Johnson Controls LX Series User Manual

LX Series Unit Ventilator Controller
User’s Guide
Code No. LIT-12011486
Issued June 22, 2009
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
Sensor Configuration Wizard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Control Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
LONMARK Functional Profile. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Units in LONWORKS Networks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
Language Selection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Selecting a Measurement System or Selecting a Language . . . . . . . . . . . . . . . . . . . . . 16
Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
10k Ohm or Digital Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Analog Inputs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
4 to 20 mA Analog Input, Externally Supplied . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Sensors and Switches. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Auxiliary Alarm Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Bypass Contact Input. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
CO
Level Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
2
Discharge Temperature Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Economizer Enable Input. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Emergency Contact Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Fan Speed Selector Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Fan State Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Mixed Air Temperature Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Mode Selector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Occupancy Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Outdoor Enthalpy Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
1LX Series Unit Ventilator Controller User’s Guide
Outdoor Humidity Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Outdoor Temperature Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Return Air Temperature Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Setpoint Offset Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Space Enthalpy Input. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Space Humidity Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Space Temperature Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Water Temperature Input. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Window Contact Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Outputs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Analog Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Analog Output Protection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Digital Outputs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Staged Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Output Selections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Fan Speed 1–3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Heating Outputs 1–4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Cooling Outputs 1–4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Reversing Valve. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Humidifier and Dehumidifier Outputs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Minimum Fresh Air Enable (MIN_FRESH_AIR_ENABLE) . . . . . . . . . . . . . . . . . . . . . . . . . 30
Economizer Enable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Heat Valve ON-OFF. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Cool Valve ON-OFF. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Heat Cool Valve ON-OFF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Heat Valve Open or Close. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Cooling Valve Open or Close. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Heat Cool Valve Open or Close. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Fan Speed Modulate (FAN_SPEED_MOD) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Heating Modulate (HEATING_MOD). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
LX Series Unit Ventilator Controller User’s Guide2
Heating or Cooling Valve Modulate (HEATING_VALVE_MOD) (COOLING_VALVE_MOD)31
Fresh Air Damper Modulate (FRESH_AIR_DAMPER_MOD) . . . . . . . . . . . . . . . . . . . . . . . 31
Fresh Air Damper Open or Close . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Mode Selection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Network Variables Used for Mode Selection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Occupied Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Starting Occupied Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Ending Occupied Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Unoccupied Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Starting Unoccupied Mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Ending Unoccupied Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Bypass Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Starting Bypass Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Ending Bypass Mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Standby Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Starting Standby Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Ending Standby Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Slave Mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
State Selection and Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Supervisory Control and Scheduling. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Calculating the Space Temperature Setpoint . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
The Effect of nviSetPoint on the Active Setpoints . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
The Effect of a Setpoint Offset on the Active Setpoints. . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Ventilation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .38
Ventilation Separate from Free Cooling. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Control of the Fresh Air Intake. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Outputs That Control the Fresh Air Damper . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Humidity Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Cooling State . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Free Cooling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
LX Series Unit Ventilator Controller User’s Guide 3
When Free Cooling is Used. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Mechanical Cooling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Cooling Demand . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Cooling Output Sequence . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Ending the Cooling State. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Heating States . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Heating Demand . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Heating Output Sequence . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Cooling Outputs Used to Heat. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Ending the Heating State. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Night Purge. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Morning Warm-up State . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Using Night Purge and Morning Warm-up with DCV . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Fan Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Terminal Load . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Heating Terminal Load . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Cooling Terminal Load . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Networking Operations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Slave Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Load Shedding. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Setting-up Network Connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Network Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Optimum Start . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Requirements for Optimum Start. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Emergency Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Emergency Initiation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Normal Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
The PID Loop. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Proportional . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Integral . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
LX Series Unit Ventilator Controller User’s Guide4
Gain . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Time. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
How It Is Used . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Derivative . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Gain . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Time. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
Deadband . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
Alarm Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
Alarm Features. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Alarm Types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
Alarm Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
Heartbeat Alarms. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Disconnect Alarms. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Emergency Mode Alarms. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
User-Set Alarms. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Setting up the Unit Ventilator Controller. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Persistent Network Variables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Setting Units. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Input Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Output Configuration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
Output Signal Types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
Configuring an Output. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
Configuring an Output Represented as a Functional Block. . . . . . . . . . . . . . . . . . . . . . . . . 71
Heating-Cooling Configuration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
Optimum Start . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
Fan-Valve Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
PID Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
Alarm Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Space and Return Temperatures and Humidity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Levels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
CO
2
LX Series Unit Ventilator Controller User’s Guide 5
Discharge Temperature and Auxiliary Alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
Mixed Air Temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
Fan Alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
General Settings Configuration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
Radiation Heating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
Options Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
Optimum Start . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
Frost Protection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
Humidity Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
Network Input Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
Heartbeat Alarms. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
Network Output Configuration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
Object Manage. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
Object Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
Communication Failure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
Electrical Fault . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
Out of Limits. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
Disabled. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
In Alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
In Override. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
Out of Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
Network Variables. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
nviApplicMode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
nviCO2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
nviDischargeTemp. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
nviEconoEnable. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
nviEmergCmd. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
nviExtCmdOutputx . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
nviFanSpeedCmd. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
nviFanState. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
LX Series Unit Ventilator Controller User’s Guide6
nviHotWater . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
nviMixedAirTemp. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
nviOccCmd and nviOccManCmd . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
nviOutdoorEnth . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
nviOutdoorRH . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
nviOutdoorTemp . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
nviReturnTemp. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
nviSetPoint. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
nviSetPointOffset. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
nviShedding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
nviSlave . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
nviSpaceEnth. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
nviSpaceRH . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
nviSpaceTemp . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
nviWaterTemp . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
nvoCtrlOutputx. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
nvoDischargeSetPt . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
nvoEconoEnable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
nvoEffectSetPt . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
nvoFanSpeed . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
nvoHwInputx . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
nvoOccState. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
nvoUValarm. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
nvoUVstate. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
nvoSpaceTemp . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
nvoTerminalLoad. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
nvoUnitStatus. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
Standard Network Variable Types (SNVTs). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
SNVT_hvac_emerg (103). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
SNVT_hvac_mode (108) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
LX Series Unit Ventilator Controller User’s Guide 7
SNVT_hvac_status (112). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
Alarm State. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102
SNVT_lev_percent (81) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103
SNVT_occupancy (109) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103
SNVT_ppm (29) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
SNVT_switch (95). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
Switch Definition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
SNVT_temp_p (105) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106
SNVT_tod_event (128) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106
LX Series Unit Ventilator Controller User’s Guide8
LX Series Unit Ventilator Controller
User's Guide

