Johnson Controls JXHX1252N, JXHX2452N, JXHX1852N, JXHX3652N, JXMHX1852N Engineering Manual

...
MINI 2-WAY
VARIABLE REFRIGERANT FLOW (VRF) SYSTEM
ENGINEERING GUIDE New Release Form 121.00-EG1 (512)
MINI 2-WAY
VARIABLE REFRIGERANT FLOW (VRF) SYSTEM
Issue Date:
May 25, 2012
IMPORTANT!
FORM 121.00-EG1 ISSUE DATE: 5/31/2012
JOHNSON CONTROLS
2
READ BEFORE PROCEEDING!
GENERAL SAFETY GUIDELINES
This equipment is a relatively complicated apparatus. During installation, operation maintenance or service, individuals may be exposed to certain components or conditions including, but not limited to: refrigerants, materials under pressure, rotating components, and both high and low voltage. Each of these items has the potential, if misused or handled improperly, to cause bodily injury or death. It is the obligation and respon­sibility of operating/service personnel to identify and recognize these inherent hazards, protect themselves, and proceed safely in completing their tasks. Failure to comply with any of these requirements could result in serious damage to the equipment and the property in which it is situated, as well as severe personal injury or death to themselves and people at the site.
This document is intended for use by owner-authorized operating/service personnel. It is expected that these individuals possess independent training that will en­able them to perform their assigned tasks properly and safely. It is essential that, prior to performing any task on this equipment, this individual shall have read and understood this document and any referenced mate­rials. This individual shall also be familiar with and comply with all applicable governmental standards and regulations pertaining to the task in question.
CHECK OF DENSITY LIMIT
The room in which the air conditioner is to be in­stalled requires a design that in the event of refrig­erant gas leaking out, its density will not exceed a set limit.
The refrigerant (R410A), which is used in the aircon­ditioner, is safe, without the toxicity or combustibil-
ity of ammonia, and is not restricted by laws imposed to protect the ozone layer. However, since it contains more than air, it poses the risk of suffocation if its den­sity should rise excessively. Suffocation from leakage of refrigerant is almost non-existent.
With the recent increase in the number of high density buildings, however, the installation of multi air condi­tioner systems is on the increase because of the need for effective use of floor space, individual control, en­ergy conservation by curtailing heat and carrying pow­er, etc. Most importantly, the multi air conditioner sys­tem is able to replenish a large amount of refrigerant compared to conventional individual air conditioners. If a single unit of the multi air conditioner system is to be installed in a small room, select a suitable model and installation procedure so that if the refrigerant ac­cidentally leaks out, its density does not reach the limit (and in the event of an emergency, measures can be made before injury can occur).
ASHRAE and the International Mechanical Code of the ICC as well as CSA provide guidance and define safeguards related to the use of refrigerants, all of which define a Refrigerant Concentration Level (RCL) of 25 pounds per 1,000 cubic feet for R410A refriger­ant. For additional guidance and precautions related to refrigerant safety, please refer to the following docu­ments:
International Mechanical Code 2009 (IMC-2009) (or more recently revised)
ASHRAE 15 ASHRAE 34
INDOOR UNIT NOMENCLATURE
FORM 121.00-EG1 ISSUE DATE: 5/31/2012
3
JOHNSON CONTROLS
J UMHX 12 62N
SERIES
CAPACITY
SLIM CONCEALED DUCT TYPE
JOHNSON CONTROLS
OUTDOOR UNIT NOMENCLATURE
J CHX R 036 52N
CAPACITY
SALT-AIR DAMAGE RESISTANT
2-WAY FLOW MINI
JOHNSON CONTROLS
SERIES
OUTDOOR UNITS
KEY CLASS 36 52
JCHX Variable Refrigerant Flow
System
Refrigerant R410A is used in the outdoor units.
* Salt-Air Damage Resistant Specications.
JCHX03652N
JCHXR03652N*
JCHX05252N
JCHXR05252N*
INDOOR UNITS
KEY CLASS 7 9 12 15 18 24 36 48 54
JX 4-Way Air
Discharge Semi-Con­cealed
JXM 4-Way Air
Discharge Mini Semi­Concealed
JA 1-Way Air Dis-
charge Semi­Concealed
JU Concealed
Duct Type
JUM Slim Concealed
Duct Type
JD Concealed-
Duct High Static Pressure
JT Ceiling-
Mounted
JK Wall-Mounted
Type
JF Floor-Standing
Type
JFM Concealed-
Floor Standing Type
JAHX0752N JAHX0952N JAHX1252N
JUHX0762N JUHX0962N JUHX1262N JUHX1562N JUHX1862N JUHX2462N JUHX3662N JUHX4862N JUHX5462N
JUMHX0762N JUMHX0962N JUMHX1262N JUMHX1562N JUMHX1862N
JKHX0752N JKHX0952N JKHX1252N JKHX1862N JKHX2452N
JFHX0762N JFHX0962N JFHX1262N JFHX1562N JFHX1862N JFHX2462N
JFMHX0762N JFMHX0962N JFMHX1262N JFMHX1562N JFMHX1862N JFMHX2462N
JXHX1252N JXHX1852N JXHX2452N JXHX3652N
JXMHX1252N JXMHX1852N
JDHX3652N JDHX4852N
JTHX1252N JTHX1852N JTHX2452N
TABLE OF CONTENTS
FORM 121.00-EG1 ISSUE DATE: 5/31/2012
JOHNSON CONTROLS
4
INTRODUCTION .......................................................................................................................................................5
1. OFFERINGS ........................................................................................................................................................14
2. OUTDOOR UNIT DIMENSIONS AND SPECIFICATIONS .................................................................................17
3. INDOOR UNIT DIMENSIONS AND SPECIFICATIONS .....................................................................................27
4-Way Air Discharge Ceiling Semi-Concealed, Standard And Mini (JX, JXM Type) ......................................26
1-Way Air Discharge Ceiling Semi-Concealed (JA Type) ...............................................................................47
Slim Concealed Duct, Standard and Slim (JU, JUM Type) ............................................................................56
Concealed Duct High Static Pressure (JD Type)............................................................................................94
Ceiling Mounted Exposed Horizontal (JT T ype) ...........................................................................................101
Wall Mounted Exposed (JK Type) ................................................................................................................ 111
Floor Exposed (JF Type) ............................................................................................ ..................................124
Floor Concealed (JFM Type) ........................................................................................................................139
4. FRESH AIR INTAKE, SEMI-CONCEALED DUCT AND CONCEALED DUCT TYPES ...................................156
5. ELECTRICAL WIRING .....................................................................................................................................158
6. OUTDOOR UNIT WIRING DIAGRAMS ............................................................................................................168
7. INDOOR UNIT WIRING DIAGRAMS ................................................................................................................171
8. CAPACITY RATIO OF OUTDOOR UNITS .......................................................................................................196
9. COOLING CAPACITY OF INDOOR UNITS .....................................................................................................204
Note: 1. All data herein is subject to change without notice.
