Johnson Controls LN Series, LN-VAVCF-12 Installation Instructions Manual

Page 1
LN Series Variable Air Volume (VAV) LN-VAVCF-12 Controller
Installation Instructions
LN-VAVCF-12

Application

The LN Series Variable Air Volume (VAV) LN-VAVCF-12 controller is designed to control various types of variable air volume equipment.
The controller is based on L peer-to-peer communication between controllers and is
ONMARK® network certified.
using the LN Series Variable Air Volume Preloaded Application. For more information regarding configuration using the preloaded application, refer to the LN Series Variable Air Volume (VAV) Preloaded Application User’s Guide (LIT-12011830).

North American Emissions Compliance

United States

ONWORKS® technology for
Code No. LIT-12011802
Issued April 24, 2014
Supersedes January 30, 2013

Installation

For proper installation and subsequent opera tion of the LN-VAVCF-12 controller, follow these recommendations:
Inspect the controller for shipping damage. Do no inst
all damaged devices.
Allow for proper clearance of device casing, wirin ter
minals, and service pin for easy acce rdware configuration, and maintena
ha
The controllers are designed to operate under the following conditions:
Ambient temperature between 32 to 122°F
(0 to 50°C)
Relative humidity from 0 to 90
ncondensing
no
ss,
nce.
%,
g
t
Complianc
This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions:
1. This device may not cause harmful interference an
2. This device must accept any interference received, including interference that may caus un
Warning (Part 15.21)
Changes or modifications not expressly approved by the party responsible for compliance could void the user’s authority to operate the equipment.
e Statement (Part 15.19)
d
desired operation.

Canada

Industry Canada Statement
The term IC before the certification/registration number only signifies that the Industry Canada technical specifications were met.
Le terme « IC » précédant le numéro d'accréditation/ inscription signifie simplement que le produit est conforme aux spécifications techniques d'Industry Canada.
Ensure proper ventilation of devices and eas where corroding, deteriorating, or expl
ar
rs, fumes, or gasses may be present.
vapo
Record the Neuron® ID located on the box and on
,
e
the side of the controller. You need it fo commissioning the device.
IMPORTANT: Work in a static-free area. Discharge any static electricity you may have accumulated. Discharge static electricity by touching a known, securely grounded object. Do not handle the controller without proper protection against static discharge. Use a wrist strap when handling the controller. Secure the wrist strap clamp to earth ground.
avoid
osive
r
LN Series Variable Air Volume (VAV) LN-VAVCF-12 Controller Installation Instructions 1
Page 2

Dimensions

Fig: ln_vavcf_12_dim ensions
Figure 1: LN-VAVCF-12 Dimensions, mm (in.)
Figure 2: LN-VAVCF-12 Components
Fig: ln_vavcf_12_components
LN Series Variable Air Volume (VAV) LN-VAVCF-12 Controller Installation Instructions2
Page 3

Mounting

Figure 3: Mounting a LN-VAVCF-12 on a Damper
Shaft
Figure 4: Damper Shaft Markings
This mounting procedure pertains to the LN-VAV CF-12 controller with built-in actuators. Units with a damper actuator only have one screw.
The controller is specially designed for mounting onto an air duct or within a panel using the integrated mounting collar and the provided screw. This mounting arrangement opposes the torque applied to the damper shaft.
3. Locate the damper position by the marking
typically found on the end of the damper shaft (Figure 4).
1. Place the controller into position on the damp e r shaft so wiring connections are easily accessible.
Note: The controller must fit onto the damper shaft so the base of the controller is parallel to the VAV box and perpendicular to the damper shaft. If the damper shaft has an external bushing that prevents the controller from being mounted flush to the side of the VAV box, use a spacer of the same thickness to compensate and to ensure the controller is at a right-angle to the shaft to prevent binding.
IMPORTANT: Protect the controller from dripping water, condensation, and other moisture. Water or moisture could result in an electrical short, which may damage or affect the operation of th e co ntro ller.
2. Using a power screwdriver , attach the controller to the VAV box with the provided screw through the controller’s mounting bracket. You may also mark the screw position on the VAV box, drill a hole, then attach the controller to the VAV box.
IMPORTANT: Do not overtighten the screws. Overtightening may strip the threads and will void the warranty.
4. Determine the direction required to close the damper Clockwise (CW) or Counterclockwise (CCW). Turn the damper shaft with a pair of pliers to fully close the damper for 90° VAV boxes or fully open the damper for 45° or 60° VAV boxes.
5. Press and hold down the Actuator Clutch for Manual Adjustment button and turn the controller’s shaft coupler until it touches the mechanical end-stop to either the fully closed position (90° VAV boxes) or the fully open position (45° or 60° VAV boxes). See Figure 2.
6. Position mechanical stops: a. For 90° VAV boxes: if the d amper closes CCW,
turn the coupler to the CCW mechanical stop limit. If the damper closes CW, tur n the coupler to the CW mechanical stop limit. The open mechanical stop is factory preset for 90° VAV boxes.
b. For 45° or 60° VAV boxes: the mechanical
stops must be set for both the fully closed and fully open damper positions. By installing the controller at the fully open position, the controller provides the open mechanical stop for 45° and 60° VAV boxes. The closed damper seal provides the fully closed stop.
7. Tighten the U-Bolt clamp on to the damper shaft using an 8 mm (5/16 in.) wrench or socket. Tighten the bolts between 11 and 15 N·m (100 and 130 lb·in).
8. Test for free damper shaft movement: Press and hold down the Actuator Clutch for Manual Adjustment button and manually turn the actuator coupling to ensure the actuator can rotate from fully closed to fully opened positions without binding.
9. Connect the VAV box flow sensor tubing to the controller’s Pressure Sensor Inputs. Create a condensation trap in the pneumatic tubing by forming it into a vertical loop.
LN Series Variable Air Volume (VAV) LN-VAVCF-12 Controller Installation Instructions 3
Page 4
10. Finalize the installation by rotating the damper to
!
Figure 5: T ypical Power and Net work Connections with an LN Series Communicating Sensor Input a nd
Floating Actuator Output
the full open position.
CAUTION: Risk of Property Damage.
Rotate the damper to the full-open position before starting the air handler. Failure to rotate the damper to the full­open position may result in damage to the Variable Air Volume (VAV) box or ductwork when the air handler is started.
MISE EN GARDE : Risque de dégâts matériels.
Faire pivoter le registre pour le placer en position d'ouverture complète avant de démarrer l'unité de traitement d'air. Le non-respect de cette directive risque d'endommager le caisson de l'unité à volume d'air variable (VAV) ou le réseau de conduites au démarrage de l'unité de traitement d'air.

