The outdoor units are designed to be connected to a matching indoor
coil with sweat connect lines. Sweat connect units are factory charged
with refrigerant for a matching indoor coil plus 15 feet of field supplied
lines.
Matching indoor coils are available with a thermal expansion valve or
an orifice liquid feed sized for the most common usage. The orifice size
and/or refrigerant charge may need to be changed for some indoor-outdoor unit combinations, elevation differences or total line lengths. Refer
to Application Data covering “General Piping Recommendations and
Refrigerant Line Length” (Part Number 036-61920-001).
SECTION II: SAFETY
This is a safety alert symbol. When you see this symbol on
labels or in manuals, be alert to the potential for personal
injury.
Understand and pay particular attention to the signal words DANGER,
WARNING, or CAUTION.
DANGER indicates an imminently hazardous situation, which, if not
avoided, will result in death or serious injury
WARNING indicates a potentially hazardous situation, which, if not
avoided, could result in death or serious injury
.
.
CAUTION indicates a potentially hazardous situation, which, if not
avoided may result in minor or moderate injury
alert against unsafe practices and hazards involving only property damage
Improper installation may create a condition where the operation of
the product could cause personal injury or property damage.
Improper installation, adjustment, alteration, service or maintenance can cause injury or property damage. Refer to this manual
for assistance or for additional information, consult a qualified contractor, installer or service agency.
This product must be installed in strict compliance with the
enclosed installation instructions and any applicable local, state,
and national codes including, but not limited to building, electrical,
and mechanical codes.
R-410A systems operate at higher pressures than R-22 systems.
Do not use R-22 service equipment or components on R-410A
equipment. Service equipment
Must Be Rated for R-410A.
. It is also used to
501054-UIM-A-0909
501054-UIM-A-0909
INSPECTION
As soon as a unit is received, it should be inspected for possible damage during transit. If damage is evident, the extent of the damage
should be noted on the carrier’s delivery receipt. A separate request for
inspection by the carrier’s agent should be made in writing. See Local
Distributor for more information.
Requirements For Installing/Servicing R-410A Equipment
• Gauge sets, hoses, refrigerant containers, and recovery system
must be designed to handle the POE type oils, and the higher
pressures of R-410A.
• Manifold sets should be 800 psig high side and 250 psig low side
with 550 psig low side restart.
• All hoses must have a 700 psig service pressure rating.
• Leak detectors should be designed to detect HFC refrigerant.
• Recovery equipment (including refrigerant recovery containers)
must be specifically designed to handle R-410A.
• Do not use an R-22 TXV.
• A liquid-line filter drier is required on every unit.
LIMITATIONS
The unit should be installed in accordance with all National, State and
Local Safety Codes and the limitations listed below:
1.Limitations for the indoor unit, coil and appropriate accessories
must also be observed.
2.The outdoor unit must not be installed with any duct work in the air
stream. The outdoor fan is the propeller type and is not designed
to operate against any additional external static pressure.
3.The maximum and minimum conditions for operation must be
observed to assure a system that will give maximum performance
with minimum service.
AIR TEMPERATURE DB AT
OUTDOOR COIL, °F
Min.Max.Min.Max.
CoolHeatCoolHeat
50-101157557
1. Operation below this temperature is permissible for a short period of time,
during morning warm-up.
4.This unit is not designed to operate with a low ambient kit. Do not
modify the control system to operate with any kind of low ambient
kit.
5.The maximum allowable line length for this product is 75 feet.
AIR TEMPERATURE AT
INDOOR COIL, °F
WB
Cool
DB
Heat
50
1
WB
Cool
7280
DB
Heat
SECTION III: UNIT INSTALLATION
LOCATION
Before starting the installation, select and check the suitability of the
location for both the indoor and outdoor unit. Observe all limitations and
clearance requirements.
The outdoor unit must have sufficient clearance for air entrance to the
condenser coil, for air discharge and for service access. See Figure 1.
NOTE: For multiple unit installations, units must be spaced a minimum
of 18 inches apart. (Coil face to coil face.)
If the unit is to be installed on a hot sun exposed roof or a black-topped
ground area, the unit should be raised sufficiently above the roof or
ground to avoid taking the accumulated layer of hot air into the outdoor
unit.
