Johnson Controls LB-FMS1655-F01, LB-FMS1655-F11, LB-FMS1655-F04, LB-FMS1655-F10, LB-FMS1655-F12 Installation Manual

...
FMS-1655 Room Pressure Controller (BACnet
®
/ N2 only products)
LB-FMS1655-F01
LB-FMS1655-F02
LB-FMS1655-F03
LB-FMS1655-F04
LB-FMS1655-F10
LB-FMS1655-F11
LB-FMS1655-F12
LB-FMS1655-F13
Application
These installation instructions guide the installer through the installation of the FMS-1655 Room Pressure Controller. Please read these instructions thoroughly before beginning installation.
North American Emissions Compliance
United States
This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when this equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area may cause harmful interference, in which case users will be required to correct the interference at their own expense.
LB-FMS1655-S01
LB-FMS1655-S02
LB-FMS1655-S03
LB-FMS1655-S04
LB-FMS1655-T01
LB-FMS1655-T02
LB-FMS1655-T03
LB-FMS1655-T04
Code No. LIT-12013117, Rev. A
Issued August 2018
Canada
This Class (A) digital apparatus meets all the requirements of the Canadian Interference-Causing Equipment Regulations.
Cet appareil numérique de la Classe (A) respecte toutes les exigences du Règlement sur le matériel brouilleur du Canada.
Installation
NOTICE
Risk of Property Damage. Ensure that the power source conforms to the requirements of the equipment. Failure to use a correct power source may result in permanent damage to the equipment.
NOTICE
Risque de dégâts matériels.
S’assurer que la source d’alimentation électrique est conforme aux spécications de l’équipement. L’utilisation d’une source
d’alimentation électrique inappropriée risque d’endommager irrémédiablement l’équipement.
IMPORTANT: The FMS-1655 Room Pressure Controller must be wired to 24 VAC only. Wiring the unit to 110 VAC will cause serious damange and void the warranty.
Use of the software that is in (or constitutes) this product or access to the cloud or hosted services applicable to this product, if any, is subject to applicable terms set forth at www.johnsoncontrols.com/techterms. Your use of this product constitutes an agreement to such terms. If you do not agree to be bound by such terms, you may return the unused product to your place of purchase.
Central Monitoring Station
The Next Generation in Critical Airow Controls
Room Pressure Controller
JCI CMS-1655
JCI FMS-1655
JCI FMS-1655
Notes
Warning
Failure to follow the wiring diagrams could result in damage to your equipment and could void your warranty. Under no circumstances should a single transformer be split between actuator and controller. Doing so
will damage the actuator, the transformer, the controller or all units. A single 120/24V 30Va transformer is required for the controller and a separate 120/24V 20Va transformer is required for the actuator. This equipment contains electrostatic sensitive components. To prevent possible damage, take precautions to prevent electrostatic discharge when handling or servicing this equipment by wearing an approved ESD grounding wrist strap connected to an earth ground source.
Controller
FAST ACTING
ELECTRONIC ACTUATOR
CORRECT
120/24VAC, 30Va Transformer Supplied by JCI
Due to continuous improvement, TRIATEK reserves the right to change product specifications without notice.
120/24VAC, 20Va Third Party Transformer
Actuator
CORRECT
CONTROLLER SETTINGS
FMS-1655 Room Pressure Controller Settings
This form should be completed during the initial configuration for each room pressure controller. Be sure to configure the unit for either Positive, Negative, or both using the Isolation Mode Configuration setup procedure.
