Johnson Controls M4-CGM Series, M4-CGM09090 Installation Manual

M4-CGM General Purpose Application
Controllers Installation Guide
Part No. 24-10143-01698 Rev. B
2019-10-18

Application

The CGM09090 General Purpose Application MS/ TP Controller (CGM) are equipment controllers that run pre-engineered and user-programmable applications, and provides the inputs and outputs required to monitor and control a wide variety of HVAC and other facility equipment. CGM controllers operate on an RS-485 BACnet® MS/TP Bus as BACnet Advanced Application Controllers (B-AACs) and integrate into Johnson Controls® and third­party BACnet systems.
CGM equipment controllers include an integral real­time clock, which enables the controllers to monitor and control schedules, calendars, and trends, and operate for extended periods of time as stand-alone controllers when offline from the Metasys® system network.

Communications Protocols

The CGM controllers can communicate using BACnet MS/TP, N2, or wireless Zigbee®. By default, the CGM controllers communicate using the BACnet MS/TP protocol. The BACnet protocol is a standard for ANSI, ASHRAE, and the International Standards Organization (ISO) for building controls.
The CGM controllers can be used as functional replacements for legacy N2 controllers. The N2­capable MS/TP equipment controller models provide a cost-effective upgrade and modernization path for customers with existing N2 controllers. For installation and commissioning support, and tips for efficient and safe replacement, refer to the Modernization Guide for Legacy N2 Controllers (LIT-12012005) and the controller­specific documentation. For information about mapping N2 Objects in controllers with switchable communications protocols, refer to the N2
Compatibility Options chapter of the Controller Tool Help (LIT-12011147).
To configure CGM controllers to communicate using the N2 communications protocol, see Configuring
N2 communications.
The CGM controller can also be installed in a wireless application using aZFR/ZFR Pro Wireless Field Bus Router. To configure these controllers to communicate using the wireless communications protocol, see Configuring wireless communications.

North American Emissions Compliance

United States

This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when this equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area may cause harmful interference, in which case the users will be required to correct the interference at their own expense.

Canada

This Class (A) digital apparatus meets all the requirements of the Canadian Interference­Causing Equipment Regulations.
Cet appareil numérique de la Classe (A) respecte toutes les exigences du Règlement sur le matériel brouilleur du Canada.

Installation

Observe the following guidelines when installing a CGM Controller:
• To minimize vibration and shock damage to the controller, transport the controller in the original container.
• Verify that all parts shipped with the controller.
• Do not drop the controller or subject it to physical shock.
*241014301698B*
(For factory use only)
M4-CGM09090

Parts included

• One CGM controller with removable terminal blocks (Input/Output, Power, FC, and SA bus are removable)
• One installation instructions sheet

Materials and special tools needed

• Three fasteners appropriate for the mounting surface (M4 screws or #8 screws)
• One 20 cm (8 in.) or longer piece of 35 mm DIN rail and appropriate hardware for DIN rail mount (only)
• Small straight-blade screwdriver for securing wires in the terminal blocks

CGM09090 physical features

The following figure displays the physical features of the CGM controllers, and the accompanying table provides a description of the physical features and a reference to further information where required.
Table 1: CGM09090 physical features
Physical Feature: Description and References
6 Cover Lift Tab (see Removing the controller cover)
Sensor Actuator (SA) Bus Terminal Block: Orange terminal
7
(see SA bus terminal block) Field Controller (FC) Bus Terminal Block: Blue terminal
8
(see FC bus terminal block (or N2 protocol as required)) End-of-Line (EOL) Switch (see Setting the End-of-Line
9
(EOL) switch)
Universal Serial Bus (USB) 2.0 host type A Port
10
11
12
13 FC Bus Port RJ-12 6-pin Modular Jack (see FC bus port) 14 LED Status Indicators (see Table 11)
15
Note: The USB feature is not currently supported.
Binary Input (BI) Terminal Block: White terminals; dry Contact Maintained or Pulse Counter/Accumulator Mode (see Table 5)
Universal Inputs (UI) Terminal Block: White terminals; can be defined as Voltage Analog Input (0-10 VDC), Current Analog Input (4-20 mA), Resistive Analog Inputs (0-600k ohm), or Dry Contact Binary Input (see Table 5)
Sensor (SA Bus) Port: RJ-12 6-Pin Modular Jack (see SA Bus
port)

