Johnson Controls 15 SEER - YZE / HC5B / HL5B SERIES, YZE Series, HC5B Series, HL5B Series Installation Manual

R-410A
INSTALLATION MANUAL
OUTDOOR SPLIT-SYSTEM HEAT PUMP
MODELS: 15 SEER - YZE / HC5B / HL5B SERIES 2 TO 5 TONS
TABLE OF CONTENTS
GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
SAFETY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
UNIT INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
INSTALLATIONS REQUIRING TXV . . . . . . . . . . . . . . . . . . . . . . . . . .5
ELECTRICAL CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
LIST OF FIGURES
Typical Installation with Required Clearances . . . . . . . . . . . . . . . . . . .3
Tubing Hanger . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Underground Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Heat Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Typical Field Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Communications Harness Connection . . . . . . . . . . . . . . . . . . . . . . . . .6
CFM Selection Board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Communicating HP with Communicating Air Handler or Furnace . . . .7
Communicating HP with Non-Communicating Air Handler
or Furnace using Communicating Interface Control . . . . . . . . . . . . . . .7
Thermostat Wiring – Two-Stage Heat Pumps -
Two-Stage Variable Speed Furnaces . . . . . . . . . . . . . . . . . . . . . . . . .8
EVACUATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
SYSTEM CHARGE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
SYSTEM OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
INSTRUCTING THE OWNER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
WIRING DIAGRAM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Thermostat Wiring – Two-Stage Heat Pump -
Two-Stage Variable Speed Furnaces . . . . . . . . . . . . . . . . . . . . . . . . . 9
Thermostat Wiring – Two-Stage Heat Pump -
Variable Speed Air Handler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Thermostat Wiring – Two-Stage Heat Pump -
Variable Speed Air Handler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Thermostat Wiring – Two-Stage Heat Pump -
Variable Speed Modulating Furnace . . . . . . . . . . . . . . . . . . . . . . . . 12
Thermostat Wiring – Two-Stage Heat Pump -
Variable Speed Modulating Furnace . . . . . . . . . . . . . . . . . . . . . . . . 13
Heat Pump Flow Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Wiring Diagram 16
LIST OF TABLES
Defrost Initiate Curves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15 R-410A Saturation Properties . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
SECTION I: GENERAL
The outdoor units are designed to be connected to a matching indoor coil with sweat connect lines. Sweat connect units are factory charged with refrigerant for a matching indoor coil plus 15 feet of field supplied lines.
Matching indoor coils are available with a thermal expansion valve or an orifice liquid feed sized for the most common usage. The orifice size and/or refrigerant charge may need to be changed for some indoor-out­door unit combinations, elevation differences or total line lengths. Refer to Application Data covering “General Piping Recommendations and Refrigerant Line Length” (Part Number 036-61920-001).
SECTION II: SAFETY
This is a safety alert symbol. When you see this symbol on labels or in manuals, be alert to the potential for personal injury.
Understand and pay particular attention to the signal words DANGER,
WARNING, or CAUTION. DANGER indicates an imminently hazardous situation, which, if not
avoided, will result in death or serious injury WARNING indicates a potentially hazardous situation, which, if not
avoided, could result in death or serious injury
.
.
CAUTION indicates a potentially hazardous situation, which, if not avoided may result in minor or moderate injury alert against unsafe practices and hazards involving only property dam­age
Improper installation may create a condition where the operation of the product could cause personal injury or property damage. Improper installation, adjustment, alteration, service or mainte­nance can cause injury or property damage. Refer to this manual for assistance or for additional information, consult a qualified con­tractor, installer or service agency.
This product must be installed in strict compliance with the enclosed installation instructions and any applicable local, state, and national codes including, but not limited to building, electrical, and mechanical codes.
R-410A systems operate at higher pressures than R-22 systems. Do not use R-22 service equipment or components on R-410A equipment. Service equipment
Must Be Rated for R-410A.
. It is also used to
501054-UIM-A-0909
501054-UIM-A-0909
INSPECTION
As soon as a unit is received, it should be inspected for possible dam­age during transit. If damage is evident, the extent of the damage should be noted on the carrier’s delivery receipt. A separate request for inspection by the carrier’s agent should be made in writing. See Local Distributor for more information.
Requirements For Installing/Servicing R-410A Equipment
• Gauge sets, hoses, refrigerant containers, and recovery system must be designed to handle the POE type oils, and the higher pressures of R-410A.
• Manifold sets should be 800 psig high side and 250 psig low side with 550 psig low side restart.
• All hoses must have a 700 psig service pressure rating.
• Leak detectors should be designed to detect HFC refrigerant.
• Recovery equipment (including refrigerant recovery containers) must be specifically designed to handle R-410A.
• Do not use an R-22 TXV.
• A liquid-line filter drier is required on every unit.
LIMITATIONS
The unit should be installed in accordance with all National, State and Local Safety Codes and the limitations listed below:
1. Limitations for the indoor unit, coil and appropriate accessories must also be observed.
2. The outdoor unit must not be installed with any duct work in the air stream. The outdoor fan is the propeller type and is not designed to operate against any additional external static pressure.
3. The maximum and minimum conditions for operation must be observed to assure a system that will give maximum performance with minimum service.
AIR TEMPERATURE DB AT
OUTDOOR COIL, °F
Min. Max. Min. Max.
Cool Heat Cool Heat
50 -10 115 75 57
1. Operation below this temperature is permissible for a short period of time, during morning warm-up.
4. This unit is not designed to operate with a low ambient kit. Do not modify the control system to operate with any kind of low ambient kit.
5. The maximum allowable line length for this product is 75 feet.
AIR TEMPERATURE AT
INDOOR COIL, °F
WB Cool
DB
Heat
50
1
WB Cool
72 80
DB
Heat
SECTION III: UNIT INSTALLATION
LOCATION
Before starting the installation, select and check the suitability of the location for both the indoor and outdoor unit. Observe all limitations and clearance requirements.
The outdoor unit must have sufficient clearance for air entrance to the condenser coil, for air discharge and for service access. See Figure 1.
NOTE: For multiple unit installations, units must be spaced a minimum of 18 inches apart. (Coil face to coil face.)
If the unit is to be installed on a hot sun exposed roof or a black-topped ground area, the unit should be raised sufficiently above the roof or ground to avoid taking the accumulated layer of hot air into the outdoor unit.
Provide an adequate structural support.
ADD-ON REPLACEMENT/RETROFIT
When this unit is being used as a replacement for an R-22 unit, it is required that the outdoor unit, indoor coil, and metering device all be replaced. The following steps should be performed in order to insure proper system operation and performance. Line-set change out is also recommended.
1. Change-out of the indoor coil to an approved R-410A coil/ con­densing unit combination with the appropriate metering device.
2. Change-out of the line-set when replacing an R-22 unit with an R410-A unit is highly recommended to reduce cross-contamina­tion of oils and refrigerants.