Typical VAV Application Wiring Diagram

Figure 5 shows the typical power and network connections with a floating actuator output and sensor.
LN Series Variable Air Volume (VAV) LN-VAVCF-12 Controller Installation Instructions4
Page 5

Wiring

!
Figure 6: LN-VAVCF-12 Jumper Locations
Digital Outputs (DO)
Power Source
Net to Subnet Port
Settings
*
Factory-default positions
Subnet
Port
Wireless
Port
Jumpers for
DO1 & DO2
Jumpers for
DO3 & DO4
Triac Internal
Power*
Triac External
Powered
Typical locations: Quantity may vary according to controller model
Disabled*Enabled
IMPORTANT: Make all wiring connections in accordance with the National Electrical Code and all local regulations. Use copper conductors only. Do not exceed the control’s electrical rating.
CAUTION: Risk of Electric Shock.
Disconnect the power supply before making electrical connections to avoid electric shock.
MISE EN GARDE : Risque de décharge électrique.
Débrancher l'alimentation avant de réaliser tout raccordement électrique afin d'éviter tout risque de décharge électrique.

Recommendations:

Use the removable terminal connectors to make all wiring connections.
Disconnect the terminal connectors from the device for wiring.

Configuration Jumper Location and Identification

See Figure 6 for the controller’s on-site configurable jumpers.
Use a small flat screwdriver to tighten the terminal connector screws once you have inserted the wires.
Keep analog type cables (for power, voltage, current inputs, or TRIAC outputs) apart from other types of wiring to avoid any ambient noise transmission among wires; however, unswitched power wiring can be in the same conduit as the L
ONWORKS communication cable.
The board connectors accept wires or flat cables ranging from 22 to 14 AWG (0.645 to 1.630 mm diameter) per pole; however, power cables must remain between 18 and 14 A WG (1 .0 24 a nd 1.6 30 mm diameter).
The transformer powering the controller must be configured as a floating transformer. Do not ground the transformer.
Keep all wires away from high-speed data transmission cables (for example, Ethernet).
IMPORTANT: Do not connect the analog/digital inputs or common terminals to ground (only if otherwise stated).
Keep input and output wiring in conduits, trays, or close to the building frame, if possible.
For more information on wiring and powering a VAV controller that uses a L communications, refer to the L
ONWORKS network for
ONWORKS LN-Series
Network Communication and Interface Guide Technical Bulletin (LIT-12011253).