Introduction

The LX Series Unit Ventilator Controller (UVC) seamlessly integrates into a LONWORKS® network for the control of almost any Unit Ventilator Controller due to its wide range of output types and LONMARK® certification.
The LX Series Unit Ventilator Controller controls the following equipment:
up to four stages of mechanical heating or cooling
modulating heating or cooling valves
reversing valves for application requiring a heat pump
floating valves for heating or cooling
unit ventilator with or without an economizer
up to three fan speeds or variable speed fans
humidifier and dehumidifier
an economizer that requires analog, digital, or Pulse Width Modulation (PWM) control signals
The UVC has five digital outputs supplying 1.0 ampere at 24 VAC. These outputs produce digital or PWM signals.
There are also two tri-mode analog outputs on the circuit board. These outputs provide the following signals:
linear signals over a 0 to 10 VDC range
10 VDC digital or PWM signals
digital signals of 60 mA at 12 VDC
The controller has six inputs, each capable of one of 21 possible input types. Inputs have 12-bit resolution and are configured completely by software.
For easy maintenance and installation, the controller is equipped with plug-in connectors that accept flat cable or wires. The controller uses a TP/FT-10 78 kbps network configuration.
The information in this guide helps you to set up the UVC, understand the operation of the UVC, and troubleshoot problems of the device. Information is organized to follow the UVC configuration wizard menu.
LX Series Unit Ventilator Controller User's Guide 9

Sensor Configuration Wizard

The UVC incorporates the sensor configuration wizard. The wizard provides powerful and simple configuration tools for the hardware inputs. You can select the digital or analog inputs through the software, which means there are no circuit board jumpers to move.
Analog input signal types - resistive, voltage, current - are selected in software without hardware jumpers. Built-in conversion tables are provided for a large number of thermistors or other sensor types. You can easily create custom conversion tables by setting the offset, minimum, and maximum values in one dialog box for the input.
The sensor configuration wizard also provides direct access to network properties of the analog or digital input including the Standard Network Variable Type (SNVT), Heartbeat, Send on Delta, Override, Default Value, and Throttle settings. All input features are conveniently located on one screen, which avoids the hassle of switching back and forth between screens to fully configure an input. In addition, the wizard provides warnings of configuration errors as they occur, enabling you to correct mistakes quickly.
Shown by the LX-UVL wizard view in FX Workbench, the sensor configuration wizard exists as a separate object. A separate functional block represents each hardware input. To configure an input, select the hardware input on the left side of the LX-UVL wizard view of the device and click the Launch button. The sensor configuration wizard allows you to control network inputs not directly controlled by the Unit Ventilator Controller.

