Johnson Controls TPLC080B12MP12C, TPLC120C20MP12C, TPLC100C20MP12C, TPLC100C16MP12C, TPLC080C16MP12C Quick Reference Manual

...
NOTES:
1. If the furnace is equipped with NOx screens and is to be used with LP (propane) gas, the screens must be removed prior to start-up.
2. Drip leg in the gas line must be installed.
3. The furnace controls require correct polarity on the power supply and a proper ground.
4. Y & G must be connected to the control board for cooling operation.
5. External filters required on all configurations.
6. Electrical or gas entry is available on both casing sides.
7. To measure total static pressure add supply duct pressure to the return duct pressure, add pressure drop across the ‘A’ coil, and add pressure drop across the filter. Ignore negative signs on the readings.
8. Inlet gas pressure for natural gas should be 7” and for pro­pane should be 11” w.c. Nominal manifold gas pressure is
3.5” for natural gas and 10” w.c. for propane at max. input.
9. For downflow application the vent blower must be rotated 90 left or right as shown.
* Other airflows are available. see Tech guide for all CFM options.
LED INDICATOR
Slow Green Flash - Normal operation in standby mode Slow Amber Flash - Normal operation with call for cooling Two Amber Flashes - Normal operation with call for heat
Three Amber Flashes - Normal operation, burner is on at end of thermostat cycle.
Six Amber Flashes - Normal operation with call for heat pump heating.
Any Red Flash - Fault condition
Models
Airflow CFM (Bottom Return without Filters)
Minimum Wire Size awg @ 75'
One-Way
Maximum
Over Current
Protection
0.5" ESP (Nominal)*
D-A C-A B-A A-B
(T,Y,C,L)PLC060A12MP12C
600 815 1050 1340 14 15
(T,Y,C,L)PLC080B12MP12C
580 775 960 1290 14 15
(T,Y,C,L)PLC080C16MP12C
1000 1200 1395 1715 14 15
(T,Y,C,L)PLC100C16MP12C
980 1165 1345 1600 14 15
(T,Y,C,L)PLC100C20MP12C
1140 1330 1515 2110 12 20
(T,Y,C,L)PLC120C20MP12C
1200 1400 1510 1990 12 20
Models
Input Rate
Total Unit
Amps
Air Temp. Rise
Max Input °F
Air Temp. Rise
Min Input °F
Time For 1 ft3 Natural Gas
(1030 Btu/Ft
3
) Seconds
(On Max. Rate)
Max Min
(T,Y,C,L)PLC060A12MP12C 60,000 30,000 7.0 30-60 20-50 62 (T,Y,C,L)PLC080B12MP12C 80,000 40,000 7.5 40-70 20-50 46 (T,Y,C,L)PLC080C16MP12C 80,000 40,000 10.0 35-65 20-50 46 (T,Y,C,L)PLC100C16MP12C 100,000 50,000 10.0 35-65 20-50 37 (T,Y,C,L)PLC100C20MP12C 100,000 50,000 12.0 35-65 20-50 37 (T,Y,C,L)PLC120C20MP12C 120,000 60,000 12.0 45-75 25-55 30
This document does not replace the installation instructions, which must be referred to for detailed information.
CLEARANCES
* 24" clearance in front and 18" on side recommended for
service access.
All furnaces approved for alcove and attic installation.
DIMENSIONS
FRONT
A
SUPPLY END
RETURN END
LEFT SIDE
RIGHT SIDE
33”
Clips can be flipped into the up position for coil cabinet or plenum attachment
A-COIL
Follow allnational, local codes and standardsin addition to thisdocument. The installation must complywith regulations of theserving gas supplier, localbuilding, heating, plumbing, and other codes. In absenceof local codes, the installation must comply with the national codes andall authoritieshaving jurisdiction.
28.5”
Gas Pipe
Entry
Thermostat Wiring
14”
1”
1.5”
23”
Electrical Entry
.5”
.5”
B
24.25”
4” Diameter Vent Connection Outlet
24.38”
20”
.5”
B
.5”
Electrical Entry
Vent
Connection
Outlet
29.5”
(For Cladded door add
appoximately an additional .75”)
Application Upflow Downflow Horizontal
Top 1" 0" 0"
B-Vent 1" 1" 1"
Rear 0" 0" 0" Side 0" 0" 1"
Front* 0" 0" 0"
Floor Combustible
Combustible
1
1. For combustible floors only when used with special sub-base.
Combustible
Closet Yes Yes Yes
Line Contact No No Yes
Cabinet Size A (in) B (in)
All 'A' Cabinet Furnaces 14-1/2" 13-3/8" All 'B' Cabinet Furnaces 17-1/2" 16-3/8" All 'C' Cabinet Furnaces 21" 19-7/8"
QUICK REFERENCE GUIDE
80% MODULATING ECM MULTI-POSITION RESIDENTAL GAS FURNACES (33” TALL)
Subject to change without notice. Published in U.S.A. 535679-URG-A-0909 Copyright © 2009 by Johnson Controls, Inc. All rights reserved. Supersedes: Nothing
Johnson Controls Unitary Products
5005 York Drive
Norman, OK 73069
*535679*
Furnace is multi-position and may be installed in any of the configurations shown.
MOST COMMON INSTALLATION CONFIGURATIONS (MORE OPTIONS AVAILABLE WHICH IS COVERED IN THE INSTALLATION MANUAL)WITH INDUCER ROTATION,
AIRFLOW
AIRFLOW
HORIZONTAL LEFT
UPFLOW
DOWNFLOW
HORIZONTAL RIGHT
Must be installed on combustible floor base or coil cabinet to prevent blockage of combustible air openings
Vent blower may also be rotated 90° left or right to vent through casing top.
Vent blower may also be rotated 90° left or right to vent through casing top.
Inducer blower may be rotated 90° either way to vent through casing side, as shown below.
These are Category I units and the vent system must be installed in accordance with latest edition of the National Fuel Gas Code, Z223.1/NFPA 54, or in Canada, CSA B149.1.
These furnaces should be vented with type B vent pipe. No single - wall vent pipe or vent connectors are allowed. This furnace be vented into a masonry chimney.
only
should not
These are modulating furnaces which vary the gas input between 50% and 100% of full rate. To make it easier to check that the furnace is not overfired or underfired, put the furnace in TEST MODE and clock the gas meter. See Installation Booklet for details of TEST MODE.
AIRFLOW
AIRFLOW
Optional - Vent blower may also be rotated 90° left or right to vent through casing side.
Combustion Air Entry
Bottom blockoff plate - Remove for bottom return applications
Junction Box (May be moved to other side)
Vent blower must be rotated 90° left or right to vent through casing side.
For downflow applications, the gas valve must be rotated upwards as shown
Loading...