2. Drawings and performance data should not be used for submittal purposes
INTRODUCTION
FORM 121.00-EG1 ISSUE DATE: 5/31/2012
5
JOHNSON CONTROLS
Suitability. Johnson Controls Mini 2-way Vari­able Refrigerant Flow (VRF) system is ideal for com­mercial office buildings subject to diverse loads and varying occupant levels. Also, the 2-way VRF system is ideal for schools, hotels, nursing homes and other commercial living spaces where occupants will want to control the temperature setting in their zone. In all cases the system runs quietly, for a comfortable, pro­ductive environment.
Zone Control.
In buildings with multiple zones that require separate comfort controls, you need options. Johnson Controls Mini 2-way (VRF) systems give you the heating and cooling flexibility you need, combined with the reliability and energy efficiency you expect from Johnson Controls. You get the freedom to create comfortable, efficient buildings, without being limited by ductwork runs.
Flexibility.
Johnson Controls Mini 2-way VRF sys­tems offer multiple configurations for both new and existing buildings. Multi-zone temperature control al­lows the system to handle diverse heating and cooling
loads, while giving occupants the ability to adjust tem­perature to satisfy their individual comfort needs. In addition, variable refrigerant flow heating and cooling uses energy efficiently, because VRF uses only refrig­erant without air or water as a heat transfer medium.
Installation.
Johnson Controls Mini 2-way VRF systems are modular which are easy to transport and install. As remodeling occurs and building extensions are planned, the VRF systems modularity allows to simply add on to the system within the system param­eters.
Control.
Johnson Controls Mini 2-way VRF sys­tems are available with a variety of zone controls and network controls that are responsive and provide im­mediate response to changes in zone loads. With wired controls, wireless controls and a network portal that supports BACnet®, LONWORKS® and Johnson Con­trols N2 protocols, the Mini 2-way VRF system will have the solution to meet the needs of the owners and tenants.
JOHNSON CONTROLS Mini 2-WAY VARIABLE
FORM 121.00-EG1 ISSUE DATE: 5/31/2012
JOHNSON CONTROLS
6
REFRIGERANT FLOW SYSTEM BENEFITS
Johnson Controls Mini 2-way Variable Refrigerant Flow (VRF) systems are easy to select with flexibility built in to the unit choices. With responsive controls and advanced inverter controlled compressor technol­ogy, they offer immediate response to changes in zone loads with the compressor precisely delivering the right amount of refrigerant to each zone. VRF systems pro­vide increased occupant comfort, with zone control, all occupants enjoy consistent room temperature regard­less of variations in load during the day. VRF systems provide efficient operation resulting in high COP’s, in excess of 4.0 at full load conditions.
Johnson Controls Mini 2-way VRF systems outdoor units have a modular design and compact footprint, choosing a Johnson Controls VRF system means easy installation and commissioning. With multiple unit connectivity, up to 9 indoor units can be connected to one condensing unit and the system takes advantage of building load diversity. Diversity ratios of 50% to 130% allow for a smaller outdoor unit. Johnson Con­trols Mini 2-way outdoor units come in 2 sizes, 3 ton and 4.4 ton.
OUTDOOR UNITS
FORM 121.00-EG1 ISSUE DATE: 5/31/2012
7
JOHNSON CONTROLS
• Ultra-quiet operation as low as 22 dBA
• Range from 3-4.4 tons
• 208/230 volt — single-phase power supply
• Modular design for increased capacity from com-
pact footprint
• Ultra quiet operation as low as 51d (dBA)
• Maximum piping lengths up to 984 feet
• Up to 9 indoor units can be connected
INDOOR UNITS
• Range from 7,500-48,000 btu
• 208/230 volt — single-phase power supply
•
Ceiling,wallandoormountedmodelsavailable
• Concealed, semi-concealed and exposed models
available
• All units can be controlled with any Johnson Con­trols VRF zone controller.
CONTROLS
• Variety of controls available, all provide control of mode, temperature, on/off and fan speed
• Remote unit controls
• Optional wireless remote controls
• Optional system diagnostics capability
• Network controls available
• Network portal that supports BACnet
®
, LON-
WORKS® and Johnson Controls N2 protocols.
• Standard operation uses return air sensor, but can
beconguredtousethesensorinthecontroller.
FEA TURES AND OPTIONS
FORM 121.00-EG1 ISSUE DATE: 5/31/2012
JOHNSON CONTROLS
8
• Flexible Piping Design:
Outdoor Unit Features and Options:
• Range from 3-4.4 tons
• 208/230V, Single Phase, 60Hz
• Environmentally responsible R-410A refrigerant
• Ultra quiet operation as low as 51dBA
• Modular design for easy installation and compact
footprint
• Up to 9 indoor units can be connected
• Wide Operating Range (Outdoor Ambient)
• Cooling 14 °F to 109 °F
• Heating -4 °F to 59 °F
• 656 Feet - Maximum Total Liquid Line
• 492 Feet - Maximum Outdoor To Most Dis-
tant Indoor Unit
• 164 Feet - Maximum Vertical Between In­door and Outdoor (Outdoor Above Indoor)
• 131 Feet - Maximum Vertical Between In­door and Outdoor (Outdoor Below Indoor)
Indoor Unit Features and Options:
High Wall Mounted (JKHX Type)
• Lowest indoor unit cost per Btuh of cooling
• Surface mounts on walls
• Bottom discharge – should be mounted at least 5’
abovetheoorand12”fromceiling
• Wireless remote ready – comes with built-in wire-
less receiver
•
Anti-moldwashablelter(notMERVrated)
• 3-speed AC motor (not ECM)
• Condensate pump not included
JKHX Series - High Wall Mounted Indoor Unit
LD16391
Ceiling Mounted Horizontal Exposed
FORM 121.00-EG1 ISSUE DATE: 5/31/2012
9
JOHNSON CONTROLS
(JTHX Type)
Low prole (8.5” tall) – great for commercial
•
spaces
• Mounts against ceiling with horizontal discharge
4 Way Air Discharge Semi-Concealed Cassette (JXHX and JXMHX Type)
• Great for large spaces 1and1.5tonunitstinthespaceofa2’X2’ceil-
• ing(JXMHXType)
•
Bottomreturn–canbemountedushwithwall
• Anti-moldwashablelter(notMERVrated)
• 3-speed DC motor (ECM)
• Condensate pump not included
JTHX Ceiling Mounted - Horizontal Exposed
1 Way Air Discharge Semi-Concealed Cassette (JAHX Type)
Only13”tall–tsintightceilingplenums
•
• Anti-moldwashablelter(notMERVrated)
• 3-speed DC motor (ECM)
• Condensate pump built in
LD16392
• 1, 1.5, 2 and 3 ton units available in 30" x 30" unit
size(JXHXType)
• Individual louvers can be disabled for use in cor-
ners
Anti-moldwashablelter(notMERVrated)
•
• 3-speed DC motor (ECM)
Condensatepumpwith25”liftbuiltin
•
LD16395
JXHX 4-Way Air Discharge - Semi-Concealed Cassette
Vertical Floor Mounted, Exposed (JFHX Type)
• Good choice for renovations where replacing heating only radiators
Airdischargedirectioniseasilycongured
•
• Front panel removes without tools for easy servic-
ing
Anti-moldwashablelter(notMERVrated)
•
• Pipes can be connected to either side of the unit
from the bottom or rear
• Wired controller can be mounted in the unit.