Control Features

The Unit Ventilator Controller provides Proportional plus Integral plus Derivative (PID) loops for advanced control of humidity, discharge temperature, and space temperature. Each PID loop has an individual, configurable deadpan. In addition, each PID loop provides gain and time adjustment for the integral and derivative terms, and gain adjustment for the proportional term.
Whereas space temperature control is done with a PI loop only , the presence of the derivative term adds the ability to precisely adjust space temperature control to provide better comfort and increased savings.
The PID loop is especially useful in controlling the CO2 concentration, since this can vary quickly and greatly as individuals enter and exit meeting rooms, and work
areas. The quick response of the PID loop also maintains duct pressure within acceptable limits.
Humidification and dehumidification sequences provide the UVC with the ability to maintain the space humidity at the desired level. The Unit Ventilator Controller also provides advanced control features often associated with air handlers. These features include Optimum Start and load shedding.
LX Series Unit Ventilator Controller User's Guide10
The Optimum Start function maintains statistics that enable the Unit Ventilator Controller to predict the warm-up or cool-down time period needed to make the building ready for occupancy. The precise Optimum Start period is calculated every day using the current outdoor air temperature.

LONMARK Functional Profile

The LX Series Unit Ventilator Controller uses LONWORKS network protocol and is LONMARK certified for interoperability on any LONWORKS network. The Unit Ventilator Controller is set up through its own configuration wizard and the Sensor configuration wizard. You can use FX Workbench or any other network management tool to install the device onto the network and bind variable connections.
Figure 1 shows that the Unit Ventilator Controller meets the LONMARK standard by providing the network variable inputs, network variable outputs, and configuration properties specified by the profile. In addition, the Unit Ventilator Controller provides many extra network variable inputs and outputs. These extra network variables provide a greater flexibility and number of functions than required in the LONMARK profile.
For example, you can use network input nviSlave, to slave the UVC to another unit, whereas network output nvoUnitStatus, enables the UVC to act as the master node. The Unit Ventilator Controller has network inputs that permit the use of outside enthalpy sensors and space enthalpy sensors. These inputs provide better calculation of the cooling or heating effect of the outside air upon the conditioned space.
The input object has conversion tables and hardware properties present as configuration properties in the area marked Manufacturer Configuration Properties. By choosing from a list of standard thermistors, you can select different conversion properties. The conversion tables configuration property allows you to create your own custom tables. Hardware properties, located in the same area, allow you to modify your input from the software object.
LX Series Unit Ventilator Controller User's Guide 11
nviSpaceTemp
SNVT_ temp_p
nviApplicMode
SNVT_ hvac_ mode
nviSetP tOffset
SNVT_ temp_p
nviOutdoorTem p
SNVT_ temp_p
nviOutdoorR H
SNVT_lev_ percent
nviSpaceRH
SNV T_ lev_ percent
nviCO2
SNVT_ ppm
nviEmergCmd
SNV T_ hvac_ emerg
Occ. Temperature Set Points (mandatory)
nviEconoEnable
SNVT_ switch
nviFanState
SNVT_ switch
nviFanSpeedCmd
SNVT_ switch
nv iM ixed A ir Te m p
SNVT_ temp_p
nviOccManCmd
SNVT_ occupancy
nviReturnTemp
SNVT_ temp_p nviShedding
SNVT_ switch
nviS lav e
SNVT_ hvac_ status
nviSupplyTem p
SNVT_ temp_p
nviOccCm d
SNV T_ tod_event
nviSpaceEnth SNV T_ enthalpy
nviOutdoorE nth
SNVT_ enthalpy
nviWaterTemp SNVT_ temp_p
nviHotWater SNVT_ switch
nviSetpoint
SNVT_ temp_p
Manufacturer Configuration Properties
LX-UVL- 1 Unit Ventilator
Object Type # 808 0
Mandatory
Netw ork
Variables
Optional Netw ork
Variables
C o n fig ura t io n P r o p e r tie s
Maximum S end Time (mandatory)
Minimum Send Time (optional)
Maximum R eceive Time ( optional)
CO 2 limit (optional)
Local Bypass Time (optional)
Manufacturer
Netw ork
Variables
Please see the m anual for details.
Wizard for configuration provided.
nvoSpaceTemp
SNVT_ temp_p
nv oU n itSta tu s
SNVT_ hvac_ status
nv oE ffe c tS e tp t
SNVT_ temp_p
nvoEconoEnable
SNVT_ switch
nvoFanSpeed
SNVT_ switch nv oO ccS ta te
SNVT_ occupancy
nvoTerminalLoad
SNV T_ lev_ percent
nvoCtrlO utput1
SNVT_ switch
. . .
nvoCtrlO utput7
SNVT_ switch
nvoSupplySetPt
SNVT_ temp_p
Figure 1: LX Series Unit Ventilator Controller:
L
ONMARK Functional Profile
LX Series Unit Ventilator Controller User's Guide12
Figure 2 shows the Unit Ventilator Controller input object and the output object.
6 x LX-UVL-1 Hardware Input
Object Type #1
Mandatory
Network
Variables
Configuration Properties
Offset ( optional)
Maximum Range (optional)
Minimum Range (optional)
Minimum Send Delta (optional)
Maximum Send Time (optional)
Minimum Send Time (optional)
Override Value (optional)
Manufacturer Configuration Properties
Object M ajo r Ve rsion Object Minor Version
Input Signal Conditioning
Hardware Properties
Translation Table
Default Value
nvoHwInput1
SNVT _xxx
nviExtCmdOutput1
SNVT _switch
Figure 2: LX Series Unit Ventilator Controller Inputs and Outputs
7 x LX-UVL-1 Hardware Output
Object Type #3
Mandatory
Network Variables
Configuration Properties
Maximum Receive Time ( optional)
Override Value (optional)
Manufacturer Configuration Properties
Ob je c t Major Ve rsion Ob je c t Minor Ve rsion
Output Signal Conditioning
PWM Period
Hardware Properties
Default Value
LX Series Unit Ventilator Controller User's Guide 13
The node object displays the nvoUVstate and nvoUValarm variables as manufacturer’s variables. These variables provide information about the alarm conditions in the Unit Ventilator Controller and about the operating state of the device (Figure 3).
LX-UVL - 1 Node
Object Type #0
nviRequest
SNVT _obj_request
Mandatory Network
Variables
Optional Network Variables
Configuration Properties
Location (optional) Device Major Version (optional) Device Minor Version (optional)
Manufacturer
Network
Variables
nvoStatus
SNVT _obj_ status
nvoFileDirectory
SNVT _ address
nvoUVstate SNVT _state_64
nvoUValarm
SNVT _state_64
Manufacturer Configuration Properties
Maximum Send Time
Figure 3: LX Series Unit Ventilator Controller
Node Object Type

