See the following page for a complete Table of Contents.
NOTES, CAUTIONS AND WARNINGS
The installer should pay particular attention to the words:
NOTE, CAUTION, and WARNING. Notes
clarify or make the installation easier. Cautions
to prevent equipment damage. Warnings
alert installer that personal injury and/or equipment damage may result if installation procedure is not handled
properly.
30 ELECTRIC HEAT LIMIT CONTROL SETTING . . . . . 34
31 ELECTRIC HEAT ANTICIPATOR SETPOINTS . . . . 35
32 UNIT CONTROL BOARD FLASH CODES . . . . . . . . 37
Pg. #
Johnson Controls Unitary Products3
364985-XIM-B-0508
GENERAL
YORK Model BQ units are single package heat pumps
equipped with optional factory installed electric heaters. These are designed for outdoor installation on a
rooftop or slab.
The units are completely assembled on rigid, permanently attached base rails. All piping, refrigerant
charge, and electrical wiring is factory installed and
tested. The units require electric power, gas connection, duct connections, installation of combustion air
inlet hood, flue gas outlet hoods and fixed outdoor air
intake damper (units without ec onomizer or motorized
damper option only) at the point of installation.
The supplemental electric heaters have nickel-chrome
elements and utilize single point power connection.
SAFETY CONSIDERATIONS
Due to system pressure, moving parts and electrical
components, installation and servicing of air conditioning equipment can be hazardous. Only qualified,
trained, service personnel should install, repair, maintain or service this equipment.
Observe all precautions in the literature, on labels and
tags accompanying the equipment whenever working
on air conditioning equipment. Be sure to follow all
other safety precautions that apply.
•530.18-N1.14V -Man. Outdoor Air Damper Accy
0 - 100%
•035-07364-000 -Motorized Outdoor Air Damper
Accy.
•035-19422-000 –Electric Heat Accessory
•035-19405-000 -Barometric Relief Damper
•530.46-N1.1V -Dual Enthalpy Accessory
•530.18-N1.10V -Power Exhaust Accessory
RENEWAL PARTS
Contact your local York® parts distribution center for
authorized replacement parts.
APPROVALS
Design listed by CSA as follows:
•For use as a heat pump only with or without
optional electric heat.
•For outdoor installation only.
•For installation on combustible material.
Wear safety glasses and work gloves, and follow all
safety codes. Use a quenching cloth and have a fire
extinguisher available for all brazing operations.
INSPECTION
As soon as a unit is received, it should be inspected for
possible damage during transit. If damage is evident,
the extent of the damage should be noted on the carrier's freight bill. A separate request for inspection by
the carrier's agent should be made in writing. Refer to
Form 50.15-NM for additional information.
REFERENCE
Additional information on the design, installation, operation and service of this equipment is available in the
following reference forms:
•364985 -General Installation
•035-19404-000 -Economizer Accessory
•530.18-N1.13V -Man. Outdoor Air Damper
Accessory 0 - 35%
This product must be installed in strict compliance with the enclosed installation instructions
and any applicable local, state, and national
codes including, but not limited to, building,
electrical, and mechanical codes.
Improper installation may create a condition
where the operation of the product could cause
personal injury or property damage.
The installer should pay particular attention to the
words: NOTE, CAUTION and WARNING. Notes are
intended to clarify or make the installation easier. Cautions are given to prevent equipment damage. Warnings are given to alert installer that personal injury and/
or equipment damage may result if installation procedure is not handled properly.
4Johnson Controls Unitary Products
364985-XIM-B-0508
PRODUCT NOMENCLATURE
3-5 Ton Sunline Simplicity Model Number Nomenclature
A = Direct Drive
B = Direct Drive/Single Input Economizer
D = Direct Drive/Motorized Damper
N = Belt Drive
P = Belt Drive/Single Input Economizer
R = Belt Drive/Motorized Damper
T = Belt Drive High Static
U = Belt Drive High Static/Single Input Economizer
V = Belt Drive High Static/Motorized Damper
Voltage
2 = 208/230-3-60
4 = 460-3-60
5 = 575-3-60
Product Style
A = Style A
These four digits will not be assigned until a quote is requested, or an order placed.