Room Name / Number
Unit Model Number and Serial Number (ESN)
Analog Input
Normal Operating Pressure (reading with door closed)
Sensor Input Mode (normal or inverted)
Sensor Input Range (zero-based or offset)
Sensor Pressure Range
Positive Isolation Setpoint
Negative Isolation Setpoint
Neutral Isolation Setpoint
Pressure Deadband
Analog Output
Operating Mode (Direct or PID)
Analog Output Range (zero-based or offset)
Analog Output Upper Limit (0 – 100%)
Analog Output Lower Limit (0 – 100%)
Analog Output Input Channel (AI-1 thru AI-4, TI-1 or TI-2)
Analog Output Action (Direct or Reverse)
Analog Output Range (zero-based or offset)
Door Switch
Operating Mode (normally-open or normally-closed)
Delay Setting (0 - 240 secs)
Relay Output
Trigger Mode (Setpoints, Isolation Mode or Occupancy)
Input Channel (AI-1 thru AI-4, TI-1 or TI-2)
Positive Isolation High Setpoint
Positive Isolation Low Setpoint
Negative Isolation High Setpoint
Negative Isolation Low Setpoint
Relay Acting Mode (Direct or Reverse)
Delay Setting (0 - 180 secs)
PID Constants
Proportional Constant (0.5 – 100.0 %)
Integral Constant (0.0 – 100.0 %)
Derivative Constant (0.0 – 100.0 %)
Alarm Limits
Positive Isolation High Alarm Setpoint
Positive Isolation High Warning Setpoint
Positive Isolation Low Warning Setpoint
CONTROLLER SETTINGS
FMS-1655 Isolation Room Pressure Controller Settings
Positive Isolation Low Alarm Setpoint
Negative Isolation High Alarm Setpoint
Negative Isolation High Warning Setpoint
Negative Isolation Low Warning Setpoint
Negative Isolation Low Alarm Setpoint
Audible Alert
Enabled Input Channels (AI-1 thru AI-4, TI-1, TI-2)
Operating Mode (audible or silent)
Delay Time Base (secs or mins)
Delay Setting (0 – 60)
Alarm Quiet Period Starting Hour (0 – 23)
Alarm Quiet Period Ending Hour (0 – 23)
Engineering Units
Inches of Water or Pascals
Due to continuous improvement, TRIATEK reserves the right to change product specifications without notice.
INSTALLATION MANUAL
Table of Contents
GENERAL
Specifications………………………………………………………………………………...……………………………………………1 - 2 Part Number Guide…………………………………………………………………………………………………………………………2 Overview……………………………………………………………………..…………………….………………………………………3 - 4
MOUNTING/WIRING
FMS-1655 Flush Mount With Internal Sensor Introduction…………………………………………………………………………………………………………………………………5
Mounting Procedure………………………………………………………………………………………....……………………………5 - 6
Internal Sensor Illustration………………………………………………………………………….....……………………………………7
FMS-1655 With Remote Sensor Introduction…………………………………………………………………………………………………………………………………9
Mounting Procedure………………………………………....………………………………………………………………………………9
FMS-1655 With Standard Remote Sensor Illustrations………………………………………………………………………....…10 - 11
Remote Sensor Configuration Illustration……………………………………………………………………………………………..12
Analog Output to Electric and Pneumatic Damper Actuator Illustrations (Internal Sensor Model)………………....………13 - 14
Analog Output to Variable Speed Drive Illustration (Internal Sensor Model)………………………………………………..………15 Analog Output to Modulated Air Controller Illustration (Internal Sensor Model)……………………………………………………16 Analog Output to Pneumatic Damper Actuator Illustration (Internal Sensor Model)………………………………………………17 Analog Output to Variable Speed Drive Illustration……………………………………………………………………………………18 Adding Remote Pressure Sensor with 4-20mA Out to Internal Sensor Model Illustration……………………………………19 Analog Input to 2 Remote Pressure Sensor 4-20mA Out Illustration……………………………………………………………… 21 Analog Input to 3 Remote Pressure Sensor 4-20mA Out Illustration……………………………………………………………… 22 Analog Input to 4 Remote Pressure Sensor 4-20mA Out Illustration……………………………………………………………… 23 Analog Input to Temperature Sensor Illustration……………………………………………………………………………………… 24
Custom Sensor Illustration………………………………………........................................................................……………………25
Digital Input to Door Switch Illustration………………………………………………………………………………………………… 26 Digital Input to Occupancy Sensor……………………………………………………………………………………………………28 Relay Output Alarm Illustration………………………….………………………………………………………………………………29
Relay Output to Warning Illustration……………......…………………………………………………………………………………30
Relay Output 1 Illustration…………………........………………………………………………………………………………………31
Relay Output 2 Illustration………………........……....…………………………………………………………………………………32
Power Illustration……………………………...….…………………………………………………………………………………………33 Isolated Power Supply………………………..……………………………………………………………………………………………34
COMMUNICATIONS - BACnet MS/TP
