Multi-Stage Electromechanical Temperature Controls
Code No. LIT-1922270
T46 Series Fan Coil Thermostat
Description
The T46 Series Thermostat is used to control
line voltage, fan coil, and heating zone valves
on heating, cooling, and combination heating
and cooling systems. Models are available
with single-pole, single-throw (SPST) or
single-pole, double-throw (SPDT) contact
action for standard duty (nominal 1/4 hp,
6 A non-inductive) applications. Thermostats
are available with or without fan speed control
or built-in thermometers. Various system
switch combinations are available, including
fan speed selection.
Field-installable faceplate combinations of
knob or concealed adjustment are possible.
Also, the T46 is available with or without
thermometer indication. These thermostats
have plastic locking covers with an
Allen-head screw to discourage unauthorized
tampering. Standard models are supplied
with the thermostat faceplate installed with
knob adjustment and thermometer.
Refer to the T46 Series Fan Coil Thermostats
Product Bulletin (LIT-125655) for important
product application information.
Selection Charts
T46 Series Fan Coil Thermostat
Product Code
Number
System
Switch
Fan
Switch
Heating
T46ABH-1C Auto-off-fan None
T46ADH-1C Off-auto None
Cooling
T46JBH-1C Auto-off-fan None
T46JDH-1C Off-auto None
T46JEA-1C On-off Low-med-high
Heating and Cooling
T46SAA-1C Heat-off-cool Low-med-high
T46SAH-1C Heat-off-cool None
T46SDA-1C Off-auto Low-med-high
T46SDH-1C Off-auto None
Technical Specifications
Range Thermostat 40 to 90°F (5 to 30°C)
Thermometer 50 to 90°F (10 to 30°C)
Differential Mechanical Approximately 0.7°F (0.4°C)
Operating See next page
Finish Cover Almond
Faceplate Gold metallic with dark brown border and lettering
Mounting Double gang box, separable mounting plate
Material Base 0.050 in. (1 mm) cold rolled steel
Cover 0.090 in. (2 mm) high-impact plastic
Sensing Element Liquid-filled for positive trouble-free operation
Shipping Weight Individual Pack 1 lb (0.45 kg)
Overpack of 20 Units 20 lb (9.07 kg)
Thermometer Bimetal type for accuracy and clarity, can be field-calibrated
Wiring Connections Color coded No. 16 AWG wires, 8 in. (203 mm) long
The performance specifications are nomina l and con form to accep table ind ustry stand ards. For applicati ons at con ditions be yond these specification s, consult th
Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2015 Johnson Controls, Inc.
Features
• knob or concealed setpoint adjustment
• low and high temperature dial stops that
are concealed and adjustable throughout
setpoint range
• can be set for a locked dial
• narrow differential without the need for
anticipator
• standard internal dual Celsius and
Fahrenheit scales
• switch mechanism and wiring connections
go into the switch box to isolate electrical
circuits from the sensing element
• mounts on a standard double outlet box
• separable mounting plate allows easy
mounting and wiring without removing
thermostat cover
• locking cover reduces unauthorized
tampering
• high-impact plastic enclosure
• smooth action multi-position slide switches
Applications
These thermostats control fan coil and zone
heating valves on a wide variety of heating
and cooling combinations for conditioned
space.
for dependable service
Replacement Parts
Product Code Number Description
CVR88A-600R Thermostat Cover Assembly for knob adjustment models with thermometer,
KNB26A-600R Plastic push on knob for thermostat
BKT48A-600R Mounting plate for T46
°F scale, faceplate supplied unassembled
Accessories
Product Code
Number
Faceplate Selection
Mounting
Position
PLT333-1R
PLT333-3R Vertical Concealed Yes Fahrenheit
PLT333-5R Vertical Knob Yes Celsius
PLT333-12R Vertical Concealed No –
1. Faceplates must be ordered in multiples of ten.
2. Supplied with standard wholesaler models.
2
Vertical Knob Yes Fahrenheit
T46 Series Fan Coil Thermostats
1
Typ e o f
Adjustment
Thermometer
Cutout
Temperature
Scale
R-72
5
4
3
2
1
0
02468
2.2
1.1
Operating Differential F
0
Operating Differential C
0
Amperage Load
T46A, T46S Heating
Operating Differential for T46A and Heating Side of T46S
t46heat.eps
5
4
3
2
1
0
02468
2.2
1.1
Operating Differential F
0
Operating Differential C
0
Amperage Load
T46J, T46S Cooling
Operating Differential for T46J and Cooling Side of T46S
t46cool.eps
Grey
Black
L1 (Hot)
Neutral
Orange
Red
To Fan
To Heating
T46ABH Auto-Off-Fan Selector Switch
with Continuous Fan (Heating Only)
t46auht.eps
Grey
Black
Neutral
Orange
Blue
To Fan
To Cooling
T46JBH Auto-Off-Fan Selector Switch
with Continuous Fan (Cooling Only)
t46auco.eps
Black
L1 (Hot)
Neutral
Orange
To Fan
Changeover
Control
Grey
Valve
Red
Blue
B
R
Y
Fan
Off
T46SDH Off-Auto Selector Switch.
Used on Fan-Coil Unit with Cycling Valve and Continuous Fan.
Terminal Markings Shown for
A19CAC Changeover Control (Heating and Cooling)
t46_2.eps
Multi-Stage Electromechanical Temperature Controls
T46 Series Fan Coil Thermostat (Continued)
Technical Specifications (Continued)
Electrical Ratings
Motor Ratings 120 V 208 V 240 V 277 V
T46 System and Fan Switches
AC Full Load A 12.0 6.9 6.0 5.2
AC Locked Rotor A 34.8 19.1 17.4 14.4
AC Non-Inductive A 6.5 6.5 6.5 –
Pilot Duty 125 VA, 24 to 277 VAC
T46 Thermostat Only
AC Full Load A 6.0 3.5 3.0 –
AC Locked Rotor A 34.8 19.1 17.4 –
AC Non-Inductive A 6.5 6.5 6.5 –
Pilot Duty 125 VA, 24 to 277 VAC
Operating Differentials
Typical Wiring Application for Heating
Typical Wiring Application for Cooling
Note: The heavy line in each of the above figures is the nominal
operating temperature differential. Production thermostats may vary
from the norm, as indicated by the dotted line.
The performance specifications are no minal and co nform t o acceptab le ind ustry standar ds. For appl ications at condition s beyond these specifica tions, consult th
Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2015 Johnson Controls, Inc.
Typical Wiring Application for Combination
R-73