The Simplicity®LINC Gateway operates as a Modbus® Client
providing an interface between a BACnet® MS/TP control system
and devices that communicate using the Modbus RTU protocol.
The Simplicity
BACnet Building Automation System (BAS).
The Simplicity
products equipped with Simplicity
4/2/2008 as well as prior Simplicity
Intelli-Comfort™ controllers.
®
LINC allows monitoring and control by a third-party
®
LINC is preconfigured to provide an interface to UP
®
controllers manufactured after
®
Elite™ and Simplicity® with
®
The Simplicity
unit and utilizes 24 VAC power from the unit’s control transformer.
One port is connected to the UP controller. The other port must be
connected to the BACnet MS/TP network.
The Simplicity
operational data points from the controller and expose them on a
BACnet MS/TP network.
NOTE: Not all Simplicity
LINC mounts inside the control panel of the UP
®
LINC Gateway is preconfigured to obtain
®
operating parameters are controlled/
monitored by the Simplicity
®
LINC.
R
C
24 — must be grounded
close to the Simplicity LINC
24V power is polarity sensitive, incorrect
wiring could result in board damage.
FIGURE 1: WIRE CONNECTIONS
®
The shield must be
connected to ground at
each device.
1031990-UAD-A-0313
1031990-UAD-A-0313
1
0
4
0
16
0
0
0
21
CONNECTION
The Simplicity®LINC has 2 ports, one for connection to the BAS
network (BACnet) and one to the Simplicity
BACNET NETWORK
The only connection required in the field is to the BACnet (BAS)
network.
NOTE: Proper termination and grounding of the shields must
be observed.
DIP switches A0-A7 on the Simplicity
selection of the MAC Address. The MAC Address identifies the
Simplicity
99. The default DIP switch setting is 1.
A Device Instance (DE) Modifier is used by the Simplicity
and defaulted to 230. The combination of the DE Modifier and
the default DIP switch setting creates a default DE of 23001.
The default Unit Name is YORK_RTU.
®
LINC to other devices and must be between 1 and
MAC Address of 21
1 2 3 4 5 6 7 8
16
32
64
128
1
2
4
8
A0
A1
A2
A3
A4
A5
A6
A7
®
board (Modbus).
®
LINC board allow
ON
®
LINC
DIP switches B0-B3 on the Simplicity
selection of the BACnet transfer speed.The default speed is set
at 38.4k baud. Other speeds can be chosen as shown in Table
1
The UP device communicates with the Simplicity
the Modbus RTU protocol on an RS485 connection. Connection
and addressing of the UP product is completed at the factory.
No further adjustment should be done.
The default Simplicity® board address is 1 and must
remain on address 1 to correctly communicate with
Simplicity
Com/Setup button 3 times in succession.
If a problem arises with the Simplicity
exposed by the Simplicity
controller software can be manipulated using a Microsoft
Windows-based PC with the Simplicity
(downloadable from the UP website). To connect the PC to the
UP controller, a FREEnet USB adaptor (Part No.
S103101967000), which is an RS232 to RS485 adapter, and
FREEnet adapter cable (S102538682000) are required and
available through SOURCE1 (Toll-free at 1-800-536-6112).