SS Drain Pan
CPC Controller, DFS, APS
Johnson Controller, DFS, APS
Honeywell Controller, DFS, APS
Novar Controller, DFS, APS
Simplicity IntelliComfort Controller
Simplicity IntelliComfort Controller w/ModLinc
2" Pleated Filters
BAS Ready Economizer (2-10 V. D. C. Actuator without a Controller)
Any Combination of Additional Options that Don’t Have an Option Code Pre-assigned
Product Generation
1 = First Generation
2 = Second Generation
Standard Cabinet
AA = None
AB = Phase Monitor
AC = Coil Guard
AD = Dirty Filter Switch
AE = Phase Monitor & Coil Guard
AF = Phase Monitor & Dirty Filter Switch
AG = Coil Guard & Dirty Filter Switch
AH = Phase Monitor, Coil Guard & Dirty Filter Switch
AS = Bottom Drain Connection
RC = Coil Guard & American Flag
TA = Technicoat Condenser Coil
TJ = Technicoat Evaporator Coil
TS = Technicoat Evaporator and Condenser Coil
ZZ = If desired option combination is not listed above, ZZ will be assigned and configuration options will be
located in digits 15-18.
Configuration Options (not required for all units)
Additional Options
Hinged Filter Door & Toolless Access Cabinet
BA = Hinged Filter Door & Toolless Access Panels
BA = Hinged Filter Door & Toolless Access Panels
BA = Hinged Filter Door & Toolless Access Panels
BB = Phase Monitor, Hinged Filter Door & Toolless
Read these instructions before continuing this appliance installation. This is an outdoor combination heating and cooling unit. The installer must assure that
these instructions are made available to the consumer
and with instructions to retain them for future reference.
1.Install this unit only in a location and position as
specified on page 6 of these instructions.
2.This equipment is not to be used for temporary
heating of buildings or structures under construction.
LIMITATIONS
These units must be installed in accordance with the
following national and local safety codes:
In U.S.A
•National Electrical Code ANSI/NFPA No. 70.
.:
In Canada
:
•Current Canadian Electrical Code C22.1.
•Local plumbing and waste water codes.
•Other applicable local codes.
Refer to the Unit Application Data Table 1 and the
Electrical Data table for the unit.
If components are to be added to a unit to meet local
codes, they are to be installed at the dealer's and/or
the customer's expense.
Size of unit for proposed installation should be based
on heat loss/heat gain calculation made according to
the methods of the Air Conditioning Contractors of
America (ACCA).
This unit is not to be used for temporary heating of
buildings or structures under construction.
TABLE 1: UNIT APPLICATION DATA (BQ)
UNIT MODEL NUMBER036048060
Voltage Variation,
Min. / Max.
Wet Bulb Temper ature (ºF) of Air on
Evaporator Coil, Min. / Max
Dry Bulb Temperature (ºF) of Air on
Condenser Coil, Min. / Max.
1. Utilization range “A” in accordance with ARI Standard 110.
1
Supply Air CFM, Nom.120016002000
208/230187 / 253
460414 / 506
575518 / 630
LOCATION
Use the following guidelines to select a suitable location for these units.
1.Unit is designed for outdoor installation only.
2.Condenser coils must have an unlimited supply of
air.
3.Where a choice of location is possible, position the
unit on either north or east side of building.
4.For ground level installation, use a level concrete
slab with a minimum thickness of 4 inches. The
length and width should be at least 6 inches
57 / 72
0 / 120
greater than the unit base rails. Do not tie slab to
the building foundation.
5.Roof structures must be able to support the weight
of the unit and its options and/or accessories. Unit
must be installed on a solid level roof curb or
appropriate angle iron frame.
6.Maintain level tolerance to 1/2 inch maximum
across the entire length or width of the unit.
If a unit is to be installed on a roof curb or special frame
other than a YORK roof curb, gasketing must be
applied to all surfaces that come in contact with the unit
underside.
6Johnson Controls Unitary Products
364985-XIM-B-0508
RIGGING AND HANDLING
Exercise care when moving the unit. Do not remove
any packaging until the unit is near the place of installation. Rig the unit by attaching chain or cable slings to
the lifting holes provided in the base rails. Spreader
bars, whose length exceeds the largest dimension
across the unit, MUST BE USED.