• Condensate pump not included
JAHX 1 Way Air Discharge - Semi-Concealed Cassette
LD16393
LD16394
JFHX - Vertical Floor-Mounted
Exposed
Vertical Floor Mounted, Concealed
FORM 121.00-EG1 ISSUE DATE: 5/31/2012
JOHNSON CONTROLS
10
(JFMHX Type)
SameastheJFHXExposed,butwithoutcasing
•
• Low external static – discharge grille should be
attached to the unit discharge with very little or no ducting
• Front panel removes without tools for easy servic­ing
Anti-moldwashablelter(notMERVrated)
•
• Pipes can be connected to either side of the unit
from the bottom or rear
• Condensate pump not included
Horizontal Concealed (JUHX Type)
High external static pressure up to 0.48” allows
• enhancedltrationorlongerductruns
• Industry-leading low sound levels from 22 dBA
• Condensate pump built in
• Easy to install and maintain
• 3 speed AC motor (not ECM)
•
Standardround8”takeoffscaneasilyberemoved
if a rectangular plenum is desired
LD16399
JUHX - Horizontal Concealed
LD16397
JFMHX - Vertical Floor-Mounted
Concealed
Horizontal Concealed Slim (JUMHX Type)
Ultra-slimprole:7.9incheshighforallmodels
•
• DC fan motor greatly reduces power consumption
(ECM)
• Ideal for any application with short plenums
•
Anti-mold washable lters included, but use of lterreturngrilleissuggested
• Easy maintenance and service by external electri-
cal box
• 0.16 in. w.g. static pressure enables ductwork to
betted
• Condensate pump built in
High Static Concealed Horizontal (JDHX Type)
High external static pressure up to 0.70” allows
• enhancedltrationorlongerductruns
• Can be used as 1:1 split system if required. Great
for large zones
• 3 speed AC motor (not ECM)
• Condensate pump not included
• This unit has a draw-through coil – a P-trap will
be required for the condensate
JUMHX - Horizontal Concealed Slim
LD16398
LD16400
JDHX - High-Static Horizontal Concealed
Controller features and options:
FORM 121.00-EG1 ISSUE DATE: 5/31/2012
11
JOHNSON CONTROLS
Simplied Wired Remote Control
• Cost effective individual zone control
• Thin and easy to read
• Simple to install – 2 low-voltage wires to the in-
door unit
• On / Off
• Mode Selection – choose heating, cooling, or auto
• Temperature set point
• Built in remote temperature sensor
•
Airowdirection(forindoorunitsthathavelou-
vers)
• Fan Speed Control
• 72 Hour Memory
Retention on Power Fail
• Mode Selection – choose heating, cooling, or auto
•
Airowdirection(forindoorunitsthathavelou-
vers)
• Fan speed control
• Controls up to 8 indoor units
LD16402
JRCS-TM80BGN - Standard Wired Remote Control
JRCS-KR1EGN - Simplified
Wired Remote Control
Standard Wired Remote Control
• Thin and Easy to Read
• Simple to install – 2 low-voltage wires to the in-
door unit
• Temperature set point
• 7 Day Timer, 6 time periods per day
• Temperature set-back
• Systems diagnostics capability (with connector
cable)
• Built in remote temperature sensor
LD16401
Wireless Remote Control
• Wireless unit for portable controls
• One remote can control many units
• On / Off
• Mode Selection – choose heating, cooling, or auto
• Temperature set point
•
Airowdirection(forindoorunitsthathavelou-
vers)
• Fan Speed Control
• Built in remote temperature sensor
•
Highwallmountedindoorunits(JKHX)havere-
ceivers built in, all other units require a receiver
thatmustbemountedintheeld
Wireless Remote Control
LD16497
Wired Remote Sensor
FORM 121.00-EG1 ISSUE DATE: 5/31/2012
JOHNSON CONTROLS
12
Schedule Timer
• Cost effective individual zone control
• Thin and easy to read
• Simple to install – 2 low-voltage wires to the in-
door unit
• Once installed and wired, the EEPROM automati­cally changes the control from the return sensor to the remote sensor
LD16404
JART-K45AGBN - Wired Remote Sensor
System Controller
• Capable of handling up to 64 indoor units
• 4 zones – each with up To 16 indoor units
• Up to 30 outdoor units to a single control line
• Can operate system without individual zone con-
trollers
• All zone control functionality is available
• Can take power from the U1/U2 system
• Important notes:
• No clock included
• Cannot be used for setback – addition of the
schedule timer only allows on/off control
• Timer controls up to 64 Units into 1,4, or 8 groups
• 7 Day Timer ,6 Time Periods/Day (On/Of f only , no
setback)
• 100 hour backup battery
• Usually tied to a System Controller, but can be
used stand-alone
LD16406
JSHA-TM64AGBN - Schedule Timer
Intelligent Controller
• Controls up to 128 units in two groups
• Up to 256 units / 4 groups with Communica-
tions Adapter
• 6.5 inch touch screen panel
• Web accessible
• Individual zone override
• Provides tenant billing data
• Available alarm contact