3. If change-out of the line set is not practical, then the following pre­cautions should be taken.
• Inspect the line set for kinks, sharp bends, or other restrictions, and for corrosion.
• Determine if there are any low spots which might be serving as oil traps.
• Flush the line set with a commercially available flush kit to remove as much of the existing oil and contaminants as possible.
• Install a suction line filter-drier to trap any remaining contami­nants, and remove after 50 hours of operation.
4. If the outdoor unit is being replaced due to a compressor burnout, then installation of a 100% activated alumina suction-line filter drier in the suction-line is required, in addition to the factory installed liquid-line drier. Operate the system for 10 hours. Monitor the suction drier pressure drop. If the pressure drop exceeds 3 psig, replace both the suction-line and liquid-line driers. After a total of 10 hours run time where the suction-line pressure drop has not exceeded 3 psig, replace the liquid line drier, and remove the suction-line drier. Never leave a suction-line drier in the system longer than 50 hours of run time.
2 Johnson Controls Unitary Products
FIGURE 1: Typical Installation with Required Clearances
THERMOSTAT
NEC CLASS 1
WIRING
TO INDOOR BLOWER
NEC CLASS 2 WIRING
TO COIL
WEATHERPROOF
DISCONNECT SWITCH
48” OVERHEAD CLEARANCE
24” SERVICE ACCESS CLEARANCE
18” FRONT
& SIDES
NOTE:
ALL OUTDOOR WIRING MUST BE WEATHERPROOF
SEAL OPENINGS WITH PERMAGUM OR EQUIVALENT
GROUND INSTALLA TION
The unit may be installed at ground level on a solid base that will not shift or settle, causing strain on the refrigerant lines and possible leaks. Maintain the clearances shown in Figure 1 and install the unit in a level position.
Normal operating sound levels may be objectionable if the unit is placed directly under windows of certain rooms (bedrooms, study, etc.).
Condensate will drain from beneath the coil of the outdoor unit during the defrost cycle. Normally this condensate may be allowed to drain directly on the ground.
501054-UIM-A-0909
LIQUID LINE FILTER-DRIER
The heat pumps have a solid core bi-flow filter/dryer located on the liq­uid line.
NOTE: Replacements for the liquid line drier must be exactly the same as marked on the original factory drier. See Source 1 for O.E.M.
replacement driers.
Failure to do so or using a substitute drier or a granular type may result in damage to the equipment.
The outdoor unit should not be installed in an area where mud or ice could cause personal injury. Remember that condensate will drip from the unit coil during heat and defrost cycles and that this condensate will freeze when the temperature of the outdoor air is below 32°F.
Elevate the unit sufficiently to prevent any blockage of the air entrances by snow in areas where there will be snow accumulation. Check the local weather bureau for the expected snow accumulation in your area.
Isolate the unit from rain gutters to avoid any possible wash out of the foundation.
ROOF INSTALLATION
When installing units on a roof, the structure must be capable of sup­porting the total weight of the unit, including a pad, lintels, rails, etc., which should be used to minimize the transmission of sound or vibra­tion into the conditioned space.
UNIT PLACEMENT
1. Provide a base in the pre-determined location.
2. Remove the shipping carton and inspect for possible damage.
3. Compressor tie-down bolts should remain tightened.
4. Position the unit on the base provided. NOTE: Heat pumps will defrost periodically resulting in water drainage.
The unit should not be located where water drainage may freeze and create a hazardous condition - such as sidewalks and steps.
Johnson Controls Unitary Products 3
R-410A / R-22 Filter-Drier
Source 1 Part No.
026 - 25512 - 000 All Sizes
Apply with Models
YZH
PIPING CONNECTIONS
This system uses R-410A refrigerant which operates at higher pres­sures than R-22. No other refrigerant may be used in this system. Gauge sets, hoses, refrigerant containers, and recovery system must be designed to handle R-410A. If you are unsure, consult the equipment manufacturer.
Never install a suction-line filter drier in the liquid line of an R-410A system. Failure to follow this warning can cause a fire, injury or death.
The outdoor unit must be connected to the indoor coil using field sup­plied refrigerant grade copper tubing that is internally clean and dry. Units should be installed only with the tubing sizes for approved system combinations as specified in Tabular Data Sheet. The charge given is applicable for total tubing lengths up to 15 feet. See Application Data Part Number 347077 for installing tubing of longer lengths and elevation differences.
NOTE: Using a larger than specified line size could result in oil return problems. Using too small a line will result in loss of capacity and other problems caused by insufficient refrigerant flow. Slope horizontal vapor lines at least 1" every 20 feet toward the outdoor unit to facilitate proper oil return.
501054-UIM-A-0909
Liquid Line
Incorrect
Correct
Tape
Sheet Metal Hanger
Insulated Vapor Line
TO INDOOR COIL
TO O UTDO OR UNIT
LIQUID LINE
CAP
PVC
CONDUIT
INSULATED
VAPOR LINE
PRECAUTIONS DURING LINE INSTALLATION
1. Install the lines with as few bends as possible. Care must be taken not to damage the couplings or kink the tubing. Use clean hard drawn copper tubing where no appreciable amount of bending around obstruction is necessary. If soft copper must be used, care must be taken to avoid sharp bends which may cause a restriction.
2. The lines should be installed so that they will not obstruct service access to the coil, air handling system or filter.
3. Care must also be taken to isolate the refrigerant lines to minimize noise transmission from the equipment to the structure.
4. The vapor line must be insulated with a minimum of 1/2" foam rub­ber insulation (Armaflex or equivalent). Liquid lines that will be exposed to direct sunlight and/or high temperatures must also be insulated.
Tape and suspend the refrigerant lines as shown. DO NOT allow tube metal-to-metal contact. See Figure 2.
5. Use PVC piping as a conduit for all underground installations as shown in Figure 3. Buried lines should be kept as short as possible to minimize the build up of liquid refrigerant in the vapor line during long periods of shutdown
6. Pack fiberglass insulation and a sealing material such as perma­gum around refrigerant lines where they penetrate a wall to reduce vibration and to retain some flexibility.
7. See Form 690.01-AD1V for additional piping information.
Dry nitrogen should always be supplied through the tubing while it is being brazed, because the temperature required is high enough to cause oxidation of the copper unless an inert atmosphere is pro­vided. The flow of dry nitrogen should continue until the joint has cooled. Always use a pressure regulator and safety valve to insure that only low pressure dry nitrogen is introduced into the tubing. Only a small flow is necessary to displace air and prevent oxidation.
PRECAUTIONS DURING BRAZING SERVICE VALVE
Precautions should be taken to prevent heat damage to service valve by wrapping a wet rag around it as shown in Figure 4. Also, protect all painted surfaces, insulation, and plastic base during brazing. After braz­ing cool joint with wet rag.
This is not a backseating valve. The service access port has a valve core. Opening or closing valve does not close service access port.