Units may also be moved or lifted with a forklift. Slotted
openings in the base rails are provided for this purpose. Fork lengths must be a minimum of 42 inches.
Remove the nesting brackets from the four corners on
the top of the unit. All screws that are removed when
removing the brackets must be replaced on the unit.
Refer to Table 8 for unit weights and to the Figure 6 for
approximate center of gravity.
Before lifting a unit, make sure that all panels
are in place and that its weight is distributed
equally on all cables so it will lift evenly.
CLEARANCES
A closed return duct system shall be used. This shall
not preclude use of economizers or outdoor fresh air
intake. The supply and return air duct connections at
the unit should be made with flexible joints to minimize
noise.
The supply and return air duct systems should be
designed for the CFM and static requirements of the
job. They should NOT be sized to match the dimensions of the duct connections on the unit.
When fastening ductwork to side duct flanges
on unit, insert screws through duct flanges
only. DO NOT insert screws through casing.
Outdoor ductwork must be insulated and
waterproofed.
Refer to Figures 7 and 10 for information concerning
side and bottom supply and return air duct openings.
CONDENSATE DRAIN
Plumbing must conform to local codes. Use a sealing
compound on male pipe threads. Install a condensate
drain line from the 3/4" NPT female con nection on the
unit to an open drain.
All units require certain clearances for proper operation
and service. Installer must make provisions for adequate ventilation air. Refer to Dimensions and Clearances shown in Figures 7 thr ough 10 and T able 18 for
the clearances required for combustible construction,
servicing, and proper unit operation.
Do not permit overhanging structures or shrubs
to obstruct outdoor air discharge outlet, combustion air inlet or vent outlets.
DUCTWORK
Ductwork should be designed and sized according to
the methods in Manual Q of the A ir Conditioning Contractors of America (ACCA).
NOTE: The condensate drain operates in a negative
pressure in the cabinet. The condensate drain
line MUST be trapped to provide proper drainage. See Figure 1.
FIGURE 1 - RECOMMENDED DRAIN PIPING
Johnson Controls Unitary Products7
364985-XIM-B-0508
COMPRESSORS
Units are shipped with compressor mountings factoryadjusted and ready for operation.
Units with scroll compressors have a shipping bracket
which must be removed after the unit is set in place.
See Figure 2.
COMPRESSOR
MOUNTING
BRACKET BASE
REMOVE THESE
SCREWS (2)
MOUNTING
BRACKET TOP
(REMOVE)
FILTERS
One-inch or two-inch filters can be supplied with each
unit. Filters must always be installed ahead of the
evaporator coil and must be kept clean or replaced with
same size and type. Dirty filters will reduce the capacity
of the unit and will result in frosted coils or safety shutdown. Minimum filter area and required sizes are
shown in Physical Data Table 7.
SERVICE ACCESS
The following removable panels provide access to all
serviceable components:
•Compressor compartment
•Electric Heat compartment
•Blower compartment
•Main control box
•Filter compartment
Refer to the Dimensions and Clearances shown in Figures 7 and 11 for location of these access panels.
WIRE TIE (CUT AND REMOVE)
FIGURE 2 - COMPRESSOR RESTRAINING
BRACKET
Do not loosen compressor mounting bolts.
Make sure that all screws and panel latches
are replaced and properly positioned on the
unit to maintain an airtight seal.
8Johnson Controls Unitary Products
364985-XIM-B-0508
TYPICAL POWER WIRING
REFER TO THE ELECTRICAL DATA
TABLES TO SIZE THE DISCONNECT
SWITCH, OVERCURRENT PROTECTION AND WIRING.
TYPICAL CONTROL WIRING
COOLING / HEATING (24 VOLT THERMOSTAT)
THERMOSTAT
TERMINALS
ADD
JUMPER
1
RH
RC
UNIT TERMINAL
STRIP TB1
R
Y
W
G
1
24 VOLT THERMOSTAT 2ET07701024. TO CONTROL THE ECONOMIZER ON THE SECOND
STAGE COOLING OR TO HAVE AN ELECTRIC HEAT ACCESSORY WITH TWO STAGES OF
HEAT, USE THERMOSTAT 2TH0471024.