Power Wiring

Device power requirements: 24 VAC +15%, Class 2 Note: To conform to Class 2 requirements in the
United State s, use tran sformers of 100 VA at 24 VDC or less to power the controller.
For power and ground wiring, use the heaviest gauge wire based on a maximum of 14 AWG and a minimum of 18 AWG.
We recommend wiring only one controller per 24 VAC transformer.
If only one 24 VAC transformer is available, determine the maximum number of VAVs that can be supplied on a single power cable supplied by a 100 VA transformer, according to the cable’s wire gauge and the total cable length from Table 1.
Avoid installation conditions that fall outside the parameters of Table 1.
LN Series Variable Air Volume (VAV) LN-VAVCF-12 Controller Installation Instructions 5
Page 6
Figure 7: Power Wiring – AC
Figure 8: Power Wiring – DC
Ta b le 1: Maximum Number of VAV Devices on a Power Run
AWG Power Run
Total Cable Length
4
14 14 60 m (200 feet) 5 3 2 14 45 m (150 feet) 5 4 3 14 30 m (100 feet) 5 5 4 16 60 m (200 feet) 3 2 1 16 45 m (150 feet) 5 3 2 16 30 m (100 feet) 5 4 3 18 45 m (150 feet) 3 2 1 18 30 m (100 feet) 5 3 2
1. Typical VAV controller with one LN Series Communicating Sensor and actuator active. No external loads.
2. Typical VAV controller with one LN Series Communicating Sensor, 2 TRIAC loads (1.6 VA each), 1 analog output (20 mA), and actuator active.
3. Typical VAV controller with one LN Series Communicating Sensor, 4 TRIAC loads (1.6 VA each), 2 analog outputs (20 mA each), and actuator active.
4. Device terminals are not capable of accepting two 14 AWG wires (when daisy-chaining devices). Use a wire nut with a pig tail to make such a connection.
75 m (250 feet) 4 2 1
Maximum Number of Devices at 7 VA per
Device
1
Maximum Number of Devices at 10 VA per
Device
2
Maximum Number of Devices at 15 VA per
Device
3
Use an external fuse on the 24 VAC side (secondary side) of the transformer to protect all devices against power line spikes (Figure 7).
IMPORTANT: Maintain consistent polarity when connecting controllers and devices to the transformer. Connect the COM of each controller and each peripheral to the same terminal on the secondary side of the transformer.
IMPORTANT: The COM terminals of the controller are internally wired to the 24V COM terminal of the power supply. Connecting a peripheral or another controller to the same transformer without maintaining polarity between these devices will cause a short circuit. The transformer must be floating (it should not be grounded).

Input Wiring

The controller has physical connections for six inputs, which are software configurable from within the device’s Graphical Programming Interface (GPI) LN plug-in, the LN plug-in when using LN Builder, or the LN wizard when using the BSC Workbench. Each input can be configured for digital, resistive, current, or voltage signals. You must configure the input types properly in the software plug-in or wizard to ensure proper input readings.
IMPORTANT: Before connecting any input equipment to the controller, refer to the manufacturer’s installation guide.
Note: For wire length less than 75 feet (23 m), use either a shielded or unshielded 18 AWG wire.
Note: For a wire up to 200 feet (61 m) long, a shielded 18 AWG wire is recommended.
LN Series Variable Air Volume (VAV) LN-VAVCF-12 Controller Installation Instructions6
Page 7

Wiring Digital Inputs

Figure 9: Digital Dry Cont act (NO and
NC)
Figure 10: Resistive Input – RTD/Thermistor
Input
Figure 11: Resistive Input – 10k Ohm
Potentiometer Input
Figure 12: Current Input – 2-Wire
Transduce r Powered by the Con troller
Figure 13: Current Input – 3-Wire
Transducer, Externally Powered
Figure 14: Current Input – Transducer with
Its Own Power Source
Figure 15: Voltage Input – 3-Wire Transducer
Figure 16: V oltage Input – Transducer with Its
Own Power Source
Use this configuration to monitor digital dry contracts, as well as pulsed contacts (Figure 9).

Resistive 10k ohm Inputs

Use this input configuration to monitor 100k ohm RTDs, 10k ohm Type 2 and Type 3 thermistors, and potentiometers (Figure 10 and Figure 11).
For a 3-wire, 0 to 20 mA transducer powered by an external 24 AC/DC power supply, connect the current input as shown in Figure 13.
If the transducer is powered by its own power source, connect the current input as shown in Figure 14.

Wiring Voltage Inputs

Voltage inputs have a range of 0 to 10 VDC or 0 to 5 VDC.
Note: When you use a 100k ohm input, the wire length should be short to avoid a possible temperature offset; for example, 18 AWG wire, 25 feet (7.6 m) in length creates an offset of 2°F (1.1°C).

Wiring Current Inputs

Current inputs can have a range of 4 to 20 mA. Depending on the transducer power requ irements, you can use any one of the following input configurations.
If you are using a 2-wire, 4 to 20 mA transducer powered by the controller’s internal 15 VDC power supply, connect the current input as shown in the Figure 12.
If you are using a 3-wire, 0 to 10 V or 0 to 5 V transducer, connect the voltage input as shown in Figure 15 if you are using a 3-wire, 0 to 10 V or 0 to 5 V transducer.
If the transducer is powered by its own power source, connect the voltage input as shown in Figure 16.

