Johnson Controls SEN-600-1, SEN-600-4 Installation Guide

SEN-600-1 and SEN-600-4 Remote Indoor Temperature
Figure 1: Sensor Dimensions, in./mm
125
86
29
24-9954- 7, Rev. B
Sensors
Installation Instructions
Refer to the QuickLIT website for the most up-to-date version of this document.

Application

The SEN-600-1 and SEN-600-4 remote sensors are designed to allow remote indoor temperature sensing in applications with the T600 Series programmable and non-programmable thermostats and the TEC2000 Series Network Thermostats. The SEN-600-1 and SEN-600-4 contain an integral sensor and circuitry to interface with the T600 and TEC2000 Series Thermostats. Additionally, the SEN-600-4 has an override button and Light-Emitting Diode (LED) indicator to enable and indicate occupancy override from the remote sensor. Up to three remote sensors can be wired together for averaging.
Note: The SEN-600-4 remote indoor sensor is only intended for use with programmable T600 Series thermostats. Additionally, if the SEN-600-4 is used with a T600 non-programmable thermostat, the LED does not light up to indicate occupancy status.

Mounting

Prior to installing the sensor, install the T600 or TEC2000 Series Thermostat following the installation instructions provided with the thermostat.
Location Considerations
Locate the sensors as follows:
on a partitioning interior wall, and approximately 5 ft (1.5 m) above the floor in a location of average temperature
away from direct sunlight, radiant heat, outside walls, behind doors, air discharge grills, stairwells, or outside doors
Part No. 24-9954-7, Rev. B

