Johnson Controls LP-NRM552-000C, LP-NRM652-000C, LP-NRM503-000C, LP-NRM502-000C, LP-NRM511-000C Installation Manual

...
Page 1
Network Room Modules
Installation Guide
Part No. 24-85638-1214 , Rev. E
Issue Date June 14, 2010
Network Room Modules
Page 2
120
25 (0.98)
Display
80 (3.15)
35
(1)
(2)
Setpoint Adjustment
(3)
°C / °F B u tto n
(4)
Fan Button for fan speed adjustme nt
(5)
(1.38)
LCD Displ ay
Dial for Temperature
with back-light
(4.72)
Service tool socket
(6)
in Celsius and
Fahrenheit units
Figure 1: Dimensions, mm (in.)
I
Page 3
Figure 2: Removing the Cover from the Base
II
Page 4
31 (1.22 )
2 x Ø 4.2 (0.16)
66 (2.60)66 (2.60)
60 (2.3 6)
4,3 (0.17 )
4,3 (0.17) 4,3 (0.17)
33
33
38
5.7 (0.22)
34 (1.34)
67 (2.64)
60 (2.36 )
67 (2.64)
34 (1.34)
5.7 (0.22)
(1.30)
29 (1.14 )
(1.30)
(1.50)
Figure 3: Wall Mounting Base Dimensions, mm (in.)
III
Page 5
Figure 4: Dual-Switch DIP Switch Block
Figure 5: Terminal Block Connection
IV
Page 6
Figure 6: Service Port (4-pin) for LP-NRM0xx-000C Series
Figure 7: Port (6-pin Modular Jack) for LP-NRM5xx-000C and
LP-NRM6xx-000C Series
V
Page 7
Network Room Modules
Installation Guide
READ THIS INSTRUCTION SHEET AND THE SAFETY WARNINGS
CAREFULLY BEFORE INSTALLING, AND SAVE IT FOR FUTURE USE
Part No. 24-85638-1214, Rev. E
Issue Date June 14, 2010
General Features
Network Room Modules (NRMs) are designed for use with Johnson Controls® Facility Explorer FX06, FX07, FX14, and FXVMA Field Controllers.
The Liquid Crystal Display (LCD), alo ng with a dial and push button(s) on the front of the NRM, allow the occupant to view and adjust the setpoint temperature in the controller, and to manually override the speed of the fan in the controlled equipment.
The NRM connects to the Local Link Display Bus of the FX field controller. Configure the NRM with the FX Builder programming tool, which is part of the FX Tools Pro Software package.
The LP-NRM0xx-000C Series NRM requires a 15 to 24 VAC/VDC power supply from the FX Control ler or from an e xternal p ower so urce, and has a 4-pin service port (Figure 6).
The LP-NRM5xx-000C and LP-NRM6xx-000C Series NRMs require a 15 VDC power supply from the FX Controller or from an external power source, and have a 6-pin Modular Jack service port (Figure 6).
North American Emissions Compliance
United States
This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interferen ce when this equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference, in which case the user will be required to correct the interference at his/her own expense.
1Network Room Modules Installation Guide
Page 8
Canada
This Class (A) digital app aratus meet s all the r equirements of the Canadian Interference-Causing Equipment Regulations.
Cet appareil numérique de la Classe (A) respecte toutes les exigences du Règlement sur le matériel brouilleur du Canada.
Tools
Flat-head screwdrivers, 3 mm and 5 mm (1/8 to 5/32 in.)
Drill, bits, and appropriate 4 mm (3/16 in.) screws and plugs
Pointed tool (available from Johnson Controls, Ordering Code TM-9100-8900 in Europe, or T-4000-119 in North America)
Figure 1: Dimensions, mm (in.)
(1) LCD Display with backlight (2) Dial for temperature set point adjustment (3) °C/°F Button
(feature available in specific models, see Ordering Codes)
(4) Fan button for fan speed adjustment
(feature available in specific models, see Ordering Codes)
(5) Service port (6) Display in Celsius and Fahrenheit units
Mounting
The NRM mounts directly on a wal l surface in the roo m you want to control . Choose a location for the NRM while considering th e following information:
Place the room module where the o ccupant can easily read the LCD an d use the controls.
Place the module where the ambien t temperature is represe ntative of the general room conditions if you want to use the built- i n temperature sensor to measure space temperature. For example, there should be a sufficient amount of ai r circulation.
Avoid cold or warm air drafts, radiant heat, and direct sunlight.
Place some insulating material in the wiring access hole or conduit to prevent the introduction of air fro m outside the room.
2 Network Room Modules Installation Guide
Page 9
Figure 2: Removing the Cover from the Base
1. Remove the retaining screw (if inserted) from the top of the module
enclosure.
2. Remove the module cover from the base by inserting a pointed tool into the narrow slot at the center top of the cover. While pressing down gently, pry the base away from the cover. As the two parts separate, remove the tool and continue to pull the cover away from the base until the cover is free.
