I
Note: When replacing an existing thermostat,
remove and use wire tags to identify terminal designations.
To install and wire the thermostat:
Shock Hazard.
Disconnect power supply before wiring connections are made to prevent electrical shock or possible damage to the equipment.
T500MSP-1 T500HPP-1
T500HCP-1
T500HPP-2
Figure 2: T500 Dimensions, mm (in.)
127 (5)
101.6 (4)
Dimn
22.2 (7/8)
1. Lift the thermostat cover and insert a small coin into the slot located in the bottom center of the thermostat case and twist 1/4 turn. (See Figure 3.) Grasp the base from the bottom two corners and separate from the thermostat.
2. Swing the thermostat out from the bottom, and lift up and out of the base. Place the rectangular opening in the base over the equipment control wires protruding from the wall and, using the base as a template, mark the location of the two mounting holes. No leveling is required.
3. Use the supplied anchors and screws for mounting on drywall or plaster. Drill two 4.7 mm (3/16 in.) holes at the marked locations, tap nylon anchors flush to wall surface, and fasten. (See Figure 4.)
4. Connect the wires from the existing system to the thermostat terminals according to wiring designations in Table 2, Table 3, Table 4, or Table 5. Push extra wire back into the wall. Wires must be flush to the plastic base. Plug hole with a fireproof material to prevent drafts from affecting ambient temperature readings.
2
T500 Series Programmable Thermostats Product/Technical Bulletin
!
CAUTION:
Equipment Damage Hazard.
Before applying power, make all wiring connections and check the connections. Short-circuited or improperly connected wires may result in permanent damage to the unit.
Figure 4: Mounting the Base
Figure 3: Separating the T500 from the Base
T500 Series Programmable Thermostats Product/Technical Bulletin
3
nstalling the Thermostat Cover Lock
I
If desired, insert the plastic lock piece into the bottom of the mounted base. The ends of the lock piece should fit snugly under the lock pins extending from the bottom of the mounted base. The tab in the middle of the lock piece should extend downward from the mounted base. (See Figure 5.)
To release the locking mechanism, press the lock piece up and into the base while gently prying open the thermostat at the same time. Use caution to avoid cracking the thermostat base or cover.
eattaching the Thermostat and Cover
R
to the Installed Base
1. Position the thermostat inside the cover, and attach on the hinged tabs located at the top of the base.
2. Swing the thermostat and cover down, and press on the bottom center edge until they snap in place. (See Figure 6.)
Plastic Lock Pin
Snap
plastic lock
into place.
Figure 5: Installing the Thermostat Lock
Thermostat Base
Hinged Ta b s
Figure 6: Installing the T500 Thermostat
4
T500 Series Programmable Thermostats Product/Technical Bulletin
IP Switch Selections
D
!
CAUTION:
Equipment Damage Hazard.
Before selecting a minimum on/off time, ensure the equipment can tolerate the following maximum hourly cycle rates: 7.5 cycles per hour when using 4-minute on/off, or 15 cycles per hour when using 2-minute on/off.
Table 1: DIP Switch Selections
DIP Switch Switch
Selection
1
2 (Smart Fan)
3
4
5
Continued on next page . . .
On Allows 2-event (day, night) programming.
Off Allows 4-event (morning, day, evening, night) programming.
On During the
Off Allows the fan to cycle with equipment or run continuously if the
On Allows 2-minute minimum on/off time for heating and cooling equipment.
Off Allows 4-minute minimum on/off time for heating and cooling equipment.
On Locks the keyboard, disabling buttons to prevent tampering. (Only the
Off Unlocks the keyboard.
On
Off
Description
equipment or runs continuously if the
Fan
after programming the thermostat. Smart Fan remembers that the fan should run continuously during these events after that.
During the Pressing the continuously for that night only.
At the end of the cycling or continuous fan) for the
pressed, regardless of the event. Changing between events does not affect the fan.
∨∨∨∨ and ∧∧∧∧ buttons will function. See
Programming Changes While the Keyboard is Locked, [Keyboard Locked]
T500HCP-1, T500HPP-2, T500MSP-1 only:
switch.
T500HPP-1 only:
the auxiliary heat is on. The compressor will remain off for 2 minutes after the auxiliary heat is turned off to ensure that the heat pump coil has cooled.
T500HCP-1, T500HPP-2, T500MSP-1 only:
call for heat.
T500HPP-1 only:
heat to be on simultaneously.
morning, day, and evening
button need only be pressed once during the morning, day, or evening event
night
event, the fan automatically cycles with the equipment by default.
Fan
button during the night event overrides and causes the fan to run
night
event, Smart Fan remembers the fan selection (automatic
in this bulletin.)
Compressor/Auxiliary Interlocked: Turns off the compressor when
Compressor/Auxiliary Normal: Allows the compressor and auxiliary
events, the fan automatically cycles with the
Fan
button is pressed. To run continuously, the
morning, day, and evening
Programming the Thermostat, Making
Allows the fan to delay with the plenum
Allows fan to operate immediately with a
events and reverts back.
Fan
button is
Outdoor
Temporary [1 Hour]
and
and
T500 Series Programmable Thermostats Product/Technical Bulletin
5
DIP Switch (Cont.)