Provide an adequate structural support.
ADD-ON REPLACEMENT/RETROFIT
When this unit is being used as a replacement for an R-22 unit, it is
required that the outdoor unit, indoor coil, and metering device all be
replaced. The following steps should be performed in order to insure
proper system operation and performance. Line-set change out is also
recommended.
1.Change-out of the indoor coil to an approved R-410A coil/ condensing unit combination with the appropriate metering device.
2.Change-out of the line-set when replacing an R-22 unit with an
R410-A unit is highly recommended to reduce cross-contamination of oils and refrigerants.
3.If change-out of the line set is not practical, then the following precautions should be taken.
• Inspect the line set for kinks, sharp bends, or other restrictions,
and for corrosion.
• Determine if there are any low spots which might be serving as oil
traps.
• Flush the line set with a commercially available flush kit to
remove as much of the existing oil and contaminants as possible.
• Install a suction line filter-drier to trap any remaining contaminants, and remove after 50 hours of operation.
4.If the outdoor unit is being replaced due to a compressor burnout,
then installation of a 100% activated alumina suction-line filter
drier in the suction-line is required, in addition to the factory
installed liquid-line drier. Operate the system for 10 hours. Monitor
the suction drier pressure drop. If the pressure drop exceeds 3
psig, replace both the suction-line and liquid-line driers. After a
total of 10 hours run time where the suction-line pressure drop has
not exceeded 3 psig, replace the liquid line drier, and remove the
suction-line drier. Never leave a suction-line drier in the system
longer than 50 hours of run time.
2Johnson Controls Unitary Products
FIGURE 1: Typical Installation with Required Clearances
THERMOSTAT
NEC CLASS 1
WIRING
TO INDOOR
BLOWER
NEC CLASS 2
WIRING
TO COIL
WEATHERPROOF
DISCONNECT SWITCH
48” OVERHEAD
CLEARANCE
24” SERVICE
ACCESS
CLEARANCE
18” FRONT
& SIDES
NOTE:
ALL OUTDOOR WIRING
MUST BE WEATHERPROOF
SEAL OPENINGS WITH
PERMAGUM OR EQUIVALENT
GROUND INSTALLA TION
The unit may be installed at ground level on a solid base that will not
shift or settle, causing strain on the refrigerant lines and possible leaks.
Maintain the clearances shown in Figure 1 and install the unit in a level
position.
Normal operating sound levels may be objectionable if the unit is placed
directly under windows of certain rooms (bedrooms, study, etc.).
Condensate will drain from beneath the coil of the outdoor unit during
the defrost cycle. Normally this condensate may be allowed to drain
directly on the ground.
501054-UIM-A-0909
LIQUID LINE FILTER-DRIER
The heat pumps have a solid core bi-flow filter/dryer located on the liquid line.
NOTE: Replacements for the liquid line drier must be exactly the same
as marked on the original factory drier. See Source 1 for O.E.M.
replacement driers.
Failure to do so or using a substitute drier or a granular type may
result in damage to the equipment.
The outdoor unit should not be installed in an area where mud or
ice could cause personal injury. Remember that condensate will
drip from the unit coil during heat and defrost cycles and that this
condensate will freeze when the temperature of the outdoor air is
below 32°F.
Elevate the unit sufficiently to prevent any blockage of the air entrances
by snow in areas where there will be snow accumulation. Check the
local weather bureau for the expected snow accumulation in your area.
Isolate the unit from rain gutters to avoid any possible wash out of the
foundation.
ROOF INSTALLATION
When installing units on a roof, the structure must be capable of supporting the total weight of the unit, including a pad, lintels, rails, etc.,
which should be used to minimize the transmission of sound or vibration into the conditioned space.
UNIT PLACEMENT
1.Provide a base in the pre-determined location.
2.Remove the shipping carton and inspect for possible damage.
3.Compressor tie-down bolts should remain tightened.
4.Position the unit on the base provided.
NOTE: Heat pumps will defrost periodically resulting in water drainage.
The unit should not be located where water drainage may freeze and
create a hazardous condition - such as sidewalks and steps.