If the valve stem is backed out past the chamfered retaining wall, the O-ring can be damaged causing leakage or system pressure could force the valve stem out of the valve body possibly causing personal injury.
FIGURE 2: Tubing Hanger
FIGURE 3: Underground Installation
PRECAUTIONS DURING BRAZING OF LINES
All outdoor unit and evaporator coil connections are copper-to-copper and should be brazed with a phosphorous-copper alloy material such as Silfos-5 or equivalent. DO NOT use soft solder. The outdoor units have reusable service valves on both the liquid and vapor connections. The total system refrigerant charge is retained within the outdoor unit during shipping and installation. The reusable service valves are pro­vided to evacuate and charge per this instruction.
Serious service problems can be avoided by taking adequate precau­tions to assure an internally clean and dry system.
Valve can be opened by removing the plunger cap and fully inserting a hex wrench into the stem and backing out counter-clockwise until valve stem just touches the chamfered retaining wall.
Connect the refrigerant lines using the following procedure:
1. Remove the cap and Schrader core from both the liquid and vapor service valve service ports at the outdoor unit. Connect low pres­sure nitrogen to the liquid line service port.
2. Braze the liquid line to the liquid valve at the outdoor unit. Be sure to wrap the valve body with a wet rag. Allow the nitrogen to con­tinue flowing. Refer to the Tabular Data Sheet for proper liquid line sizing.
3. Carefully remove the rubber plugs from the evaporator liquid and vapor connections at the indoor coil.
4. Braze the liquid line to the evaporator liquid connection. Nitrogen should be flowing through the evaporator coil.
FIGURE 4: Heat Protection
4 Johnson Controls Unitary Products
The evaporator is pressurized.
501054-UIM-A-0909
5. Slide the grommet away from the vapor connection at the indoor coil. Braze the vapor line to the evaporator vapor connection. After the connection has cooled, slide the grommet back into original position. Refer to the Tabular Data Sheet for proper vapor line siz­ing.
6. Protect the vapor valve with a wet rag and braze the vapor line connection to the outdoor unit. The nitrogen flow should be exiting the system from the vapor service port connection. After this con­nection has cooled, remove the nitrogen source from the liquid fit­ting service port.
7. Replace the Schrader core in the liquid and vapor valves.
8. Go to SECTION IV for TXV installation.
9. Leak test all refrigerant piping connections including the service port flare caps to be sure they are leak tight. DO NOT OVER­TIGHTEN (between 40 and 60 inch - lbs. maximum).
10. Evacuate the vapor line, evaporator and the liquid line, to 500 microns or less.
NOTE: Line set and indoor coil can be pressurized to 250 psig with dry nitrogen and leak tested with a bubble type leak detector. Than release the nitrogen charge.
NOTE: Do not use the system refrigerant in the outdoor unit to purge or leak test.
11. Replace cap on service ports. Do not remove the flare caps from the service ports except when necessary for servicing the system.
Do not connect manifold gauges unless trouble is suspected. Approximately 3/4 ounce of refrigerant will be lost each time a stan­dard manifold gauge is connected.
5. Reinstall the liquid line to the top of the thermal expansion valve. Hand modify the liquid line to align with casing opening.
6. Install the TXV equalizer line into the vapor line as follows: a. Select a location on the vapor line for insertion of the equal-
izer line which will not interfere with TXV bulb placement.
b. Use an awl to punch through the suction tube and insert the
awl to a depth to achieve a 1/8” diameter hole.
7. Install TXV equalizer line in 1/8” hole previously made in vapor line. Equalizer line should not be bottomed out in vapor line. Insert equalizer line at least 1/4” in the vapor line. Braze equalizer line making sure that tube opening is not brazed closed.
Dry nitrogen should always be supplied through the tubing while it is being brazed, because the temperature required is high enough to cause oxidation of the copper unless an inert atmosphere is pro­vided. The flow of dry nitrogen should continue until the joint has cooled. Always use a pressure regulator and safety valve to insure that only low pressure dry nitrogen is introduced into the tubing. Only a small flow is necessary to displace air and prevent oxidation.
All connections to be brazed are copper-to-copper and should be brazed with a phosphorous-copper alloy material such as Silfos-5 or equivalent. DO NOT use soft solder.
Install the TXV bulb to the vapor line near the equalizer line, using the two bulb clamps furnished with the TXV assembly. Ensure the bulb is making maximum contact. Refer to TXV installation instruction for view of bulb location.
12. Release the refrigerant charge into the system. Open both the liq­uid and vapor valves by removing the plunger cap and with an allen wrench back out counter-clockwise until valve stem just touches the chamfered retaining wall. See - PRECAUTIONS DURING BRAZING SERVICE VALVE.
13. Replace plunger cap finger tight, then tighten an additional 1/12 turn (1/2 hex flat). Cap must be replaced to prevent leaks.
Never attempt to repair any brazed connections while the system is under pressure. Personal injury could result.
See SYSTEM CHARGE section for checking and recording system charge.
SECTION IV: INST ALLA TIONS REQUIRING TXV
For installations requiring a TXV, the following are the basic steps for installation. For detailed instructions, refer to the Installation Instructions accompanying the TXV kit.
Install TXV kit as follows:
1. First, relieve the holding charge by depressing the Schrader valve located in the end of the liquid line.
2. After holding charge is completely discharged, loosen and remove the liquid line fitting from the orifice distributor assembly. Note that the fitting has right
3. Remove the orifice from the distributor body using a small diame­ter wire or paper clip. Orifice is not used when the TXV assembly is installed.
4. After orifice is removed, install the thermal expansion valve to the orifice distributor assembly with supplied fittings. Hand tighten and turn an additional 1/8 turn to seal. Do not overtighten fittings
hand threads.
.
In all cases, mount the TXV bulb after vapor line is brazed and has had sufficient time to cool.
1. Bulb should be installed on a horizontal run of the vapor line if pos­sible. On lines under 7/8" O.D. the bulb may be installed on top of the line. With 7/8" O.D. and over, the bulb should be installed at the position of about 2 or 10 o'clock.
2. If bulb installation is made on a vertical run, the bulb should be located at least 16 inches from any bend, and on the tubing sides opposite the plane of the bend. The bulb should be positioned with the bulb tail at the top, so that the bulb acts as a reservoir.
3. Bulb should be insulated using thermal insulation provided to pro­tect it from the effect of the surrounding ambient temperature.
SECTION V: ELECTRICAL CONNECTIONS
GENERAL INFORMATION & GROUNDING
Check the electrical supply to be sure that it meets the values specified on the unit nameplate and wiring label.
Power wiring, control (low voltage) wiring, disconnect switches and over current protection must be supplied by the installer. Wire size should be sized per NEC requirements.
All field wiring must USE COPPER CONDUCTORS ONLY and be in accordance with Local, National Fire, Safety & Electrical Codes. This unit must be grounded with a separate ground wire in accor­dance with the above codes.
