Johnson Controls HC-67x3 Installation Guide

24-7701-179, Rev. B
100% RHSetpoint
10
0
0
5
V Out
Proportional
Band
Note: The actual output voltage may exceed 10 VDC.
Installation Instructions HC-67x3 Issue Date March 2016
HC-67x3 Humidity Controllers

Application Requirements

The HC-67x3 Humidity Controllers proportionally ramp their output as the humidity changes in the proportional band. The setpoint is at the low end of the proportional band for Direct Acting (DA) and at the high end for Reverse Acting (RA) (shown in Figure 1) for both wall mount and duct probe humidity controllers.
Figure 1: 0 to 10 Volt, RA Application
Configure the controller prior to installation for the following: setpoint, proportional band, action, and output signal. Proceed to the appropriate controller section.

Installation

IMPORTANT: The HC-67x3 Series Humidity
Controllers is intended to provide an input to equipment under normal operating conditions. Where failure or malfunction of the HC-67x3 Series Humidity Controllers could lead to personal injury or property damage to the controlled equipment or other property, additional precautions must be designed into the control system. Incorporate and maintain other devices, such as supervisory or alarm systems or safety or limit controls, intended to warn of or protect against failure or malfunction of the HC-67x3 Ser i es Humidity Controllers.
IMPORTANT: Le HC-67x3 Series Humidity Controllers est destiné à transmettre des données entrantes à un équipement dans des conditions normales de fonctionnement. Lorsqu'une défaillance ou un dysfonctionnement du HC-67x3 Series Humidity Controllers risque de provoquer des blessures ou d'endommager l'équipement contrôlé ou un autre équipement, la conception du système de contrôle doit intégrer des dispositifs de protection supplémentaires. Veiller dans ce cas à intégrer de façon permanente d'autres dispositifs, tels que des systèmes de supervision ou d'alarme, ou des dispositifs de sécurité ou de limitation, ayant une fonction d'avertissement ou de protection en cas de défaillance ou de dysfonctionnement du HC-67x3 Series Humidity Controllers.
The controller is available in both a wall mount or duct probe package to suit a variety of sensing application needs. Refer to the Mounting section for a complete list of the tools required for installation.

Parts Included

mounting base for U.S. wallbox or surface mounting
No. 6-32 x 7/8 in. oval-head screw (2)
No. 4-40 x 1/4 in. he x-head cover screw (in the
mounting base)
© 2016 Johnson Controls, Inc. 1 Part No. 24-7701-179, Rev. B www.johnsoncontrols.com
drywall clip mounting kit (includes two each No. 6-20 x 1.25 in. pan-head tapping screws, spring clips, and spacers)

Accessories

Product Code Number
Description
ACC-INSL-1*
Surface Mounting Pad (10/bag)
TE-67MB-600
Mounting Base Kit
** Contains 10 original style and 10 new style doors.
BaseCover
1. Loosen (do not remove) the cover screw with a 1/16 in. (1.5 mm) Allen wrench.
2. Swing the cover down from the base.
No. 6
Screws
Cover Screw
Table 1: Accessories and Replacement Parts for the Wall Mount Humidity Controller
ACC-DWCLIP-0 ACC-INSL-0*
GRD10A-608 T-4000-119
TE-67D0-601** TE-67D0-602**
* These foam pads help prevent drafts from entering the unit through the wall and make installation easier when mounting on an uneven surface.
Drywall Clip Mounting Kit (10/bag) Wallbox Mounting Pad (10/bag)
Plastic Guard with Baseplate and Mounting Ring Allen-head Adjustment Tool (30/bag)
Door Replacement Kit with Johnson Controls logo Door Replacement Kit without logo

Mounting

Location Considerations

IMPORTANT: To avoid damage to the
circuit board and components, do not mount the unit in a location where high concentrations of corrosive vapors are present.
The HC-67x3 controller is shipped with one mounting base for both surface and wallbox mounting. To mount the HC-67x3, release the cover from the base as described in Figure 2.
be careful not to drop or mount the unit where it could be exposed to excessive vibration. The following ambient operating conditions apply:
Temperature: 32 to 122°F (0 to 50°C)
Humidity: 0 to 100% Relative Humidity (RH),
non-condensing; 85°F (29°C) maximum dew point
To mount the HC-67x3 to a wallbox:
1. Pull the cable or wiring through the wallbox and base.
2. Rotate the mounting base, so one of the arrows on the base points up.
Figure 2: Removing the Cover from the Base

Wallbox Mounting: Special Tools Needed

Use a 1/16 in. (1.5 mm) Allen wrench or T-4000-119 Allen-head adjustment tool for mounting.

Wallbox Mounting: Location Considerations

Locate the humidity transmitter on an inside wal l, free from drafts, and out of direct sunlight. The HC-67x3 is shock and vibration resistant; however,
2 TRUERH Series HC-67x3 Humidity Controllers Installation Instructions
3. Fasten the base to the wallbox with the No. 6 screws provided. (See Figure 3.)
Note: These instructions assume a standard 2 x 4 in. (52 x 104 mm) U.S. wallbox is used.
Figure 3: Wallbox Mounting
4. Place the bottom edge of the cover against the bottom lip of the base, and rotate it up onto the base. (See Figure 4.)
5. Tighten the cover screw.
Base
Cover Screw
Cover
Base
Cover Screw
Cover
Figure 4: Attaching the Cover to the Base
Note: Once installed, the unit cannot be removed
from the wall unless the cover screw is loosened as described in Figure 2.
IMPORTANT: Seal the drilled hole or use an ACC-INSL-0 Foam Pad Kit to help reduce drafts entering the unit. (See Table 1.) Drafts could result in false readings.
needed as shown in Figure 6. Do not use the spacers for 5/8 in. (16 mm) drywall.
Note: For replacement spring clips, spacers, and screws, order the ACC-DWCLIP-0 Drywall Clip Mounting Kit. (See Table 1.)

Surface Mounting: Special Tools Needed

hole saw with 1-3/8 in. (35 mm) diameter blade
1/16 in. (1.5 mm) Allen wrench or
T-4000-119 Allen-head adjustment tool
drill with 1/8 in. (3 mm ) drill b it To mount the surface model to drywall, refer to
Figure 6 and proceed as follows:
1. Bend the top and bottom edges of mounting base at the perforations until they break off. (See Figure 5.)
2. Drill a 1-3/8 in. (35 mm) hole in the surface where the unit is to be mounted, and pull the wiring through the drilled hole.
3. Mark the location of the two mounting screws, and drill the holes.
4. Insert the spring clips on each side of the drilled 1-3/8 in. (35 mm) hole, and use the spacers if
Figure 5: Removing the Breakaway Tabs
5. Pull the wiring through the base of the unit.
6. Center the two holes in the base over the two drilled holes, and fasten the base to the drywall using the No. 6 screws provided. (See Figure 6.)
7. Place the bottom edge of the cover against the bottom lip of the base, and rotate it up onto the base as shown in Figure 4.
8. Tighten the cover screw.
9. Once installed, the HE-67xx cannot be removed from the wall unless the cover screw is loosened as described in Figure 2.
IMPORTANT: To prevent drywall damage, do not overtighten the screws.
TRUERH Series HC-67x3 Humidity Controllers Installation Instructions 3
Loading...
+ 4 hidden pages