Johnson Controls Unitary Products3
R-410A / R-22 Filter-Drier
Source 1 Part No.
026 - 25512 - 000All Sizes
Apply with Models
YZH
PIPING CONNECTIONS
This system uses R-410A refrigerant which operates at higher pressures than R-22. No other refrigerant may be used in this system.
Gauge sets, hoses, refrigerant containers, and recovery system
must be designed to handle R-410A. If you are unsure, consult the
equipment manufacturer.
Never install a suction-line filter drier in the liquid line of an R-410A
system. Failure to follow this warning can cause a fire, injury or
death.
The outdoor unit must be connected to the indoor coil using field supplied refrigerant grade copper tubing that is internally clean and dry.
Units should be installed only with the tubing sizes for approved system
combinations as specified in Tabular Data Sheet. The charge given is
applicable for total tubing lengths up to 15 feet. See Application Data
Part Number 347077 for installing tubing of longer lengths and elevation
differences.
NOTE: Using a larger than specified line size could result in oil return
problems. Using too small a line will result in loss of capacity and other
problems caused by insufficient refrigerant flow. Slope horizontal vapor
lines at least 1" every 20 feet toward the outdoor unit to facilitate proper
oil return.
501054-UIM-A-0909
Liquid
Line
Incorrect
Correct
Tape
Sheet Metal Hanger
Insulated Vapor Line
TO INDOOR COIL
TO O UTDO OR UNIT
LIQUID LINE
CAP
PVC
CONDUIT
INSULATED
VAPOR LINE
PRECAUTIONS DURING LINE INSTALLATION
1.Install the lines with as few bends as possible. Care must be taken
not to damage the couplings or kink the tubing. Use clean hard
drawn copper tubing where no appreciable amount of bending
around obstruction is necessary. If soft copper must be used, care
must be taken to avoid sharp bends which may cause a restriction.
2.The lines should be installed so that they will not obstruct service
access to the coil, air handling system or filter.
3.Care must also be taken to isolate the refrigerant lines to minimize
noise transmission from the equipment to the structure.
4.The vapor line must be insulated with a minimum of 1/2" foam rubber insulation (Armaflex or equivalent). Liquid lines that will be
exposed to direct sunlight and/or high temperatures must also be
insulated.
Tape and suspend the refrigerant lines as shown. DO NOT allow tube
metal-to-metal contact. See Figure 2.
5.Use PVC piping as a conduit for all underground installations as
shown in Figure 3. Buried lines should be kept as short as possible
to minimize the build up of liquid refrigerant in the vapor line during
long periods of shutdown
6.Pack fiberglass insulation and a sealing material such as permagum around refrigerant lines where they penetrate a wall to reduce
vibration and to retain some flexibility.
7.See Form 690.01-AD1V for additional piping information.
Dry nitrogen should always be supplied through the tubing while it
is being brazed, because the temperature required is high enough
to cause oxidation of the copper unless an inert atmosphere is provided. The flow of dry nitrogen should continue until the joint has
cooled. Always use a pressure regulator and safety valve to insure
that only low pressure dry nitrogen is introduced into the tubing.
Only a small flow is necessary to displace air and prevent oxidation.
PRECAUTIONS DURING BRAZING SERVICE VALVE
Precautions should be taken to prevent heat damage to service valve
by wrapping a wet rag around it as shown in Figure 4. Also, protect all
painted surfaces, insulation, and plastic base during brazing. After brazing cool joint with wet rag.
This is not a backseating valve. The service access port has a
valve core. Opening or closing valve does not close service access
port.
If the valve stem is backed out past the chamfered retaining wall,
the O-ring can be damaged causing leakage or system pressure
could force the valve stem out of the valve body possibly causing
personal injury.
FIGURE 2: Tubing Hanger
FIGURE 3: Underground Installation
PRECAUTIONS DURING BRAZING OF LINES
All outdoor unit and evaporator coil connections are copper-to-copper
and should be brazed with a phosphorous-copper alloy material such
as Silfos-5 or equivalent. DO NOT use soft solder. The outdoor units
have reusable service valves on both the liquid and vapor connections.
The total system refrigerant charge is retained within the outdoor unit
during shipping and installation. The reusable service valves are provided to evacuate and charge per this instruction.
