Johnson Controls (H, Y, C)IDM048B21E, C)IDM036B21E, C)IDM030B21E Engineering Manual

ENGINEERING MANUAL
INVERTER-DRIVEN MULTI-SPLIT SYSTEM HEAT PUMP AIR CONDITIONERS
Engineering Manual
TC-16004
Technical Catalog for Outdoor Unit
 ●Ducted Medium Static (EconoFresh) Type (H,Y,C)IDM030B21E (H,Y,C)IDM036B21E (H,Y,C)IDM048B21E with EF-456NE
TC-16004-rev.2
i
IMPORTANT NOTICE AND SAFETY SUMMARY
1. Introduction
2. Important Safety Instructions
This manual should be considered as a permanent part of the air conditioning equipment and should remain with the air conditioning equipment.
(Transportation/Installation Work) > (Refrigerant Piping Work) > (Electrical Wiring Work) > (Ref. Charge Work) > (Test Run) > (User)
This Engineering Manual concentrates on heat pump air conditioning units. Read this manual carefully before performing installations or operations.
Signal Words
Indicates a hazardous situation that, if not avoided, could result in death or serious injury.
Indicates a hazardous situation that, if not avoided, could result in minor or moderate injury.
Indicates information considered important, but not hazard-related (for example, messages relating to property damage).
General Precautions
To reduce the risk of serious injury or death, read these instructions thoroughly and follow all warnings or cautions included in all manuals that accompanied the product and are attached to the unit. Refer back to these instructions as needed.
This system should be installed by personnel certied by Johnson Controls, Inc. Personnel must be
qualied according to local, state and national building and safety codes and regulations. Incorrect installation could cause leaks, electric shock, re or explosion. In areas where Seismic ‘’Performance requirements are specied, the appropriate measures should be taken during installation to guard
against possible damage or injury that might occur in an earthquake if the unit is not installed correctly, injuries may occur due to a falling unit.
Use appropriate Personal Protective Equipment (PPE), such as gloves and protective goggles and, where appropriate, have a gas mask nearby. Also use electrical protection equipment and tools
suited for electrical operation purposes. Keep a quenching cloth and a re extinguisher nearby during
brazing. Use care in handling, rigging, and setting of bulky equipment.
When transporting, be careful when picking up, moving and mounting these units. Although the unit may be packed using plastic straps, do not use them for transporting the unit from one location to another. Do not stand on or put any material on the unit. Get a partner to help, and bend with
your knees when lifting to reduce strain on your back. Sharp edges or thin aluminum ns on the air conditioner can cut ngers, so wear protective gloves.
Do not touch or adjust any safety devices inside the indoor or outdoor units. All safety features, disengagement, and interlocks must be in place and functioning correctly before the equipment is put into operation. If these devices are improperly adjusted or tampered with in any way, a serious accident can occur. Never bypass or jump-out any safety device or switch.
Johnson Controls will not assume any liability for injuries or damage caused by not following steps
outlined or described in this manual. Unauthorized modications to Johnson Controls products are
prohibited as they…
May create hazards which could result in death, serious injury or equipment damage. Will void product warranties. May invalidate product regulatory certications. May violate OSHA standards.
ii
TC-16004-rev.2
Take the following precautions to reduce the risk of property damage.
Be careful that moisture, dust, or variant refrigerant compounds not enter the refrigerant cycle during installation work. Foreign matter could damage internal components or cause blockages.
If air lters are required on this unit, do not operate the unit without the air lter set in place. If the air
lter is not installed, dust may accumulate and breakdown may result.
Do not install this unit in any place where silicon gases can coalesce. If the silicon gas molecules attach themselves to the surface of the heat exchanger, the nned surfaces will repel water. As a result, any amount of drainage moisture condensate can overow from the drain condensate pan and
could run inside of the electrical box, possibly causing electrical failures.
When installing the unit in a hospital or other facility where electromagnetic waves are generated from nearby medical and/or electronic devices, be prepared for noise and electronic interference Electromagnetic Interference (EMI). Do not install where the waves can directly radiate into the electrical box, controller cable, or controller. Inverters, appliances, high-frequency medical equipment, and radio communications equipment may cause the unit to malfunction. The operation of the unit may also adversely affect these same devices. Install the unit at least 10 ft. (approximately 3m) away from such devices.
When a wireless controller is used, locate at a distance of at least 3.3 ft. (approximately 1m) between
the indoor unit and electric lighting. If not, the receiver part of the unit may have difculty receiving
operation commands.
Do not install the unit in any location where animals and plants can come into direct contact with the outlet air stream. Exposure could adversely affect the animals and plants.
Do not install the unit with any downward slope to the side of the drain boss. If you do, you may have
drain water owing back which may cause leaks.
Be sure the drain hose discharges water properly. If connected incorrectly, it may cause leaks.
Do not install the unit in any place where oil can seep onto the units, such as table or seating areas in restaurants, and so forth. For these locations or social venues, use specialized units with oil-resistant features built into them. In addition, use a specialized ceiling fan designed for restaurant use. These specialized oil-resistant units can be ordered for such applications. However, in places where large quantities of oil can splash onto the unit, such as a factory, even the specialized units cannot be used. These products should not be installed in such locations.
If the wired controller is installed in a location where electromagnetic radiation is generated, make sure that the wired controller is shielded and cables are sleeved inside conduit tubing.