• Real time diagnostics
• Diagnostic history of system past & present
JSHA-KC64AGN - System Controller
LD16405
• Maximum installation of two System Controls
• Requires separate power supply
LD16407
OEM Portal
FORM 121.00-EG1 ISSUE DATE: 5/31/2012
13
JOHNSON CONTROLS
• BAS to VRF interface
• LONworks
®
or BACnet
®
• Only way to control a VRF system with BAS
• This allows communication between the propri-
etary VRF controls network and the BMS
• Field labor is required to add this to the BMS
LD16496
Indoor units
FORM 121.00-EG1 ISSUE DATE: 5/31/2012
JOHNSON CONTROLS
14
1. Offerings
Type
4-Way Air Discharge Semi­Concealed Type (JX Type)
4-Way Air Discharge Mini Semi-Concealed Type (JXM T ype)
1-Way Air Discharge Semi­Concealed Type (JA Type)
Concealed Duct Type (JU Type)
Slim Concealed Duct Type (JUM Type)
Concealed Duct High-Static Pressure Type (JD Type)
97 12 15 18 24 36 48 54
JXHX1252N JXHX1852N
JXMHX1252N JXMHX1852N
JAHX0752N
JUHX0762N JUHX1262NJUHX0962N JUHX1562N JUHX1862N JUHX2462N
JUMHX0762N JUMHX1262NJUMHX0962N JUMHX1562N JUMHX1862N
JAHX0952N JAHX1252N
JXHX2452N JXHX3652N
JUHX3662N JUHX4862N JUHX5462N
JDHX3652N
JDHX4852N
Ceiling-Mounted Type (JT Type)
Wall-Mounted Type (JK Type)
Floor-Standing Type (JF Type)
Concealed-Floor Standing Type (JFM Type)
JTHX1852NJTHX1252N JTHX2452N
JKHX0752N
JFHX0762N JFHX1262NJFHX0962N JFHX1562N JFHX1862N JFHX2462N
JFMHX0762N JFMHX1262NJFMHX0962N JFMHX1562N JFMHX1862N JFMHX2462N
JKHX0952N JKHX1252N JKHX2452NJKHX1862N
Indoor units
FORM 121.00-EG1 ISSUE DATE: 5/31/2012
15
JOHNSON CONTROLS
96
96,000 (28.1)96/
108,000 (31.6)
Type
Capacity: BTU/h (kW)
DC inverter unit
36 52
38,200 (11.2)
52,900 (15.5)
Cooling / Heating
Outdoor
Unit
13-3/8
11-21/32
48-7/16
/ 42,700 (12.5)
6-
11/16
2-
3/4
1/2 1/2
25-31/32
8-5/8
Air intake
1/2
5-29/32
Air discharge
37
1/2
4-
5/16
25/32
13/32
3-29/32
25/32
13/32
15-15/16
14-31/32
19/32
3-3/16
Air discharge
/ 60,000 (17.6)
Air intake
23/32
2-3/8
* Outdoor unit model name beginning with letters “JCHXR”
Refer to the Section 1. Salt-Air Damage Resistant Specications”.
6-13/16
5-1/2
7-3/4
4-23/32
6-9/16
2-25/32
JCHX03652/05252 JCHXR03652/05252*
JCHX03652N/05252N
JCHXR03652N/05252N*
23-5/8
22-9/16
5-9/16
1-13/32
2-3/8
4-11/32
5-1/8
4-3/4
2-27/32
7-25/32
6-5/8
Salt-Air Damage Resistant Specifications (Anti-Corrosion)
FORM 121.00-EG1 ISSUE DATE: 5/31/2012
JOHNSON CONTROLS
16
Relevant Parts Material Standard Specifications
Salt-Air Damage
Resistant Specifications
Outdoor unit model name beginning with letters "CHXR"
Outer box/side plate/ drain pan between the stud
Base frame
Fan guard
Fin Aluminum No treatment
Tube Copper No treatment Zinc rich treatment (whole)
Tube plate
Heat
Exchanger
Propeller fan
Fan
Motor Motor maker's standard spec.
Installation frame
Electrical component box
Tapping screws
Hot-dip zinc-coated steel sheet
Hot-dip aluminum-zinc coated steel sheet
Resin (Polypropylene) No treatment No treatment
Hot-dip zinc-coated steel sheet
Resin
Aluminum
Hot-dip zinc-coated steel sheet
--
Hot-dip zinc-coated steel sheet
Hot-dip zinc-coated steel sheet
SUS410
Polyester powder double coating (both sides) ( 40 m)
No treatment
No treatment
No treatment
No treatment
No treatment
Polyester powder double coating (both sides) ( 120 m)
No treatment
Hexavalent chromium-free coating
Polyester powder double coating (both sides) ( 120 m)
Polyester powder double coating (both sides) ( 120 m)
Zinc rich treatment
Zinc rich treatment (whole)
No treatment
Urethane coating ( 30 m)
Urethane coating ( 30 m)
Motor maker's spec. for salt-air damage resistant (urethane coating)
Polyester powder double coating (both sides) ( 120 m)
Polyester powder coating ( 120 m)
Hexavalent chromium-free coating + urethane coating
2
3
Stud supplementary bracket
PC board No treatment Dessicant coating ( 30 m)--
Accumulator Receiver tank
Welded portion Copper tube No treatment Urethane coating
Outer surface Copper tube No treatment Urethane coating
Refrigeration
cycle tube
Fixing bracket
Notes:
1 Consult us before introducing a salt-air damage resistant model as it requires a special treatment. 2 The specifications are subject to change without notice for development. 3 Contact us for the delivery schedule.
Hot-dip zinc-coated steel sheet
Steel Epoxy coating + alkyd coating
Hot-dip zinc-coated steel sheet
No treatment
No treatment
Polyester powder double coating ( 120 m)
Zinc rich double coating + urethane coating ( 70 m)
Polyester powder double coating (both sides) ( 80 m)
4
5
6
7
8
1-1. Specications
FORM 121.00-EG1 ISSUE DATE: 5/31/2012
17
JOHNSON CONTROLS
2. Outdoor Unit Dimensions and Specifications
Unit specications (A)
MODEL No.