Serious service problems can be avoided by taking adequate precautions to assure an internally clean and dry system.
Valve can be opened by removing the plunger cap and fully inserting a
hex wrench into the stem and backing out counter-clockwise until valve
stem just touches the chamfered retaining wall.
Connect the refrigerant lines using the following procedure:
1.Remove the cap and Schrader core from both the liquid and vapor
service valve service ports at the outdoor unit. Connect low pressure nitrogen to the liquid line service port.
2.Braze the liquid line to the liquid valve at the outdoor unit. Be sure
to wrap the valve body with a wet rag. Allow the nitrogen to continue flowing. Refer to the Tabular Data Sheet for proper liquid line
sizing.
3.Carefully remove the rubber plugs from the evaporator liquid and
vapor connections at the indoor coil.
4.Braze the liquid line to the evaporator liquid connection. Nitrogen
should be flowing through the evaporator coil.
FIGURE 4: Heat Protection
4Johnson Controls Unitary Products
The evaporator is pressurized.
501054-UIM-A-0909
5.Slide the grommet away from the vapor connection at the indoor
coil. Braze the vapor line to the evaporator vapor connection. After
the connection has cooled, slide the grommet back into original
position. Refer to the Tabular Data Sheet for proper vapor line sizing.
6.Protect the vapor valve with a wet rag and braze the vapor line
connection to the outdoor unit. The nitrogen flow should be exiting
the system from the vapor service port connection. After this connection has cooled, remove the nitrogen source from the liquid fitting service port.
7.Replace the Schrader core in the liquid and vapor valves.
8.Go to SECTION IV for TXV installation.
9.Leak test all refrigerant piping connections including the service
port flare caps to be sure they are leak tight. DO NOT OVERTIGHTEN (between 40 and 60 inch - lbs. maximum).
10. Evacuate the vapor line, evaporator and the liquid line, to 500
microns or less.
NOTE: Line set and indoor coil can be pressurized to 250 psig with dry
nitrogen and leak tested with a bubble type leak detector. Than release
the nitrogen charge.
NOTE: Do not use the system refrigerant in the outdoor unit to purge or
leak test.
11. Replace cap on service ports. Do not remove the flare caps from
the service ports except when necessary for servicing the system.
Do not connect manifold gauges unless trouble is suspected.
Approximately 3/4 ounce of refrigerant will be lost each time a standard manifold gauge is connected.
5.Reinstall the liquid line to the top of the thermal expansion valve.
Hand modify the liquid line to align with casing opening.
6.Install the TXV equalizer line into the vapor line as follows:
a.Select a location on the vapor line for insertion of the equal-
izer line which will not interfere with TXV bulb placement.
b.Use an awl to punch through the suction tube and insert the
awl to a depth to achieve a 1/8” diameter hole.
7.Install TXV equalizer line in 1/8” hole previously made in vapor
line. Equalizer line should not be bottomed out in vapor line. Insert
equalizer line at least 1/4” in the vapor line. Braze equalizer line
making sure that tube opening is not brazed closed.
Dry nitrogen should always be supplied through the tubing while it
is being brazed, because the temperature required is high enough
to cause oxidation of the copper unless an inert atmosphere is provided. The flow of dry nitrogen should continue until the joint has
cooled. Always use a pressure regulator and safety valve to insure
that only low pressure dry nitrogen is introduced into the tubing.
Only a small flow is necessary to displace air and prevent oxidation.
All connections to be brazed are copper-to-copper and should be
brazed with a phosphorous-copper alloy material such as Silfos-5 or
equivalent. DO NOT use soft solder.
Install the TXV bulb to the vapor line near the equalizer line, using the
two bulb clamps furnished with the TXV assembly. Ensure the bulb is
making maximum contact. Refer to TXV installation instruction for view
of bulb location.
12. Release the refrigerant charge into the system. Open both the liquid and vapor valves by removing the plunger cap and with an
allen wrench back out counter-clockwise until valve stem just
touches the chamfered retaining wall. See - PRECAUTIONS
DURING BRAZING SERVICE VALVE.