SECOND STAGE COOLING IS NOT REQUIRED ON UNITS LESS ECONOMIZER.
3
SECOND STAGE HEATING IS ONLY REQUIRED ON UNITS WITH A TWO STAGE
ELECTRIC HEATER OR 2 STAGE GAS HEAT.
4
REMOVE JUMPER J2 FROM TERMINALS 4 AND 9 ON JUMPER PLUG CONNECTOR
P6 ON UNITS WITH ECONOMIZER. TERMINALS A1 AND A2 PROVIDE A RELAY
OUT-PUT TO CLOSE THE OUTDOOR ECONOMIZER DAMPERS WHEN THE
THERMOSTAT SWITCHES TO THE SET-BACK POSITION.
Y1
Y2
W1
W2
G
C
24 VOLT
TRANSFORMER
COOLING / HEATING (ELECTRONIC THERMOSTAT)
SINGLE STAGE
THERMOSTAT
TERMINALS
ADD
JUMPER
1
ELECTRONIC PROGRAMMABLE THERMOSTAT 2ET07701024 (INCLUDES SUBBASE).
TO CONTROL THE ECONOMIZER ON SECOND STAGE COOLING, USE THERMOSTAT
2TH04700224.
1
UNIT TERMINAL
RH
RC
Y
W
G
STRIP TB1
R
Y1
W1
G
C
24 VOLT
TRANSFORMER
FIGURE 3 - TYPICAL FIELD POWER & CONTROL WIRING
Johnson Controls Unitary Products9
THERMOSTAT
The room thermostat should be located on an inside
wall approximately 56 inches above the floor where it
will not be subject to drafts, sun exposure or heat from
electrical fixtures or appliances. Follow the manufacturer's instructions enclosed with the thermostat for
general installation procedure. A minimum of seven
color-coded insulated wires (#18 AWG) should be used
to connect the thermostat to the unit.
POWER AND CONTROL WIRING
Field wiring to the unit must conform to provisions of
the National Electrical Code, ANSI / NFPA No. 70 (in
U.S.A.), current Canadian Electrical Code C22.1 (in
Canada) and/or local ordinances. The unit must be
electrically grounded in accordance with NEC and CEC
(as specified above) and/or local codes. Voltage tolerances, which must be maintained at the compressor
terminals, during starting and running conditions, are
indicated on the unit Rating Plate and the Unit Application Data table.
The internal wiring harness furnished with this unit is
an integral part of a CSA design certified unit. Field
alteration to comply with electrical codes should not be
required.
A fused disconnect switch should be field provided for
the unit. The switch must be separate from all other circuits. Wire entry at knockout openings require conduit
fittings to comply with NEC (in U.S.A.), CEC (in Canada) and/or local codes. If any of the wire supplied with
the unit must be replaced, replacement wire must be of
the type shown on the wiring diagram and the same
minimum gauge as the replaced wire.
Use copper conductors properly sized to carry the load.
Each unit must be wired with a separate branch circuit
fed directly from the meter panel and properly fused.
364985-XIM-B-0508
When connecting electrical power and control
wiring to the unit, waterproof type connectors
MUST BE USED so that water or moisture
cannot be drawn into the unit during normal
operation. The above waterproofing conditions
will also apply when installing a field-supplied
disconnect switch.
Refer to the Typical Field Wiring Figure 3 and to the
appropriate unit wiring diagram for control circuit and
power wiring information.
TABLE 2: CONTROL WIRE SIZES
Wire Size
18 AWG150 Feet
1. From the unit to the thermostat and back to the unit.
Maximum Length
1
OPTIONS/ACCESSORIES
ELECTRIC HEAT
The factory- or field-installed heaters are wired for single point power supply. Power supply need only be
brought into the single point terminal block and thermostat wiring to the low voltage terminal strip located in
the upper portion of the unit control box.
These CSA approved heaters are located within the
central compartment of the unit with the heater elements extending into the supply air chamber. Refer to
Figure 7 for access panel location.