POWER SOURCE
PERFORMANCE
Capacity
Outdoor Unit JCHX03652N, JCHXR03652N*
208 - 230 V / 1ø / 60 Hz
Cooling Heating
BTU / h 38,200 42,700
kW 11.2 12.5
Air circulation (Hi) CFM 3,530
1
ELECTRICAL RATINGS
Voltage rating V 208 230 208 230
Available voltage range V 187 - 253 187 - 253
Running amperes A 14.6 13.6 14.6 13.6
Max. running amperes * A 23.6 23.6
Power input kW 2.76 2.76 2.88 2.88
Max. power input kW 4.85 4.85
Power factor % 91 88 95 92
Max. starting amperes A Approx. 1 Approx. 1 Approx. 1 Approx. 1
FEATURES
Controls Microprocessor
Defrost control Reverse cycle, microprocessor control
Service function
Sensor temp. recall function
Past service warnings recall function
Refrigerant amount at shipment lbs. (kg) R410A - 7.7 (3.5)
Refrigerant control Electronic expansion valve
Operation sound (Hi)
Power level
Pressure level 51
dB-A
67
External finish Galvanized steel plate with powder paint
Color (Approximate value) Munsell code 1Y 8.5 /0.5
Refrigerant tubing
Limit of tubing length ft. (m) 492 (150)
Limit of elevation difference
between the 2 units
Refrigerant tube diameter
Liquid tube in. (mm) 3/8 (9.52)
Gas tube in. (mm) 5/8 (15.88)
ft. (m)
Refrigerant tubing kit / Joint kit Optional
DIMENSIONS & WEIGHT
Height in. (mm) 48-7/16 (1230)
Unit dimensions
Net weight lbs. (kg) 229 (104)
Shipping weight lbs. (kg) 247 (112)
Shipping volume ft
Rated conditions
Cooling : Indoor air temperature 80°F DB / 67°F WB ; Outdoor air temperature 95°F DB Heating : Indoor air temperature 70°F DB ; Outdoor air temperature 47°F DB / 43°F WB
* Full-load conditions at Indoor / Outdoor capacity ratio 100%
Cooling : Indoor air temperature 89°F DB / 73°F WB ; Outdoor air temperature 109°F DB / 78°F WB
1
*
Outdoor unit model name beginning with letters "JCHXR"
Refer to the Section 1 "Salt-Ait Damage Resistant Specications".
Width in. (mm) 37 (940)
Depth in. (mm) 13-13/32 (340)
3 (m3
) 19.8 (0.56)
Outdoor unit is higher than indoor unit : 164 (50)
Outdoor unit is lower than indoor unit : 131 (40)
Unit dimensions
Package dimensions
52-13/32 (1331)
40 (1016)
16-11/32 (415)
DATA SUBJECT TO CHANGE WITHOUT NOTICE
Unit specications (B)
FORM 121.00-EG1 ISSUE DATE: 5/31/2012
JOHNSON CONTROLS
18
MODEL No.
POWER SOURCE
PERFORMANCE
Capacity
Outdoor Unit JCHX05252N, JCHXR05252N*
208 - 230 V / 1ø / 60 Hz
Cooling Heating
BTU / h 52,900 60,000
kW 15.5 17.6
Air circulation (Hi) CFM 3,530
1
ELECTRICAL RATINGS
Voltage rating V 208 230 208 230
Available voltage range V 187 - 253 187 - 253
Running amperes A 23.5 21.9 23.5 21.9
Max. running amperes * A 28.0 28.0
Power input kW 4.57 4.57 4.58 4.58
Max. power input kW 5.72 5.72
Power factor % 93 91 94 91
Max. starting amperes A Approx. 1 Approx. 1 Approx. 1 Approx. 1
FEATURES
Controls Microprocessor
Defrost control Reverse cycle, microprocessor control
Service function
Sensor temp. recall function
Past service warnings recall function
Refrigerant amount at shipment lbs. (kg) R410A - 7.7 (3.5)
Refrigerant control Electronic expansion valve
Operation sound (Hi)
Power level
Pressure level 52
dB-A
68
External finish Galvanized steel plate with powder paint
Color (Approximate value) Munsell code 1Y 8.5 /0.5
Refrigerant tubing
Limit of tubing length ft. (m) 492 (150)
Limit of elevation difference
between the 2 units
Refrigerant tube diameter
Liquid tube in. (mm) 3/8 (9.52)
Gas tube in. (mm) 3/4 (19.05)
ft. (m)
Refrigerant tubing kit / Joint kit Optional
DIMENSIONS & WEIGHT
Height in. (mm) 48-7/16 (1230)
Unit dimensions
Net weight lbs. (kg) 229 (104)
Shipping weight lbs. (kg) 247 (112)
Shipping volume ft
Width in. (mm) 37 (940)
Depth in. (mm) 13-13/32 (340)
3 (m3
) 19.8 (0.56)
Outdoor unit is higher than indoor unit : 164 (50)
Outdoor unit is lower than indoor unit : 131 (40)
Unit dimensions
Package dimensions
52-13/32 (1331)
40 (1016)
16-11/32 (415)
DATA SUBJECT TO CHANGE WITHOUT NOTICE
Rated conditions
Cooling : Indoor air temperature 80°F DB / 67°F WB ; Outdoor air temperature 95°F DB Heating : Indoor air temperature 70°F DB ; Outdoor air temperature 47°F DB / 43°F WB
* Full-load conditions at Indoor / Outdoor capacity ratio 100%
Cooling : Indoor air temperature 89°F DB / 73°F WB ; Outdoor air temperature 109°F DB / 78°F WB
1
*
Outdoor unit model name beginning with letters "JCHXR"
Refer to the Section 1 "Salt-Ait Damage Resistant Specications".
1-2. Major Component Specications
FORM 121.00-EG1 ISSUE DATE: 5/31/2012
19
JOHNSON CONTROLS
Specifications Unit Specifications (1)
Outdoor unit (A)
MODEL No.