Units in LONWORKS Networks

Note: Use this section if you are using the Imperial System of measure. The Imperial System and the International System (SI) are the two main
measurement systems used today. Table 1 compares Imperial units and SI units.
Table 1: Comparing Imperial and SI Units
Imperial Units SI
inch centimeter yard meter mile kilometer degrees Fahrenheit degrees Centigrade
Echelon® SNVTs are based upon SI units. Thus, the most basic structure of the
ONWORKS network is SI based. This basis can lead to some unavoidable
L problems in data conversion if you are using Imperial units.
LX Series Unit Ventilator Controller User's Guide14
The LX-UVL wizard in FX Workbench provides some automatic conversion between SI and Imperial units. However, these are not ideal conversions because a whole number in one system becomes a long decimal fraction in the other. For example, 72°F is approximately equal to 22.22222°C.
Value is written in
Imperial Units.
Data is displayed
for monitoring in
Imperial Units.
Value is translated
to SI units.
Value is rounded.
Value is stored
in SNVT.
Value is read
from SNVT.
Value is rounded.
Value is translated
to SI units.
Units
Figure 4: Writing and Reading Data in Imperial Units in the
ONWORKS Network
L
The values created by converting Imperial to SI or SI to Imperial are subject to rounding errors. If you enter an Imperial value into a LONWORKS SNVT by using the LX-UVL Controller configuration wizard, the value is converted after it is entered, then rounded and written to the SNVT. When you want to monitor the SNVT, the value must be read from the SNVT, converted, and rounded again before it is displayed. Due to the two conversions and two rounding operations, the value may differ slightly from what you originally entered (Figure 4).
The same process and resulting rounding error applies to Standard Configuration Property Types (SCPTs).
Instructions for changing or modifying the units of measure used on your computer are provided in the Selecting a Measurement System or Selecting a Language section.

Language Selection

The following may require you to change your language settings:
You changed your regional settings by selecting a different region in the Regional and Language Options dialog box.
You are working on a site that is in a linguistic region other than your own.
You are dissatisfied with the language displayed on program menus and dialog boxes.
LX Series Unit Ventilator Controller User's Guide 15
You can change your language settings in the Advanced tab of the Regional and Language Options dialog box. Instructions are provided in the following Selecting a Measurement System or Selecting a Language section.

Selecting a Measurement System or Selecting a Language

To select units of measurement or to select a language:
1. In Microsoft® Windows XP® operating system, click Start > Control Panel. The Control Panel appears.
2. In the Control Panel, open Date, Time, Language, and Regional Options.
3. Under the list titled Pick a Task, select and open the second item titled Change the format of numbers, dates, and times (Figure 5).
Figure 5: Date, Time, Language, and Regional Options Screen
LX Series Unit Ventilator Controller User's Guide16
4. Select your language region from the drop-down list provided. The number,
time, and date formats fill automatically (Figure 6).
Figure 6: Regional and Language Options Dialog Box
5. In the Number box, verify the number format uses a decimal point to indicate
numerals representing values less than 1. For example, use 123,456,789.00, not 123 456 789,00. You must use a decimal point for the correct display of
numerals.
6. In the Regional Options dialog box, click Customize.
LX Series Unit Ventilator Controller User's Guide 17
7. Click on the drop-down arrow next to the box labeled Measurement system and select Metric (Figure 7).
Figure 7: Customize Regional Options
8. Verify the Decimal symbol box contains a decimal symbol. If the Decimal symbol box does not contain a decimal symbol, select the symbol in the box, and click Apply.
9. Click OK.
10. Click the Advanced tab and choose a language region by selecting from the drop-down list. Verify the correct language appears on program menus.
11. Click OK.
You have now set the units to appear in the LX-UVL wizard. If you have chosen to display Imperial units, remember that the SNVTs are still using SI units. If you are viewing the data in Imperial units, you are viewing a converted, rounded value.
LX Series Unit Ventilator Controller User's Guide18

