CURRENT MONITORING
Off
Loss of belt/coupling shear
Off
Electrical
failure
Fan/pump
On
Calibrated
Trip
Point
Now you can easily detect when drive belts slip,
break, or pump couplings shear. In fact, a typical
HVAC motor that loses its load has a reduction of
current draw of up to 50%. That's why our sensors
are the industry standard for status.
Maximize Reliability
Minimize Installed Cost
H808
808 Series
Mini Solid-Core Adjustable Setpoint Dig i tal
Output Current Switches
38
The Hawkeye 808 Series is a high per for mance miniature solid-core current
status switch. Its low minimum setpoint (0.75A) and small size make it ideal for
monitoring status of small to medium motor loads. With an amperage range of
0.75 to 50 amps, the 808 series can accurately detect belt loss, coupling shear, or
other mechanical failure on loads from 1/5 to 40HP.
APPLICATIONS
■ Detect belt loss, coupling shear and mechanical failure
■ Verify lighting circuit and other electrical service run times
■ Monitor status of industrial process equipment
■ Monitor status of critical motors (compressor, fuel, etc.)
High performance miniature solid-core
■ Low (0.75A) minimum setpoint...eliminates the need for multiple wraps of
the conductor through the sensor even on loads as small as 1/5HP
■ Small size fi ts easily inside small starter enclosures
■ Adjustable/Removable mounting bracket optimizes in fi eld versatility
■ Status LEDs for easy setup and local indication
■ 1 Amp status output for increased application fl exibility
Monitor status of fans, pumps & elec trical loads
■ Detects belt loss and mechanical failure...ideal for fan/pump
status monitoring
■ Reliable cost-eff ective fan/pump status sensor...the 808 series replaces
pressure switches and other elec tro me chan i cal devices...no fi tting
or tapping required
■ Adjustable set point (0.75-50A)
■ 100% solid state...no moving parts to fail
■ 5-year limited warranty
ORDERING INFORMATION
MODEL AMPERAGE RANGE OUTPUT TYPE (Max.) TRIP POINT ADJUSTMENT STATUS OPEN LED STATUS CLOSED LED
H808 0.75 - 50A N.O. 1.0A@30VAC/DC
H806* 0.75 - 50A N.C. 0.1A@30VDC
H809** 0.75 - 50A N.O. 0.2A@120VAC/DC
*Hx06 Models requi re a constant source of 5-30VDC power to the status contacts.
**CE not currently available o n this product
ACCESSORIES
DIN Rail Clip Set...See page 234
800.354.8556
503.598.4564
www.veris.com
©2006Veris Industries
800.354.8556
503.598.4564
www.veris.com
©2006Veris Industries
Motor
Fan or Pump
CONTROLLER
DI
CONTACTOR
ø 0.71"
(18 mm)
ø 0.21"
(.5 mm)
ø1.80"
(46 mm)
2.77"
(70 mm)
1.02"
(26 mm)
1.79"
(45 mm)
2.25"
(57 mm)
0.90"
(23 mm)
0.20"
(.5 mm)
Removable/Adjustable Mounting Bracket
H808 SERIES
APPLICATIONS/WIRING EXAMPLE DIMENSIONAL DRAWINGS
CURRENT MONITORING
39
SPECIFICATIONS
Amperage Range 0.75 to 50A
Sensor Power In duced
Output Digital switch (see ordering table)
Insulation Class 600VAC rms
Frequenc y Range 50/60 Hz.
Temperature Range 15° to 50°C
Humidit y Range 0 - 95% non-condensing
Hysteresis 10% (typical)
Trip Setpoint Adjustable 0.75 to 50A
Dimensions…(L x W x H) 2.77" (70mm) x 1.79" (45mm) x 1.02" (26mm)
Sensor Ho le Size 0.71" (18mm) diameter
Status Cont acts (Hx06 Models):
Supply Voltage 5-30VDC, continuous supply
Off -state Leakage (max.) 24µA@30VDC
On-state Voltage Drop 1.7VDC (max.)@0.1A
Do not use the LED status indicators as evid ence of applied voltage.
800.354.8556
503.598.4564
www.veris.com
©2006Veris Industries