LN Series Communicating Sensor Wiring

The LN Series Communicating Sensors are room temperature sensors with backlit display and graphic menus. Connect the LN Series Communicating Sensor to the controller with a standard Category 5e Ethernet patch cable fitted with RJ-45 connectors.
LN Series Variable Air Volume (VAV) LN-VAVCF-12 Controller Installation Instructions 7
Page 8
If you make your own patch cable, use Category 5e
Figure 17: T568A and T568B Crimp Wire
Sequence for an RJ-45 Connector
T568A T
568
B
Stripe Solid
12345678
1234567
8
Pair 3 Pair 1 Pair 2 Pair 4 Pair 2
Pair 1Pair 3Pair
4
Key
:
Figure 18: Pins on RJ-45 Jack Face
cable crimped with the RJ-45 connectors either as T568A or T568B. .
IMPORTANT: Do not crimp one connector as T569A and the other as T568B on the same cable.
IMPORTANT: Protect the controller’s connector from being pulled on when a cable to the LN Series Communicating Sensor is connected. Create a strain-relief by looping and attaching it to a solid object with a nylon tie so a tug on the cable does not pull out the connector from the controller
Table 2: T568A and T568B Terminations for an
RJ-45 Connector
Pin T568A (at both
cable ends)
T568A (at both cable ends)
Pair Color Pair Color
1 3 white/green
stripe
2 3 green solid 2 orange solid 3 2 white/orange
stripe
4 1 blue solid 1 blue solid 5 1 white/blue stripe 1 white/blue stripe 6 2 orange solid 3 green solid 7 4 white/brown
stripe
8 4 brown solid 4 brown solid
2 white/orange
stripe
3 white/green
stripe
4 white/brown
stripe
Figure 17 shows the result of a crimped RJ-45 connector.
Patch cables fitted with connectors that Johnson Controls supplies are wired as T568B.
For more information and requirements for connecting the LN Series Communicating Sensors, including information about network topology and length, cable type, and setting the Subnet ID, refer to the LN Series
Communicating Sensor Installation Instructions (LIT-12011795) and the L
ONWORKS LN-Series Network
Communication and Interface Guide Technical Bulletin (LIT-12011253).

Output Wiring

The LN-VAVCF-12 controller has physical connections for digital outputs. The power source type for digital outputs is hardware configurable and must be configured by changing the jumper settings on the printed circuit board (for jumper selection, see
Configuration Jumper Location and Iden tif icat ion
Note: For a wire length less than 75 ft (23 m), use either a shielded or unshielded 18 AWG wire.
Note: For a wire length up to 200 ft (61 m) long, we recommend using a shielded 18 AWG wire.
).
LN Series Variable Air Volume (VAV) LN-VAVCF-12 Controller Installation Instructions8
Page 9
Note: The wire should be shielded on the controller
Figure 19: Digital Output with External Power
Supply – Relay
Figure 20: Digital Output with Internal Power
Supply – Relay
Figure 21: Digital Output with External Power
Supply – Floating Actuator
Figure 22: Digital Output with Int ernal Supply –
Floating Actuator
side; keep the shield length as short as possible.
IMPORTANT: Before connecting any output device (actuator, relay, etc.) to the controller, refer to the manufacturer’s installation guide.

Wiring Digital Outputs (DOx)

Y o u can configure the digit al output s either as powe red outputs or non-powered outputs. When wiring digital outputs:
the non-powered output type does not have any voltage on the output terminals when the output is active. Power must be supplied externally.
the powered output type has 24 VAC on the output terminals when the output is active. Power is therefore supplied internally by the controller.
If a 24 V AC relay is being controlled, connect the di gital output according to Figure 19 (external power supply) and Figure 20 (internal power supply).
Note: The LN-VAVCF-12 controller is shipped with all digital outputs configured as powered outputs. Maximum output current for all digita l outputs (power ed or non-powered) is .05 A continuous or 1 A at 15% duty cycle for a 10-minute period.
IMPORTANT: To measure the state of a digital output (TRIAC), an external load must be connected.
DO1 and DO2 share the same C1-2 common termin a l and are controlled by a single jumper; therefore, they must be set identically. Similarly, DO2 and DO3 (VAV and VVT products only) share the same C3-4 comm on terminal and are controlled by a single jumper and must be set identically . The jumpers specify whether an internal or external power source is being used. See
Configuration Jumper Location and Identification
.
If a floating actuator is being controlled, connect the digital output as shown in Figure 21 and Figure 22.
Note: In Figure 21 an external power supply is used; in Figure 22 an internal power supply is used.

Wiring Universal Outputs (UOx)

The universal outputs can be configured to provide either a linear signal ranging from 0 to 10 VDC or a discrete signal of 0 to 12 VDC.
LN Series Variable Air Volume (VAV) LN-VAVCF-12 Controller Installation Instructions 9
The discrete signal can be used to generate a Pulse Wave Modulation (PWM) signal or a simple two-state signal. These outputs are protected by an auto-reset fuse.
Wiring Discrete Outputs
If a 12 VDC relay is being controlled, connect it to a universal output (Figure 23).
Page 10
If an analog actuator is being controlled, connect the
Figure 25: Voltage 0 to 10 VDC Universal Output –
Analog Actuator
Figure 26: Communications Wiring
Figure 27: LONWORKS Network Free Topology
Controller
LN-Series Sensor
22AWG (0.65mm) Unshielded Twisted Pair Network Cable
Free-Topology
Network
Cat5
e network cable
: LN
Series Sensor Subnetwork
Bus and L
ONWORKS
Network
0 to 10 VDC output, along with an external 24 VAC power source, to the analog actuator as shown in Figure 25.

