Configured Split Condenser Model Number Nomenclature
A = Standard Motor
Airflow
Product Generation
1 = First Generation
2 = Second Generation
Voltage
Heat Type & Nominal Heat Capacity
P
C
240
C00 A
2
A
AA
2
A
Product Style
A = Style A
2 = Non Pwr’d Conv Outlet
1 = Disconnect
T = Options 1 & 5
S = Options 5
D = Options 1 & 2
C = Option 2
B = Option 1
Options
5 = Pwr’d Conv Outlet
Nomenclature
General
These condensing units are designed for outdoor installation on
a roof or at ground level. Every unit is completely piped and
wired at the factory and is shipped ready for immediate
installation. Only the liquid and suction lines to the evaporator
coil, the filter drier, the thermostat wiring and the main power
wiring are required to complete the installation. Each unit is
dehydrated, evacuated, leak tested and pressure tested at 450
psig before being pressurized with a holding charge of
refrigerant R-410A for shipment and/or storage.
All controls are located in the front of the unit and are readily
accessible for maintenance, adjustment and service. All wiring
(power and control) can be made through the front of the unit.
2Johnson Controls Unitary Products
This Split-System (Air Condensing / Heat Pump / Air
Handling) unit is one component of an entire system. As
such it requires specific application considerations with
regard to the rest of the system (air handling unit, duct
design, condensing unit, refrigerant piping and control
scheme).
Failure to properly apply this equipment with the rest of
the system may result in premature failure and/or
reduced performance / increased costs. Warranty
coverage specifically excludes failures due to improper
application and Unitary Products specifically disclaims
any liability resulting from improper application.
Please refer to the equipment Technical Guide,
Installation Manual and the piping applications bulletin
247077 or call the applications department for Unitary
Products @ 1-877-UPG-SERV for guidance.
430645-YIM-D-0610
Safety Considerations
Installer should pay particular attention to the words: NOTE,
CAUTION, and WARNING. Notes
make the installation easier. Cautions are given to prevent
equipment damage. Warnings are given to alert installer that
personal injury and/or equipment damage may result if
installation procedure is not handled properly.
Improper installation may create a condition where the
operation of the product could cause personal injury or
property damage. Improper installation, adjustment,
alteration, service or maintenance can cause injury or
property damage. Refer to this manual for assistance or
for additional information, consult a qualified contractor,
installer or service agency.
Before performing service or maintenance operations on
unit, turn off main power switch to unit. Electrical shock
could cause personal injury. Improper installation,
adjustment, alteration, service or maintenance can
cause injury or property damage. Refer to this manual.
For assistance or additional information consult a
qualified installer, service agency or the gas supplier.
are intended to clarify or
Reference
This instruction covers the installation and operation of the
basic condensing unit. For refrigerant piping installation
instructions refer to document 247077 “Application Data General Piping Recommendations for Split System Air
Conditioning and Heat Pumps”. For information on the
installation and operation of the evaporator blower units, refer
to Instruction Manual No. 508526.
All accessories come with a separate Installation Manual.
Renewal Parts
Contact your local Source 1 Center for authorized replacement
parts.
Agency Approvals
Design certified by CSA as follows:
1.For use as a cooling/heating uni t.
2.For outdoor installation only.
Inspection
As soon as a unit is received, it should be inspected for possible
damage during transit. If damage is evident, the extent of the
damage should be noted on the carrier’s freight bill. A separate
request for inspection by the carrier’s agent should be made in
writing.
This system uses R-410A Refrigerant which operates at
higher pressures than R-22. No other refrigerant may be
used in this system. Gage sets, hoses, refrigerant
containers and recovery systems must be designed to
handle R-410A. If you are unsure, consult the
equipment manufacturer. Failure to use R-410A
compatible servicing equipment may result in property
damage or injury.
This product must be installed in strict compliance with
the enclosed installation instructions and any applicable
local, state and national codes including, but not limited
to, building, electrical, and mechanical codes.