The complete connection diagram and schematic wiring label is located on the inside surface of the unit service access panel and this instruc­tion.
Johnson Controls Unitary Products 5
501054-UIM-A-0909
Corner Cover
Control Wiring
Power Wiring
Service Access
Panel
Ambient Temperature Sensor
COMMUNICATIONS PORT
CONTROL BOARD
COMMUNICATIONS HARNESS
JUNCTION BOX
FIELD CONNECTIONS POWER WIRING
1. Install the proper size weatherproof disconnect switch outdoors and within sight of the unit.
2. Remove the screws at the bottom of the corner cover. Slide corner cover down and remove from unit. See Figure 5.
3. Run power wiring from the disconnect switch to the unit.
4. Remove the service access panel to gain access to the unit wiring. Route wires from disconnect through power wiring opening pro­vided and into the unit control box.
5. Install the proper size time-delay fuses or circuit breaker, and make the power supply connections.
6. Energize the crankcase heater if equipped to save time by pre­heating the compressor oil while the remaining installation is com­pleted.
NOTE: To eliminate erratic operation, seal the hole in the wall at the thermostat with permagum or equivalent to prevent air drafts affecting the operation of in the thermostat.
FIELD CONNECTIONS CONTROL WIRING ­COMMUNICATING
1. The Communication Harness is provided with the communicating thermostat.
2. Route low voltage four conductor shielded thermostat communica­tions harness into junction box and connect to communications port on control board. See Figure 6.
3. The complete connection diagram and schematic wiring label is located on the inside surface of the unit service access panel.
If unit is going to be setup as a communicating system, the conven­tional wiring must be removed from the Outdoor Control Board.
FIGURE 5: Typical Field Wiring
FIELD CONNECTIONS CONTROL WIRING ­CONVENTIONAL
1. Route low voltage wiring into bottom of control box as shown in Figure 5. Make low voltage wiring connections inside the junction box per Figures 10 - 15.
2. The complete connection diagram and schematic wiring label is located on the inside surface of the unit service access panel.
3. Replace the corner cover and service access panel removed in Steps 2 and 4 of the “Field Connections Power Wiring” section.
NOTE: Ambient temperature sensor should extend below control box by 1”.
4. All field wiring to be in accordance with national electrical codes (NEC) and/or local-city codes.
5. Mount the thermostat about 5 ft. above the floor, where it will be exposed to normal room air circulation. Do not place it on an out­side wall or where it is exposed to the radiant effect from exposed glass or appliances, drafts from outside doors or supply air grilles.
6. Route the 24-volt control wiring (NEC Class 2) from the outdoor unit to the indoor unit and thermostat.
FIGURE 6: Communications Harness Connection
4. Replace the corner cover and service access panel removed in Steps 2 and 4 of the “Field Connections Power Wiring” section.
NOTE: Ambient temperature sensor should extend below control box by 1”.
5. Route the 24-volt control wiring (NEC Class 2) from the outdoor unit to the indoor unit and thermostat.
6. All field wiring to be in accordance with national electrical codes (NEC) and/or local-city codes.
7. Mount the thermostat about 5 ft. above the floor, where it will be exposed to normal room air circulation. Do not place it on an out­side wall or where it is exposed to the radiant effect from exposed glass or appliances, drafts from outside doors or supply air grilles.
NOTE: To eliminate erratic operation, seal the hole in the wall at the thermostat with permagum or equivalent to prevent air drafts affecting the operation of in the thermostat.
6 Johnson Controls Unitary Products
DEHUMIDIFICATION CONTROL
HEAT
DELAY COOL
ADJUST
A
B
C
D
A
B
C
D
LED 2
R
C
Y1
Y2
Touch Control
Communicating
Control
Air Handler/Furnace
Communicating
Control
Heat Pump
Communicating
Control
GND or C
GND or C
B-
R
A+
GND or C
GND or C
B-
R
A+
GND or C
GND or C
B-
R
A+
R
C
Y1
Y2
HUM
W2
DHUM
W
G
C
R
O
Y
Y2
HUM
W2
DHUM
W
G
C
R
O
Y
Y2
Touch Control
Communicating
Control
Communicating
Indoor
Interface Control
Non-Communicating
Indoor Unit
Heat Pump
Communicating
Control
Wire per
non-comm.
installation
manual
Assume that
connections
are from
thermostat
GND or C
GND or C
B-
R
A+
GND or C
GND or C
B-
R
A+
GND or C
GND or C
B-
R
A+
A dehumidification control accessory 2HU06700124 may be used with variable speed air handlers or furnaces in high humidity areas. This control works with the variable speed indoor unit to provide cooling at a reduced air flow, lowering evaporator temperature and increasing latent capacity. The humidistat in this control opens the humidistat contacts on humidity rise. To install, refer to instructions packaged with the acces­sory and Figures 10 - 15. Prior to the installation of the dehumidification control, the jumper across the HUMIDISTAT terminals on the indoor variable speed air handler or furnace CFM selection board must be removed.
During cooling, if the relative humidity in the space is higher than the desired set point of the dehumidification control, the variable speed blower motor will operate at lower speed until the dehumidification con­trol is satisfied. A 40-60% relative humidity level is recommended to achieve optimum comfort.
If a dehumidification control is installed, it is recommended that a mini­mum air flow of 325 cfm/ton be supplied at all times.
CFM SELECTION BOARD SETTINGS
For proper system operation the CFM Selection Board jumpers must be set properly.
Refer to the Tabular Data Sheet for the recommended air flow settings for each size condensing unit.
Set the cooling speed per the instructions for the air handler or furnace by selecting the correct COOL and ADJ taps. Verify the airflow using the LED display on the CFM selection board.
The HUMIDISTAT jumper must also be removed if a dehumidistat is installed.
If installed as a communicating system (outdoor, indoor and thermo­stat), the system will automatically adjust to the optimal airflow settings. These parameters can also be modified using the communicating ther­mostat. Refer to the communicating thermostat owner’s manual for this procedure. Manual setting of the airflow jumpers on the ID equipment is not necessary with the communicating thermostat.