Figure 3: Wall Mounting Base Dimensions, mm (in.)
1. Hold the module base on the wall to cover the electrical outlet and mark
the position of at least two holes. Drill the holes and insert the plastic plugs (wall anchors) into the holes.
2. Mount the module base on the wal l and secure with at least two screws.
For other mounting options, see Ordering Codes and refer to the corresponding installation sheets.
Addressing
Figure 4: Dual-Switch DIP Switch Block
NRM models which are not addressable have a fixed physical address of
191. For those models which are addressable, the NRM's address must be
set using its dual-switch DIP switch block, locat ed on the printed wiring board. See Table 1 for details on addressing the NRM.
Note: You must cycle power to the NRM (disconnect/reconnect the NRM
or cycle power to the field controller) for the address chang e to t ake effect.
Table 1: NRM Addressing
DIP Switch Address
191 OFF OFF 192 OFF ON 193 ON OFF 194 ON ON
Switch 2 Switch 1
3Network Room Modules Installation Guide
Page 10
Wiring
CAUTION: Risk of Electric Shock.
Disconnect power supply before making electrical connections to avoid electric shock.
IMPORTANT: The Complementary Metal Oxide Semiconductor (CMOS) circuits in the controller are sensitive to static electr icity. Take suitable precautions.
IMPORTANT: The LP-NRM0xx-000C Series NRM accepts VAC or VDC power. The LP-NRM5xx-000C and LP-NRM6xx-000C Series accept VDC power only.
IMPORTANT: Use this NRM Room Command Module only as an
operating control. Where failure or malfunction of the NRM could lead to personal injury or property damage to the contro lled equipment or other property, additional precautions must be designed into the control system. I ncorporate and maintain other devices, such as supervisory or alarm systems or safety or limit controls, intended to warn of or protect agai nst failure or malfunction of the NRM.
IMPORTANT: The installation of electrical wiring must conform to local codes and should be carri ed out by authorized per sonnel only. Users should ensure that all Johnson Controls products are used safely and without risk to health or property.
4 Network Room Modules Installation Guide
Page 11
Figure 5: Terminal Block Connection
Terminations are made on the terminal block in the base of the module, which is accessible after removing the cover from the base.
The screw terminals accept up to 1.5 mm
Keep low-voltage wiring separated from power line voltage wiring.
Do not run wiring close to transformers or high frequency generating equipment.
Complete and verify all wiring connections before applying power to the module.
Use screw terminals RT+, RT-, and COM to connect to the FX controller display (local ink) bus terminals (LL+, LL-, and COM, respectively).
Note: RT+ and RT- are polarity sensitive and are not interchangeable.
If shielded cable is used, connect the shield to a clean earth ground at one end only.
Connect the power supply voltage to the terminals as marked:
- 15-24 VAC/VDC and COM (common) for the LP-NRM0xx-000C Series NRM
- 15 VDC and COM (common) for the LP-NRM5xx-000C and LP-NRM6xx-000C Series NRMs
2
(16 AWG) wires.
Service Port
The service port is located on the lower edge of the module. There are two different types of service ports, depending on the NRM Series you are using:
4-Pin Service Port
See Figure 6 for service port wiring for LP-NRM0xx-000C Series NRM. Use the 4-pin service port to download app lications into the connected FX
Controller using the Programming Key (pass-through feature). The NRM supplies power to the Programming Key.
6-Pin Modular Jack Service Port
See Figure 7 for service port wiring for LP-NRM5xx-000C and LP-NRM6xx-000C Series NRMs.
Use the 6-pin Modular Jack service p ort to connect a Medium User Interface (MUI) for monitoring and adjusting parameters in the control application of the connected FX controlle r. The NRM supplies power to the MUI from the FX controller through the 6-p i n Modular Jack service port.
5Network Room Modules Installation Guide
Page 12
Ordering Codes
Table 2: Network Room Modules (Available in Europe)
Product Code Features/Options
Size (mm)
LP-NRM001-000C 80 x 80 Program LP-NRM002-000C Yes Yes No No No LP-NRM003-000C Yes Yes Yes No No LP-NRM511-000C MUINoNoNoNoYes LP-NRM502-000C Yes Yes No No No LP-NRM503-000C Yes Yes Yes No No
Service Port Type
Key
LCD Display
No No No No No
Temperature
Adjust Dial
Fan Speed
Selector Button
°F/°C
Addressable
Table 3: Network Room Modules (Available in North America)
Product Code Features/Options
Size, mm (inch)
LP-NRM511-000C 80 x 80 LP-NRM552-000C Yes Yes No Yes No LP-NRM553-000C Yes Yes Yes Yes No
mm (3.15 x
3.15 in.)