Unit Ventilator Controller Installation Overview

Figure 8 shows one possible installation of the Unit Ventilator Controller. Inputs, outputs, ducts, and heating or cooling units have been marked for your convenience.
Note: Not all possible sensors are shown.
LX-UVL- 1 Installation Overview
Unit Ventilator Enclosure
Damper
Intake A ir
Filter
OAH
Fresh Air
(Economizer)
Damper
Damper
Unit Ventilator Enclosure
Mixed
Air
C O
3 Fan
Speeds
Return
MAT DATOAT
Air
RAT
Heating
Coolin g
Unit Ventilator Enclosure
Humidifier
Discharge
Air
Sensor Symbols
Humidity Temperature Carbon Dioxide
Digital Input
Humidity
Temperature
Setpoint Offsett
MAT Mixed Air Temperature
C O
OAH Outside Air Humidity
OAT Outside Air Temperature
Occupancy
Conditioned Space
RAT Return Air Temperature DAT Discharge Air Temperature
Figure 8: Possible LX-UVL Installation

Inputs

The Unit Ventilator Controller has six universal inputs. You can configure universal inputs by using the Unit Ventilator Controller configuration wizard. Universal inputs are configured as either:
analog inputs sensing either current or voltage, or
digital inputs or 10k ohm resistance inputs Note: Because the Unit Ventilator Controller can connect to a maximum of six
sensors, you may want to connect some sensors using the LONWORKS network. All valid network inputs have priority over hardware inputs.
LX Series Unit Ventilator Controller User's Guide 19

10k Ohm or Digital Input

The universal input, when configured as a 10k ohm or digital input, accepts a 10k ohm resistance input or a digital input such as a switch, also known as a cold contact.
The 10k ohm resistance range accommodates 10k ohm thermistors used in space temperature sensors or duct temperature sensors, or a 10k ohm potentiometer used as a setpoint offset.
Use the conversion table for resistance input of more than 10k ohm. The digital range accommodates the occupancy contact, bypass switch, and window switch.
See Figure 9 for wiring information for both 10k ohm resistance and digital inputs.
LX-UVL
1
I
+
Both inputs are configured as 10 k Ohm
or Digital Input Configuration could be done
with either the LX -UVL wizard in or the
Hardware Input Wizard
Figure 9: 10k Ohm or Digital Input
3
I2I
++ + + +
I4 I6I5
––
Thermistor
10kO hm
Contact
NO -NC
LX Series Unit Ventilator Controller User's Guide20

Analog Inputs

Analog inputs include current inputs with a range of 4 – 20 mA, and voltage inputs with a range of 0 – 10 VDC.

4 to 20 mA Analog Input, Externally Supplied

Current inputs require a power supply either on the sensor or wired in series with the sensor. To construct the current input, a 500-ohm 0.25-watt resistor is placed across the Unit Ventilator Controller’s input terminals. See Figure 10 and Figure 11.
LX--UVL
1
I
++++++
I2I
3
4
I
I
5
––
6
I
1 8
0
Resistor:
500
Ω −
Watt
Internal 24
powersupply
¼
VDC
4–20mA
+
Controller source
output 4 – 20 mA
Sensor
Figure 10: Sensor Powered Analog Input
LX-UVL
Resistor:
500
24
VDC
1
I ++++++
Ω −
– +
I2I
Watt
3
¼
4
I
I
5
––
4–20mA
6
I
1 8
0
O=ohm
Senso
r
+
O=ohm
Figure 11: Externally Powered Analog Input
LX Series Unit Ventilator Controller User's Guide 21

Sensors and Switches

The following sensors and switches can be connected to the Unit Ventilator Controller. See Table 3 for the sensor and switches preferred SNVT types.

Auxiliary Alarm Input

This input is used to relay an alarm from an external device onto the building network.

Bypass Contact Input

If the UVC is in unoccupied or standby mode, you can use switch closure on the bypass contact input to cause the controller to enter occupied mode for the time period time set as the bypass time.

CO2 Level Input

Use this input to monitor the CO2 concentration. The CO2 concentration can be used for Demand Control Ventilation (DCV) and to set the minimum damper
position during heating or cooling operations. If you do not want to use the CO2 concentration input, the minimum damper
position can be set in a fixed position, or as a fixed percentage of fresh air intake. You can find the fresh air intake percentage by a calculation of the return air, outdoor air, and mixed air temperatures.