501054-UIM-A-0909
FIGURE 8: Communicating HP with Communicating Air Handler or
Furnace
FIGURE 7: CFM Selection Board
Johnson Controls Unitary Products 7
FIGURE 9: Communicating HP with Non-Communicating Air Handler
or Furnace using Communicating Interface Control
501054-UIM-A-0909
HP 24A Two Stage Heat Pump – Two Stage Variable Speed Furnace (With Hot Heat Pump Operation)
O
Reversing Valve
Energized in Cool
C
24 – Volt Common
R
24 – Volt Hot
W1 OUT
First Stage Heat
W2 OUT
Second Stage Heat
Y2 OUT
Second Stage Compressor
Y1
Single Stage Compressor
X/L
Malfunction Light
Y2
Second Stage Compressor
W
Auxiliary Heat
BS
Bonnet Sensor
BSG
Bonnet Sensor
TWO STAGE HEAT PUMP
Bonnet Sensor
(Optional)
C
24 – Volt Common
Y1
First Stage Compressor
L
Malfunction Light
Y2
Second Stage Compressor
G
Fan
*PP32U71124 *PP32U72124
THERMOSTAT
R
24 – Volt Hot
E/W1
First Stage Aux. Heat
W2
Second Stage Aux. Heat
DHM
Dehumidistat
HM
Humidistat
O
Reversing Valve
Energized in Cool
Change FFuel jumper
on the heat pump control
to “ON”
Part Numbers:
SAP = Legacy
126768 = 031-09137 18395 = 031-01996 340512 = 031-09178
1
1
Part Numbers:
SAP = Legacy
265904 = 031-09169
2
C
24 – Volt Common
R
24 – Volt Hot
Y1
Single Stage Compressor
TWO STAGE
VARIABLE SPEED
FURNACE CONTROL
G
Fan
TWO STAGE
VARIABLE SPEED
FURNACE
W/W1
First Stage Heat
Y/Y2
Second or Full
Stage Compressor
W2
Second Stage Heat
O
Reversing Valve
X/L
Malfunction Light
DHUM
Dehumidification
2
Move HEAT PUMP
jumper to “YES”
Move DHUM
jumper to “YES”
if humidistat is to be used.
PV(8/9)
ID MODELS
(F/L)*(8/9)V
YORKGUARD VI
CONTROL
(G/L)(8/9)V
YZE
OD MODELS
YZH H*5 H*8
24VAC Humidifier
(Optional)
Step 1 of the Thermostat
Installer Table must be
set to Heat Pump
E2/P Switch must be in the
E2 position
Step 2 of the Thermostat
Installer Table must be
set to 2
Step 5 of Thermostat User
Configuration Menu must
be set to “ON” for
Dehumidification
Change Hot Heat Pump
jumper on the heat pump
control to “ON”
For additional connection diagrams for all UPG equipment refer to “Low Voltage System Wiring” document available online at www.upgnet.com in the Product Catalog Section.
FIGURE 10: Thermostat Wiring – Two-Stage Heat Pumps - Two-Stage Variable Speed Furnaces
8 Johnson Controls Unitary Products
HP 24C Two Stage Heat Pump – Two Stage Variable Speed Furnace (With Hot Heat Pump Operation)
O
Reversing Valve
Energized in Cool
C
24 – Volt Common
R
24 – Volt Hot
W1 OUT
First Stage Heat
W2 OUT
Second Stage Heat
Y2 OUT
Second Stage Compressor
Y1
Single Stage Compressor
X/L
Malfunction Light
Y2
Second Stage Compressor
W
Auxiliary Heat
BS
Bonnet Sensor
BSG
Bonnet Sensor
TWO STAGE HEAT PUMP
Bonnet Sensor
(Optional)
Change FFuel jumper
on the heat pump control
to “ON”
Part Numbers:
SAP = Legacy 126768 = 031-09137 18395 = 031-01996 340512 = 031-09178
1
1
Part Numbers:
SAP = Legacy
265904 = 031-09169
2
C
24 – Volt Common
R
24 – Volt Hot
Y1
Single Stage Compressor
TWO STAGE
VARIABLE SPEED
FURNACE CONTROL
G
Fan
TWO STAGE
VARIABLE SPEED
FURNACE
W/W1
First Stage Heat
Y/Y2
Second or Full
Stage Compressor
W2
Second Stage Heat
O
Reversing Valve
X/L
Malfunction Light
DHUM
Dehumidification
2
Move HEAT PUMP
jumper to “YES”
Move DHUM
jumper to “YES”
if humidistat is to be used.
PV(8/9)
ID MODELS
(F/L)*(8/9)V
YORKGUARD VI
CONTROL
(G/L)(8/9)V
YZE
OD MODELS
YZH H*5 H*8
C
24 – Volt Common
R
24 – Volt Hot
Y1
First Stage Compressor
O
Reversing Valve
Energized in Cool
L
Malfunction Light
Y2
Second Stage Compressor
G
Fan
*DN22H00124 *DP22U70124
THERMOSTAT
E/W1
First Stage Aux. Heat
W2
Second Stage Aux. Heat
C
24 – Volt Common
Y
First Stage Compressor
O/B
Reversing Valve
L
Malfunction Light
Y2
Second Stage Compressor
G
Fan
*PP32U70124
THERMOSTAT
E
Emergency Heat
R
24 – Volt Hot
(Heat XFMR)
RC 24 – Volt Hot (Cool XFMR)
AUX
Auxiliary Heat
Step 1 of Thermostat Installer/Configuration
Menu must be set to “HP2”
Selection of GAS/ELEC
switch on thermostat
not necessary
Thermostat Installer Setup
0170-System Type-
must be set to 12
3 Heat/2 Heat Pump
Thermostat Installer Setup
0190-Changeover Valve-
must be set to 0
O/B terminal
Energized in Cooling
Thermostat Installer Setup
0200-Backup Heat Source-
must be set to 1
Heat Pump Backup Heat
Source is Fossil Fuel
External Humidistat
(Optional)
Open on Humidity Rise
Thermostat Installer Setup
0210-External Fossil Fuel
Kit- must be set to 1
Heat Pump Control
is Controlling Heat Pump
Backup Heat
Change Hot Heat Pump
jumper on the heat pump
control to “ON”
3
501054-UIM-A-0909
FIGURE 11: Thermostat Wiring – Two-Stage Heat Pump - Two-Stage Variable Speed Furnaces
Johnson Controls Unitary Products 9
501054-UIM-A-0909
HP 27A Two Stage Heat Pump – Variable Speed Air Handler (With Hot Heat Pump Operation)
O
Reversing Valve
Energized in Cool
C
24 – Volt Common
R
24 – Volt Hot
W1 OUT
First Stage Heat
W2 OUT
Second Stage Heat
Y2 OUT
Second Stage Compressor
Y1
Single Stage Compressor
X/L
Malfunction Light
Y2
Second Stage Compressor
W
Auxiliary Heat
BS
Bonnet Sensor
BSG
Bonnet Sensor
TWO STAGE HEAT PUMP
C
24 – Volt Common
Y1
First Stage Compressor
L
Malfunction Light
Y2
Second Stage Compressor
G
Fan
*PP32U71124 *PP32U72124
THERMOSTAT
R
24 – Volt Hot
E/W1
First Stage Aux. Heat
W2
Second Stage Aux. Heat
DHM
Dehumidistat
HM
Humidistat
Step 1 of the Thermostat
Installer Table must be
set to Heat Pump
O
Reversing Valve
Energized in Cool
1
24VAC Humidifier
(Optional)
Part Numbers:
SAP = Legacy
159481 = 031-09157
2
COM
24 – Volt Common
R
24 – Volt Hot
W1
First Stage Aux. Heat
W2
Second Stage Aux. Heat
Y1
Single Stage Compressor
Y/Y2
Second or Full
Stage Compressor
O
Reversing Valve
Energized in Cool
X/L
Malfunction Light
HUM
Dehumidification-
Open on Humidity Rise
VARIABLE SPEED
AIR HANDLER CONTROL
G
Fan
Move the MODE
jumper to “HP”
Move the HUM STAT
jumper to “YES”
if humidistat is to be used.