Service Port Type
MUINoNoNoNoYes
LCD Display
Temperature
Adjust Dial
Fan Speed
Selector Button
°F/°C
Addressable
LP-NRM611-000C 120 x 80 LP-NRM652-000C Yes Yes No Yes No LP-NRM653-000C Yes Yes Yes Yes No
6 Network Room Modules Installation Guide
mm (4.72 x
3.15 in.)
MUINoNoNoNoYes
Page 13
Table 4: NRM Mounting Kits and Accessories
Ordering Codes Description
TM-1100-8931 Plastic Base for Surface Mounting - White TM-9100-8941-W Recessed Wall Box Mounting Kit - White TM-9100-8951-W Panel Mounting Kit - White NS-WALLPLATE-0 Wall plate kit used to mount an 80 x 80 mm ( 3.15 x 3.15 in.)
NRM onto a 2 x 4 in. wall box.
TM-9100-8900 Special Tool (to open module) - Europe T-4000-119 Special Tool (to open module) - North America LP-KIT100-000C Programming Key
Table 5: Recommended FX Controller and MUI/NRM
Configuration Limits
FX Controller Type MUI/NRM Configuration Limits
FX06 One MUI and one NRM FX06 Rev A One MUI and one NRM FX07 One MUI and one NRM FX07 Rev A One MUI and one NRM FX14 One MUI and two NRMs FX14 Rev A One MUI and two NRMs FX14 Rev B One MUI and two NRMs FX15 Universal NRM is not supported FX15 NRM is not supported FX15 Rev A NRM is not supported FX16 NRM is not supported FX16 Rev A NRM is not supported FX16 Rev B NRM is not supported FXVMA One MUI and one NRM FXVMA Rev A One MUI and one NRM
1. One addressable NRM is required.
1 1 1
7Network Room Modules Installation Guide
Page 14
Technical Specific ations
NRM Technical Specifications (Part 1 of 2)
Product Network Room Module Power Requirements
LP-NRM0xx-000C Series
14.3 to 27.6 VDC at 500 mW maximum or 24 VAC ±15%, 50/60 Hz, at 1 VA maximum
Class 2 or Safety Extra-Low Voltage (SELV)
Power Requirements LP-NRM5xx-000C and LP-NRM6xx-000C
9.8 to 16.5 VDC (15 VDC nominal) at 35 mA maximum
Class 2 or SELV
Series Ambient Operating
Conditions
0 to 50°C (32 to 122°F) 10 to 90% RH noncondensing (and max. 30°C [86°F] dew point)
Ambient Storage Conditions
-20 to 70°C (0 to 160°F) 5 to 95% RH noncondensing (and max. 30°C [86°F] dew point)
Terminations Terminal block with screw terminals in base for
1.5 mm
2
/ 16 AWG (max.) wires.
Recommended tightening torque 0.5 Nm.
Temperature Sensor R TD Platinum element, PTC, 1k ohm at 0°C (32°F),
Pt1000 Class A, DIN EN 60751 Suitable for residential and commercial office environments only.
Display and Controls LCD display with three digits and seven symbols.
Dial and push button(s).
Communications Interface
N2 Open Protocol communication Service bus RS485 at 9600
baud
Service Port Model LP-NRM0xx:
4-pin service port for FX Programming Key with 9 VDC power
Models LP-NRM5xx and LP-NRM6xx: 6-pin Modular Jack service port for MUI with 15 VDC power
Mounting Direct surface mount.
Plastic base for surface mount with wiring conduits. Recessed wall box and panel mounting kits available on request (see
Dimensions (H x W x D)
8 Network Room Modules Installation Guide
80 x 80 x 35 mm (3.15 x 3.15 x 1.4 in.) 120 x 80 x 35 mm (4.72 x 3.15 x 1.4 in.)
Ordering Codes).
Page 15
NRM Technical Specifications (Part 2 of 2)
Housing Material ABS + polycarbonate, self-extinguishing UL94-HB Housing Protection IP30 (EN60529) Shipping Weight 0.2 kg (7 oz), 80 x 80 mm (3.15 x 3.15 in.) housing
or 0.25 kg (9 oz), 120 x 80 mm (4.72 x 3.15 in.) housing
Compatible FX Controllers and Firmware Versions
FX06, V 2.32 and higher FX07, V 3.01 and higher FX14, V 2.32 and higher FXVMA, all versions
Compliance Europe
CE Mark – Johnson Controls, Inc., declares that the Network Room Modules (NRMs) are in compliance with the essential requirements and other relevant provisions of the EMC Directive 2004/108/EC.
Canada
UL Listed (PAZX7), C22.2 No. 205, Signal Equipment Industry Canada, ICES-003
United States
UL Listed (PAZX), UL 916, Energy Management Equipment FCC compliant to CFR 47, Part 15, Subpart B, Class A
Agency Listings UL916 and CUL Listed
This document is subject to change without notice.
9Network Room Modules Installation Guide