Switch Selection
Description
6
On
Off
7
LED 1 icon
T500HPP-1, T500MSP-1 only:
T500HPP-1, T500MSP-1 only:
T500HPP-1, T500MSP-1 only:
off/on (See Table 5.)
8
LED 2 icon
T500HPP-1, T500MSP-1 only:
off/on (See Table 5.)
4 Events Per Day
Smart Fan Disabled
Heat/Cool: 4 Min ute
(Minimum On)
Keyboard Unlocked
Fan Immediate
with Heat Call
1
2
3
4
5
O N
2 Events Per Day
Smart Fan Enabled
Heat/Cool: 2 Minute (Min imum On)
Keyboard Locked
Fan On with Plenum Switch
Figure 7: T500HCP-1 Factory-Set DIP Switch
Settings (All Off)
Allows multi-stage heating or cooling.
Allows single-stage heating or cooling.
Optional selection: LCD icon comes on with LED 1.
Optional selection: LCD icon comes on with LED 2.
Table 2: T500HCP-1 Output Terminal Designations
Terminal Function
W1
Y1
G
R
24V
24V(c)
RS2
RS1
RS+V
Energizes on call for heating
Energizes on call for cooling
Energizes fan on call for heating or cooling or by pressing
Fan
button
Independent switching voltage
24 VAC from equipment transformer
24 VAC (common) from equipment transformer
Connections for outdoor air temperature or indoor remote sensors; refer to instructions included with sensors.
W1
Y1
24V
24V(c)
RS2
RS1
RS+V
Heating
Cooling
Fan
Common
Figure 8: T500HCP-1 Wiring Terminals
6
T500 Series Programmable Thermostats Product/Technical Bulletin
G
R
Hcp-1wire
4 Events Per Day
Smart Fan Disabled
Heat/Cool: 4 Minute
(Minimum On)
Keyboard Unlocked
Compressor/Auxiliary
Normal
Single Stage
LED 1 Icon Off
LED 2 Icon Off
1
2
3
4
5
6
7
8
ON
Figure 9: T500HPP-1 DIP Factory-Set
DIP Switch Settings
1st Stage Compressor
24VAC
Figure 10: T500HPP-1 Wiring Terminals
2 Events Per Day
Smart Fan Enabled
Heat/Cool: 2 Minute (Minimum On)
Keyboard Locked Compressor/Auxiliary
Interlocked Multi-stage
LED 1 Icon (Filter)
LED 2 Icon (Wrench/Fault)
W2
Table 3: T500HPP-1 Output Terminal Designations
Terminal Function
W2
Y2
W1
Y1
G
R
24V
24V(c)
O
B
LED 1
LED 2
RS2
RS1
RS+V
NO
COM
NC
Energizes auxiliary heat as second-stage heating in emergency heat mode
Energizes compressor No. 2 on call for second-stage heating or cooling
Energizes auxiliary heat as last-stage heating or first-stage in emergency heat
Energizes compressor No. 1 on call for heating or cooling
Energizes fan on call for heating or cooling or by pressing
Fan
button
Independent switching voltage
24 VAC from equipment transformer
24 VAC (common) from equipment transformer
Energizes reversing valve in the cooling mode
Energizes reversing valve in the heating mode
Input connection that energizes LED 1 or LED 2 from remote status device (See Figure 9 and Table 6.)
Connections for outdoor air temperature or indoor remote sensors; refer to instructions included with sensors.
The relay coil is de-energized in the night event. In all other events, the relay coil is energized. (See Figure 16.)
T500 Series Programmable Thermostats Product/Technical Bulletin
7
4 Events Per Day
Smart Fan Disabled
Heat/Cool: 4 Minute
(Minimum On)
Keyboard Unlocked
Fan Immediate
with Heat Call
1
2
3
4
5
ON
2 Events Per Day
Smart Fan Enabled
Heat/Cool: 2 Minute (Minimum On)
Keyboard Locked
Fan On with Plenum Switch
Table 4: T500HPP-2 Output Terminal Designations
Terminal Function
Single-Stage Heat Pump Thermostat
Conventional Single-Stage Heat/Cool Thermostat
Figure 11: T500HPP-2 Factory-Set DIP Switch
Settings (All Off)
RS2 RS1
RS+V
Compressor
Fan
24VAC
Common
W1
B
Hpp-2wire
Figure 12: T500HPP-2 Wiring Terminals
Note:
W1*
Jumpered to Y1 (See Note.)
Energizes on call for heating (See Note.)
Y1
Energizes compressor contactor
Energizes on call for cooling (See Note.)
(See Note.)
G
R
Energizes fan on call for heating or cooling or by pressing
Fan
button
Independent switching voltage (See Note.)
24V
24V(c)
24 VAC from equipment transformer
24 VAC (common) from equipment transformer
RS2 RS1
RS+V
O
Connections for outdoor air temperature or indoor remote sensors; refer to instructions included with sensors
Energizes
Not used reversing valve in the cooling mode
B
Energizes
Not used reversing valve in the heating mode
Single-Stage Heat Pump:
Leave the factory-installed jumper connected between W1 and Y1 and wire O or B as shown in Figure 12.
Conventional Single-Stage Heat/Cool:
Remove the factory-installed jumper between W1 and Y1 and wire as shown in Figure 12. Note that the O and B terminals are not used in this application.
8
T500 Series Programmable Thermostats Product/Technical Bulletin
Loading...
+ 16 hidden pages