VARIABLE SPEED
AIR HANDLER
2
Part Numbers:
SAP = Legacy
126768 = 031-09137 18395 = 031-01996 340512 = 031-09178
1
AV
ID MODELS
SV MV
YZE
OD MODELS
YZH H*5
YORKGUARD VI
CONTROL
H*8
24VAC
Electronic Air Cleaner
(Optional)
E2/P Switch must be in the
E2 position
Step 2 of the Thermostat
Installer Table must be
set to 2
Step 5 of Thermostat User
Configuration Menu must
be set to “ON” for
Dehumidification
EAC(24 VAC out)
Electronic Air Cleaner
Refer to AH documentation
for W1 and W2 electric
heat staging options.
HUM OUT
(24 VAC out)
Second stage auxiliary
heat will be controlled by
the thermostat, not the
heat pump control when
wired as shown.
Change Hot Heat Pump
jumper on the heat pump
control to “ON”
FIGURE 12: Thermostat Wiring – Two-Stage Heat Pump - Variable Speed Air Handler
10 Johnson Controls Unitary Products
HP 27C Two Stage Heat Pump – Variable Speed Air Handler (With Hot Heat Pump Operation)
O
Reversing Valve
Energized in Cool
C
24 – Volt Common
R
24 – Volt Hot
W1 OUT
First Stage Heat
W2 OUT
Second Stage Heat
Y2 OUT
Second Stage Compressor
Y1
Single Stage Compressor
X/L
Malfunction Light
Y2
Second Stage Compressor
W
Auxiliary Heat
BS
Bonnet Sensor
BSG
Bonnet Sensor
TWO STAGE
HEAT PUMP
C
24 – Volt Common
R
24 – Volt Hot
Y1
First Stage Compressor
O
Reversing Valve
Energized in Cool
L
Malfunction Light
Y2
Second Stage Compressor
G
Fan
*DN22H00124
*DP22U70124
THERMOSTAT
E/W1
First Stage Aux. Heat
W2
Second Stage Aux. Heat
Step 1 of Thermostat
Installer/Configuration
Menu must be set to “HP2”
Selection of GAS/ELEC
switch on thermostat
not necessary
C
24 – Volt Common
Y
First Stage Compressor
O/B
Reversing Valve
L
Malfunction Light
Y2
Second Stage Compressor
G
Fan
*PP32U70124
THERMOSTAT
E
Emergency Heat
R
24 – Volt Hot
(Heat XFMR)
RC
24 – Volt Hot
(Cool XFMR)
Thermostat Installer Setup
0170-System Type-
must be set to 12
3 Heat/2 Heat Pump
Thermostat Installer Setup
0190-Changeover Valve-
must be set to 0
O/B terminal
Energized in Cooling
Thermostat Installer Setup
0200-Backup Heat Source-
must be set to 0
Heat Pump Backup Heat
Source is Electric
AUX
Auxiliary Heat
1
24VAC Humidifier
(Optional)
Part Numbers:
SAP = Legacy
159481 = 031-09157
2
COM
24 – Volt Common
R
24 – Volt Hot
W1
First Stage Aux. Heat
W2
Second Stage Aux. Heat
Y1
Single Stage Compressor
Y/Y2
Second or Full
Stage Compressor
O
Reversing Valve
Energized in Cool
X/L
Malfunction Light
HUM
Dehumidification-
Open on Humidity Rise
VARIABLE SPEED
AIR HANDLER CONTROL
G
Fan
Move the MODE
jumper to “HP”
Move HUM STAT
jumper to “YES”
if humidistat is to be used.
VARIABLE SPEED
AIR HANDLER
2
Part Numbers:
SAP = Legacy
126768 = 031-09137 18395 = 031-01996 340512 = 031-09178
1
AV
ID MODELS
SV MV
YZE YZH
H*5
YORKGUARD VI
CONTROL
H*8
24VAC
Electronic Air Cleaner
(Optional)
EAC(24 VAC out)
Electronic Air Cleaner
External Humidistat
(Optional)
Open on Humidity Rise
HUM OUT
(24 VAC out)
Refer to AH documentation
for W1 and W2 electric
heat staging options.
Second stage auxiliary
heat will be controlled by
the thermostat, not the
heat pump control when
wired as shown.
OD MODELS
Change Hot Heat Pump
jumper on the heat pump
control to “ON”
3
Part Number:
S1-2HU16700124
3
501054-UIM-A-0909
FIGURE 13: Thermostat Wiring – Two-Stage Heat Pump - Variable Speed Air Handler
Johnson Controls Unitary Products 11
501054-UIM-A-0909
HP 28A Two Stage Heat Pump – Variable Speed Modulating Furnace (With Hot Heat Pump Operation)
O
Reversing Valve
Energized in Cool
C
24 – Volt Common
R
24 – Volt Hot
W1 OUT
First Stage Heat
W2 OUT
Second Stage Heat
Y2 OUT
Second Stage Compressor
Y1
Single Stage Compressor
X/L
Malfunction Light
Y2
Second Stage Compressor
W
Auxiliary Heat
BS
Bonnet Sensor
BSG
Bonnet Sensor
YORKGUARD VI
CONTROL
TWO STAGE HEAT PUMP
Bonnet Sensor
(Optional)
C
24 – Volt Common
Y1
First Stage Compressor
L
Malfunction Light
Y2
Second Stage Compressor
G
Fan
*PP32U71124 *PP32U72124
THERMOSTAT
R
24 – Volt Hot
E/W1
First Stage Aux. Heat
W2
Second Stage Aux. Heat
DHM
Dehumidistat
HM
Humidistat
O
Reversing Valve
Energized in Cool
C
24 – Volt Common
R
24 – Volt Hot
Y1
Single Stage Compressor
VARIABLE SPEED
MODULATING
FURNACE CONTROL
G
Fan
VARIABLE SPEED
MODULATING
FURNACE
Y/Y2
Second or Full
Stage Compressor
HUM
Dehumidification-
Open on Humidity Rise
W
Modulating Heat
Change FFuel jumper
on the heat pump control
to “ON”
1
Part Numbers:
SAP = Legacy
171334 = 031-09153
2
2
Move HUMIDISTAT
jumper to “YES”
if humidistat is to be used.