Mounting

Figure 1: CGM09090 Physical Features
Table 1: CGM09090 physical features
Physical Feature: Description and References
Binary Outputs (BO) Terminal Block: Black terminals; 24
1
VAC Triac (see Table 5) Configurable Outputs (CO) Terminal Block: Black
2
terminals; can be defined as Voltage Analog Output (0-10 VDC) or Binary Output (24 VAC Triac) (see Table 5)
Analog Output (AO) Terminal Block: Black terminals;
3
can be defined as Voltage Analog Output (0-10 VDC) or Current Analog Output (4-20 mA) (see Table 5)
Device Address Rotary Switch Block: Decimal Addressing
4
(see Setting the device address) Supply Power Terminal Block: Gray terminals; 24 VAC,
5
Class 2 (see Supply power terminal block)
Observe the following guidelines when mounting a CGM controller:
• Ensure the mounting surface can support the controller, DIN rail, and any user-supplied enclosure.
• Mount the controller horizontally on 35 mm DIN rail whenever possible.
• Mount the controller in the proper mounting position.
• Mount the controller on a hard, even surface whenever possible in wall-mount applications.
• Use shims or washers to mount the controller securely and evenly on the mounting surface.
• Mount the controller in an area free of corrosive vapors and observe the Ambient Conditions requirements in Table 14.
• Provide for sufficient space around the controller for cable and wire connections for easy cover removal and good ventilation through the controller (50 mm [2 in.] minimum on the top, bottom, and front of the controller).
• Do not mount the controller on surfaces prone to vibration, such as duct work.
M4-CGM General Purpose Application Controllers Installation Guide2
• Do not mount the controller in areas where electromagnetic emissions from other devices or wiring can interfere with controller communication.
On panel or enclosure mount applications, observe the following additional guidelines :
• Mount the controller so that the enclosure walls do not obstruct cover removal or ventilation through the controller.
• Mount the controller so that the power transformer and other devices do not radiate excessive heat to the controller.
• Do not install the controller in an airtight enclosure.
Figure 2: Controller mounting position
Figure 3: Back of controller

DIN rail mount applications

To mount a CGM controller horizontally on a 35 mm DIN rail (recommended method), complete the following steps:
1. Securely mount a 20 cm (8 in.) or longer section of 35 mm DIN rail horizontal and centered in the desired space so that the controller mounts in the horizontal position.

Mounting features and dimensions

See the Figure 3 for mounting dimensions in millimeters. Figure 3 also illustrates the DIN rail channel and the mounting clips in an extended position.
2. Pull the two bottom mounting clips outward from the controller to the extended position (Figure 3).
3. Hang the controller on the DIN rail by the hooks at the top of the (DIN rail) channel on the back of the controller (Figure 3), and position the controller snugly against the DIN rail.
4. Push the bottom mounting clips inward (up) to secure the controller on the DIN rail.
To remove the controller from the DIN rail, pull the bottom mounting clips out to the extended position and carefully lift the controller off the DIN rail.

Wall mount applications

To mount a CGM controller directly on a wall or other flat vertical surface, complete the following steps:
1. Pull the two bottom mounting clips outward and ensure they are locked in the extended position as shown in Figure 3.
M4-CGM General Purpose Application Controllers Installation Guide 3
2. Mark the mounting hole locations on the wall using the dimensions in one of the mount positions shown in Figure 2. Or hold the controller up to the wall or surface in a proper mount position and mark the hole locations through the mounting clips.
3. Drill holes in the wall or surface at the marked locations, and insert appropriate wall anchors in the holes (if necessary).
ATTENTION
Mise En Garde: Risque de dégâts matériels:
Ne pas mettre le système sous tension avant d'avoir vérifié tous les raccords de câblage. Des fils for­mant un court-circuit ou connectés de façon incor­recte risquent d'endommager irrémédiablement l'équipement.
4. Hold the controller in place, and insert the screws through the mounting clips and into the holes (or anchors). Carefully tighten all of the screws.
Important: Do not over-tighten the mounting screws. Over-tightening the screws may damage the mounting clips.

