Johnson Controls SE-ZEC510-1, SE-ZEC500-1 Installation, Operation And Maintenance Manual

Smart Equipment Controls
Installation, Operation and Maintenance Manual
Form No. SECIOM.A
Effective Date: 07/05/19
Page 1
Installation, Operation, and Maintenance
Manual
Johnson Contr ols
SE-ZEC500-1 and SE-ZEC510-1 Controllers
Smart Equipment Controls
Installation, Operation and Maintenance Manual
Form No. SECIOM.A
Effective Date: 07/05/19
Page 2
Table of Contents
Initial Setup .............................................................................................................................................................................. 3
Mounting .............................................................................................................................................................................. 3
Networking .......................................................................................................................................................................... 4
Field Controller (FC) Bus ................................................................................................................................................ 4
SE-ZEC Controller Address ............................................................................................................................................ 4
End-of-line (EOL) Switch ................................................................................................................................................. 5
Optional Components ......................................................................................................................................................... 5
Sensor Actuator (SA) Bus ............................................................................................................................................... 5
Supply Air Temp. Sensor ................................................................................................................................................ 5
Discharge Air Temp. Sensor ........................................................................................................................................... 6
Occupancy Sensor .......................................................................................................................................................... 6
Control Sequences .................................................................................................................................................................. 7
Controller Parameters ............................................................................................................................................................. 7
Parameter Descriptions ....................................................................................................................................................... 7
Static Parameters (All Applications) ................................................................................................................................ 7
Application Specific Parameters ................................................................................................................................... 11
Factory Programmed Parameters ..................................................................................................................................... 12
Default Parameters ....................................................................................................................................................... 12
Size Dependent Parameters ......................................................................................................................................... 13
Sequence Dependent Parameters ................................................................................................................................ 14
Commissioning ...................................................................................................................................................................... 16
Mobile Access Portal (MAP) Gateway .............................................................................................................................. 16
VAV Handheld Balancing Tool .......................................................................................................................................... 17
Troubleshooting .................................................................................................................................................................... 17
er Status LED ............................................................................................................................................................. 18
Pow
Communication Bus Problems .......................................................................................................................................... 18
I/O Wiring ...................................................................................................................................................................... 18
Duplicate Addresses ..................................................................................................................................................... 18
Correcting Physical Communication Bus Problems ...................................................................................................... 18
Parts and Accessories .......................................................................................................................................................... 18
Additional Information ........................................................................................................................................................... 19
Smart Equipment Controls
Installation, Operation and Maintenance Manual
Form No. SECIOM.A
Effective Date: 07/05/19
Page 3

Initial Setup

Mounting

To mount the SE-ZEC Controllers:
1. Ensure that you have the appropriate personal protective equipment (PPE), such as a hard hat, safety glasses, steel toe boots, and gloves.
2. Disconnect power to the VAV unit.
3. Set the MS/TP address, and ensure the end of line (EOL) switch is set to off. Instructions on setting the VAV address and EOL are in the sections below.
4. Place the SE-ZEC Controller in the proper mounting position on the actuator shaft so that the wiring connections are easily accessible. Make sure the SE-ZEC Controller base is parallel to the VAV box (perpendicular to the damper shaft). If needed, use a spacer to offset tipping of the SE-ZEC Controller caused by the shaft bushings.
5. Use the alignment marks to center the captive spacer to ensure sufficient movement in either direction.
Fig
. 1: Captive Spacer Alignment Marks
Alignment guide
6. Sec
7. Locate the damper position using the typical marking on the end of the damper shaft.
8. Note the direction, clockwise (CW) or counterclockwise (CCW), required to close the damper. The actuator setup
9. Push down and hold the manual override button and turn the SE-ZEC Controller until it contacts the mechanical
10. Ti
11. Put a loop in the pneumatic tubing, to trap condensation, when you attach the tubing to the SE-ZEC Controller
ure the self-drilling #10 screw through the captive spacer with a power screwdriver and 4” (100 mm) extension socket. Otherwise, use a punch to mark the position of the shoulder washer, and then drill a hole into the VAV box using a 5/16” drill bit. Insert the mounting screw and tighten against the spacer.
depends on the necessary amount of rotation required for the damper to go from full-open to full-closed. For 90° rotation, install the damper full-closed.
end-stop at either the full-closed or full-open position.
. 2: Manual Override and Coupler
Fig
ghten the square coupler bolt to the shaft using a 5/16” (8 mm) wrench or a 3/8” (10 mm) 12-point socket.
Tighten to 95 to 105 lb·in (10.5 to 11.5 N·m)
pressure transducer ports. Loop the tubing before you make the final connections.
Smart Equipment Controls
Installation, Operation and Maintenance Manual
Form No. SECIOM.A
Effective Date: 07/05/19
Page 4
12. Push the manual override button, and turn the actuator coupling manually to ensure the actuator can rotate from full-closed to full-open positions without bindi ng.
13. Complete the mounting by rotating the damper to the full-open position.