Fuses are supplied, where required, by the factory.
Some KW sizes require fuses and others do not. Refer
to Table 3 for minimum CFM limitations and to Tables
9 through 14 for electrical data.
The instruction for the optional economizer/motorized
damper and rain hood can be found in form 03507364-000. Use these instructions when field assembling an economizer rain hood onto a unit. The outdoor
and return air dampers, the damper actuator, the
damper linkage, the outdoor and return air divider baffles, and all the control sensors are factory mounted as
part of the “Factory installed” economizer/motorized
damper options.
MINIMUM SUPPLY AIR CFM
HEATER SIZE NOMINAL KW
ECONOMIZER AND POWER EXHAUST DAMPER
SET POINT ADJUSTMENTS AND INFORMATION
Remove the economizer access panel from the unit.
Loosen but do not remove the two panel latches.
Locate the economizer control module, where the following adjustments will be made.
POWER EXHAUST/BAROMETRIC RELIEF DAMPER AND
RAIN HOOD
The instructions for the power exhaust/barometric relief
damper and rain hood can be found in form 530.18N1.10V.
All of the components, including the dampers, hardware, and mounting instructions are shipped in a single
package external from the unit and must be field
assembled and installed.
Power exhaust is only available as a field installed
accessory.
Extreme care must be exercised in turning all
setpoint, maximum, and minimum damper
positioning adjustment screws to prevent twisting them off.
Check that the damper blades move smoothly without
binding; carefully turn the Minimum Position Adjusting
screw (found on the damper control module) fully
clockwise and then set the thermostat indoor fan switch
to the on position and then off, or energize and deenergize terminals “R” to “G”.
Johnson Controls Unitary Products11
364985-XIM-B-0508
MINIMUM POSITION ADJUSTMENT
With thermostat set to indoor fan on position, or terminals “R” to “G” energized, turn the Minimum Position
Adjusting screw (located on the damper control module) counterclockwise until the desired minimum
damper position has been attained.
ENTHALPY SET POINT ADJUSTMENT
The enthalpy setpoint may now be set by selecting the
desired setpoint shown in the Enthalpy Setpoint Adjustment Figure 4. Adjust as follows:
•For a single enthalpy operation carefully turn the
setpoint adjusting screw (found on the damper
control module) to the “A”, “B”, “C” or “D” setting
corresponding to the lettered curve of the Enthalpy
Setpoint Adjustment Figure 4.
•For a dual enthalpy operation, carefully turn the
setpoint adjusting screw fully clockwise past the
“D” setting.
POWER EXHAUST DAMPER SETPOINT (WITH OR WITHOUT POWER EXHAUST)
•With no power exhaust option, adjust the Exha u st
Air Adjustment Screw fully clockwise.
•With power exhaust option, each building pressurization requirement will be different. The point at
which the power exhaust comes on is determined
by the economizer damper position (Percent
Open). The Exhaust Air Adjustment Screw should
be set at the Percent Open of the economizer
damper at which the power exhaust is needed. It
can be set from 0 to 100% damper open.
INDOOR AIR QUALITY
Indoor air quality (indoor sensor input): Terminal AQ
accepts a +2 to +10 Vdc signal with respect to the
(AQ1) terminal. When the signal is below it's setpoint,
the actuator is allowed to modulate normally in accordance with the enthalpy and mixed air sensor inputs.
When the AQ signal exceeds it's setpoint setting and
there is no call for free cooling, the actuator is proportionately modulated from the 2 to 10 Vdc signal, with 2
Vdc corresponding to full closed and 10 Vdc corresponding to full open. When there is no call for free
cooling, the damper position is limited by the IAQ Max
damper position setting. When the signal exceeds it's
setpoint (Demand Control Ventilation Setpoint) setting
and there is a call for free cooling, the actuator modulates from the minimum position to the full open position based on the highest call from either the mixed air
sensor input or the AQ voltage input.
•Optional CO
Space Sensor Kit Part #
2
2AQ04700324
•Optional CO
Unit Sensor Kit Part # 2AQ04700424
2
Replace the economizer access panel.
12Johnson Controls Unitary Products
Loading...
+ 28 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.