Wiring

Observe the following guidelines when wiring a CGM controller:
CAUTION
Risk of Electric Shock:
Disconnect the power supply before making electrical connections to avoid electric shock.
ATTENTION
Mise En Garde: Risque de décharge électrique:
Débrancher l'alimentation avant de réaliser tout rac­cordement électrique afin d'éviter tout risque de décharge électrique.
CAUTION
Risk of Property Damage:
Do not apply power to the system before checking all wiring connections. Short circuited or improperly con­nected wires may result in permanent damage to the equipment.
Important: Do not exceed the controller electrical ratings. Exceeding controller electrical ratings can result in permanent damage to the controller and void any warranty.
Important: Use copper conductors only. Make all wiring in accordance with local, national, and regional regulations.
Important: Electrostatic discharge can damage controller components. Use proper electrostatic discharge precautions during installation, setup, and servicing to avoid damaging the controller.
For detailed information about configuring and wiring an MS/TP Bus, FC bus, and SA bus, refer to the MS/TP Communications Bus Technical Bulletin (LIT-12011034). For detailed information about wiring an N2 network, refer to the N2 Communications Bus Technical Bulletin (LIT-636018).

Terminal blocks and bus ports

See CGM09090 physical features for terminal block and bus port locations on the CGM controller. Observe the following guidelines when wiring a CGM controller.

Input and Output terminal blocks

On the CGM controller models, the input and output terminal blocks are removable. All of the input terminal blocks are mounted on the bottom of the controller, and the output terminal blocks are mounted on the top of the controller. For information about removing a terminal block, see
Removing a terminal block. For more information
about I/O terminal functions, requirements, and ratings, see Terminal wiring guidelines, functions,
ratings, and requirements.
M4-CGM General Purpose Application Controllers Installation Guide4

FC bus terminal block (or N2 protocol as required)

The FC bus terminal block is a blue, removable, 4­terminal plug that fits into a board-mounted pin header.
Use a 3-wire twisted, shielded cable, as shown in Figure 4, to wire the removable FC bus terminal block plugs on the controller, and other controllers, in a daisy-chain configuration. For more information about FC Bus terminal functions, requirements, and ratings, see Table 7.
Figure 4: FC Bus terminal block wiring
Figure 5: SA Bus Terminal Block Wiring
Table 3: SA bus configuration
Description
1 Wiring for a terminating device on SA bus 2 SA bus terminal block plugs 3 Wiring for a daisy chained device on SA bus
Cable shield connection
4
5 Connects to the next device on the SA bus
Note: Connect the shields to ensure they are continuous the entire length with only one ground location.
Table 2: FC bus configuration
Description
1 Wiring for a terminating device on the FC bus 2 FC bus terminal block plugs 3 Wiring for a daisy-chained device on an FC bus segment 4 Connects to the next device on the FC bus 5 Isolated Shield connection terminal
Note: The FC bus Shield (SHLD) terminal is isolated and can be used to connect (daisy chain) the shields for FC bus wiring.

SA bus terminal block

The SA Bus terminal block is an orange, removable, 4-terminal plug that fits into a board-mounted jack.
Use a 4-wire twisted, shielded cable, as shown in Figure 5, to wire the removable SA Bus terminal block plugs on the controller, and other SA bus devices, in a daisy-chain configuration. See
Terminal wiring guidelines, functions, ratings, and requirements for more information.
Note: The POWER terminal supplies 15 VDC. The POWER terminal can be used to connect (daisy chain) the 15 VDC power leads on the SA bus.
Note: Do not use the modular SA Bus port and the terminal block SA Bus simultaneously. Only use one of these connections at a time.
Note: The CGM controller is the EOL for the SA Bus.