Networking

Field Controller (FC) Bus

The field controller (FC) Bus terminal block is a blue, removable, 4-terminal plug that is keyed to only fit in to the board­mounted, gray FC Bus jack. Wire the removable FC Bus terminal block plugs on the SE-ZEC Controller and other FC Bus controllers in a daisy-chain configuration usin g 3-wire twisted, shielded cable.
Fig. 3: FC Bus Connections

SE-ZEC Controller Address

SE-ZEC Controllers are master devices on BACnet MS/TP (SA or FC) Buses. Before operating field controllers on a Bus, you must set a valid and unique device address for each controller on the Bus. You set a field controller’s device address by setting the positions of the switches on the devise address DIP switch block at the top of the controller. Device addresses 4-127 are the valid addresses for the SE-ZEC controller. SE-ZEC Controllers ship with all address switches set to ON. Set a valid and unique device address on the field controller before applying power to the controller on the Bus. The DIP switch block has eight switches numbered 128, 64, 32, 16, 8, 4, 2, and 1.
To set the device addresses on a ZEC field controller:
1. Set all of the switches on the field controller’s device address DIP switch block (128 through 1) to OFF.
2. Set one or more of the seven address switches from 64 to 1 to ON, so that the sum of the switch numbers set to ON equals the intended device address. Set the highest number switch that is less than or equal to the intended device address to ON. Then continue setting lower numbered switches until the total equals the intended address.
For example: If the intended device address is 21, set the switches so that 16 + 4 + 1 = 21. a. Set switch 16 to ON b. Set switch 4 to ON c. Set switch 1 to ON
3. Set a unique and sequential device address for each of the field controllers connected on the FC Bus, starting with device address 4. To ensure the best Bus performance, set sequential device address es with no gaps in the de vice
Smart Equipment Controls
Installation, Operation and Maintenance Manual
Form No. SECIOM.A
Effective Date: 07/05/19
Page 5
address range (4, 5, 6, and so on). The field controllers do not need to be physically connected on the Bus in their numerical device address order.
4. Write each field controller’s device address on the white label below the DIP switch block on the controller’s cover.

End-of-line (EOL) Switch

The EOL switch must be set to ON for the two devices located at either end of each bus segment on an FC bus. The EOL switches must be set to OFF for all other devices on the bus segment on an FC bus.

Optional Components

Sensor Actuator (SA) Bus

Factory or field supplied zone sensors are wired to the SA bus on the SE-ZEC Controller. The SA Bus is a brown, removable 4-terminal plug that is keyed to only fit into the board mounted SA bus. Wire the removable SA bus terminal block plugs on the SE-ZEC Controller and other field devices in a daisy-chain configuration using 4-wire, shielded cable.
Fig. 4: SA Bus Connections

