Johnson Controls H808 Series Catalog Page

CURRENT MONITORING
Off
Loss of belt/coupling shear
Off
Electrical failure
Fan/pump On
Calibrated
Trip
Point
Now you can easily detect when drive belts slip, break, or pump couplings shear. In fact, a typical HVAC motor that loses its load has a reduction of current draw of up to 50%. That's why our sensors are the industry standard for status.
H808


Maximize Reliability
Minimize Installed Cost
H808
808 Series
Mini Solid-Core Adjustable Setpoint Dig i tal Output Current Switches
38
The Hawkeye 808 Series is a high per for mance miniature solid-core current status switch. Its low minimum setpoint (0.75A) and small size make it ideal for monitoring status of small to medium motor loads. With an amperage range of
0.75 to 50 amps, the 808 series can accurately detect belt loss, coupling shear, or other mechanical failure on loads from 1/5 to 40HP.
APPLICATIONS
Detect belt loss, coupling shear and mechanical failure
Verify lighting circuit and other electrical service run times
Monitor status of industrial process equipment
Monitor status of critical motors (compressor, fuel, etc.)
High performance miniature solid-core
Low (0.75A) minimum setpoint...eliminates the need for multiple wraps of
the conductor through the sensor even on loads as small as 1/5HP
Small size fi ts easily inside small starter enclosures
Adjustable/Removable mounting bracket optimizes in fi eld versatility
Status LEDs for easy setup and local indication
1 Amp status output for increased application fl exibility
Monitor status of fans, pumps & elec trical loads
Detects belt loss and mechanical failure...ideal for fan/pump
status monitoring
Reliable cost-eff ective fan/pump status sensor...the 808 series replaces
pressure switches and other elec tro me chan i cal devices...no fi tting or tapping required
Adjustable set point (0.75-50A)
100% solid state...no moving parts to fail
5-year limited warranty
ORDERING INFORMATION
MODEL AMPERAGE RANGE OUTPUT TYPE (Max.) TRIP POINT ADJUSTMENT STATUS OPEN LED STATUS CLOSED LED
H808 0.75 - 50A N.O. 1.0A@30VAC/DC H806* 0.75 - 50A N.C. 0.1A@30VDC H809** 0.75 - 50A N.O. 0.2A@120VAC/DC
*Hx06 Models requi re a constant source of 5-30VDC power to the status contacts. **CE not currently available o n this product
ACCESSORIES
DIN Rail Clip Set...See page 234
800.354.8556
503.598.4564
   
www.veris.com
©2006Veris Industries
800.354.8556
503.598.4564
www.veris.com
©2006Veris Industries
Motor
Fan or Pump
CONTROLLER
DI
CONTACTOR
ø 0.71" (18 mm)
ø 0.21" (.5 mm)
ø1.80"
(46 mm)
2.77"
(70 mm)
1.02"
(26 mm)
1.79"
(45 mm)
2.25"
(57 mm)
0.90"
(23 mm)
0.20" (.5 mm)
Removable/Adjustable Mounting Bracket
H808 SERIES
APPLICATIONS/WIRING EXAMPLE DIMENSIONAL DRAWINGS
CURRENT MONITORING
39
SPECIFICATIONS
Amperage Range 0.75 to 50A Sensor Power In duced Output Digital switch (see ordering table) Insulation Class 600VAC rms Frequenc y Range 50/60 Hz. Temperature Range 15° to 50°C Humidit y Range 0 - 95% non-condensing Hysteresis 10% (typical) Trip Setpoint Adjustable 0.75 to 50A Dimensions…(L x W x H) 2.77" (70mm) x 1.79" (45mm) x 1.02" (26mm) Sensor Ho le Size 0.71" (18mm) diameter Status Cont acts (Hx06 Models): Supply Voltage 5-30VDC, continuous supply Off -state Leakage (max.) 24µA@30VDC On-state Voltage Drop 1.7VDC (max.)@0.1A
Do not use the LED status indicators as evid ence of applied voltage.
800.354.8556
503.598.4564
www.veris.com
©2006Veris Industries
Loading...