Wiring Illustration………………………………………………………………………………………………………...…………………36
COMMUNICATIONS - METASYS N2 OPEN
Wiring Illustration…………………………………………………………………………………………………....………………………37
FMS-1655 QUICK START GUIDE
Quick Start Guide………………………………………………………………………………………………………....………………38
Main Display Screen………………………………………………………………….....…………………………………………………38
Automated Clean Cycle ………………………………………………………………...……………………………………………38 - 39
Configuring Room Pressure Monitor…………………………………………......………………………………………………………39
Setting Up Analog Output………………………………………………………..………………………………………………………39 Enabling Door Switch………………………………………………………………………………………………………………39 - 40
Setting Up Alarm Relay Output....……………………………………………….………………………………………………………40
Setting Alarm Limits...…………………………………………..…………………………………………………………………………40
Changing Isolation Mode.……………………………………..........……………………………………………………………………40
INSTALLATION MANUAL
Table of Contents
Invoking Auto Clean Cycle.………………………………..........…………………………………………………………......……….....40
Changing Network Settings..………………………….....…………………………………………………………………………………40
Adding Password Security…………………………...……………………………………………………………………………………40
Changing Display Settings……………….……………………………………………………………………………......…………40 - 41
Built-in Diagnostics………………………...………………………………………………………………………………………………41
MODULE SETTINGS
Configuring Display Module Settings……………………………...……………………………………………………………………43
Configuring Main Controller Module Settings………....………………………………………………………………………………44
Configurations and Settings………………………………………………………………………………………………………………45
BACnet® OBJECTS
Analog Input Objects………………………...…….………………………………………………………………………………………46 Analog Output Objects……………………..……...………………………………………………………………………………………46 Binary Input Objects………………………..……..………………………………………………………………………………………46
Binary Output Objects……………………....………..……………………………………………………………………………………46
Analog Value Objects……………………....…………..……………………………………………………………………………46 - 47
Multistate Output Objects……………..………………...…………………………………………………………………………………47
METASYS® N2 OBJECTS
Analog Input Objects…………………………....…………………………………………………………………………………………48
Analog Output Objects……………………….....…………………………………………………………………………………………48
Binary Input Objects……………………………...………………………………………………………………………………………48
Binary Output Objects………………………….....………………………………………………………………………………………48
Internal Float Value Objects………………………..………………………………………………………………………………48 - 49
Multistate Output Objects……………………….....………………………………………………………………………………………49
CLEANING THE DISPLAY
Cleaning the FMS-1655……………………….....………………………………………………………………………………………51
DIAGRAMS
Wiring Illustration……………………………………………………………………......…………………………………………………52
Integrated Flush Mount Wiring Box Dimensions………………....……………………………………………………………………53
Flush Mount Bracket Dimensions………………………………………………………………………………………………………54 Thin Mount Wiring Box Dimensions……………………..………………………………………………………………………………55
FLOW DIAGRAMS
Unit Setup Tree………………………………….....………………………………………………………………………………………57
System Setup Tree……………...……………………………………………………………………………………………………58 - 60
Display Setup Tree…………....……………………………………………………………………………………………………………61
Diagnostics Tree………………..…………………………………………………………………………………………………………62
Due to continuous improvement, TRIATEK reserves the right to change product specifications without notice.Due to continuous improvement, JCI reserves the right to change product specifications without notice. Due to continuous improvement, JCI reserves the right to change product specifications without notice.
GENERAL
Specications
Electrical
Optional External Remote Sensor Distance……………………………………………………………………………………………………Up to 1,000 feet
Optional External Remote Sensor....………………………………………………………………………………Wiring 18-22 AWG, shielded twisted pair
Power Supply..…………………………………………………………………………………………………………………………………24 Vac ±10%, 30Va
Accuracy of Measurement.....……………………………………………………………………………………………………………………………±0.5%FS
Pressure Range (NIST Traceable / Individual certication available as option)…………………………………………………………………±0.2500 “WC Pressure/Flow……………………………………………………………………………………………………………………………………up to 0.25 ”WC 4 Analog Inputs…………………………………………………………………………………………………………………4-20mAdc, 0-5Vdc or 0-10Vdc 4 Analog Outputs………………………………………………………………………………………………………………4-20mAdc, 0-5Vdc or 0-10Vdc
2 Thermistor Inputs…………………………………………………………………………………………………………NTC Type 2 or 3, 10kΩ @ 25°C
4 Digital Inputs………………………………………………………………………………………………0-5Vdc or 0-24Vdc, Active-High or Active-Low
3 Relay Outputs...………………………………………………………………………………………………………………………………………1A@24Vdc
Control Signal Wire Size............……………………………………………………………………………………………………………………18-22 AWG