POWER SOURCE
Controller P.C.B Assembly
Control circuit fuse 250V, 5A
Compresser
Type Rotary (Hermetic)
Model ... Code No. C-9RVN273H0W ... 80867080
Motor rated output kW 2.1
Compressor Oil (ETHER FV68S) gal (cc) 0.50 (1,900)
Coil resistance
(Ambient temperature 77°F)
Safety devices
Overload protector
(Operating temperature)
Microprocessor safety devices
Crank case heater V, W 230, 30
Open°F (°C) 230 (110)
Close°F (°C) 203 (95)
Compressor discharge gas temperature control
JCHX03652N, JCHXR03652N*
208 - 230 V / 1ø / 60 Hz
CR-CHX03652
INV (Inverter)
V - U: 0.169, U-W: 0.169,
W-V: 0.169
Compressor current detection circuit
High pressure switch
Set pressure ON / OFF in. WG 456 / 551
Fan...(Number diameter / length in. (mm))
Propeller (1 ... ø18-7/64 (ø460)) ×2
Fan motor
Model No. DAJ12-95B61A, B-CR
Source DC340V / 3 phase
No. of pole 8
Nominal output W 90
Coil resistance
(Ambient temperature 68°F)
Safety device
Operating temperature
Run capacitor VAC, μF
Open°F (°C) 284 (140)
Close°F (°C)
RED - WHT : 30.5 WHT - BLK : 30.5
BLK - RED : 30.5
Heat exchanger
Coil Aluminum plate fin / Copper tube
Rows...fin pitch in. (mm) 3 ... 7/128 (1.4)
Face area ft
* Outdoor unit model name beginning with letters “JCHXR”
Refer to the Section 1 “2. Salt-Air Damage Resistant Specications”.
2 (m2
) 11.7 (1.08)
DATA SUBJECT TO CHANGE WITHOUT NOTICE
Outdoor unit (B)
FORM 121.00-EG1 ISSUE DATE: 5/31/2012
JOHNSON CONTROLS
20
Unit Specifications (2)
MODEL No.
POWER SOURCE
Controller P.C.B Assembly
Control circuit fuse 250V, 5A
Compresser
Type Rotary (Hermetic)
Model ... Code No. C-9RVN273H0W ... 80867080
Motor rated output kW 4.0
Compressor Oil (ETHER FV68S) gal (cc) 0.50 (1,900)
Coil resistance
(Ambient temperature 77°F)
Safety devices
Overload protector
(Operating temperature)
Microprocessor safety devices
Crank case heater V, W 230, 30
Open°F (°C) 230 (110)
Close°F (°C) 203 (95)
Compressor discharge gas temperature control
JCHX05252N, JCHXR05252N*
208 - 230 V / 1ø / 60 Hz
CR-CHX06052
INV (Inverter)
V - U: 0.169, U-W: 0.169,
W-V: 0.169
Compressor current detection circuit
High pressure switch
Set pressure ON / OFF in. WG 456 / 551
Fan...(Number diameter / length in. (mm))
Propeller (1 ... ø18-7/64 (ø460)) ×2
Fan motor
Model No. DAJ12-95B61A, B-CR
Source DC340V / 3 phase
No. of pole 8
Nominal output W 90
Coil resistance
(Ambient temperature 68°F)
RED - WHT : 30.5 WHT - BLK : 30.5
BLK - RED : 30.5
Safety device
Operating temperature
Run capacitor VAC, μF
Open°F (°C) 284 (140)
Close°F (°C)
Heat exchanger
Coil Aluminum plate fin / Copper tube
Rows...fin pitch in. (mm) 3 ... 7/128 (1.4)
Face area ft
2 (m2
) 11.7 (1.08)
* Outdoor unit model name beginning with letters “JCHXR”
Refer to the Section 1 “2. Salt-Air Damage Resistant Specications”.
DATA SUBJECT TO CHANGE WITHOUT NOTICE
6-11/16
13-3/8
11-21/32
25/32
13/32
14-31/32
15-15/16
13/32
19/32
25-31/32
37
Air
discharge
8-5/8 5-29/32
1/2 1/2
1/21/2
2-
3/4
4-5/16
1
2
3
4
5
6
7
8
9
2-7/32
4-19/32
11-11/32
10-25/32
5/16
2-3/8
2-7/16
R1-3/16
R3/4
7
8
7
6
5
4
7
8
3-7/16
2-1/4
1-13/16
7
6
5
4
1-13/32
2-3/8
4-11/32
5-1/8
7-25/32
5-9/16 23-5/8
22-9/16
6-13/16
3-3/16
2-25/32
48-7/16
23/32
4-23/32
5-1/2
6-9/16
7-3/4
6-5/8
8-15/16
8-9/32
7-8/32
6-11/16
5-29/32
4-3/4
2-27/32
Air
intake
Air
discharge
7
8
2
3
9
3-29/32
25/32
6
5
2-3/8
7
4
Air intake
Installation anchoring hole (4-R6.5 or R1/4"), anchor bolt: M10 or 13/32''
Refrigerant tubing (liquid tube), flared connection ø3/8'' (ø9.52)
Refrigerant tubing (gas tube), flared connection ø5/8'' (ø15.88)
Refrigerant tubing port
Electrical wiring port ø1-3/8'' (ø35)
Electrical wiring port ø1-7/64'' (ø28)
Electrical wiring port ø55/64'' (ø22)
Electrical wiring port ø33/64'' (ø13)
Auxiliary connection tube ø5/8'' to ø3/4'' (ø15.88 to ø19.05) 6 hp only
2 x ø32 or ø1/4'' holes (holes for drain)
Of the 4 ø32 or ø1/4'' holes, use 1 of the 2 holes specified
for drain use to install the drain port.
Use rubber plugs to seal the remaining 3 holes.
1
For R410A only
Unit: inch
1-3. Dimensional Data
FORM 121.00-EG1 ISSUE DATE: 5/31/2012
21
JOHNSON CONTROLS
JCHX03652N, JCHXR03652N JCHX05252N, JCHXR05252N
1-4. Refrigerant Flow Diagram
FORM 121.00-EG1 ISSUE DATE: 5/31/2012
JOHNSON CONTROLS
22
JCHX03652N JCHXR03652N JCHX05252N JCHXR05252N
Suction
1-5. Sound Data
NOTE
Model
Sound Power Level
Condition
Sound Power Level (dB)
Frequency at center of sound pressure band (Hz)
JCHX03652N, JCHXR03652N
67 dB (A) Cooling
10
20
30
40
50
60
70
80
NC – 70
NC – 60
NC – 50
NC – 40
NC – 30
NC – 20
63 125 250 500 1000 2000 4000 8000
90
1. dBA = A – weighted sound power level (A – scale according to IEC)
2. Reference acoustic intensity 0 dB = 10
–13
W/ft
2
FORM 121.00-EG1 ISSUE DATE: 5/31/2012
23
JOHNSON CONTROLS
JCHDZ07263N
JCHDZR07263N
JCHDZ09663N
JCHDZR09663N
(1) Sound Power Level
JCHX03652N, JCHXR03652N
NOTE
Model
SoundPower Level
Condition
SoundPowerLevel(dB)
JCHX05252N,JCHXR05252N
68dB(A) Cooling
10
20
30
40
50
60
70
80
NC‒70
NC‒60
NC‒50
NC‒40
NC‒30
NC‒20
63 125 250 500 1000 2000 4000 8000
90
Frequencyatcenterofsoundpressureband(Hz)
1.dBA=A‒weightedsoundpowerlevel(A‒scaleaccordingtoIEC)
2.Referenceacousticintensity0dB=10
‒13
W/ft
2
JCHX05252N, JCHXR05252N
FORM 121.00-EG1 ISSUE DATE: 5/31/2012
JOHNSON CONTROLS
24
Octave Band Level (dB)*
* 0 dB = 0.0002 µbar
Frequency at center of sound pressure band (Hz)
Front
Quiet Mode
10
20
30
40
50
60
70
80
NC – 70
NC – 60
NC – 50
NC – 40
NC – 30
NC – 20
63
Overall
125 250 500 1000 2000 4000 8000
90
Approximate minimum audible limit for continuous noise
(2) Sound Pressure Level
FORM 121.00-EG1 ISSUE DATE: 5/31/2012
25
JOHNSON CONTROLS
JCHDZ07263N, JCHDZR07263N
JCHDZ09663N, JCHDZR09663N
JCHX0352N, JCHXR03652N
Model
Sound Pressure Level Cooling
Condition
JCHX03652N, JCHXR03652N
Front 51 dB (A) Quiet Mode 48 dB (A)
3.3 ft. in front at height of 4.9 ft.