Communications Wiring

Approved cable types for LONWORKS® communications are 22 AWG (0.65 mm), twisted pair, UNSHIELDED.
The L
ONWORKS communication wire is polarity
insensitive, and can be laid out in a bus, star, loop or free topology. For loop topology, polarity is important; take special care when connecting the L network to avoid a short circuit.
Note: We recommend bus topology network configuration for all L
ONWORKS communication wiring
because it allows for easy network troubleshooting. Connect both wires to the LON1 and LON2 terminals of
the controller. If inserting multiple wires in the terminals, make sure to properly twist wires together prior to inserting them in the terminal connectors (Figure 26).
ONWORKS
You can also refer to the Echelon® Junction Box and
Wiring Guideline for Twisted Pair L
ONWORKS Networks
(Part No. 005-0023-01).
IMPORTANT: Use proper network terminators depending on the type of network topology used. Failure to do so may result in communication errors between controllers. Do not use multiple gauges of cable on the same communication bus, as this may also result in communication errors.

Supported Quantity of Sensors Per Controller

LN VAV/VVT controllers support 4 LN Communicating Sensors. See Table 3 for the maximum allowable sensors per controller. You must set the Subnet ID of all sensors within the address range listed in Table 3.
Ta b le 3: Number of LN Communicating Sensors
Controller Models Support
Controller Series Maximum
Number of Sensors
LN-VAV/VVT 4 1–4

Selecting Network Terminators

For bus topology, two network terminators are required (one at each end of the bus topology channel). For a free topology, one network terminator is required. You can put it anywhere on the channel.
When used with an LN Series Communicating Sensor, the network can be accessed at the sensor’s audio plug port when the two Net to Subnet Port Settings jumpers inside the controller are set to Enable. For jumper location, see Configuration Jumper Location and Identification). Setting these jumpers to Enable connects the main L
ONWORKS network to the LN
Series Communicating Sensor subnetwork Cat 5e cable, creating a free topology L
ONWORKS network with
maximum allowable total length of all segments combined to be no more than 1,600 feet (500 meters).
Subnet ID Address Range
For information and detailed explanations on network topology and wire length restrictions, refer to th e
ONWORKS LN-Series Network Communication and
Interface Guide Technical Bulletin (LIT-12011253).
LN Series Variable Air Volume (VAV) LN-VAVCF-12 Controller Installation Instructions10
The Cat 5e cable length may also be restricted by the maximum allowable subnetwork bus len gt h. For mo re information, refer to the LN Series Communicating Sensors Installation Instructions (LIT-12011795).
Page 11
This configuration mixes the cable gauge used for the
Figure 28: Metal Enclosure Mount
Figure 29: Telephone Socket Location
network, which under rare conditio ns ma y ca us e communication problems. To avoid these problems, carefully test for good communication on the entire network. If there are any network problem s, s ee
Troubleshooting
.

Wireless Installation

The LN-VAVCF-12 controller can receive input signals from wireless devices when connected to a wireless receiver and programmed with GPI software. Compatible wireless devices include temperature sensors, duct sensors, window and door contacts, and light switches. These devices are easy to install, and can be mounted on a wide range of building materials.
For information on selecting mounting locations for the LN Series wireless option controllers, refer to the LN
Series Wireless Solution Guide Technical Bulletin (LIT-12011628).

Mounting the Wireless Receiver

There are three mounting options: on a wall or ceiling with double-sided tape, on a wall or ceiling with mounting screws, or on a metal enclosure using a 1/2-inch National Pipe Thread (NPT) hub.
Regardless of the mounting method, the wireless receiver should be 16 inches (41 cm) or more away from the controller or any other network cables.
2. Place the Wireless Receiver onto the metal enclosure and align the NPT hub to the hole.
3. Use the cap to tighten the Wireless Receiver onto the enclosure.

Connecting the Wireless Receiver

Connect the wireless receiver to the controller with the included 6.5 foot (2 m) telephone cable (4P4C modular connectors). Locate the telephone socket inside the device (Figure 29).
Wall or Ceiling Mount with Double-Sided Tape
To mount on a wall using double-sided tape, first apply the tape to the back of the receiver and then stick the receiver onto the desired wall or ceiling location.
Wall or Ceiling Mount with Screws
To mount the wireless receiver with screws:
1. Separate the front and back plates on the receiver to open it.
2. Use the mounting holes on the back plate to mark the wall or ceiling location.
3. Drill the holes.
4. Clean the holes, insert wall anchors, and fasten the back plate with the screws.
Metal Enclosure Mount
To mount onto a metal enclosure:
1. Affix the 1/2-inch NPT hub to the bottom of the Wireless Receiver. Ensure the cap of the NPT hub is undone.