Elite Condenser Fan #1 Output Status
(0=output is OFF, 1=output is ON)
Elite Condenser Fan #2 Output Status
Input Status (0=output is OFF, 1=output
is ON)
Elite Fan Overload Switch Input Status
(1=closed, 0=open / fault)
Elite Gas Valve #1 Input Status
(1=energized, 0=not energized)
Elite Gas Valve #2 Input Status
(1=energized, 0=not energized)
Elite Gas Valve #3 Input Status
(1=energized, 0=not energized)
Elite High Pressure Switch for
Compressor #1 Input Status (1=closed,
0=open / fault)
Elite High Pressure Switch for
Compressor #2 Input Status (1=closed,
0=open / fault)
Elite High Pressure Switch for
Compressor #3 Input Status (1=closed,
0=open / fault)
Elite High Pressure Switch for
Compressor #4 Input Status (1=closed,
0=open / fault)
Elite Indoor Fan Output Status
(0=output is OFF, 1=output is ON)
Elite Limit Switch #1 Input Status
(1=closed, 0=open / fault)
Elite Limit Switch #2 Input Status
(1=closed, 0=open / fault)
Elite Limit Switch #3 Input Status
(1=closed, 0=open / fault)
Elite Low Pressure Switch for
Compressor #1 Input Status (1=closed,
0=open / fault)
6Johnson Controls Unitary Products
TABLE 2: POINTS LIST IN DESCRIPTION ORDER (CONTINUED)
1031990-UAD-A-0313
Read/
Write
BACnet
Object
Type
BACnet
Object
Inst
DescriptorDefault MinMax Point Description
R(5) BI47E_LPS2n/an/an/a
R(5) BI52E_LPS3n/an/an/a
R(5) BI56E_LPS4n/an/an/a
R(2) AI32EXH_DAMP_OUTn/an/an/a
R(5) BI30EX_FAN_STATn/an/an/a
R / W(5) BV10EX_VFD_INSTn/an/an/a
R / W(2) AV91FAN_SPD_1ST_COOL700100
R / W(2) AV92FAN_SPD_1ST_HEAT1000100
R / W(2) AV93FAN_SPD_ALL_COOL1000100
R / W(2) AV94FAN_SPD_ALL_HEAT1000100
R / W(2) AV90FAN_SPD_NO_HEAT_COOL500100
R(5) BI1024_STG_EXP_PRESn/an/an/a
R(5) BI32FRECOOL_STATn/an/an/a
R(5) BI104FREEZE_STAT_1n/an/an/a
R(5) BI105FREEZE_STAT_2n/an/an/a
R(5) BI106FREEZE_STAT_3n/an/an/a
R(5) BI107FREEZE_STAT_4n/an/an/a
R(5) BI68HEAT_1_STATn/an/an/a
R(5) BI69HEAT_2_STATn/an/an/a
R(5) BI70HEAT_3_STATn/an/an/a
R(2) AI76H1_ACCUM_HRSn/an/an/a
R(2) AI77H2_ACCUM_HRSn/an/an/a
R(2) AI78H3_ACCUM_HRSn/an/an/a
R / W(5) BV25HEATING_ENAn/an/an/a
R / W(2) AV27HGR_HUM_STPT500100
R(5) BI18HGR_STATn/an/an/a
Elite Low Pressure Switch for
Compressor #2 Input Status (1=closed,
0=open / fault)
Elite Low Pressure Switch for
Compressor #3 Input Status (1=closed,
0=open / fault)
Elite Low Pressure Switch for
Compressor #4 Input Status (1=closed,
0=open / fault)
Exhaust Damper Output Status (0100%)
Exhaust Fan Output Status (0=output is
OFF, 1=output is ON)
Exhaust VFD Installed
Fan Speed: 1st Stage Cooling
Fan Speed: 1st Stage Heating
Fan Speed: All Stages Cooling
Fan Speed: All Stages Heating
Fan Speed: No Heating No Cooling
Four Stage Expansion board Present
Free Cooling Mode Status (0=comps
not overridden by Econo, 1=comps
overridden)
Freeze Stat # 1
Freeze Stat # 2
Freeze Stat # 3
Freeze Stat # 4
H1 Heating Output #1 Status (0=output
is OFF, 1=output is ON)
H2 Heating Output #2 Status (0=output
is OFF, 1=output is ON)
H3 Heating Output #3 Status (0=output
is OFF, 1=output is ON)
Heating #1 Accumulated Run Time (in
hours)
Heating #2 Accumulated Run Time (in
hours)
Heating #3 Accumulated Run Time (in
hours)
Heating Mode Enabled
Hot Gas Reheat Humidity Setpoint
(percent Humidity)
Hot Gas Reheat Output Status
(0=output is OFF, 1=output is ON)
Johnson Controls Unitary Products7
Loading...
+ 15 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.