Model
Sound Pressure Level Cooling
Condition
Octave Band Level (dB)*
* 0 dB = 0.0002 µbar
Frequency at center of sound pressure band (Hz)
JCHX05252N, JCHXR05252N
Front 52 dB (A) Quiet Mode 49 dB (A)
Front
Quiet Mode
3.3 ft. in front at height of 4.9 ft.
10
20
30
40
50
60
70
80
NC – 70
NC – 60
NC – 50
NC – 40
NC – 30
NC – 20
63 125 250 500 1000 2000 4000 8000
90
Approximate minimum audible limit for continuous noise
Overall
JCHX05252N, JCHXR05252N
FORM 121.00-EG1 ISSUE DATE: 5/31/2012
JOHNSON CONTROLS
26
MODEL No.
FORM 121.00-EG1 ISSUE DATE: 5/31/2012
27
JOHNSON CONTROLS
3. Indoor Unit Dimensions and Specifications
4-Way Air Discharge Ceiling Semi-Concealed, Standard and Mini (JX, JXM Types) Unit specifications (A)
POWER SOURCE
PERFORMANCE
Capacity
Air circulation (Hi / Me / Lo) CFM 550 / 495 / 450
Moisture removal (High) Pints / h 4.65
ELECTRICAL RATINGS
Voltage rating V 208 230 208 230
Available voltage range V 187 - 253 187 - 253
Running amperes A 0.19 0.22 0.21 0.21
Power input W 26 29 19 20
Power factor % 66 57 43 41
Max. starting amperes A 1111
FEATURES
Controls Microprocessor
Fan speeds 3 and Automatic control
Air filter Washable, easy access, long life (2,500 hr)
Refrigerant control Electronic expansion valve
Operation sound (
Refrigerant tubing connections Flare type
Refrigerant tube diameter
Drain connection 25 A, OD 1-1/4"
Drain pump Max. head 2.1 ft. above drain connection
Panel Optional (JPNR-XH3652N)
Remote controller Optional (JRCS-TM80BGN, JRCS-SH80AABWLN)
Refrigerant tubing kit / Accessories Optional / –
Color (Approximate value) Munsell 2.5GY 9.0 / 0.5, RAL 9001-GL (resemblant color)
DIMENSIONS & WEIGHT
Unit dimensions
Net weight lbs. (kg) 56 (25.5)
Shipping weight lbs. (kg) 53 (24) 16 (7)
Shipping volume ft
Hi / Me / Lo
Liquid tube in. (mm) 1 / 4 (6.35)
Gas tube in. (mm) 1 / 2 (12.7)
Height in. (mm) 11-15 / 32 (291)
Width in. (mm) 37-13 / 32 (950)
Depth in. (mm) 37-13 / 32 (950)
Indoor Unit JXHX1252N
208 - 230 V / 1ø / 60 Hz
Cooling Heating
BTU / h 12,000 14,000
kW 3.6 4.2
) dB-A 31 / 29 / 27
Indoor unit (including panel)
11-5 / 32 (283)
35-1 / 8 (892)
35-5 / 8 (905) 38-31 / 32 (990)
3 (m3
) 8.1 (0.228) 3.8 (0.104)
Package
Body Panel
4-3 / 32 (104)
39-11 / 16 (1008)
1
2
3
4
5
6
Rated conditions
Cooling : Indoor air temperature 80°F DB / 67°F WB ; Outdoor air temperature 95°F DB
Heating : Indoor air temperature 70°F DB ; Outdoor air temperature 47°F DB / 43°F WB
7
8
2
FORM 121.00-EG1 ISSUE DATE: 5/31/2012
JOHNSON CONTROLS
28
4-Way Air Discharge Ceiling Semi-Concealed, Standard and Mini (JX, JXM Types) Unit specifications (B)
3
4
5
MODEL No. POWER SOURCE PERFORMANCE
Capacity
Air circulation (Hi / Me / Lo) CFM 565 / 495 / 450
Moisture removal (High) Pints / h 4.65
ELECTRICAL RATINGS
Voltage rating V 208 230 208 230
Available voltage range V 187 - 253 187 - 253
Running amperes A 0.23 0.26 0.23 0.22
Power input W 30 33 25 25
Power factor % 63 55 52 49
Max. starting amperes A 1111
FEATURES
Controls Microprocessor
Fan speeds 3 and Automatic control
Air filter Washable, easy access, long life (2,500 hr)
Refrigerant control Electronic expansion valve
Operation sound (
Refrigerant tubing connections Flare type
Refrigerant tube di­ameter
Drain connection 25 A, OD 1-1/4"
Drain pump Max. head 2.1 ft. above drain connection
Panel Optional (JPNR-XH3652N)
Remote controller Optional (JRCS-TM80BGN, JRCS-SH80AABWLN)
Refrigerant tubing kit / Accessories Optional / –
Color (Approximate value) Munsell 2.5GY 9.0 / 0.5, RAL 9001-GL (resemblant color)
DIMENSIONS & WEIGHT
Unit dimensions
Net weight lbs. (kg) 56 (25.5)
Shipping weight lbs. (kg) 53 (24) 16 (7)
Shipping volume ft
Hi / Me / Lo
Liquid tube in. (mm) 1 / 4 (6.35)
Gas tube in. (mm) 1 / 2 (12.7)
Height in. (mm) 11-15 / 32 (291)
Width in. (mm) 37-13 / 32 (950)
Depth in. (mm) 37-13 / 32 (950)
Indoor Unit JXHX1852N
208 - 230 V / 1ø / 60 Hz
Cooling Heating
BTU / h 19,000 21,000
kW 5.6 6.3
) dB-A 31 / 29 / 27
Indoor unit (including panel)
11-5 / 32 (283)
35-1 / 8 (892)
35-5 / 8 (905) 38-31 / 32 (990)
3 (m3
) 8.1 (0.228) 3.8 (0.104)
Package
Body Panel
4-3 / 32 (104)
39-11 / 16 (1008)
6
7
8
Rated conditions
Cooling : Indoor air temperature 80°F DB / 67°F WB ; Outdoor air temperature 95°F DB
Heating : Indoor air temperature 70°F DB ; Outdoor air temperature 47°F DB / 43°F WB
MODEL No.
