Johnson Controls T-4110 Catalog Page

Code No. LIT-1921700
T-4110 Single Temperature
Low Volume Thermostat
for Ceiling Terminal Units
Issued January 15, 2008
T-4110
Single Temperature Low Volume Output Thermostat for Ceiling Terminal Units
Description
The T-4110 Thermostat is a low volume output, single-temperature thermostat designed for mounting in ceiling terminal units.
Refer to T-4000 Series Pneumatic Room Thermostat Product Bulletin (LIT-7171060P) for important product information
Repair Information
If the T-4110 Single Temperature Low Volume Output Thermostat for Ceiling Terminal Units fails to operate within its specifications, replace the unit. For a replacement thermostat, contact the nearest Johnson Controls® representative.
Selection Charts
T-4110 Thermostat
Code Number Description
T-4110-1 Direct Acting, Less Aspirator T-4110-2 Direct Acting, With Aspirator T-4110-3 Reverse Acting, Less Aspirator T-4110-4 Reverse Acting, With Aspirator
Accessories for T-4110
Code Number Description
R-3710 Series 0.005 or 0.007 inch Restrictors
Features
• mounts in:
- room air sampling chamber
- return air grille
- diffuser, when equipped with an optional protective cover which incorporates an aspirator to power the thermostat from duct air pressure
• available as Direct Acting (DIR) or Reverse Acting (REV) models
• features a long, flexible, plastic lever connected to its set point adjuster, which extends through the ceiling or diffuser, allowing adjustment from inside a room
Technical Specifications
T-4110 Thermostat
Sensitivity Adjustable from 1 to 3 psig/°F (12 to 38 kPa/°C)
Flow Capacity 45 SCIM (12 mL/s) with .007 in. Restrictor
Air Consumption 45 SCIM (12 mL/s) or 25 SCIM (7 mL/s) depending on Restrictor Supply Pressure 13 to 25 psig (91 to 175 kPa)
Flexible Set Point Lever Range 66 to 82°F Air Connections Two, Control and Aspirator
Factory set at approximately 2.5 psig/°F (32 kPa/°C)
25 SCIM (7 mL/s) with .005 in. Restrictor
nominal 20 psig (140 kPa)
The performance specifications are nomina l and conf orm to accep table industr y standar ds. For ap plications a t condition s beyond th ese specification s, consult the local Johnson Controls o ffice. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2011 Johnson Controls, Inc.
www.johnsoncontrols.com