Johnson Controls Unitary Products3
430645-YIM-D-0610
Physical Data
Table 1: PC090 - 240 and PD180 - 240 Physical Data
Number of motors
Motor HP (ea.) 1/3 3/4 1/3 1/3 3/4 3/4
Rotation
RPM850110085085011001100
Nominal CFM
REFRIGERANT
1
2
DIMENSIONS (inches)
WEIGHTS (lb)
COMPRESSORS
SYSTEM DATA
OUTDOOR COIL DATA
CONDENSER FAN DATA
4
3
System #123.927.554.027.060.034.0
System #2---------27.0---34.0
System #17.510157.52010
System #2---------7.5---10
System #1122121
System #2---------1---1
System #1224242
System #2---------2---2
System #175009800150007500196009800
System #2---------7500---9800
PC090PC120PC180PD180PC240PD240
1.01.01.01.01.01.0
CWCWCWCWCWCW
1. Holding Charge is the amount in the unit as shipped from the factory.
2. Includes matched evaporator unit with 25 ft of piping.
3. All Compressors include crankcase heater.
4. When viewing the shaft end of the motor.
Models
4Johnson Controls Unitary Products
430645-YIM-D-0610
Table 2: Unit Application Data
208/230-3-60187/252
Voltage Variation
Min. / Max.
1
460-3-60432/504
575-3-60540/630
Ambient Air on Condenser Coil
Min. /Max.
2
Suction Pressure at Compressor and
Corresponding Temp. at Saturation
Min. / Max.
1.Utilization range “A” in accordance with ARI Standard 110.
2.These units can operate in an ambient temperature of
125°F providing the wet bulb temperature of the air entering the evaporator coil does not exceed 67°F. Unit can
operate to 0°F if equipped with a low ambient kit.
40°F/125°F
101.6 psig / 156.6 psig
32.0 ºF / 55.0 ºF
Installation
Limitations
These units must be installed in accordance with all national
and local safety codes. If no local codes apply, installation must
conform to the appropriate national codes. Units are designed
to meet National Safety Code Standards. If components are to
be added to a unit to meet local codes, they are to be installed
at the dealer's and/or the customer's expense.
3.The heat pump and the evaporator should be positioned to
minimize the number of bends in the refrigerant piping.
4.The heat pump should be as close to the evaporator as
practical.
5.The heat pump should not be installed where normal
operating sounds may be objectionable.
6.The evaporator should be located within the building, either
outside or inside the conditioned space.
Rooftop Locations
Be careful not to damage the roof. Consult the building
contractor or architect if the roof is bonded. Choose a location
with adequate structural strength to support the unit.
The heat pump must be mounted on level supports. The
supports can be channel iron beams or wooden beams treated
to reduce deterioration.
Minimums of two (2) beams are required to support each unit.
The beams should: (1) be positioned perpendicular to the roof
joists. (2) Extend beyond the dimensions of the section to
distribute the load on the roof. (3) Be capable of adequately
supporting the concentrated loads at the corners. These beams
can usually be set directly on the roof. Flashing is not required.
NOTE: On bonded roofs, check for special installation
requirements.
Location
Use the following guidelines to select a suitable location for
both the condensing unit and the evaporator.
1.The heat pump is designed for outdoor installation only.
2.The condenser fans are the propeller type and are not
suitable for use with ductwork in the condenser air stream.
Ground Level Locations
It is important that the units be installed on a substantial base
that will not settle, causing strain on the refrigerant lines and
possible leaks. A one-piece concrete slab with footers that
extend below the frost line is recommended. The slab should
not be tied to the building foundation, as noise will telegraph
through the slab.
Weight (lbs.)Center of Gravity (in.)4 Point Load Location (lbs.)
ShippingOperatingXYABCD
Figure 1: Corner Weights & Center Of Gravity
NOTE: Front of unit is considered the side having the control
box.
Concrete piers can also support ground level units. These piers
should (1) extend below the frost line, (2) be located under each
of the section's four corners, and (3) be sized to carry the load
of the corner it supports.
On either rooftop or ground level installations, rubber padding
can be applied under the unit to lessen any transmission of
Holes are provided in the base rails for bolting the unit to its
foundation.
For ground level installations, precautions should be taken to
protect the unit from tampering and unauthorized persons from
injury. Screws on access panels will prevent casual tampering.
Further safety precautions such as a fenced enclosure or
locking devices on the panels may be advisable. Check local
authorities for safety regulations.
vibration.
6Johnson Controls Unitary Products
430645-YIM-D-0610
Clearances
The unit must be installed with sufficient clearance for air to
enter the condenser coils, for air discharge and for servicing
access. See Table Table 4 for clearances.
NOTE: Additional clearance is required to remove the
compressors out the back of the unit.
Table 4: Minimum Clearances
Clearance DescriptionDistance in Inches
Overhead (Top)120
Front36
Rear36
Left Side30
Right Side30
1
Bottom
1.In all installations where snow ac cu mulates and winter oper-
ation is expected, additional height mus t be prov id ed to
insure normal condenser airflow.