Supply Air Temp. Sensor

Factory or field-supplied supply air temperature sensors can be used to measure the supply air temperature at the inlet of the VAV box. The supply air temperature is wired between terminals ICOM3 and IN3 on the SE-ZEC Controller. The sensor should be mounted in the inlet duct centered in the side of the ductwork. Avoid installing the sensor near an elbow, take off or transition. Avoid blocking air to the primary airflow sensor.
Factory provided nickel (1k ohm) temperature sensors have 4” long probes and stainless steel mounting flanges with (2) provided hex-head self-drilling mounting screws. Sensors come equipped with 10 ft. plenum rated cables with ¼” internal thread insulated quick-connect terminations on leads. Install sensor by drilling a hole into the ductwork, inserting the sensor, and securing with provided screws. The sensor tip should not touch any part of the ductwork.
With the supply air temperature sensor installed, the SE-ZEC controller will change its control sequence based on the measured supply air temperature. When parameter Heating Limit Enable is TRUE the controller will not allow re-heat to engage when the supply air temperature is greater than the value set in Heating Supply Air Limit.
Additionally, the controller will switch to warmup mode when warmup conditions are present. Warmup conditions are present when the supply air temperature (SAT) sensor value exceeds the zone temperature (ZNT) sensor in unoccupied mode or exceeds it by the Warmup Differential in occupied mode. While in Warmup mode the minimum flow will be set to the Warmup Min Flow.
Smart Equipment Controls
Installation, Operation and Maintenance Manual
Form No. SECIOM.A
Effective Date: 07/05/19
Page 6
SE-ZEC Occupancy Determination
Controller Type
ZEC500 (Standalone)
ZEC510 (Networked)
The controller will switch from
Setpoint the state is set to Occupied
The controller will read the occupancy
between Occupied and Unoccupied
The building automation system
and Unoccupied states. A room

Discharge Air Temp. Sensor

Factory or field supplied discharge air temperature sensors can be used to measure the temperature of the air being discharged from the VAV box. The discharge air temperature sensor is wired between terminals ICOM1 and IN1 on the SE-ZEC controller. The sensor should be mounted a minimum of 36” from the discharge of the unit and be centered in the side of the ductwork. Avoid installing the sensor near an elbow, take off, or transition.
Factory provided nickel (1k ohm) temperature sensors have 4” long probes and stainless steel mounting flanges with (2) provided hex-head self-drilling mounting screws. Sensors come equipped with 10 ft. plenum rated cables with ¼” internal thread insulated quick-connect terminations on leads. Install sensor by drilling a hole into the ductwork, inserting the sensor, and securing with provided screws. The sensor tip should not touch any part of the ductwork.

Occupancy Sensor

The SE-ZEC Controllers adjust the heating and cooling temperature setpoints, as well as the airflow setpoints based on the zone occupancy. There are three different states of zone occupancy:
Occupied Mode
o Uses Occupied Heating (68°F) and Occupied Cooling (72°F) temperature setpoints as well as Occupi
eating and Occupied Cooling Airflow setpoints
H
o For Series Fan Powered Terminals the Fan is always on o For Parallel Fan Powered Terminals the Fan is only on during a call for heating
Standby Mode
o Uses Standby Heating (66°F) and Standby Cooling (77°F) temperature setpoints as well as Unoccupi
H
eating and Unoccupied Cooling Airflow setpoints
o For Series Fan Powered Terminals the Fan is always on o For Parallel Fan Powered Terminals the Fan is only on during a call for heating
Unoccupied Mode
o Uses Unoccupied Heating (55°F) and Unoccupied Cooling (85°F) temperature setpoints as well as
Unoccupied Heating and Unoccupied Cooling Airflow setpoints
o For Series Fan Powered Terminals the Fan is only on during a call for heating or cooling o For Parallel Fan Powered Terminals the Fan is only on during a call for heating
ed
ed
Table 1 below shows how occupancy states are determined for the SE-ZEC Controllers.
Terminal Unit Type
Single Duct Terminal Unit
Fan Powered Terminal Unit
Table 1: SE-ZEC Occupancy Determination
Occupied to Unoccupied states by comparing the measured airflow to the Occupancy Determination Flow Setpoint. When the measured airflow is below the Occupancy Determination Flow Setpoint the state is set to Unoccupied. When the measured airflow is above the
Occupancy Determination Flow
sensor wired between IN2 and ICOM2 on the controller to switch
The building automation system (BAS) will schedule when t he controller will switch from Occupied and Unoccupied states. A room occupancy sensor (wired to IN2 and ICOM2 on the controller) can be used to temporarily set the VAV box to Standby mode when occupancy is not sensed.
(BAS) will schedule when the controller will switch from Occupied
Loading...
+ 13 hidden pages