Connecting to the Controller Wireless Port

Each controller has a wireless port where you connect the telephone cable. Uncover the controller to locate the wireless port on the PCB board (marked as Wireless Module).
LN Series Variable Air Volume (VAV) LN-VAVCF-12 Controller Installation Instructions 11
Page 12

Disconnecting the Wireless Port

!
To disconnect the plugged-in telephone cable from the controller’s wireless port, pass a pointed object through the hole above the wireless port and press on the top of the connector while gently pulling out the cable.

Terminal Block Cover

In certain jurisdictions, terminal block covers are required to meet local safety regulations. Terminal block covers are available for all controllers and are used to conceal the controllers’ wire terminals. Terminal block covers are optional and sold separately.

Maintenance

CAUTION: Risk of Electric Shock.
Disconnect the power supply before making any electrical connections to avoid electric shock.
MISE EN GARDE : Risque de décharge électrique.
Débrancher l'alimentation avant de réaliser tout raccordement électrique afin d'éviter tout risque de décharge électrique.
clean the outside of the front plate and the inside of the back plate with a dry cloth.
verify the tension of all wires and cables each time you service the controller.

Disposal

The Waste Electrical and Electronic Equipment (WEEE) Directive sets regulations for the recycling and disposal of products. The WEEE 2002/96/EG Directive applies to stand-alone products that can function on their own and are not a part of another system or piece of equipment. For this reason, Johnson Controls® products are exempt from the WEEE Directive. Nevertheless, they are marked with the WEEE symbol, indicating the devices are not disposed with municipal waste.
Dispose of products at the end of their useful life according to local regulations and the WEEE Directive.
Each controller requires minimal maintenance, but it is important to:

Troubleshooting

Table 4: Troubleshooting (Part 1 of 3)
Problem Possible Cause Solution
Device is powered but does not turn on.
Device cannot communicate on L network.
ONWORKS
Fuse is blown. Disconnect the power. Check the fuse integrity. Reconnect
the power.
Power supply polarity Verify consistent polarity is maintained between all
controllers and the transformer. Ensure that the 24 V COM terminal of each controller is connected to the same terminal on the secondary side of the transformer. See Figure 7 and Figure 8.
Absent or incorrect supply voltage
Overloaded power transformer
Network not wired property Double-check the wire connections are correct. Absent or incorrect network
terminators
1. Check power supply voltage between 24 VAC + and 24 COM pins to ensure it is within acceptable limits.
2. Check for a tripped fuse or circuit breaker.
Verify the transformer used is powerful enough to supply all controllers.
Check the network terminator(s).
15%
LN Series Variable Air Volume (VAV) LN-VAVCF-12 Controller Installation Instructions12
Page 13
Table 4: Troubleshooting (Part 2 of 3)
Problem Possible Cause Solution
Controller communicates well over a short network but does not communicate on a large network.
Hardware input is not reading the correct value.
Hardware output is not operating correctly.
Flow sensor is not giving proper readings.
Network length Check that the total wire length does not exceed
specifications. See to Table 1.
Wire type Check that the wire type agrees with the specifications.
Network wiring problem Verify the wire connections are correct. Absent or incorrect network
terminators
Extra capacitance Verify that no extra capacitan c es are connected to the
Number of devices on network segment exceeded
Network traffic Query node statistics to check for errors. Use a LON
Input wiring problem Check that the wiring is correct according to this manual
Open circuit or short circuit Using a voltmeter, check the voltage on the input terminal.
Configuration problem Using a device configuration plug-in or wizard, check the
Over-voltage or over-current at an input
Blown fuse (auto reset) Disconnect the power and outputs terminals. Wait a few
Output wiring problem Check that the wiring is correct according to this manual
Configuration problem Using the device configuration plug-in or wizard, check the
0-10 V output, 24 VAC powered actuator is not moving
Tubing connection problem Verify the tubing is installed properly and that the tubing is
Device is not calibrated properly
Verify your wire is UNSHIELDED. See Typical VAV Application Wiring Diagram.
Check the network terminators. Incorrect or broken terminators make the communication integrity dependent upon a device’s location on the network.
network other than the standard FTT circuit, and a maximum of 3 meter stub (in bus topology).
The number of devices on a channel should never exceed
64. Use a router or a repeater in accordance to the
ONWORKS LN-Series Network Communication and
L Interface Guide Technical Bulletin (LIT-12011253).
protocol analyzer to check network traffic.
and according to the peripheral device’s manufacturer.
Short circuit (0 V) and open circuit (5 V).
configuration of the input. Refer to the device’s user guide for additional information.
An over-voltage or over-current at one input can affect the reading of other inputs. Respect the allowed voltage/ current range limits of all inputs. See the input range limits in the Technical Specifications
seconds to allow the auto-reset fuse to cool down. Check the power supply and the output wiring. Reconnect the power.
and according to the peripheral device’s manufacturer.
configuration of the output. Refer to the device user’s guide for more information.
Check the polarity of the 24 VAC power supply connected to the actuator while connected to the controller. Reverse the 24 VAC wire if necessary. Check the jumper setting for the external power supply as shown in Figure 21.
not bent. Ensure the high and low pressure sensors are not inverted.
Recalibrate the VAV controller. Refer to the controller user guide for more information about VAV controller calibration.
section.
LN Series Variable Air Volume (VAV) LN-VAVCF-12 Controller Installation Instructions 13
Page 14
Table 4: Troubleshooting (Part 3 of 3)
Problem Possible Cause Solution
Wireless Device is not working correctly.
Damper is not opening or closing properly.
Rx/TX LEDs RX LED is not blinking. Data is not being received from the L TX LED is not blinking. Data is not being transmitted onto the L
Device not associated to controller
Power discharge Recharge the device with light (if solar-powered) or replace
Device too far from the Wireless Receiver
Configuration Problem Using the device configuration plug-in or wizard, check the
Mechanical stops not in proper position
Drive time not set up correctly for external damper
VAV still in Calibration mode Complete the calibration process in LN-Builder. Controller in Override Set the Override to OFF in the object manage screen in
Using the device configuration plug-in or wizard, check the configuration of the input. Refer to the device’s user guide for more information.
the battery (if battery-powered). Ensure sufficient light intensity (200lx for 4 hours/day).
Reposition the device to be within the range of the Wireless Receiver. Refer to the LN Series Wireless Solution Guide Technical Bull etin (LIT-120116828).
configuration of the input. Refer to the LN Series Wireless
Solution Guide Technical Bulletin (LIT-12011628)
The two mechanical stops must be positioned to stop the damper motion when it is completely closed and completely opened. The mechanical stops can be moved by increments of 5°.
Ensure the external damper drive time is set to the correct value (in the plug-in or wizard).
LN-Builder.
.
ONWORKS data bus.
ONWORKS data bus.