13. Replace plunger cap finger tight, then tighten an additional 1/12
turn (1/2 hex flat). Cap must be replaced to prevent leaks.
Never attempt to repair any brazed connections while the system is
under pressure. Personal injury could result.
See SYSTEM CHARGE section for checking and recording system
charge.
SECTION IV: INST ALLA TIONS REQUIRING
TXV
For installations requiring a TXV, the following are the basic steps for
installation. For detailed instructions, refer to the Installation Instructions
accompanying the TXV kit.
Install TXV kit as follows:
1.First, relieve the holding charge by depressing the Schrader valve
located in the end of the liquid line.
2.After holding charge is completely discharged, loosen and remove
the liquid line fitting from the orifice distributor assembly. Note that
the fitting has right
3.Remove the orifice from the distributor body using a small diameter wire or paper clip. Orifice is not used when the TXV assembly
is installed.
4.After orifice is removed, install the thermal expansion valve to the
orifice distributor assembly with supplied fittings. Hand tighten and
turn an additional 1/8 turn to seal. Do not overtighten fittings
handthreads.
.
In all cases, mount the TXV bulb after vapor line is brazed and has
had sufficient time to cool.
1.Bulb should be installed on a horizontal run of the vapor line if possible. On lines under 7/8" O.D. the bulb may be installed on top of
the line. With 7/8" O.D. and over, the bulb should be installed at
the position of about 2 or 10 o'clock.
2.If bulb installation is made on a vertical run, the bulb should be
located at least 16 inches from any bend, and on the tubing sides
opposite the plane of the bend. The bulb should be positioned with
the bulb tail at the top, so that the bulb acts as a reservoir.
3.Bulb should be insulated using thermal insulation provided to protect it from the effect of the surrounding ambient temperature.
SECTION V: ELECTRICAL CONNECTIONS
GENERAL INFORMATION & GROUNDING
Check the electrical supply to be sure that it meets the values specified
on the unit nameplate and wiring label.
Power wiring, control (low voltage) wiring, disconnect switches and over
current protection must be supplied by the installer. Wire size should be
sized per NEC requirements.
All field wiring must USE COPPER CONDUCTORS ONLY and be
in accordance with Local, National Fire, Safety & Electrical Codes.
This unit must be grounded with a separate ground wire in accordance with the above codes.
The complete connection diagram and schematic wiring label is located
on the inside surface of the unit service access panel and this instruction.
Johnson Controls Unitary Products5
501054-UIM-A-0909
Corner
Cover
Control
Wiring
Power
Wiring
Service
Access
Panel
Ambient
Temperature
Sensor
COMMUNICATIONS PORT
CONTROL BOARD
COMMUNICATIONS
HARNESS
JUNCTION
BOX
FIELD CONNECTIONS POWER WIRING
1.Install the proper size weatherproof disconnect switch outdoors
and within sight of the unit.
2.Remove the screws at the bottom of the corner cover. Slide corner
cover down and remove from unit. See Figure 5.
3.Run power wiring from the disconnect switch to the unit.
4.Remove the service access panel to gain access to the unit wiring.
Route wires from disconnect through power wiring opening provided and into the unit control box.
5.Install the proper size time-delay fuses or circuit breaker, and
make the power supply connections.
6.Energize the crankcase heater if equipped to save time by preheating the compressor oil while the remaining installation is completed.
NOTE: To eliminate erratic operation, seal the hole in the wall at the
thermostat with permagum or equivalent to prevent air drafts affecting
the operation of in the thermostat.
FIELD CONNECTIONS CONTROL WIRING COMMUNICATING
1.The Communication Harness is provided with the communicating
thermostat.
2.Route low voltage four conductor shielded thermostat communications harness into junction box and connect to communications
port on control board. See Figure 6.
3.The complete connection diagram and schematic wiring label is
located on the inside surface of the unit service access panel.
If unit is going to be setup as a communicating system, the conventional wiring must be removed from the Outdoor Control Board.
FIGURE 5: Typical Field Wiring
FIELD CONNECTIONS CONTROL WIRING CONVENTIONAL
1.Route low voltage wiring into bottom of control box as shown in
Figure 5. Make low voltage wiring connections inside the junction
box per Figures 10 - 15.