FC bus port

The FC bus port on the front of the controller is an RJ-12, 6-position modular jack that provides a connection for the Mobile Access Portal (MAP) Gateway, or the ZFR/ZFR Pro Wireless Field Bus Router.
The FC bus port is connected internally to the FC bus terminal block. See Table 7 for more information. The FC bus port pin assignment is shown in Figure 6.
M4-CGM General Purpose Application Controllers Installation Guide 5
Note: The MAP Gateway serves as a replacement for the BTCVT, which is no longer available for purchase, but continues to be supported.
Figure 6: Pin number assignments for FC bus and SA bus ports on equipment controllers

SA Bus port

The Sensor (SA Bus) port on the front of the controller is an RJ-12, 6-position modular jack that provides a connection for the MAP Gateway, BTCVT, the VAV Balancing Tool, the DIS1710 local controller display, specified network sensors, or other SA Bus devices with RJ-12 plugs. When the CGM is configured for N2 network communication, you must download and commission the controller using the SA Bus port.
Note: The MAP Gateway serves as a replacement for the BTCVT, which is no longer available for purchase, but continues to be supported.
The Sensor port is connected internally to the SA bus terminal block. See Table 7 for more information. The Sensor port pin assignment is shown in Figure 6.

Supply power terminal block

The 24 VAC supply power terminal block is a gray, removable, 2-pin terminal plug that fits into a board­mounted jack on the top right of the controller.
Wire the 24 VAC supply power wires from the transformer to the HOT and COM terminals on the terminal plug as shown in Figure 7. For more information about the Supply Power Terminal Block, see Table 7.
Figure 7: 24 VAC supply power terminal block wiring
Table 4: Supply power terminal block wiring
Description
1 Supply power terminal block 2 Supply power terminal header
Wires from Johnson Controls 24 VAC, class 2 power
3
transformer 4 24 VAC (Orange wire) 5 COM (Brown wire)
Note: The supply power wire colors may be different on transformers from other manufacturers. Refer to the transformer manufacturer’s instructions and the project installation drawings for wiring details.
Important: Connect 24 VAC supply power to the equipment controller and all other network devices so that transformer phasing is uniform across the network devices. Powering network devices with uniform 24 VAC supply power phasing reduces noise, interference, and ground loop problems. The equipment controller does not require an earth ground connection.
Important: Power wires must be less than 30 meters between controller and transformer

Terminal wiring guidelines, functions, ratings, and requirements

This section provides further guidelines on input and output wiring, maximum cable length versus load current, and SA Bus and supply power wiring.
For information about removing a terminal block from the controller, see Removing a terminal block.
M4-CGM General Purpose Application Controllers Installation Guide6