Power Supply………………………Class 2, 24Vac ±10%, 30VA universal 120/240 to 24 Vac, 60/50 Hz, step-down isolation transformer provided
Communications
BACnet® MS/TP network....…………………………………………………………………………………………Two-Wire Twisted Pair, RS-485 signaling
Metasys N2 network...………………………………………………………………………………………………Two-Wire Twisted Pair, RS-485 signaling Recommended Cable Type...……………………………………………………………………………………………………………………… Belden 3107A
Touchscreen User Interface
LCD Size....……………………………………………………………………………………………………………………………………………3.2” diagonal
LCD Type.....……………………………………………………………………………………………………………………………………………Transmissive
Resolution...………………………………………………………………………………………………………………………………………240 x 320 portrait Viewing Area..……………………………………………………………………………………………………………………………50.60 mm x 66.80 mm Color Depth.…………………………………………………………………………………………………………………………………18-bit or 262K colors
Backlight Color.....………………………………………………………………………………………………………………………………………………White
Luminous Intensity...………………………………………………………………………………………………………………………………Min 2500 cd/m2 Recommended Cable Type (applicable to surface mount models FMS-1655-s-x only)…………………………………………………… Belden 3125A
Mechanical
FMS-1655 Internal Sensor Flush Mount Housing (Brushed Stainless Steel) Housing..……………………………………………5.6”W x 8.5”H x 1.9”D FMS-1655 Display Module Housing………………………………………………………………………………………………………3”W x 5”H x 1.13”D Stainless Steel Cover Plate for Flow Tube……………………………………………………………………………………………2.7”W x 4.5”H x 0.2”D Stainless Steel Cover Plate for Remote Sensor………………………………………………………………………………………2.7”W x 4.5”H x 0.2”D FMS-1655 with Flow Tube Cover Plate……………………………………………………………………………………………………………approx. 3.5 lb FMS-1655 with Optional External Remote Sensor………………………………………………………………………………………………approx. 4.0 lb FMS-1655 Mounting Options...……………………………………………………………………………………………………………………Surface, Flush Flow Tube Cover Plate Mounting.. ……………………………………………………………………………………………………………………………Flush
Environmental
Operating Temperature..…………………………………………………………………………………………………………………32° to 125° F Operating
Operating Humidity……………………………………………………………………………………………………………10% - 95% RH, Non-condensing
- 1 -
Due to continuous improvement, JCI reserves the right to change product specifications without notice.
- -
BRAND
LB = Johnson Controls
UNIT
FMS = Flow Monitor Station (FMS)
SERIES
1655 = BACnet / N2 Controller 1655L = LonWorks Controller 1655M = BACnet Monitor
STYLE
S = Surface mount F = Flush mount T = Thin mount
INTERNAL SENSOR
0 = No internal sensor 1 = Standard internal sensor
REMOTE SENSOR
0 = No remote sensors 1 = One remote sensor 2 = Two remote sensors 3 = Three remote sensors 4 = Four remote sensors (Not available with LonWorks Controllers)
(BACnet / N2 controllers only)
(Flush mount controller only)
(Not available with LonWorks Controllers)
GENERAL
Specications
FCC Compliance Statement
This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions:
This device may not cause harmful interference, and
This device must accept any interference received, including interference that may cause undesired operation.
Please Note: This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to Part 15 of the FCC Rules.
These limits are designed to provide reasonable protection against harmful interference in a commercial installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee the interference will not occur in a particular installation. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense.
Caution: To comply with the limits for an FCC Class A computing device, always use the isolated power supply module and recommended interface cables with this unit.
The Federal Communications Commission warns that changes or modifications to the unit not expressly approved by the part responsible for compliance could void the user’s authority to operate the equipment.
This Class-A digital apparatus complies with Canadian ICES-003. Cet appareil numérique de la classe-A est conforme à la norme NMB-003 du Canada.
- 2 -
Due to continuous improvement, TRIATEK reserves the right to change product specifications without notice.Due to continuous improvement, JCI reserves the right to change product specifications without notice.
GENERAL
Overview
The JCI FMS-1655 Room Pressure Controller is an ultra-sensitive instrument used to monitor and/or control air pressure in hospital rooms, labs, and clean rooms. This unit is capable of measuring and displaying differential air pressures as low as 0.0001 “WC or 0.0249 Pa. The FMS-1655 may be used to control differential pressures down to
0.0040 ”WC or 1 Pa.
