Johnson Controls H608 Series Catalog Page

CURRENT MONITORING
Off
Loss of belt/coupling shear
Off
Electrical failure
Fan/pump On
Calibrated
Trip
Point
Now you can easily detect when drive belts slip, break, or pump couplings shear. In fact, a typical HVAC motor that loses its load has a reduction of current draw of up to 50%. That's why our sensors are the industry standard for status.
H608


Maximize Reliability
Minimize Installed Cost
30
H608
The Hawkeye 608 Series is a high per for mance miniature split-core current status switch. Its low minimum setpoint (1.25A) and small size make it ideal for monitoring status of small to medium motor loads. With an amperage range of
1.25 to 50 amps, the 608 series can accurately detect belt loss, coupling shear, or other mechanical failure on loads from 1/5 to 40HP.
APPLICATIONS
Detect belt loss, coupling shear and mechanical failure
Verify lighting circuit and other electrical service run times
Monitor status of industrial process equipment
Monitor status of critical motors (compressor, fuel, etc.)
608 Series
Mini Split-Core Adjustable Setpoint Dig i tal Output Current Switches
High performance miniature split-core
Low (1.25A) minimum setpoint...eliminates the need for multiple wraps
of the conductor through the sensor even on loads as small as 1/5HP
Small size fi ts easily inside small starter enclosures
Self-gripping iris eliminates the need for drill mounting...easy installation
Status LEDs for easy setup and local indication
1 Amp status output for increased application fl exibility
Monitor status of fans, pumps & elec trical loads
Detects belt loss and mechanical failure...ideal for fan/pump
status monitoring
Reliable cost-eff ective fan/pump status sensor...the 608 series replaces
pressure switches and other elec tro me chan i cal devices...no fi tting or tapping required
Adjustable set point (1.25-50A)
100% solid state...no moving parts to fail
Mounting bracket for installation fl exibility
5-year limited warranty
ORDERING INFORMATION
MODEL AMPERAGE RANGE OUTPUT TYPE (Max.) TRIP POINT ADJUSTMENT STATUS OPEN LED STATUS CLOSED LED
H608 1.25 - 50A N.O. 1.0A@30VAC/DC H606* 1.25 - 50A N.C. .1A@30VDC H609 ** 1.25 - 50A N.O. .2A@120VAC/DC
*Hx06 Models requi re a constant source of 5-30VDC power to the status contacts **CE not currently available o n this product
ACCESSORIES
DIN Rail Clip Set...See page 234
800.354.8556
503.598.4564
   
www.veris.com
©2006Veris Industries
800.354.8556
503.598.4564
www.veris.com
©2006Veris Industries
2.34"
(60 mm)
2.0"
(51 mm)
2.15"
(55 mm)
3.52"
(90 mm)
2.87"
(73 mm)
1.28"
(33 mm)
Removable Mounting Bracket
0.68"
(17 mm)
0.52"
(13 mm)
2.0"
(51 mm)
0.92"
(24 mm)
Motor
Fan or Pump
CONTROLLER
DI
S
t
a
t
u
s
O
p
e
n
CONTACTOR
H608 SERIES
CURRENT MONITORING
APPLICATIONS/WIRING EXAMPLE
DIMENSIONAL DRAWINGS
31
SPECIFICATIONS
Amperage Range 1.25 to 50A Sensor Power In duced Output Digital switch (see ordering table) Insulation Class 600VAC rms Frequenc y Range 50/60 Hz. Temperature Range -15° to 60°C
YES !NO !
The H608 Won’t Hang At the Bot tom of the Box.
The H608’s self gripping teeth free up the installer’s hands making it possible to per form a one hand cal i bra tion.
Humidit y Range 0 - 95% non-condensing Hysteresis 10% (typical) Trip Setpoint Adjustable 1.25 to 50A Dimensions…(L x W x H) 2.34" (60mm) x 2.15"(55mm) x .92"(24mm) Sensor Opening Size…(L x W) 0.52" (13mm) x 0.68" (17mm) Status Cont acts (Hx06 Models): Supply Voltage 5-30VDC, permanently connected Off -state Lea kage (max.) 24µA@30VDC On-state Voltage Drop 1.7VDC (max.)@0.1A
NO !
NO !
800.354.8556
YES !
YES !
The H608 Eliminates Extra Enclosures.
The H608’s small size (2.33" x 2.0") eliminates the need for extra electrical enclosures and saves you installation time.
The H608 Does Not Require Extra Wraps.
With a low 1.25 Amp turn-on, multiple wraps of wire through the sensor are eliminated even on loads as small as 1/5HP.
503.598.4564
Do not use the LED status indicators as evid ence of applied voltage.
www.veris.com
©2006Veris Industries
Loading...