Part Numbers:
SAP = Legacy
126768 = 031-09137 18395 = 031-01996 340512 = 031-09178
1
PC(8/9)
ID MODELS
FC(8/9)C FL(8/9)C
YZE
OD MODELS
YZH
H*5 H*8
Step 1 of the Thermostat
Installer Table must be
set to Heat Pump
E2/P Switch must be in the
E2 position
Step 2 of the Thermostat
Installer Table must be
set to 2
Step 5 of Thermostat User
Configuration Menu must
be set to “ON” for
Dehumidification
24VAC Humidifier
(Optional)
Change Hot Heat Pump
jumper on the heat pump
control to “ON”
FIGURE 14: Thermostat Wiring – Two-Stage Heat Pump - Variable Speed Modulating Furnace
12 Johnson Controls Unitary Products
HP 28C Two Stage Heat Pump – Variable Speed Modulating Furnace (With Hot Heat Pump Operation)
O
Reversing Valve
Energized in Cool
C
24 – Volt Common
R
24 – Volt Hot
W1 OUT
First Stage Heat
W2 OUT
Second Stage Heat
Y2 OUT
Second Stage Compressor
Y1
Single Stage Compressor
X/L
Malfunction Light
Y2
Second Stage Compressor
W
Auxiliary Heat
BS
Bonnet Sensor
BSG
Bonnet Sensor
YORKGUARD VI
CONTROL
TWO STAGE
HEAT PUMP
Bonnet Sensor
(Optional)
C
24 – Volt Common
R
24 – Volt Hot
Y1
Single Stage Compressor
VARIABLE SPEED
MODULATING
FURNACE CONTROL
G
Fan
VARIABLE SPEED
MODULATING
FURNACE
Y/Y2
Second or Full
Stage Compressor
HUM
Dehumidification-
Open on Humidity Rise
W
Modulating Heat
Change FFuel jumper
on the heat pump control
to “ON”
1
Part Numbers:
SAP = Legacy
171334 = 031-09153
2
2
Move HUMIDISTAT
jumper to “YES”
if humidistat is to be used.
Part Numbers:
SAP = Legacy
126768 = 031-09137 18395 = 031-01996 340512 = 031-09178
1
PC(8/9)
ID MODELS
FC(8/9)C FL(8/9)C
YZE
OD MODELS
YZH
H*5 H*8
C
24 – Volt Common
R
24 – Volt Hot
Y1
First Stage Compressor
O
Reversing Valve
Energized in Cool
L
Malfunction Light
Y2
Second Stage Compressor
G
Fan
*DN22H00124
*DP22U70124
THERMOSTAT
E/W1
First Stage Aux. Heat
W2
Second Stage Aux. Heat
C
24 – Volt Common
Y
First Stage Compressor
O/B
Reversing Valve
L
Malfunction Light
Y2
Second Stage Compressor
G
Fan
*PP32U70124
THERMOSTAT
E
Emergency Heat
R
24 – Volt Hot
(Heat XFMR)
RC 24 – Volt Hot (Cool XFMR)
AUX
Auxiliary Heat
Step 1 of Thermostat
Installer/Configuration
Menu must be set to “HP2”
Selection of GAS/ELEC
switch on thermostat
not necessary
Thermostat Installer Setup
0170-System Type-
must be set to 12
3 Heat/2 Heat Pump
Thermostat Installer Setup
0190-Changeover Valve-
must be set to 0
O/B terminal
Energized in Cooling Thermostat Installer Setup 0200-Backup Heat Source-
must be set to 1
Heat Pump Backup Heat
Source is Fossil Fuel
External Humidistat
(Optional)
Open on Humidity Rise
Thermostat Installer Setup
0210-External Fossil Fuel
Kit- must be set to 1
Heat Pump Control
is Controlling Heat Pump
Backup Heat
Change Hot Heat Pump
jumper on the heat pump
control to “ON”
3
501054-UIM-A-0909
FIGURE 15: Thermostat Wiring – Two-Stage Heat Pump - Variable Speed Modulating Furnace
Johnson Controls Unitary Products 13
501054-UIM-A-0909
.
TXV (Cooling)
SHOWN IN COOLING POSITION.
COOLING CYCLE FLOW HEATING CYCLE FLOW
INDOOR COIL
4-WAY REVERSING VALV E
SUCTION ACCUMULATOR
COMPRESSOR
OUTDOOR COIL
FIELD CONNECTED LINE
FILTER DRYER (Solid core)
LIQUID SENSOR
FIELD CONNECTED LINE
TXV (Heating)
SECTION VI: EVACUATION
It will be necessary to evacuate the system to 500 microns or less. If a leak is suspected, leak test with dry nitrogen to locate the leak. Repair the leak and test again.
To verify that the system has no leaks, simply close the valve to the vac­uum pump suction to isolate the pump and hold the system under vac­uum. Watch the micron gauge for a few minutes. If the micron gauge indicates a steady and continuous rise, it’s an indication of a leak. If the gauge shows a rise, then levels off after a few minutes and remains fairly constant, its an indication that the system is leak free but still con­tains moisture and may require further evacuation if the reading is above 500 microns.
SECTION VII: SYSTEM CHARGE
R-410A refrigerant cylinders are rose colored, and have a dip tube which allows liquid to flow out of the cylinder in the
Always charge the system slowly with the tank in the upright
tion.
position.
The factory charge in the outdoor unit includes enough charge for the unit, a 15 ft. line set and the smallest indoor coil match-up. Some indoor coil matches may require additional charge. See tabular data sheet pro­vided in unit literature packet for charge requirements.
Do not leave the system open to the atmosphere. Unit damage could occur due to moisture being absorbed by the POE oil in the system. This type of oil is highly susceptible to moisture absorp­tion.
The TOTAL SYSTEM CHARGE must be permanently stamped on the unit data plate.
Total system charge is determined as follows:
1. Determine outdoor unit charge from tabular data sheet.
2. Determine indoor coil adjustment from tabular data sheet.
3. Calculate the line charge using the tabular data sheet if line length is greater than15 feet.
4. Total system charge = item 1 + item 2 + item 3.
5. Permanently stamp the unit data plate with the total amount of refrigerant in the system.
Use the following subcooling charging method whenever additional refrigerant is required for the system charge. A superheat charging method is not suitable for TXV equipped systems.
Upright Posi-
Refrigerant charging should only be carried out by a qualified air conditioning contractor.
Measurement Method
If a calibrated charging cylinder or accurate weighing device is avail­able, add refrigerant accordingly.
Compressor damage will occur if system is improperly charged. On new system installations, charge system per tabular data sheet for the matched coil and follow guidelines in this instruction.
Check flare caps on service ports to be sure they are leak tight. DO NOT OVERTIGHTEN (between 40 and 60 inch - lbs. maximum).
Subcooling Charging Method
For the heating operation, there is no accurate subcooling method for charging the unit. If unit charging is required during heating operation, the unit must be evacuated and charge weighed-in per the marking on the rating plate.