2.The complete connection diagram and schematic wiring label is
located on the inside surface of the unit service access panel.
3.Replace the corner cover and service access panel removed in
Steps 2 and 4 of the “Field Connections Power Wiring” section.
NOTE: Ambient temperature sensor should extend below control box
by 1”.
4.All field wiring to be in accordance with national electrical codes
(NEC) and/or local-city codes.
5.Mount the thermostat about 5 ft. above the floor, where it will be
exposed to normal room air circulation. Do not place it on an outside wall or where it is exposed to the radiant effect from exposed
glass or appliances, drafts from outside doors or supply air grilles.
6.Route the 24-volt control wiring (NEC Class 2) from the outdoor
unit to the indoor unit and thermostat.
FIGURE 6: Communications Harness Connection
4.Replace the corner cover and service access panel removed in
Steps 2 and 4 of the “Field Connections Power Wiring” section.
NOTE: Ambient temperature sensor should extend below control box
by 1”.
5.Route the 24-volt control wiring (NEC Class 2) from the outdoor
unit to the indoor unit and thermostat.
6.All field wiring to be in accordance with national electrical codes
(NEC) and/or local-city codes.
7.Mount the thermostat about 5 ft. above the floor, where it will be
exposed to normal room air circulation. Do not place it on an outside wall or where it is exposed to the radiant effect from exposed
glass or appliances, drafts from outside doors or supply air grilles.
NOTE: To eliminate erratic operation, seal the hole in the wall at the
thermostat with permagum or equivalent to prevent air drafts affecting
the operation of in the thermostat.
6Johnson Controls Unitary Products
DEHUMIDIFICATION CONTROL
HEAT
DELAY COOL
ADJUST
A
B
C
D
A
B
C
D
LED 2
R
C
Y1
Y2
Touch Control
Communicating
Control
Air Handler/Furnace
Communicating
Control
Heat Pump
Communicating
Control
GND
or C
GND
or C
B-
R
A+
GND
or C
GND
or C
B-
R
A+
GND
or C
GND
or C
B-
R
A+
R
C
Y1
Y2
HUM
W2
DHUM
W
G
C
R
O
Y
Y2
HUM
W2
DHUM
W
G
C
R
O
Y
Y2
Touch Control
Communicating
Control
Communicating
Indoor
Interface Control
Non-Communicating
Indoor Unit
Heat Pump
Communicating
Control
Wire per
non-comm.
installation
manual
Assume that
connections
are from
thermostat
GND
or C
GND
or C
B-
R
A+
GND
or C
GND
or C
B-
R
A+
GND
or C
GND
or C
B-
R
A+
A dehumidification control accessory 2HU06700124 may be used with
variable speed air handlers or furnaces in high humidity areas. This
control works with the variable speed indoor unit to provide cooling at a
reduced air flow, lowering evaporator temperature and increasing latent
capacity. The humidistat in this control opens the humidistat contacts on
humidity rise. To install, refer to instructions packaged with the accessory and Figures 10 - 15. Prior to the installation of the dehumidification
control, the jumper across the HUMIDISTAT terminals on the indoor
variable speed air handler or furnace CFM selection board must be
removed.
During cooling, if the relative humidity in the space is higher than the
desired set point of the dehumidification control, the variable speed
blower motor will operate at lower speed until the dehumidification control is satisfied. A 40-60% relative humidity level is recommended to
achieve optimum comfort.
If a dehumidification control is installed, it is recommended that a minimum air flow of 325 cfm/ton be supplied at all times.
CFM SELECTION BOARD SETTINGS
For proper system operation the CFM Selection Board jumpers must be
set properly.
Refer to the Tabular Data Sheet for the recommended air flow settings
for each size condensing unit.
Set the cooling speed per the instructions for the air handler or furnace
by selecting the correct COOL and ADJ taps. Verify the airflow using
the LED display on the CFM selection board.
The HUMIDISTAT jumper must also be removed if a dehumidistat is
installed.
If installed as a communicating system (outdoor, indoor and thermostat), the system will automatically adjust to the optimal airflow settings.
These parameters can also be modified using the communicating thermostat. Refer to the communicating thermostat owner’s manual for this
procedure. Manual setting of the airflow jumpers on the ID equipment
is not necessary with the communicating thermostat.
