Johnson Controls SE-SPU101 Series, SE-SPU1011-1, SE-SPU1012-1 Installation Instructions Manual

CCS Smart Equipment Control Board for Single Packaged Unit (SPU) Controller
Installation Instructions
SE-SPU1011-1, SE-SPU1012-1

Applications

The new SE-SPU101x controllers replace the RTU-100x controllers. All the RTU100x controllers are discontinued, including the RTU-1003-0 VAV SPU controller. T he new SEC pr oduct offering provides new controller options.
The SE-SPU101x-1 SEC Unit Control Board (UCB) is a member of the Smart Equipment Controller (SEC) product family. The controller is designed to run a pre­engineered HVAC zoning application and provide the inputs and outputs required for this application.

North American Emissions Compliance

United States

This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when this equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area may cause harmful interference, in which case the users will be required to correct the interference at their own expense.

Canada

This Class (A) digital apparatus meets all the requirements of the Canadian Interference-Causing Equipment Regulations.
Cet appareil numérique de la Classe (A) respecte toutes les exigences du Règlement sur le matériel brouilleur du Canada.
Code No. LIT-12011479
Issued June 16, 2015

Installation

Special Tools Needed

wire strippers
small flat-head screwdriver
22 AWG (0.65 mm) 3-conductor, twisted, e with a drain wire
cabl Note: This drain wire is used only to group the
shielded cable. Do not use this drain wire
ection to the board.
conn
wire nuts for 22 AWG drain wire
electrical tape
shielded
as a

Mounting

The manufacturing facility mounts the controller. All of the required power wiring, internal unit sensor wiring, and output wiring is completed and tested at the factory . The control application required for the specific UCB is factory configured and ready for operation.

Wiring

Field Wiring Connections

In addition to power connections, the UCB requires a communication bus connection. Address selection is required for networking with a CCS Building Automation System (BAS).

Power Wiring

The SEC UCB controller is factory wired for 24 VAC power.
IMPORTANT: The 24 VAC power should not be shared with other network devices. Sharing power to other network devices may cause noise, interference, and ground loop problems. You may damage the controller by sharing power to other devices.
CCS Smart Equipment Control Board for Single Packaged Unit (SPU) Controller Inst allation
Instructions
1
In certain cases, you may need to share a 24 V
Figure 1: Joystick and Push Buttons on UCB
ENTER
CANCEL
JOY
Figure 2: UCB Top Level Menu
transformer with multiple CCS devices. Be sure that you maintain consistent +, -, and common wiring terminations on the shared CCS devices.
IMPORTANT: Do not interchange +, -, and common 24 V terminations when sharing a transformer with multiple CCS devices. Interchanging these terminations can cause damage to the controller.

Setup and Adjustments

To quickly set up your CCS network:
1. On each end of the 3-conductor cable, strip the outside insulation back approximately 2 in. (51 mm).
2. Tear off excess foil shield, leaving the bare drain wire and the three insulated conductors.
3. On each end of the three insulated conductors in the cable, strip the insulation back approximately 1/8 to 1/4 in. (4 to 7 mm).
4. Choose a color pattern to follow and insert each of the three conductors into one each of the thr ee terminals on the CCS board communication connector.
Note: Be sure you observe polarity of each of the conductors in the communication cable.

Communication Bus

The UCB default address is set to 4. The available values range from 0 to 127. To view the UCB Network Address, use the joystick and the two push buttons below the LCD, to navigate through the menus to the Commissioning menu (Figure 1).
Up and down movements of the joystick move the > cursor and scroll through the selections in the active section of the menu (Figure 2).
5. Tighten each terminal until the wire is secure.
6. Ground the drain wire at one end only of the communication trunk. Do this on the last unit in line.
Use an existing hole or drill a hole and insert a sheet metal screw in the back plate below the communication connector.
Wrap the bare drain wire around the screw and tighten the screw. This is the only location where the shield is grounded.
7. Daisy chain the three-conductor wire between the remaining SPUs. Connect the drain wires together with the wire nuts. Follow the stripping and connecting procedure in Step 1 through Step .
8. Run the cable from the last unit to the location of the System Manager or Zone Coordinator. Follow the connection instructions for the System Manger or Zone Coordinator . Figure 4 displays an example communication riser.
9. Make sure all the SPUs are powered and operating properly.
Each menu selection represents either a submenu or a property. Press Enter to display the items in the submenu or the values of the selected property.
Once you navigate to the Commissioning menu, use the cursor to scroll to the Network submenu. From the Address submenu, press Enter to display the current network address. Move up or down with the joystick to display the values of other properties.
CCS Smart Equipment Control Board for Single Packaged Unit (SPU) Controller Installation Instructions2

Control Board and Wiring Diagrams

Figure 3: VAV SPU Control Board Communication Terminations
Communication Cable to
Next VAV box*
Comm unication Cable to
Next VAV box, Zone
Dampers, and Bypass
Damper
* M o v e th e 4 -p ositio n te rmin al blo c k fro m th e T h e r mos ta t in pu ts
to the FC Bus connection of the communications card.
Figure 3 shows the location of the communication cable terminations on the SPU controller board. Figure 4 shows the VA V SPU contro ller communication riser. .
CCS Smart Equipment Control Board for Single Packaged Unit (SPU) Controller Installation Instructions 3
Loading...
+ 5 hidden pages