For the cooling operation, the recommended subcooling is typically around 10°F. This may vary greatly based on each unique system.
1. Set the system running in the cooling mode by setting the thermo­stat at least 6°F below the room temperature.
2. Operate the system for a minimum of 15-20 minutes.
3. Refer to the tabular data sheet for the recommended airflow and verify this indoor airflow (it should be about 400 SCFM per ton).
4. Measure the liquid refrigerant pressure P and temperature T at the service valve.
5. Calculate the saturated liquid temperature ST from Table 2 ­R-410A, SATURATION PROPERTIES.
6. Subcooling temperature TC = Saturated T emperature (ST) - Liquid Temp (T).
Example: The pressure P and temperature T measured at the liquid service port is 360 psig and 93°F. From Table 2, the saturated tem­perature for 360 psig is 109°. The subcooling temperature TC = 109°-93°=16°F
Add charge if the calculated subcooling temperature TC in Step 6 is lower than the recommended level. Remove and recover the refrigerant if the subcooling TC is higher than the recommended level.
See rating plate for unit specific subcooling chart. See Figure 16 to trace the flow of refrigerant through the system.
FIGURE 16: Heat Pump Flow Diagram
14 Johnson Controls Unitary Products
501054-UIM-A-0909
SECTION VIII: SYSTEM OPERATION
For more information on the control operation, refer to “Operation Instructions - DEMAND DEFROST CONTROL BOARD in this Booklet.
REQUIRED CONTROL SETUP
The following steps must be taken at the time of installation to insure proper system operation.
1. Consult system wiring diagram to determine proper thermostat wiring for your system.
2. If hot heat pump configuration is desired, change HOT HEAT PUMP jumper to ON position. This setting MUST be set on the defrost control board.
3. If installation includes a fossil fuel furnace, change FUEL jumper to ON position. This setting MUST be set on the defrost control board.
4. Set low temperature cutout (LTCO), balance point (BP), switch point (SP), and Y2 Lock jumpers as desired. These settings may be modified by communicating thermostat.
5. Verify proper system functionality. Confirm room thermostat opera­tion including fault code display capability.
6. Upon completion of installation, verify that no fault codes are stored in memory. Clear the fault code memory if necessary.
DEFROST OPERATION
The following defrost curve selection jumper positions are set from fac­tory.
TABLE 1:
INDICATIONS OF PROPER OPERATION
Cooling
Cooling operation is the same as any conventional air conditioning unit.
1. The outdoor fan should be running, with warm air being dis-
2. The indoor blower (furnace or air handler) will be operating, dis-
3. The vapor line at the outdoor unit will feel cool to the touch.
4. The liquid line at the outdoor unit will feel warm to the touch.
TABLE 2:
Defrost Initiate Curves
Defrost Curve Selection
Jumper Position
Heat Pump Model N/A N/A 3 Ton N/A
charged from the top of the unit.
charging cool air from the ducts. Coils or other parts in the air cir­cuit should be cleaned as often as necessary to keep the unit clean. Use a brush, vacuum cleaner attachment, or other suitable means.
R-410A Saturation Properties
TEMP. °F
45 129.70 60 169.60 75 217.40 90 274.10 105 340.50 46 132.20 61 172.60 76 220.90 91 278.20 106 345.30 47 134.60 62 175.50 77 224.40 92 282.30 107 350.10 48 137.10 63 178.50 78 228.00 93 286.50 108 355.00 49 139.60 64 181.60 79 231.60 94 290.80 109 360.00 50 142.20 65 184.60 80 235.30 95 295.10 110 365.00 51 144.80 66 187.70 81 239.00 96 299.40 111 370.00 52 147.40 67 190.90 82 242.70 97 303.80 112 375.10 53 150.10 68 194.10 83 246.50 98 308.20 113 380.20 54 152.80 69 197.30 84 250.30 99 312.70 114 385.40 55 155.50 70 200.60 85 254.10 100 317.20 115 390.70 56 158.20 71 203.90 86 258.00 101 321.80 116 396.00 57 161.00 72 207.20 87 262.00 102 326.40 117 401.30 58 163.90 73 210.60 88 266.00 103 331.00 118 406.70 59 166.70 74 214.00 89 270.00 104 335.70 119 412.20
PRESSURE
PSIG
1234
TEMP. °F
PRESSURE
PSIG
TEMP. °F
Heating
Indications of proper Heating operation is as follows:
1. The outdoor fan should be running, with cool air being discharged from the top of the unit.
2. The indoor blower (furnace or air handler) will be operating, dis­charging warm air from the ducts.
3. The vapor line at the outdoor unit will feel warm to the touch.
4. The liquid line at the outdoor unit will feel cool to the touch.
SECTION IX: INSTRUCTING THE OWNER
Assist owner with processing warranty cards and/or online registration. Review Owners Guide and provide a copy to the owner and guidance on proper operation and maintenance. Instruct the owner or the opera­tor how to start, stop and adjust temperature setting.
When applicable, instruct the owner that the compressor is equipped with a crankcase heater to prevent the migration of refrigerant to the compressor during the OFF cycle. The heater is energized only when the unit is not running. If the main switch is disconnected for long peri­ods of shut down, do not attempt to start the unit until 8 hours after the switch has been connected. This will allow sufficient time for all liquid refrigerant to be driven out of the compressor.
The installer should also instruct the owner on proper operation and maintenance of all other system components.
MAINTENANCE
1. Dirt should not be allowed to accumulate on the outdoor coils or other parts in the air circuit. Clean as often as necessary to keep the unit clean. Use a brush, vacuum cleaner attachment, or other suitable means.
2. The outdoor fan motor is permanently lubricated and does not require periodic oiling.
3. If the coil needs to be cleaned, it should be washed with Calgon Coilclean (mix one part Coilclean to seven parts water). Allow solution to remain on coil for 30 minutes before rinsing with clean water. Solution should not be permitted to come in contact with painted surfaces.
4. Refer to the furnace or air handler instructions for filter and blower motor maintenance.
5. The indoor coil and drain pan should be inspected and cleaned regularly to prevent odors and assure proper drainage.
IT IS UNLAWFUL TO KNOWINGLY VENT, RELEASE OR DIS­CHARGE REFRIGERANT INTO THE OPEN AIR DURING REPAIR, SERVICE, MAINTENANCE OR THE FINAL DISPOSAL OF THIS UNIT.
PRESSURE
PSIG
TEMP. °F
PRESSURE
PSIG
TEMP. °F
PRESSURE
PSIG
Johnson Controls Unitary Products 15
SECTION X: WIRING DIAGRAM
FIGURE 17: Wiring Diagram
Subject to change without notice. Published in U.S.A. 501054-UIM-A-0909 Copyright © 2009 by Johnson Controls, Inc. All rights reserved. Supersedes: 361811-UIM-A-0208
Johnson Controls Unitary Products
5005 York Drive
Norman, OK 73069