501054-UIM-A-0909
FIGURE 8: Communicating HP with Communicating Air Handler or
Furnace
FIGURE 7: CFM Selection Board
Johnson Controls Unitary Products7
FIGURE 9: Communicating HP with Non-Communicating Air Handler
or Furnace using Communicating Interface Control
501054-UIM-A-0909
HP 24ATwo Stage Heat Pump – Two Stage Variable Speed Furnace (With Hot Heat Pump Operation)
For additional connection diagrams for all UPG equipment refer to “Low Voltage System Wiring” document available online at www.upgnet.com in the
Product Catalog Section.
It will be necessary to evacuate the system to 500 microns or less. If a
leak is suspected, leak test with dry nitrogen to locate the leak. Repair
the leak and test again.
To verify that the system has no leaks, simply close the valve to the vacuum pump suction to isolate the pump and hold the system under vacuum. Watch the micron gauge for a few minutes. If the micron gauge
indicates a steady and continuous rise, it’s an indication of a leak. If the
gauge shows a rise, then levels off after a few minutes and remains
fairly constant, its an indication that the system is leak free but still contains moisture and may require further evacuation if the reading is
above 500 microns.
SECTION VII: SYSTEM CHARGE
R-410A refrigerant cylinders are rose colored, and have a dip tube
which allows liquid to flow out of the cylinder in the
Always charge the system slowly with the tank in the upright
tion.
position.
The factory charge in the outdoor unit includes enough charge for the
unit, a 15 ft. line set and the smallest indoor coil match-up. Some indoor
coil matches may require additional charge. See tabular data sheet provided in unit literature packet for charge requirements.
Do not leave the system open to the atmosphere. Unit damage
could occur due to moisture being absorbed by the POE oil in the
system. This type of oil is highly susceptible to moisture absorption.
The TOTAL SYSTEM CHARGE must be permanently stamped on the
unit data plate.
Total system charge is determined as follows:
1.Determine outdoor unit charge from tabular data sheet.
2.Determine indoor coil adjustment from tabular data sheet.
3.Calculate the line charge using the tabular data sheet if line length
is greater than15 feet.
4.Total system charge = item 1 + item 2 + item 3.
5.Permanently stamp the unit data plate with the total amount of
refrigerant in the system.
Use the following subcooling charging method whenever additional
refrigerant is required for the system charge. A superheat charging
method is not suitable for TXV equipped systems.
Upright Posi-
Refrigerant charging should only be carried out by a qualified air
conditioning contractor.
Measurement Method
If a calibrated charging cylinder or accurate weighing device is available, add refrigerant accordingly.
Compressor damage will occur if system is improperly charged. On
new system installations, charge system per tabular data sheet for
the matched coil and follow guidelines in this instruction.
Check flare caps on service ports to be sure they are leak tight. DO
NOT OVERTIGHTEN (between 40 and 60 inch - lbs. maximum).
Subcooling Charging Method
For the heating operation, there is no accurate subcooling method for
charging the unit. If unit charging is required during heating operation,
the unit must be evacuated and charge weighed-in per the marking on
the rating plate.
For the cooling operation, the recommended subcooling is typically
around 10°F. This may vary greatly based on each unique system.
1.Set the system running in the cooling mode by setting the thermostat at least 6°F below the room temperature.
2.Operate the system for a minimum of 15-20 minutes.
3.Refer to the tabular data sheet for the recommended airflow and
verify this indoor airflow (it should be about 400 SCFM per ton).
4.Measure the liquid refrigerant pressure P and temperature T at the
service valve.
5.Calculate the saturated liquid temperature ST from Table 2 R-410A, SATURATION PROPERTIES.
6.Subcooling temperature TC = Saturated T emperature (ST) - Liquid
Temp (T).
Example: The pressure P and temperature T measured at the liquid
service port is 360 psig and 93°F. From Table 2, the saturated temperature for 360 psig is 109°. The subcooling temperature TC =
109°-93°=16°F
Add charge if the calculated subcooling temperature TC in Step 6 is
lower than the recommended level. Remove and recover the refrigerant
if the subcooling TC is higher than the recommended level.