Key features of the FMS-1655 include:
• Full-color touchscreen display with programmable display options and adjustable backlight
• Intuitive user interface simplifies setup and configuration of unit
• Display background changes color to indicate room status at a glance
• Patented Safety Halo™ with color-coded
180° edge lighting
• Automated clean cycle with fully programmable duration for quick turnaround of patient or isolation room
• Audible and visual alarm annunciation
• Internal or remote sensor options available with up to four sensors total (one internal, three remotes OR four remotes)
• Auxiliary universal analog inputs for use with optional sensors
• Four independent PID control loops for controlling damper actuators, speed drives, hot water valves, humidifiers, etc.
• Digital input used to monitor the door switch of the monitored room
• Relay outputs used for transmitting alarm condition to remote location
• Dedicated thermistor inputs for temperature control applications
• Multi-level password protection of touchscreen user interface
• Zero calibration feature allows in-field recalibration of zero pressure reading
• Multi-protocol native (BACnet® or Metasys® N2) for easy integration with any BMS
• Manual override of analog and relay outputs assist with test and balance procedures
• Comprehensive real-time view
• Built-in diagnostics tool
• Easy-to-install backplane/backplate assembly facilitates permanent termination of all wiring
The FMS-1655 features enhanced graphics the patented Safety Halo.™ This simple yet elegant feature significantly enhances the alarm status indication of the FMS-1655 by providing full 180-degree visibility. The Safety Halo™ is shipped from the factory enabled at full brightness, but may be dimmed or even disabled completely from the display setup menus.
The FMS-1655 is equipped with a 3.2” diagonal full-color touchscreen display in portrait orientation (240 x 320). The password-protected menu tree is very intuitive and simplifies the setup and configuration of the unit. The menus incorporate touch-based interfaces such as sliders, radio buttons, and dialog popups to facilitate the ease-of-use of the FMS-1655.
The display implements bright graphical color changes to indicate the three different alarm status indications of the monitored isolation room. These graphical backgrounds indicate “Normal” when the differential pressure is within defined limits, “Warning” when the differential pressure is approaching an out-of-limits condition, and “Alarm” when the differential pressure is outside the defined acceptable and safe limits.
The differential pressure ranges for these conditions are easily configured by the user for the specific installation when necessary, either directly from the touchscreen display or over the network from the BMS. The graphical background changes provide an at-a-glance overview of the monitored isolation room differential pressure conditions.
Alarm conditions may be defined by the user, in terms of desired differential pressure settings for the room being monitored.
When an alarm condition occurs, it may be annunciated in four user-definable ways:
1) on the display, 2) with an audible alarm, and 3) transmitted via contacts to a remote monitoring station and 4) over the BMS network. The alarm will automatically reset when the unit has sensed that the room differential pressure has returned to proper limits. The attendant may easily mute the audible alarm by touching the alarm audible button on the bottom of the display.
For many applications, it is important to have other variables such as anteroom differential pressure or relative humidity displayed along with the isolation room differential pressure. The FMS-1655 provides for this by means of three additional universal analog inputs, which may be configured for either current loop operation or voltage input operation. Each input may be scaled as needed to display correct values, and may have an engineering units selection associated. The configuration of each analog input is field selectable through the use of miniature dipswitches on the controller unit.
- 3 -
Due to continuous improvement, JCI reserves the right to change product specifications without notice.
GENERAL
Overview
For those applications requiring monitoring and/or control based on temperature variances, the FMS-1655 provide two dedicated thermistor inputs in addition to the four universal analog inputs. Therefore, a total of six analog inputs are available for control applications. The two thermistor inputs may be used with negative temperature coefficient (NTC) Type 2 or Type 3 sensors. The FMS-1655 provides four universal analog outputs, which may be configured for either current loop operation or for voltage operation.
Each analog output may be configured for proportional operation to provide a linear signal to the BMS, or for PID (proportional­integral-derivative) control operation for closed-loop feedback control of damper actuators, variable frequency (speed) drives, hot water valves, humidifiers, or other analog­controlled devices.
Each universal analog output may be field­configured for the required application using onboard configuration dipswitches on the controller module. Each analog output may also be temporarily overridden using the built­in diagnostic tools for troubleshooting during the installation and commissioning phase.
The FMS-1655 provides four digital inputs that may be used for monitoring door switches, override switches, or other devices with binary outputs. The configuration and operation of each input may be configured by the user to define the effect of a change in its state. Each digital input may have a programmable delay duration associated with it. Each digital input may be configured for either normally-closed or normally-open operation, and may also be configured to be active-high or active-low triggered. The global configuration of the digital inputs is field selectable through the use of miniature dipswitches on the controller unit.