Installation

4.94
3.38
1.13
To install the sensor:
1. Remove the security screw on the bottom of the sensor cover using a Phillips-head screwdriver. Open the thermostat by pulling on the bottom side of the sensor cover (see Figure 2).
2. Unlock the Printed Circuit Board (PCB) by carefully pressing the locking tabs to the right. Open the sensor’s PCB to the left (see Figure 3).
3. Pull out approximately 6 in. (152 mm) of wires from the wall and insert the cable through the hole in the base.
4. Align the base on the wall, and using the base as a template, mark the location of the two mounting holes on the wall. Confirm the sensor base is installed with the proper side up.
away from steam or water pipes, warm air stacks, unheated/uncooled areas, or sources of electrical interference
5. Use the supplied anchors and screws for mounting on drywall or plaster. Drill two 3/16 in. (4.7 mm) holes at the marked locations and tap nylon anchors flush to wall surface (see Figure 4).
6. Position base on the wall, insert screws through mounting base, and fasten into wall anchors. Do not overtighten screws.
7. Swing the sensor’s PCB back to the right to close. Gently press on the PCB to secure the locking tab.
SEN-600-1 and SEN-600-4 Remote Indoor Temperature Sensors Installation
Instructions
1
Wiring
!
!
Figure 2: Removing the Sensor Cover
Figure 3: Opening the Sensor PCB
Figure 4: Mounting the Sensor Base
CAUTION: Risk of Electric Shock.
Disconnect the power supply before making electrical connections to avoid electric shock.
Note: Keep sensor conductors as short as possible to minimize temperature error. If necessary, the indoor temperature displayed at the thermostat can be adjusted (refer to the appropriate T600 or TEC2000 Series Installation Instructions).
To wire the sensor:
1. Connect wires between the T600 or TEC2000 Series thermostat and the SEN-600-1 or SEN-600-4 sensors according to the appropriate wiring diagram (see Figure 5).
2. Set the switch on the PCB in the remote indoor sensor to the correct positions (see Table 1 for switch positions).
3. Reattach the sensor cover to the installed bas e (top side first) and install the security screw on the bottom.
PCB
Locking Tab
4. Verify that the sensor is functioning by checking the temperature display on the T600 or TEC2000 Series thermostat. If using the SEN-600-4 remote sensor, verify the functionality of the override button and occupancy status LED.
Note: If using the SEN-600-4, the digital input on the thermostat to which the D1 terminal on the sensor is connected must be configured for remote override (RemOVR). Refer to the appropriate T600 Installation
Instructions for details on configuring the digital input.
CAUTION: Risk of Property Damage.
Do not apply power to the system before checking all wiring connections. Short circuited or improperly connected wires may result in permanent damage to the equipment.
Table 1: Switch Positions for Single or Multiple
Sensor Installations
Number of Sensors
1 Sensor On On 2 Sensors Off On 3 Sensors Off Off
Switch 1 Switch 2
SEN-600-1 and SEN-600-4 Remote Indoor Temperature Sensors Installation Instructions2
Figure 5: Wiring Diagrams
AUX
C
D1
AU
AUX
C
D1
RS
Scom
RS
Scom
AU
C
D1D2
T600 or TEC2000 Series
RS
Scom
AUX
C
D1
RS
Scom
AU
C
D1D2
RS
Scom
SEN-600-1
SEN-600-4
T600
This is a wiring example of two remote room sensors for averaging applications (S1=Off, S2=On).
Note: Whe n w i r ing the S E N- 600-4 remote indoor sensor to a non-programmable model of the T600, the AUX terminal on the SEN-600- 4 is not us ed. Addition al ly, when using the SEN-6 00-4 remo t e indoor sensor wit h a non-programmable model of the T600, the LED does not light to indicate occupancy status.
This is a wiring example of a single remote room sensor (S1=On, S2=On).
RS
Scom
AUX
C
D1
RS
Scom
AU
C
D1D2
T600
RS
Scom
RS
Scom
AU
C
D1D2
T600 or TEC2000 Series
SEN-600-1
This is a wiring example of three remote room sensors for averaging applications (S1=Off, S2=Off).
T600
AU
C
AUX
C
D1
SEN-600-1
SEN-600-4
SEN-600-1
AUX
C
D1
AUX
C
D1
AU
T600 or TEC2000 Series
AU
C
AUX
C
D1
AU
C
TEC2x45-4
This is a wiring example of a single remote room sensor for TEC2x45-4 applications (S1=On, S2=On).
IMPORTANT:
The SEN-600-1 is not compatible with TEC2x45-4 thermostat models. On SEN-600-4 sensors, only the remote override function is compatible with TEC2x45-4 thermostat models.
SEN-600-4
SEN-600-1
RS
Scom
SEN-600-1SEN-600-1
D2
RS
Scom
D1
RS
Scom
RS
Scom
RS
Scom
RS
Scom
D1D2
RS
Scom
T600
RS
Scom
SEN-600-1
RS
Scom
C
D1D2
T600
RS
Scom
SEN-600-1
RS
Scom
RS
Scom
C
D1D2
SEN-600-4 S E N-600-4
RS
Scom
RS
Scom
SEN-600-4 SEN-600-4
RS
Scom
RS
Scom
SEN-600-1
RS
Scom
D1D2
SEN-600-1 and SEN-600-4 Remote Indoor Temperature Sensors Installation Instructions 3
RS
Scom
SEN-600-4
Troubleshooting
Table 2: Troubleshooting
Symptom Possible Cause Corrective Action
Temperature displayed at the T600 or TEC2000 Series does not correlate with the temperature at the remote sensor.
Override button on SEN-600-4 remote sensor is not functional.
Remote LED is not functional on the SEN-600-4 remote sensor.
Remote sensor is not correctly connected.
T600, TEC2000 Series, or remote sensor has failed.
SEN-600-4 is incorrectly wired to the thermostat.
The appropriate digital input on the thermostat is not configured to remote override (RemOVR).
SEN-600-4 is incorrectly wired to the thermostat.
The auxiliary output is not properly configured at the T600 programmable thermostat.
The T600 Series thermostat to which the SEN-600-4 is connected is not a programmable model.
Check wiring connections at the thermostat terminal blocks and between the thermostat and the remote sensor.
Short the appropriate sensor terminals at the thermostat. The display should indicate 122ºF (50ºC). If the reading is not 122ºF (50ºC), replace the thermostat. If the reading is 122ºF (50ºC), check the resistance across the sensor with the wires removed from the thermostat. The resistance should be 10,000 ohms at 77ºF (25ºC). If the resistance is not correct, replace the sensor.
Check wiring connections with the corresponding digital input at the thermostat, at the D1 terminal on the remote sensor, and between the thermostat and remote sensor.
Configure the appropriate digital input at the thermostat for remote override (RemOVR). Refer to the appropriate T600 Installation Instructions for details.
Check wiring connections at the auxiliary output at the programmable T600 thermostat, at the AUX terminal on the remote sensor, and between the thermostat and remote sensor.
Configure the auxiliary output at the T600 programmable thermostat for Normally Open (N.O.). Refer to the appropriate T600 Installation Instructions for details.
The LED does not indicate occupancy status on non-programmable T600 models (there is no auxiliary contact at the thermostat). Replace the T600 with a programmable model.
SEN-600-1 and SEN-600-4 Remote Indoor Temperature Sensors Installation Instructions4
Metasys® and Johnson Controls® are registered trademarks of Johnson Controls, Inc.
All other marks herein are the marks of their respective owners. © 2016 Johnson Controls, Inc.
Building Efficiency
507 E. Michigan Street, Milwaukee, WI 53202

Technical Specifications

SEN-600-1 and SEN-600-4 Remote Indoor Temperature Sensors

Power Requirements Supplied by the T600 or TEC2000 Series Thermostat Sensor Accuracy ±0.9 Fº from 32 to 158ºF; ±0.5 Cº from 0 to 70ºC Sensor Ambient Operating
Conditions Sensor Ambient Storage
Conditions Dimensions (H x W x D) 4.94 x 3.38 x 1.13 in. (125 x 86 x 29 mm) Shipping Weight 0.75 lb (0.34 kg)
The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these specifications, consult the local Johnson Controls® office. Johnson Controls, Inc. shall not be liable for damage resulting from misapplication or misuse of its products.
European Single Point of Contact: NA/SA Single Point of Contact: APAC Single Point of Contact:
JOHNSON CONTROLS WESTENDHOF 3 45143 ESSEN GERMANY
32 to 122ºF (0 to 50ºC); 0 to 95% RH noncondensing
-22 to 122ºF (-30 to 50ºC); 0 to 95% RH noncondensing
JOHNSON CONTROLS 507 E MICHIGAN ST MIL WAUKEE WI 53202 USA
JOHNSON CONTROLS C/O CONTROLS PRODUCT MANAGEMENT NO. 22 BLOCK D NEW DISTRICT WUXI JIANGSU PROVINCE 214142 CHINA
SEN-600-1 and SEN-600-4 Remote Indoor Temperature Sensors Installation Instructions 5
Published in U.S.A. www.johnsoncontrols.com
Loading...