0
LENGTH OF FORKS MUST BE A MINIMUM OF 60 INCHES.
Spreaders, longer than the largest dimension across the
unit must be used across the top of the unit.
Before lifting a unit, make sure that its weight is
distributed equally on the cables so that it will lift evenly.
Do not permit overhanging structures or shrubs to
obstruct condenser air discharge.
Rigging
Exercise care when moving the unit. Do not remove any
packaging until the unit is near the place of install ation. Rig the
unit by attaching chain or cable slings to the lifting holes
provided in the base rails. Spreader bars, whose length
exceeds the largest dimension across the unit, MUST be used
across the top of the unit.
The unit may be moved or lifted with a forklift. Slotted openings
in the base rails are provided for this purpose.
Figure 2: Typical Rigging
Johnson Controls Unitary Products7
430645-YIM-D-0610
Power Wiring
Check the available power and the unit nameplate for correct
voltage. Run the necessary number of properly sized wires to
the unit. Provide a disconnect switch (if not included with the
unit) and fusing as required (Factory disconnect is a fused
disconnect /breaker). Route the conduit through the large
knockout located near the electrical box. See Table 5 for
Electrical Data.
The disconnect switch may be bolted to the side of the unit but
not to any of the removable panels; which would interfere with
access to the unit. Make sure that no refrigerant lines will be
punctured when mounting the disconnect switch, and note that
it must be suitable for outdoor installation.
All power and control wiring must be in accordance
with National and Local electrical codes.
Do not leave the system open to the atmosphere. Unit
damage could occur due to moisture being absorbed by
the POE oil in the system. This type of oil is highly
susceptible to moisture absorption
POE (polyolester) compressor lubricants are known to cause
long term damage to some synthetic roofing materials.
Exposure, even if immediately cleaned up, may cause
embrittlement (leading to cracking) to occur in one year
or more. When performing any service that may risk
exposure of compressor oil to the roof, take precautions
to protect roofing.
Control Wiring
Route the necessary low voltage control wires from the
Simplicity™ control board to the thermostat and also between
the terminal blocks inside the heat pump and evaporator control
boxes. Refer to Figures 3 thru 6 for field wiring diagrams.
Compressors
The scroll compressors used in this product are specifically
designed to operate with R-410A Refrigerant and cannot be
interchanged.
This system uses R-410A Refrigerant which operates at
higher pressures than R-22. No other refrigerant may be
used in this system.
The compressor also uses a polyolester (POE oil), Mobil 3MA
POE. This oil is extremely hydroscopic, meaning it absorbs
water readily. POE oil can absorb 15 times as much water as
other oils designed for HCFC and CFC refrigerants. Take all
necessary precautions to avoid exposure of the oil to the
atmosphere.
Procedures which risk oil leakage include, but are not limited to,
compressor replacement, repairing refrigerant leaks, replacing
refrigerant components such as filter drier, pressure switch,
metering device or coil.
The unit is shipped with compressor mounting bolts which are
factory adjusted and ready for operation.
Do not loosen compressor mounting bolts.
Phasing
Three-phase, scroll compressors operate in only one direction.
If the scroll is drawing low amperage, has similar suction and
discharge pressures, or is producing a high noise level, the
scroll is misphased. Change the incoming line connection
phasing to obtain the proper rotation.
Scroll compressors require proper rotation to operate
properly. Failure to check and correct rotation may result
in property damage.
8Johnson Controls Unitary Products
Electrical Data
Table 5: Electrical Data - Outdoor Unit - HP Without Powered Convenience Outlet
1. Based on three, 75°C insulated copper conductors in conduit and ambient of 30°C.
2. Maximum fuse or maximum circuit breaker (HACR type per NEC).
Refer to NEC/NFPA No. 70, Articles 440-11, 12 for information on minimum disconnect sizing.
CompressorsOutdoor Fan MotorPwr Conv Outlet
Qty
RLA
(each)
MCC
(each)
LRA
(each)
Power
Supply
HP Qty
FLA
(each)
FLA
430645-YIM-D-0610
Minimum
Circuit
Ampacity
1
Maximum
Fuse Size
2
(A)
Table 6: Electrical Data - Outdoor Unit - HP With Powered Convenience Outlet
1. Based on three, 75°C insulated copper conductors in conduit and ambient of 30°C.
2. Maximum fuse or maximum circuit breaker (HACR type per NEC).
Refer to NEC/NFPA No. 70, Articles 440-11, 12 for information on minimum disconnect sizing.