The FMS-1655 provides three relay outputs, which may be configured for either direct­acting or reverse-acting operation, and may have a programmable delay associated to meet the specific needs of the required application.
A unique feature of the FMS-1655 is its ability to trigger a relay output based on the current mode of isolation, thereby providing support for transfer grilles, supplemental exhaust dampers, etc. Each relay output may also be temporarily overridden using the built-in diagnostic tools for troubleshooting during the installation and commissioning phase.
The user may set up multiple multi-level passwords to prevent unauthorized or casual access to the FMS-1655 configuration settings. Up to 10 passwords of up to eight digits may be programmed, with each having one of four associated access levels. Administrators and facility management personnel may have unrestricted access, while general staff may be assigned restricted access passwords which limit the functionality of the user menus.
Room pressure selection of positive, negative, or neutral isolation may be protected using limited access passwords, thereby eliminating the need for keylock switches and keys.
An optional keylock switch may be used to further control access to change in isolation modes. In some locales, it is prohibitive to allow an isolation room controller to switch between positive and negative modes of isolation. To accommodate this situation, the FMS-1655 may be configured at the factory for either positive- and neutral-isolation modes only or negative- and neutral-isolation modes.
The FMS-1655 provides native support for multiple networking protocols, including BACnet® MS/TP and Metasys® N2 Open. With multi-protocol native support, the FMS­1655 is able to communicate room status information to the building automation system, regardless of which protocol is used. (For applications requiring LonWorks® networking capability, contact the factory about JCI’s FMS-1655L series) The configuration of the desired protocol is field selectable through the use of miniature dipswitches on the controller unit.
The FMS-1655 provides a unique set of built-in diagnostics tools that are extremely valuable for facilitating the troubleshooting process during the installation and commissioning phase.
Included in these built-in diagnostics tools are manual override capabilities for both analog outputs and relay outputs, and a comprehensive real-time view capability that allows the real-time values and states of each analog and digital input and output to be displayed conveniently. This is an extremely useful tool that facilitates the verification and certification processes conducted by typical test and balance personnel during the commissioning of the system.
There are also options for storing configuration settings and for restoring those settings, as well as performing a complete restoration of the factory default configuration settings.
The FMS-1655 incorporates an innovative backplane/backplate assembly which greatly facilitates the installation process and permits all wiring terminations to be permanent. The FMS-1655 serves as a direct drop-in functional replacement for all previous models of the FMS-1600 series of isolation monitors.
- 4 -
MOUNTING/WIRING
FMS-1655 Flush-Mount with Internal Sensor
Introduction
The FMS-1655 flush-mount model has an integrated internal sensor and should be installed outside of the isolation room to be monitored in the corridor wall. Sensor tubing should be between this corridor and isolation room in the most direct and shortest path.
The FMS-1655 is calibrated with configuration settings programmed at the factory according to the customer specifications, if provided. Otherwise, each unit is shipped with factory­default configuration settings. The user may change these settings by following the procedures outlined in the configuration/ programming section of this manual.
The electrical connections to the FMS-1655 are made via convenient terminal block connectors on the backplane/backplate assembly as shown on page 7. All wiring should conform to local regulations and to the National Electrical Code (NEC). Precautions must be taken to avoid running sensor wiring in the same conduit as line voltage or other conductors that supply highly inductive loads such as generators, motors, solenoids, contactors, and other sources of induced noise. Use 22 AWG or larger for all electrical wiring terminations.
Following the proper installation of the FMS­1655, apply power to the unit and confirm that you hear a brief chirp at the touchscreen display, which indicates that the display module is communicating with the controller module.
There will be a six second power up delay during which the Safety HaloTM will cycle through the following colors: red, green, blue, yellow, magenta, cyan, and white. After this power up delay, the unit will display a brief five second animation of the action icons, followed by the FMS-1655 splash screen. This splash screen displays the model number, electronic serial numbers, firmware version numbers, protocol selection, and current network address. The splash screen remains displayed for about 15 seconds, and then proceeds to the main differential pressure screen.
Mounting Procedure
1. Choose a location free of airflow obstructions, and minimal air turbulence. The installation should also avoid stagnant air or “short circuiting” of the supply air to the exhaust. Typically, the FMS-1655 should be installed at eye level. It should be mounted in a location that provides convenient access such that the display may be viewed with minimal glare and the touchscreen is easily accessible to facilitate silencing the unit in the event of an alarm.