See rating plate for unit specific subcooling chart.
See Figure 16 to trace the flow of refrigerant through the system.
FIGURE 16: Heat Pump Flow Diagram
14Johnson Controls Unitary Products
501054-UIM-A-0909
SECTION VIII: SYSTEM OPERATION
For more information on the control operation, refer to “Operation
Instructions - DEMAND DEFROST CONTROL BOARD in this Booklet.
REQUIRED CONTROL SETUP
The following steps must be taken at the time of installation to
insure proper system operation.
1.Consult system wiring diagram to determine proper thermostat
wiring for your system.
2.If hot heat pump configuration is desired, change HOT HEAT
PUMP jumper to ON position. This setting MUST be set on the
defrost control board.
3.If installation includes a fossil fuel furnace, change FUEL jumper to
ON position. This setting MUST be set on the defrost control
board.
4.Set low temperature cutout (LTCO), balance point (BP), switch
point (SP), and Y2 Lock jumpers as desired. These settings may
be modified by communicating thermostat.
5.Verify proper system functionality. Confirm room thermostat operation including fault code display capability.
6.Upon completion of installation, verify that no fault codes are
stored in memory. Clear the fault code memory if necessary.
DEFROST OPERATION
The following defrost curve selection jumper positions are set from factory.
TABLE 1:
INDICATIONS OF PROPER OPERATION
Cooling
Cooling operation is the same as any conventional air conditioning unit.
1.The outdoor fan should be running, with warm air being dis-
2.The indoor blower (furnace or air handler) will be operating, dis-
3.The vapor line at the outdoor unit will feel cool to the touch.
4.The liquid line at the outdoor unit will feel warm to the touch.
TABLE 2:
Defrost Initiate Curves
Defrost Curve Selection
Jumper Position
Heat Pump ModelN/AN/A3 TonN/A
charged from the top of the unit.
charging cool air from the ducts. Coils or other parts in the air circuit should be cleaned as often as necessary to keep the unit
clean. Use a brush, vacuum cleaner attachment, or other suitable
means.
Indications of proper Heating operation is as follows:
1.The outdoor fan should be running, with cool air being discharged
from the top of the unit.
2.The indoor blower (furnace or air handler) will be operating, discharging warm air from the ducts.
3.The vapor line at the outdoor unit will feel warm to the touch.
4.The liquid line at the outdoor unit will feel cool to the touch.
SECTION IX: INSTRUCTING THE OWNER
Assist owner with processing warranty cards and/or online registration.
Review Owners Guide and provide a copy to the owner and guidance
on proper operation and maintenance. Instruct the owner or the operator how to start, stop and adjust temperature setting.
When applicable, instruct the owner that the compressor is equipped
with a crankcase heater to prevent the migration of refrigerant to the
compressor during the OFF cycle. The heater is energized only when
the unit is not running. If the main switch is disconnected for long periods of shut down, do not attempt to start the unit until 8 hours after the
switch has been connected. This will allow sufficient time for all liquid
refrigerant to be driven out of the compressor.
The installer should also instruct the owner on proper operation and
maintenance of all other system components.
MAINTENANCE
1.Dirt should not be allowed to accumulate on the outdoor coils or
other parts in the air circuit. Clean as often as necessary to keep
the unit clean. Use a brush, vacuum cleaner attachment, or other
suitable means.
2.The outdoor fan motor is permanently lubricated and does not
require periodic oiling.
3.If the coil needs to be cleaned, it should be washed with Calgon
Coilclean (mix one part Coilclean to seven parts water). Allow
solution to remain on coil for 30 minutes before rinsing with clean
water. Solution should not be permitted to come in contact with
painted surfaces.
4.Refer to the furnace or air handler instructions for filter and blower
motor maintenance.
5.The indoor coil and drain pan should be inspected and cleaned
regularly to prevent odors and assure proper drainage.
IT IS UNLAWFUL TO KNOWINGLY VENT, RELEASE OR DISCHARGE REFRIGERANT INTO THE OPEN AIR DURING
REPAIR, SERVICE, MAINTENANCE OR THE FINAL DISPOSAL
OF THIS UNIT.