Discharge Temperature Input

Use the discharge temperature input to maintain the discharge air temperature between the minimum and maximum discharge air temperature.
The discharge temperature setpoint is determined by a linear equation between the minimum and maximum discharge air temperature and the terminal load. When there is a high heating demand, the discharge temperature setpoint moves to its maximum temperature. Conversely, for a high cooling demand, the discharge temperature setpoint moves to its minimum temperature. The discharge temperature setpoint can be viewed in the nvoDischargSetPt.

Economizer Enable Input

Select this input to allow switch closure to enable the economizer . The economizer position can then be controlled in several different ways. See the Ventilation section.

Emergency Contact Input

Use switch closure on this input to cause the UVC to begin emergency operation. See the Emergency Operation

Fan Speed Selector Input

section.
Fan speed selector gives the Unit Ventilator Controller the ability to select up to three different fan speeds.
LX Series Unit Ventilator Controller User's Guide22

Fan State Input

The fan state input detects whether one of the three fan speeds is ON or OFF . If the fan state input does not correspond with one of the fan outputs for a time period known as the alarm delay, then an alarm becomes active. If the fan state input is OFF, while one of the fan outputs is ON, then equipment requiring air circulation remains OFF or does not modulate.
Note: All outputs except for the fan are disabled when the fan state is OFF.

Mixed Air Temperature Input

The mixed air temperature can be monitored by an alarm, thereby provide early warning of any malfunction.
Without mixed air and discharge air temperatures, the outside air damper cannot exceed the minimum position as determined by the Fresh Air Minimum Input Damper Position on the General Settings screen of the LX-UVL configuration wizard.
See the Return Air Temperature Input section for more information.

Mode Selector

Mode Selector enables selection of different modes of operation by means of an analog signal, such as resistance, voltage, or current input.
The modes of operation available for selection from this input are auto, heat, cool, fan only, and OFF. Table 2 describes the modes of operation.
Table 2: Modes of Operation
Mode of Operation
Auto Operates according to its setpoints and scheduled occupancy states; this means
Heat Operates according to the heating setpoints in heating mode only. The heating
Cool Operates accordin g to the cooling setpoints in cooling mode only. The cooling
Fan Only Configures the fan ON during the scheduled occupied state. Heating and cooling is
OFF Disables the control loop to OFF. All outputs are in the OFF state.
Description
that the Unit Ventilator Controller controls heating, cooling, duct pressure, and the fresh air damper, according to the setpoints and the configuration properties you enter. The Unit Ventilator Controller switches between unoccupied, occupied, standby , and bypass modes according to its schedule, and between the occupancy and bypass contacts if these contacts are present.
setpoint may change as the controller switches scheduled states. Cooling mode is unavailable. The fan is ON when heating is ON; the fan is OFF at other times unless configured as ON during occupied periods.
setpoints may change as the controller switches scheduled states. Heating mode is unavailable. The fan is ON when cooling is ON; the fan is OFF at other times unless configured as ON during occupied periods.
not available. Fan configuration is found on the Fan-Valve screen of the Unit Ventilator Controller configuration wizard.
LX Series Unit Ventilator Controller User's Guide 23

Occupancy Input

Use the switch closure on the occupancy input to set the Unit Ventilator Controller to occupied mode. The UVC exits occupied mode when the switch is opened. Unless the controller is in bypass mode, the occupied contact does not function if the network variables nviOccCmd and nviOccManCmd are set to unoccupied.

Outdoor Enthalpy Input

Use outdoor air enthalpy to determine if free cooling is permitted. The Ventilator Unit Controller also accepts input directly from an outdoor enthalpy sensor.

Outdoor Humidity Input

You can use outdoor humidity and temperature to calculate the outdoor enthalpy. Outdoor enthalpy can be used to determine if free cooling is permitted.

Outdoor Temperature Input

If outdoor humidity is available, use outdoor temperature to calculate outdoor enthalpy and Optimum Start times. Outdoor temperature or outdoor enthalpy is used to determine if free cooling is permitted. See the Optimum Start and Ventilation sections for more information.

Return Air Temperature Input

The return air temperature is used to prevent the coils from freezing due to cold bypass air. See the General Settings Configuration section.
Position the return air temperature sensor either before or after the bypass damper. Indicate the position of the return air temperature sensor in the General Settings tab of the Ventilation Controller configuration wizard.
When the return air temperature sensor is positioned before the bypass damper, return air temperature can be used instead of the space temperature. To do this, the fan must be ON and the space temperature must be unavailable.
When the return air temperature sensor is positioned after the bypass damper, use the following temperatures to calculate the required amount of intake air:
mixed air temperature
outdoor air temperature
return air temperature Return air temperature can be monitored by an alarm. See the General Settings
Configuration section for more information.