The FMS-1655 is pre-configured at the factory with the Safety Halo™ status indicator bezel connected to the internal circuitry on the display board, and has been tested for proper operation. The Safety Halo™ should not be removed from the flush mount faceplate, as it may damage the internal circuitry and/or the bezel itself. Attempting to separate the Safety Halo™ from the flush mount faceplate will void the manufacturer’s warranty.
2. Before disassembling the flush-mount electronics assembly, locate the clear pressure tubing that extends from the lower corner of the metal backplate to the nipple at the inside face of the bottom of the faceplate and disconnect it. The other end of this tubing should remain attached to the right-angle barbed fitting at the lower corner of the metal backplate.
3. Disassemble the flush-mount electronics assembly by grasping the metal backplate and pulling it apart from the faceplate.
The metal backplate is attached to the backplane subassembly which incorporates all of the wiring termination points.
4. Run the conduit and all wiring according to local regulations and National Electrical Code.
IMPORTANT: Use the 24 VAC stepdown isolation transformer, provided with the unit, to power the FMS-1655; this will prevent inadvertent ground loop issues and other problems that might otherwise be encountered.
5. Pull slack from the tube on the opposite side of the wall as the backplane/backplate assembly is moved toward the wall for mounting. On the opposite side, the return air stainless base and louvered plate must be mounted as shown on page 10. Caulk behind the stainless mounting plate so that there may be no air flow through the wall. Mount the backplane/backplate assembly to the wall with the appropriate screws (and wall anchors if using the alternate installation method).
- 5 -
Due to continuous improvement, TRIATEK reserves the right to change product specifications without notice.
6. Terminate all electrical connections at the backplane taking note of the terminal labels. Note that the power connector is distinguished as it is of a different color and separated from the other connectors. The 45-degree positioned wire openings on the connectors should greatly facilitate the wire termination process.
7. On the opposite side of the wall, a length of pressure tubing will be protruding from the wall. Cut the tubing as needed to leave approximately two inches protruding. Press the tubing onto the barbed fitting of the flow tube mounting plate (see page 10). Push the mounting plate and tube toward the wall, forcing the excess into the wall space. Fasten the mounting plate to the wall using appropriate hardware.
MOUNTING/WIRING
SUBHEAD
FMS-1655 Flush-Mount with Internal Sensor
8. Mount the louvered stainless steel cover plate to the mounting plate with the screws supplied.
9. Apply power to the FMS-1655 and confirm that following a brief initialization sequence, the unit displays the room differential pressure and the Safety Halo™ status matches that of the main display screen. FMS-1655 units are shipped from the factory in neutral isolation mode.
- 6 -
MOUNTING/WIRING
Internal Sensor
The FMS-1655 is calibrated with settings programmed in the factory according to the customer specifications. The user can change the settings by using the instructions provided in the Quick Start section of this manual beginning on page 38.
- 7 -
MOUNTING/WIRING
Notes
- 8 -
Due to continuous improvement, TRIATEK reserves the right to change product specifications without notice.
JCI reserves the right to change product specifications without notice.
MOUNTING/WIRING
FMS-1655 With Remote Sensor
Introduction
The flexibility of the FMS-1655 provides for several different configurations with respect to the sensor location.
FMS-1655 models without an internal sensor include at least one remote sensor for measuring the differential pressure of the monitored room. This remote sensor module must be installed in the wall between the monitored isolation room and the adjoining corridor or anteroom.
The remote sensor module should be installed with the attached stainless steel mounting plate facing the isolation or patient room and the reference plate facing the corridor or anteroom. Please see illustrations on pages 10 and 11 for more details.
With this sensor orientation, a positive pressure value indicates that the isolation room is positive with respect to the corridor.
A 3-conductor (22 AWG) cable MUST be connected between the remote sensor module and the main controller module for each sensor included with the unit. The length of this cable should not exceed 1,000 feet.
The display unit may be installed outside the room, at the nurses’ station, in the engineering office, or at any other location as needed.
Mounting Procedure
1. Cut an opening in the wall of the isolation room to receive the supplied low voltage mounting bracket for the remote sensor electronics. Nominal hole dimensions are
3.65” H x 2.15” W.
2. Drill a 7/16” hole through the opposite wall for the flow tube as shown.
3. Bring the 3-conductor signal wire through the cut out.
4. Install the included low-voltage mounting bracket in the drywall opening, and pull the 3-conductor signal cable through the mounting bracket.