Status LED Operation

Table 5: Status LED Operation Guide – Normal Operation
Operation Service
Initialization: the device is starting up.
One Fast Blink Fast Blink Continuous
(150 ms On, 150 ms Off, Continuous) The Status LED is Always OFF The controller is operating normally.
Firmware upgrade in is progress and the controller operation is temporarily unavailable. The new firmware is being loaded into memory and the process takes a few seconds. Do not interrupt power to the device during this time.
LN Series Variable Air Volume (VAV) LN-VAVCF-12 Controller Installation Instructions14
Page 15
Table 6: Status LED Operation Guide – Repeats every 2 seconds (highest priority first)
Operation Service Long blink continuous
(1s On, 1s Off, Continuous)
The controller is not configured. Appropriate action: Commission the contro l l er.
Long Long Long Blink (800 ms On, 300 ms Off, 800 ms On, 300 ms Off, 800 ms Off)
Long Short Short Short Blink The controller is in bypass mode.
Short Short Long Blink Poor-quality power; the device has browned-out: The
Fast Blink 12x Wink: The wink function identifies a device.
The controller is offline. Appropriate action: Set the controller online.
Appropriate Action: Set the controller online
voltage at the 24 VAC and 24 VCOM terminals has gone below the device’s acceptable limit during powerup.

Technical Specifications

LN-VAVCF-12 (Part 1 of 3)