FORM 121.00-EG1 ISSUE DATE: 5/31/2012
29
JOHNSON CONTROLS
4-Way Air Discharge Ceiling Semi-Concealed, Standard and Mini (JX, JXM Types) Unit specifications (C)
POWER SOURCE PERFORMANCE
Capacity
Air circulation (Hi / Me / Lo) CFM 705 / 565 / 495
Moisture removal (High) Pints / h 5.92
ELECTRICAL RATINGS
Voltage rating V 208 230 208 230
Available voltage range V 187 - 253 187 - 253
Running amperes A 0.29 0.26 0.30 0.31
Power input W 38 40 33 33
Power factor % 63 67 39 46
Max. starting amperes A 1111
FEATURES
Controls Microprocessor
Fan speeds 3 and Automatic control
Air filter Washable, easy access, long life (2,500 hr)
Refrigerant control Electronic expansion valve
Operation sound (
Refrigerant tubing connections Flare type
Refrigerant tube di­ameter
Drain connection 25 A, OD 1-1/4"
Drain pump Max. head 2.1 ft. above drain connection
Panel Optional (JPNR-XH3652N)
Remote controller Optional (JRCS-TM80BGN, JRCS-SH80AABWLN)
Refrigerant tubing kit / Accessories Optional / –
Color (Approximate value) Munsell 2.5GY 9.0 / 0.5, RAL 9001-GL (resemblant color)
DIMENSIONS & WEIGHT
Unit dimensions
Net weight lbs. (kg) 58 (26.5)
Shipping weight lbs. (kg) 53 (24) 16 (7)
Shipping volume ft
Hi / Me / Lo
Liquid tube in. (mm) 3 / 8 (9.52)
Gas tube in. (mm) 5 / 8 (15.88)
Height in. (mm) 11-15 / 32 (291)
Width in. (mm) 37-13 / 32 (950)
Depth in. (mm) 37-13 / 32 (950)
Indoor Unit JXHX2452N
208 - 230 V / 1ø / 60 Hz
Cooling Heating
BTU / h 25,000 27,000
kW 7.3 8.0
) dB-A 34 / 31 / 28
Indoor unit (including panel)
11-5 / 32 (283)
35-1 / 8 (892)
35-5 / 8 (905) 38-31 / 32 (990)
3 (m3
) 8.1 (0.228) 3.8 (0.104)
Package
Body Panel
4-3 / 32 (104)
39-11 / 16 (1008)
1
2
3
5
Rated conditions
Cooling : Indoor air temperature 80°F DB / 67°F WB ; Outdoor air temperature 95°F DB
Heating : Indoor air temperature 70°F DB ; Outdoor air temperature 47°F DB / 43°F WB
6
7
8
2
FORM 121.00-EG1 ISSUE DATE: 5/31/2012
JOHNSON CONTROLS
30
4-Way Air Discharge Ceiling Semi-Concealed, Standard and Mini (JX, JXM Types) Unit specifications (D)
3
4
5
MODEL No. POWER SOURCE PERFORMANCE
Capacity
Air circulation (Hi / Me / Lo) CFM 990 / 810 / 740
Moisture removal (High) Pints / h 8.24
ELECTRICAL RATINGS
Voltage rating V 208 230 208 230
Available voltage range V 187 - 253 187 - 253
Running amperes A 0.51 0.46 0.54 0.49
Power input W 74 79 76 76
Power factor % 70 75 68 67
Max. starting amperes A 1111
FEATURES
Controls Microprocessor
Fan speeds 3 and Automatic control
Air filter Washable, easy access, long life (2,500 hr)
Refrigerant control Electronic expansion valve
Operation sound (
Refrigerant tubing connections Flare type
Refrigerant tube di­ameter
Drain connection 25 A, OD 1-1/4"
Drain pump Max. head 2.1 ft. above drain connection
Panel Optional (JPNR-XH3652N)
Remote controller Optional (JRCS-TM80BGN, JRCS-SH80AABWLN)
Refrigerant tubing kit / Accessories Optional / –
Color (Approximate value) Munsell 2.5GY 9.0 / 0.5, RAL 9001-GL (resemblant color)
DIMENSIONS & WEIGHT
Unit dimensions
Net weight lbs. (kg) 58 (26.5)
Shipping weight lbs. (kg) 66 (30) 16 (7)
Shipping volume ft
Hi / Me / Lo
Liquid tube in. (mm) 3 / 8 (9.52)
Gas tube in. (mm) 5 / 8 (15.88)
Height in. (mm) 13-15 / 16 (354) 13-5 / 8 (346) 4-3 / 32 (104)
Width in. (mm) 37-13 / 32 (950) 35-1 / 8 (892)
Depth in. (mm) 37-13 / 32 (950) 35-5 / 8 (905)
Indoor Unit JXHX3652N
208 - 230 V / 1ø / 60 Hz
Cooling Heating
BTU / h 36,000 39,000
kW 10.6 11.4
) dB-A 39 / 36 / 33
Indoor unit (including panel)
3 (m3
) 9.9 (0.279) 3.8 (0.104)
Package
Body Panel
39-11 / 16 (1008)
38-31 / 32 (990)
6
7
8
Rated conditions
Cooling : Indoor air temperature 80°F DB / 67°F WB ; Outdoor air temperature 95°F DB
Heating : Indoor air temperature 70°F DB ; Outdoor air temperature 47°F DB / 43°F WB