5. Push a length of flow tube through the back hole on through the 7/16” hole in the opposite wall.
6. Attach the flow tube to the sensor port. Then, push the tube and sensor module into place and secure to the mounting enclosure with two 6-32 x 3/4 screws supplied.
7. Install the louvered cover plate.
8. On the opposite side (corridor) attach the flow tube to the barbed fitting of the flow tube mounting plate.
9. Press the mounting plate into place, allowing the excess tube length to go into the wall space. Secure with the screws and anchors.
11. At the FMS-1655 backplane, assuming the colors of the 3-conductor signal cable being red, black, and green, connect the leads to the terminals as follows:
Red: Digital SNS_PWR Black: AGND Green: AI_1
If more than one remote sensor is being used with the FMS-1655, then each must be connected as above with the green leads connected to the subsequent analog input terminals AI_2 through AI_4.
12. Connect the 3-conductor signal cable to remote sensor as follows:
Red: +Vin Black: GND Green: Io
10. Install the louvered cover plate.
- 9 -
NCNCGNDNCNCIoNC
GND
+Vin
~
~
MOUNTING/WIRING
FMS-1655 with Standard Remote Sensor (9-Pin)
CORRIDOR
Gasket
Stainless Steel Flow Tube Mounting Plate
Wall Section
(cutaway view)
Flow Tube
When Flow Tube mounting plate is located directly opposite the sensor, flow tubing must be cut as short as possible to prevent kinks.
For connection of
transmitter to FMS-1655.
Terminal
Stainless Steel Mounting Plate
Gasket
Louvered Cover Plate
ISOLATION ROOM
NCNCGNDNCNCIoNC
GND
+Vin
Thin Silicone Caulking
(apply around tube and between stainless steel plate and wall to seal unit penetration)
~
~
Orange wall bracket
to be installed first
by using the rotating
clamps for secure
wall attachment.
Standard Remote Sensor Detail
(Side View)
- 10 -
To FMS-1655 Controller
MOUNTING/WIRING
FMS-1655 with Standard Remote Sensor (9-Pin)
Stainless Steel Flow Tube Mounting Plate
ISOLATION ROOM
Gasket
Thin Silicone Caulking
(apply around tube and between stainless steel plate and wall to seal unit penetration)
Sensor installation requires the use of a three conductor wire between the sensor and the main controller module.
Flow Tube
When Flow Tube mounting plate is located directly opposite the sensor, flow tubing must be cut as short as possible to prevent kinks.
Terminal
For connection of
transmitter to
FMS-1655 .
To FMS-1655 Controller
Wall Section
(cutaway view)
~
~
NCNCGNDNCNCIoNC
Rotating clamps secure
assembly to wall board
GND
Louvered Cover Plate
+Vin
Gasket
CORRIDOR
Stainless Steel Mounting Plate
Standard Remote Sensor Detail
(Bottom View)
- 11 -
MOUNTING/WIRING
Remote Sensor Conguration
The electrical connections to the FMS-1655 made via a convenient backplate/backplate assembly is shown below. All wiring should conform to the local regulations and National Electric Code. Take care not to run sensor wiring in the same conduit as the line voltage or other conductors that supply highly inductive loads such as generators, motors, solenoids, contactors, etc. Use 22AWG or larger.
{
Recommended 4-conductor connection: Belden 1325A
Step Down Isolation Transformer
(provided with FMS Controller)
Controller Configuration Dipswitch Settings
S1 - 1 = ON, S1 - 5 = OFF (AI - 1 set at 4 - 20mA Input)
- 12 -
MOUNTING/WIRING - INTERNAL SENSOR
Analog Output to Electric Damper Actuator
Step Down Isolation Transformer
(provided with FMS Controller)
Controller Configuration Dipswitch Settings
S1 - 2 = ON, S1 - 6 = OFF (AI - 2 set as 4 - 20mA Input)
S4 - 1 = ON (AO - 1 set as Voltage Output)
- 13 -
MOUNTING/WIRING - INTERNAL SENSOR
Analog Output to Pneumatic Damper Actuator
Optional remote sensor
Step Down Isolation Transformer
(provided with FMS Controller)
Controller Configuration Dipswitch Settings
S1 - 2 = ON, S1 - 6 = OFF (AI - 2 set as 4 - 20mA Input)
S4 - 1 = ON (AO - 1 set as Voltage Output)
Due to continuous improvement, TRIATEK reserves the right to change product specifications without notice.
- 14 -