Product Codes LN-VAVCF-12 Power Requirement Voltage: 24 VAC/DC; +
Protection: 2 A user-replaceable fuse; 3 A user-replaceable fuse for Triacs when using
the internal power supply
Consumption: 10 VA typical plus all external loads Maximum Consumption: 85 VA
Environmental Operating Temperature: 0 to 50°C, (32 to 122°F)
Storage Temperature: -20 to 50°C, (-4 Relative Humidity: 0 to 90% noncondensing
General Communication: LonTalk® protocol
L
ONMARK Interoperability Guidelines: Version 3.4
Device Class: SCC VAV Processor: STM32 (ARM Cortex™ M3) MCU, 32 bit Processor Speed: 68 MHz Memory: 384 KB Nonvolatile Flash (applications), 1 MB Nonvolatile Flash (storage)
64 KB RAM
Media Channel: TP/FT-10; 78 Kbps Communication: LonTalk® protocol Status Indicator: Green LED - power status and LAN TX, Orange LED - service and LAN
RX
L
ONMARK Functional Profile (pending): Input Objects: Open-Loop Sensor #1, Output
Objects: Open - Loop Sensor #3, Node Object: #0, Real Time Clock: Real Time Keeper #3300, Scheduler: Scheduler #20020, Calendar: Calendar #20030, Programmable
Programmable Device: Static Programmable Device #410, SCC VAV #8502
Enclosure Material: FR/ABS
Dimensions (with screws): 4.8 x 8.4 x 2.5 in. (122.7 x 214.3 x 63 mm) Shipping Weight: 2.30 lb (1.05 kg)
15%, 50/60 Hz, Class 2
to 122°F)
LN Series Variable Air Volume (VAV) LN-VAVCF-12 Controller Installation Instructions 15
Page 16
LN-VAVCF-12 (Part 2 of 3)
Inputs Quantity: 4; universal software configurable
Input Types:
Digital: Dry Contact Voltage: 0 to 10 VDC (40 ohm input impedance), 0 to 5 VDC (high input impedance) Current: 0 to 20 mA with 249 ohmsexternal resistor (wired in parallel) Pulse: Dry contact; 500 milliseconds minimum ON/OFF
Resistor Support: 0 to 350k ohms. All thermistor types that operate within this range are
supported. The following temperature sensors are pre-configured:
Thermistor: Type 2 and Type 3 10k ohm (10k ohm at 25 Platinum: PT1000 1k ohm (1k ohm at 0°C [32°F]) Nickel: RTD Ni1000 (1k ohm at 0°C [32°F]) RTD Ni1000 (1k ohm at 21°C [69.8°F]) Input Resolution: 16-bit analog/digital converter
Input Resolution: 16-bit analog/digital converter Differential Pressure: 0 to 55 Pa (0 to 2.0 in W.C.) Range:
Accuracy: + Input Resolution: 0.0167 Pa (0.00007 in. H
Power Supply Output: 15 VDC; maximum 80 mA (4 inputs x 20 mA each)
Integrated Damper Actuator Motor: Belimo® LMZS-H brushless DC Motor
Torque: 35 in·lb, 4 N·m Degrees of Rotation: 95º adjustable Fits Shaft Diameter: 5/16 to 3/4 in. (8.5 to 18.2 mm) Power Supply: from controller
LN Series Communicating Sensors
Outputs Quantity of Points
Quantity of Points: 4 Models Supported: LN-SVSEN-0, LN-SVSENH-0; Communication: RS-485 Number of Sensors per controller: up to 4, in daisy-chain configuration Cable: Cat 5e, 8 conductor twisted pair Connector: RJ-45
configurable
0.5 A continuous 1A at 15% duty cycle for a 10-minute period PWM control: adjustable period from 2 to 65 seconds Floating control: requires two consecutive outputs Minimum pulse on/off: 500 milliseconds Adjustable drive time period
External or internal power supply (jumper selectable) Universal: linear (0 to 10 VDC) Digital (on/off) PWM, or floating (0 to 12 VDC); software configurable. Built-in snubbing diode to protect against back EMF, for example when used with a 12
VDC relay.
PWM control: adjustable period from 2 to 65 sec Floating control:
minimum plus on/off: 500 ms
adjustable drive time period
20 mA maximum at 12 VDC Minimum load resistance 600 ohms Output Resolution: 10-bit digital/analog converter
5.5% of reading over operating temperature range
1
: 4; 24 VAC Triac, digital (on/off), PWM, or floating; software
0)
2
°C [77°F])
LN Series Variable Air Volume (VAV) LN-VAVCF-12 Controller Installation Instructions16
Page 17
Metasys® and Johnson Controls® are registered trademarks of Johnson Controls, Inc.
All other marks herein are the marks of their respective owners. © 2014 Johnson Controls, Inc.
Building Efficiency
507 E. Michigan Street, Milwaukee, WI 53202
LN-VAVCF-12 (Part 3 of 3)
Wireless Receiver
2
Communication: EnOcean wireless standard Wireless Inputs: 18
4
Supported Wireless Receivers: Wireless Receiver 315 (LN-WMOD315-0) and Wireless Receiver 868 (LN-WMOD868-0)
Cable: Telephone cord
Connector: 4P4C modular jack Length: 6.5 ft. (2 m)
Electromagnetic Compatibility CE Emission: EN61000-6-3: 2007; Generic standards for residential, commercial, and
light-industrial environments.
CE Immunity: EN61000-6-1: 2007; Generic standards for residential, commercial, and
light-industrial environments.
FCC: This device complies with FCC rules part 15, subpart B, class B (pending)
Compliance: United States UL Listed: Under UL 916, Energy Management Equipment
Material
4
: UL94-5VA
Canada UL Listed: Under UL 916, Energy Management Equipment
Material: UL94-5VA
Europe CE Mark – Johnson Controls, Inc., declares that the products are in compliance with the
essential requirements and other relevant provisions of the EMC Directive 2004/108/EC.
1. Floating only available when controller is programmed with LN GPI software.
2. You cannot use an LN Series Communicatin g Sensor and Wireless Receiver at the same time. However, you can temporarily connect an LN Series Communicating sensor to a controller in wireless mode to perform VAV airflow balancing.
3. Available when an optional external Wireless Receiver is connected to the controller. Refer to the LN Wireless Location Guide for a list of supported EnOcean wireless modules.
4. All materials and manufacturing processes comply with the RoHS directive and are marked according to the W aste Electrical and Electronic Equipment (WEEE) directive.
3
The performance specifications are nominal and conform to acceptable industry standard. For application at conditions beyond these specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products.
LN Series Variable Air Volume (VAV) LN-VAVCF-12 Controller Installation Instructions 17
Published in U.S.A. www.johnsoncontrols.com
Loading...