Setpoint Offset Input

This input provides a means of varying the setpoint during occupied and standby modes. The values from this input are added to the pair of active setpoints. See the Calculating the Space Temperature Setpoint section.
LX Series Unit Ventilator Controller User's Guide24

Space Enthalpy Input

Use the space enthalpy input value and the outdoor space enthalpy to enable or disable free cooling. The Rooftop Unit Controller also accepts input directly from a space enthalpy sensor.

Space Humidity Input

Use the space humidity sensor to provide the UVC with the space relative humidity. Relative humidity can be used as an input to the humidity control PID loop.
The UVC can calculate space enthalpy when provided with relative humidity and temperature. Space enthalpy can be compared to outside enthalpy to enable or disable free cooling.

Space Temperature Input

The UVC uses the space temperature to control heating or cooling operations. One of the following inputs must be present for the controller to work:
space temperature
nviSlave The space temperature sensor can be a 10k ohm thermistor or provide a voltage or
current input to the board.

Water Temperature Input

The Unit Ventilator Controller provides heating or cooling through a single two-pipe system with a heating or cooling valve. If this system is used, the device must know the state, either hot or cold, of the available water. When the hardware water temperature input is used, the Unit Ventilator Controller determines if the water is hot or cold enough for heating or cooling.
The network inputs nviHotW ater and nviWaterT emp are available for receiving the water state or temperature. If nviHotWater state and value are zero, then the UVC functions as if the water is cold. If nviHotWater state and value are not zero, then the controller functions as if the water is hot. If the water temperature is colder then the space temperature, the water is considered cold; if water temperature is higher than the space temperature, the water is considered hot. Both inputs have priority over the hardware input; however, if both values are received, nviHotWater has priority over the nviWaterTemp.
LX Series Unit Ventilator Controller User's Guide 25

Window Contact Input

If the Unit Ventilator Controller is in occupied, bypass, or standby mode, and the ventilator is in operation (meaning that one of the fan speeds is ON), then a switch closure on the window contact input causes the UVC to enter unoccupied mode. All outputs are turned OFF until a demand from the unoccupied cooling and heating space temperature setpoints arrives and commands the unit into heating or cooling.
Table 3: Sensor and Switch Preferred SNVT Type
Sensor or Switch Preferred SNVT Type
Auxiliary Alarm Input SNVT_amp
Bypass Contact Input SNVT_lev_disc
CO
Level Input SNVT_ppm
2
Discharge Temperature Input SNVT_temp
Emergency Contact In put SNVT_lev_disc
Fan Speed Selector Input SNVT_lev_disc
Fan State Input SNVT_amp
Mixed Air Temperature Input SNVT_temp
Mode Selector SNVT_hvac_mode Occupancy Input SNVT_lev_disc
Outdoor Enthalpy Input SNVT_enthalpy Outdoor Humidity Input SNVT_percent Outdoor Temperature Input SNVT_temp
Return Air Temperature Input SNVT_temp
Setpoint Offset Input SNVT_temp
Space Enthalpy Input SNVT_enthalpy Space Humidity Input SNVT_lev_percent Space Temperature Input SNVT_temp
Water Temperature Input SNVT_temp
Window Contact Input SNVT_lev_disc
SNVT_amp_ac SNVT_amp_f SNVT_lev_disc
SNVT_lev_occupancy
SNVT_temp_p
SNVT_lev_occupancy
SNVT_lev_occupancy
SNVT_amp_ac SNVT_amp_f
SNVT_temp_f
SNVT_lev_occupancy
SNVT_temp_p
SNVT_temp_f
SNVT_temp_diff
SNVT_temp_f
SNVT_temp_f
SNVT_switch
SNVT_lev_percent SNVT_switch SNVT_temp_f SNVT_temp_p
SNVT_switch
SNVT_temp_f
SNVT_switch
SNVT_switch
SNVT_lev_percent SNVT_switch SNVT_lev_disc
SNVT_temp_p
SNVT_switch
SNVT_temp_f
SNVT_temp_p
SNVT_temp_f SNVT_temp_p
SNVT_temp_p
SNVT_temp_p
SNVT_occupancy
LX Series Unit Ventilator Controller User's Guide26

Outputs

The Unit Ventilator Controller has five digital outputs (DO1, DO2, DO3, DO4, and DO5), and two analog outputs (AO1 and AO2). Descriptions of these outputs follow.

Analog Output

The Unit Ventilator Controller analog outputs are versatile and can be configured as analog, digital, or PWM outputs. When the analog output is configured with the wizard as a digital output, it supplies 60 mA at 12 VDC. This ability is useful when driving relays external to the board. See Figure 12.
The characteristics of the analog outputs are described in Table 4.