Input and Output wiring guidelines

• All input and output cables, regardless of wire size or number of wires, should consist of stranded,
Table 5 provides information and guidelines about the functions, ratings, and requirements for the controller input and output terminals, and Table 6 also references guidelines for determining proper
insulated, and twisted copper wires.
• Shielded cable is not required for input or output cables.
wire sizes and cable lengths.
In addition to the wiring guidelines in Table 5, observe these guidelines when wiring controller inputs and outputs:
• Run all low-voltage wiring and cables separate from high-voltage wiring.
• Shielded cable is recommended for input and output cables that are exposed to high electromagnetic or radio frequency noise.
• Inputs/outputs with cables less than 30 m (100 ft) typically do not require an offset in the software setup. Cable runs over 30 m (100 ft) may require an offset in the input/output software setup.
I/O terminal blocks, ratings and requirements
Table 5: I/O terminal blocks, functions, ratings, requirements, and cables
Terminal Block label
UNIVERSAL
(Inputs)
Terminal label
+15 V
INn
ICOMn
Function, ratings, requirements
15 VDC Power Source for active (3-wire) input devices
connected to the Universal INn terminals. Provides 100 mA total current
Analog Input - Voltage Mode (0–10 VDC)
10 VDC maximum input voltage Internal 10k ohm Pull-down
Analog Input - Current Mode (4–20 mA)
Internal 100 ohm load impedance
Note: Current loop jumpers are fail-safe to maintain a closed 4 to 20 mA current loop, even when the power to the controller is interrupted or off. See UI current loop
jumpers.
Analog Input - Resistive Mode (0–600k ohm)
Internal 12 V. 15k ohm pull up Qualified Sensors: 0-2k ohm potentiometer, RTD (1k Nickel
[Johnson Controls® sensor], 1k Platinum, and A99B Silicon Temperature Sensor) Negative Temperature Coefficient (NTC) Sensor
Binary Input - Dry Contact Maintained Mode
1 second minimum pulse width Internal 12 V. 15k ohm pull up
Universal Input Common for all Universal Input terminals
Note: All Universal ICOMn terminals share a common,
which is isolated from all other commons.
Determine wire size and maximum cable length
Same as (Universal) INn
Note: Use 3-wire cable for
devices that source power from the +15V terminal.
See Guideline A in Table 6
See Guideline B in Table 6.
See Guideline A in Table 6.
See Guideline A in Table 6.
Same as (Universal) INn
M4-CGM General Purpose Application Controllers Installation Guide 7
Table 5: I/O terminal blocks, functions, ratings, requirements, and cables
Terminal Block label
BINARY
(Inputs)
CONFIGURABLE
(Outputs)
ANALOG
(Outputs)
Terminal label
INn
ICOMn
OUTn
OCOMn
OUTn
OCOMn
Function, ratings, requirements
Binary Input - Dry Contact Maintained Mode
0.01 second minimum pulse width Internal 18 V. 3k ohm pull up
Binary Input - Pulse Counter/Accumulator Mode
0.01 second minimum pulse width (50 Hz at 50% duty cycle) Internal 18 V. 3k ohm pull up
Binary Input Common for all Binary Input (IN) terminals
Note: All Binary ICOMn terminals share a common,
which is isolated from all other commons, except the Configurable Output (CO) common (OCOMn) when the CO is defined as an Analog Output.
Analog Output - Voltage Mode (0–10 VDC)
10 VDC maximum output voltage 10 mA maximum output current Required an external load of 1,000 ohm or more.
Binary Output - 24 VAC Triac (External Power Source only) Connects OUTn to OCOMn when activated. External Power Source Requirements: 30 VAC maximum output voltage
0.5 A maximum output current
1.3 A at 25% duty cycle Maximum 6 cycles/hour with M9220BGx-3 40 mA minimum load current
Analog Output Signal Common All Configurable Outputs (COs) defined as Analog Outputs (AOs) share a common, which is isolated from all other commons except the Binary Input common.
Binary Output Signal Common All Configurable Outputs (COs) defined as Binary Outputs are isolated from all other commons, including other CO commons.
Analog Output - Voltage Mode (0–10 VDC)
10 VDC maximum output voltage 10 mA maximum output current Required an external load of 1,000 ohm or more.
Note: The Analog Output (AO) operates in the Voltage Mode when connected to devices with impedances greater than 1,000 ohm. Devices that drop below 1,000 ohm may not operate as intended for Voltage Mode applications.
Analog Output - Current Mode (4–20 mA)
Requires and external load between 0 and 300 ohm.
Note: The Analog Output (AO) operates in the Current Mode when connected to devices with impedances less than 300 ohm. Devices with impedances greater than 300 may not operate as intended for Current Mode applications.
Analog Output Signal Common for all Analog OUT terminals.
Note: All Analog Output Common terminals (OCOMn)
share a common, which is isolated from all other commons.
Determine wire size and maximum cable length
See Guideline A in Table 6.
See Guideline A in Table 6.
See Guideline C in Table 6.
Same as (Configurable) OUTn.
See Guideline C in Table 6.
M4-CGM General Purpose Application Controllers Installation Guide8
Loading...
+ 18 hidden pages