FLA
(each)
FLA
Minimum
Circuit
Ampacity
1
Maximum
Fuse Size
2
(A)
Johnson Controls Unitary Products9
430645-YIM-D-0610
Refrigerant Mains
This Split-System (Air Condensing / Heat Pump / Air
Handling) unit is one component of an entire system. As
such it requires specific application considerations with
regard to the rest of the system (air handling unit, duct
design, condensing unit, refrigerant piping and control
scheme).
Failure to properly apply this equipment with the rest of
the system may result in premature failure and/or
reduced performance / increased costs. Warranty
coverage specifically excludes failures due to improper
application and Unitary Products specifically disclaims
any liability resulting from improper application.
Please refer to the equipment Technical Guide,
Installation Manual and the piping applications bulletin
247077 or call the applications department for Unitary
Products @ 1-877-UPG-SERV for guidance.
Line Sizing
When sizing refrigerant pipe for a split-system air conditioner,
check the following:
1.Suction line pressure drop due to friction.
2.Liquid line pressure drop due to friction.
3.Suction line velocity for oil return.
4.Liquid line pressure drop due to vertical rise. For certain
piping arrangements, different sizes of suction line pipe
may have to be used. The velocity of the refrigerant vapor
must always be great enough to carry the oil back to the
compressor.
5.Evaporator Located Below Condenser - On a split
system where the evaporator blower is located below the
condenser, the suction line must be sized for both pressure
drop and for oil return.
6.Condenser Located Below Evapora tor - When the
condenser is located below the evaporator blower, the
liquid line must be designed for the pressure drop due to
both friction loss and vertical rise. If the pressure drop due
to vertical rise and friction exceeds 60 psi, some refrigerant
will flash before it reaches the thermal expansion valve.
Flash gas
1.Increases the liquid line pressure loss due to friction that in
2.Reduces the capacity of the refrigerant control device
3.Erodes the seat of the refrigerant control device.
4.Causes erratic control of the refrigerant entering the
:
turn causes further flashing.
which starves the evaporator.
evaporator.
Take Adequate Precautions
Many service problems can be avoided by taking adequate
precautions to provide an internally clean and dry system and
by using procedures and materials that conform to established
standards.
Use hard drawn copper tubing where no appreciable amount of
bending around pipes or other obstructions is necessary. If soft
copper is used, care should be taken to avoid sharp bends that
may cause a restriction. Pack fiberglass insulation and a
sealing material such as permagum around refrigerant lines
where they penetrate a wall to reduce vibrations and to retain
some flexibility.
Support all tubing at minimum intervals with suitable hangers,
brackets or clamps.
Braze all copper-to-copper joints with Silfos-5 or equivalent
brazing material. Do not use soft solder. Insulate all suction
lines with a minimum of 1/2" ARMAFLEX or equivalent that
meets local codes. Liquid lines exposed to direct sunlight and/
or high temperatures must also be insulated. Never solder
suction and liquid lines together. They can be taped together for
convenience and support purposes, but they must be
completely insulated from each other.
The liquid and suction service ports on the condenser section
permit leak testing, evacuation, and partial charging of the field
piping and the evaporator without disturbing refrigerant stored
in the condenser during initial installation.
Before beginning installation of the main lines, be sure that the
evaporator section has not developed a leak in transit. Check
pressure at the Schrader valve located on the header of each
coil. If pressure still exists in the system, it can be assumed to
be leak free. If pressure DOES NOT exist the section will need
to be repaired before evacuation and charging is performed.
A bi-flow solid core filter-drier MUST be field-installed in the
liquid line of every system to prevent dirt and moisture from
damaging the system. Properly sized filter-driers are shipped
with each condensing section.
NOTE: Installing a filter-drier does not eliminate the need for
the proper evacuation of a system before it is charged.
A field-installed moisture indicating sight-glass should be
installed in the liquid line(s) between the filter-drier and the
evaporator coil. The moisture indicating sight-glass can be used
to check for excess moisture in the system.
Both condenser and evaporator sections have copper sealing
disks brazed over the end of liquid and suction connections.
The temperature required to make or break a brazed joint is
high enough to cause oxidation of the copper unless an inert
atmosphere is provided.
NOTE: Dry nitrogen should flow through the system at all times
when heat is being applied and until the joint has
cooled. The flow of nitrogen will prevent oxidation of the
copper lines during installation.
10Johnson Controls Unitary Products
Loading...
+ 23 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.