Analog Output Protection

Analog Outputs are protected by an auto-reset fuse with a maximum current capacity defined by the following two points:
100 mA at 68°F (20°C)
0 mA at 140°F (60°C)
Connect a diode to the relay terminal.
(Ir = 1A at Vr=25 V)
K
12Vdc Relay
Max load 200 Ohm
180
DO1 C DO2 C DO3 C DO4 C DO5 C AO1 AO2
Figure 12: Analog Output Driving an External Relay
Table 4: Tri-Mode Analog Output Characteristics
Mode Maximum Current and Voltage Voltage Range
Digital 60 mA at 12 VDC (200 ohm load) 0 – 12 VDC Analog 50 mA at 10 VDC 0 – 10 VDC (linear) PWM 50 mA at 10 VDC 0 or 10 VDC

Digital Outputs

The digital outputs of the UVC use triacs to switch the output signal. Each digital output is capable of conducting 1 ampere.
The digital outputs work as a switch to control the current (Figure 13). The current source is separate from the transformers supplying the current for the UVC controller.
LX Series Unit Ventilator Controller User's Guide 27
The UVC uses a half-wave power supply. Any other half-wave power supply that connects with the controller through the outputs or inputs must be in phase with the power supply of the controller. Do not share grounds between a full-wave and a half-wave power supply.
Power Supply
24 VAC
LC
Max. Current 1A at 24 VAC
DO1 C DO2 C DO3 C DO4 C DO5 C AO1 AO2
Figure 13: Unit Ventilator Controller Digital Outputs
You can reverse each of the digital output’s scales by using the Unit Ventilation configuration wizard. Normally , ON is a 100% output; when the output is reversed, ON is a 0% output.
You can override all digital outputs to a previously set value using the UVC object override command. The override values are set during the configuration process. The configuration wizard provides a menu for issuing object commands, including the override command. See the Object Manage section for more information.
LX Series Unit Ventilator Controller User's Guide28

Staged Outputs

You can organize the outputs into stages when there are multiple heating or cooling outputs. Stages turn on sequentially one after the other. The heating or cooling stages (n) must be open for the period of time specified in the minimum heating period before heating or cooling stage (n+1) can turn on. For example, heating stage 1 must be open for the minimum heating period before duct heating stage 2 turns on. See Figure 14.
Heating commanded to 100% ON at this time.
Stage 1
turns ON.
100%
Stage 1 ON Stage 1 ON
Heating
Effort
Time
Minimum
heating
period
Stage 2
turns ON.
Stage 2 ON
Minimum
heating
period
Stage 3
turns ON.
Stage 3 ON Stage 2 ON Stage 1 ON
Minimum
heating
period
Figure 14: Staged Outputs

Output Selections

There are 31 possible output selections. Several output selections are dependent upon other output selections. For example, cooling 1–4 can be blocked depending on the setting of the reversing valve.

Fan Speed 1–3

This output provides digital fan speed control. See the Fan Operation section for more information on fan speed operation.

Heating Outputs 1–4

Heating outputs one to four are staged outputs that are turned ON after heating valve outputs, if any, are 100% open.

Cooling Outputs 1–4

Cooling outputs 1-4 are staged outputs, which are turned ON after cooling valve outputs, if any, are 100% open.

Reversing Valve

The reversing valve has two states. If the reversing valve is defined and is ON, then cooling outputs 1–3 act as heating outputs.
LX Series Unit Ventilator Controller User's Guide 29

Humidifier and Dehumidifier Outputs

Both digital and analog humidifier and dehumidifier outputs are available. The fan must be ON to enable the humidifier and dehumidifier outputs.
The UVC uses the assigned outputs to maintain the humidity at a level defined by the humidity setpoint on the general settings menu. A delay occurs when switching between humidification and dehumidification. You can enter the time period for the delay on the general settings screen. The Unit Ventilator Controller also offers the ability to dehumidify with the cooling coil. See the Humidity Control section for more information.

Minimum Fresh Air Enable (MIN_FRESH_AIR_ENABLE)

This output enables the fresh air damper to move to the minimum position. Minimum fresh air is enabled when the occupancy state is OC_OCCUPIED, or OC_BYPASS and the fan is ON.

Economizer Enable

When this output is ON, the economizer can be used for free cooling. This output is enabled when the outdoor air temperature is below the economizer maximum outdoor temperature.

Heat Valve ON-OFF

This output operates the digital heating valve.

Cool Valve ON-OFF

This output operates the digital cooling valve.

Heat Cool Valve ON-OFF

This output operates the digital heating-cooling valve according to the water temperature.

Heat Valve Open or Close

These outputs operate heating floating valves.

Cooling Valve Open or Close

These outputs operate cooling floating valves.

Heat Cool Valve Open or Close

These outputs operate heating-cooling floating valves according to the water temperature.

Fan Speed Modulate (FAN_SPEED_MOD)

Provides a variable speed fan control output.
LX Series Unit Ventilator Controller User's Guide30
Loading...
+ 77 hidden pages