Johnson Controls T-4600 Catalog Page

Code No. LIT-1921705
T-4600 Energy Manager Heating-Cooling
Low Volume Output Thermostat
Issued January 15, 2008
T-4600
Energy Manager Heating-Cooling Low Volume Output Thermostat
Description
The T-4600 Thermostat is a low volume output, energy managing, heating-cooling thermostat. The independent setpoints can result in a deadband to encourage energy conservation by eliminating heating and cooling overlap.
Refer to T-4000 Series Pneumatic Room Thermostat Product Bulletin (LIT-7171060P) for important product information.
Repair Information
If the T-4600 Energy Manager Heating­Cooling Low Volume Output Thermostat fails to operate within its specifications, replace the unit. For a replacement thermostat, contact the nearest Johnson Controls® representative.
Features
• mounts vertically
• available in Fahrenheit or Celsius models
• two outputs
• adjustable sensitivities
• adjustable set points
• available in these models
- Dual Direct
- Dual Reverse
- Direct and Reverse
Selection Charts
T-4600 Thermostat
Code Number Description
T-4600-1 Direct Acting, Fahrenheit T-4600-2 Reverse Acting, Fahrenheit T-4600-3 Direct Acting, Celsius T-4600-5 Direct and Reverse, Fahrenheit T-4600-6 Direct and Reverse, Celsius
Accessories for T-4600
Code Number Description
R-3710 Series (two required)
0.005 or 0.007 inch Restrictors
Technical Specifications
T-4600 Energy Manager Heating-Cooling LOw Volume Output Thermostat
Sensitivity Adjustable from 1 to 3 psig/°F (12 to 38 kPa/°C)
Flow Capacity 45 SCIM (12 mL/s) with .007 in. Restrictor
Air Consumption 50 SCIM (14 mL/s) or 90 SCIM (24 mL/s) depending on Restrictor Supply Pressure 13 to 25 psig (91 to 175 kPa)
Dial Range 55 to 85°F or 12 to 28°C Air Connections Two Restricted Supply/Output for Heating and Cooling
Factory set at approximately 2.5 psig/°F (32 kPa/°C)
25 SCIM (7 mL/s) with .005 in. Restrictor
Nominal 20 psig (140 kPa)
The performance specifications are nomina l and conf orm to accep table industr y standar ds. For ap plications a t condition s beyond th ese specification s, consult the local Johnson Controls o ffice. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2011 Johnson Controls, Inc.