If there is a source of electrical interference near the power source, install noise suppression
equipment (lter).
During the test run, check the unit’s operation temperature. If the unit is used in an environment where the temperature exceeds the operation boundary, it may cause severe damage. Check the
operational temperature boundary in the manual. If there is no specied temperature, use the unit
within the operational temperature boundary of 35 to 104°F (0 to 40°C).
Read installation and appropriate user manuals for connection with PC or peripheral devices. If a warning window appears on the PC, the product stops, does not work properly or works intermittently, immediately stop using the equipment.
TC-16004-rev.2
iii
Installation Precautions
To reduce the risk of serious injury or death, the following installation precautions must be followed.
When installing the unit into…
A wall: Make sure the wall is strong enough to hold the unit’s weight. It may be necessary to
construct a strong wood or metal frame to provide added support.
A room: Properly insulate any refrigerant tubing run inside a room to prevent “sweating” that can
cause dripping and water damage to wall and oors.
Damp or uneven areas: Use a raised concrete pad or concrete blocks to provide a solid, level
foundation for the unit to prevent water damage and abnormal vibration.
An area with high winds: Securely anchor the outdoor unit down with bolts and a metal frame.
Provide a suitable air bafe.
A snowy area (only for Heat Pump Model): Install the outdoor unit on a raised platform that is
higher than drifting snow. Provide snow vents.
If the remote sensors are not used with this controller, then do not install this controller…
in a room where there is no thermostat. where the unit is exposed to direct sunshine or direct light. where the unit will be in close proximity to a heat source. where hot/cold air from the outdoors, or a draft from elsewhere (such as air vents, diffusers or
grilles) can affect air circulation.
in areas with poor air circulation and ventilation.
Do not install the unit in the following places. Doing so can result in an explosion, re, deformation, corrosion, or product failure.
Explosive or ammable atmosphere. Where re, oil, steam, or powder can directly enter the unit, such as in close proximity or directly
above a kitchen stove. Where oil (including machinery oil) may be present. Where corrosive gases such as chlorine, bromine, or sulde can accumulate, such as near a hot
tub or hot spring. Where dense, salt-laden airow is heavy, such as in coastal regions. Where the air quality is of high acidity. Where harmful gases can be generated from decomposition.
Do not position the drain pipe for the indoor unit near any sanitary sewers where corrosive gases may be present. If you do, toxic gases can seep into breathable air spaces and can cause respiratory
injuries. If the drainpipe is installed incorrectly, water leakage and damage to the ceiling, oor,
furniture, or other possessions may result. If condensate piping becomes clogged, moisture can back up and can drip from the indoor unit. Do not install the indoor unit where such dripping can cause moisture damage or uneven locations: Use a raised concrete pad or concrete blocks to provide a solid, level foundation for the unit to prevent water damage and abnormal vibration.
Before performing any brazing work, be sure that there are no ammable materials or open ames nearby.
Perform a test run to ensure normal operation. Safety guards, shields, barriers, covers, and protective
devices must be in place while the compressor/unit is operating. During the test run, keep ngers and
clothing away from any moving parts.
Clean up the site when nished, remembering to check that no metal scraps or bits of wiring have been left inside the unit being installed.
During transportation, do not allow the backrest of the forklift make contact with the unit, otherwise, it may cause damage to the heat exchanger and also may cause injury when stopped or started suddenly.
Remove gas inside the closing pipe when the brazing work is performed. If the brazing ller metal is melted with remaining gas inside, the pipes will be blown off and it may cause injury.
Be sure to use nitrogen gas for an airtight test. If other gases such as oxygen gas, acetylene gas or
uorocarbon gas are accidentally used, it may cause explosion or gas intoxication.
After installation work for the system has been completed, explain the “Safety Precautions,” the proper use and maintenance of the unit to the customer according to the information in all manuals that came with the system. All manuals and warranty information must be given to the user or left near the Indoor Unit.
iv
TC-16004-rev.2
Refrigerant Precautions
To reduce the risk of serious injury or death, the following refrigerant precautions must be followed.
As originally manufactured, this unit contains refrigerant installed by Johnson Controls. Johnson
Controls uses only refrigerants that have been approved for use in the unit’s intended home country or market. Johnson Controls distributors similarly are only authorized to provide refrigerants that
have been approved for use in the countries or markets they serve. The refrigerant used in this unit
is identied on the unit’s faceplate and/or in the associated manuals. Any additions of refrigerant into this unit must comply with the country’s requirements with regard to refrigerant use and should be obtained from Johnson Controls distributors. Use of any non-approved refrigerant substitutes will void
the warranty and will increase the potential risk of injury or death.
If installed in a small room, take measures to prevent the refrigerant from exceeding the maximum allowable concentration in the event that refrigerant gases should escape. Refrigerant gases can cause asphyxiation (0.026 lbs/ft
3
(0.42 kg/m3) based on ISO 5149 for R410A). Consult with your distributor for countermeasures (ventilation system and so on). If refrigerant gas has leaked during the installation work, ventilate the room immediately.
Check the design pressure for this product is 601 psi (4.15MPa). The pressure of the refrigerant R410A is 1.4 times higher than that of the refrigerant R22. Therefore, the refrigerant piping for
R410A shall be thicker than that for R22. Make sure to use the specied refrigerant piping. If not, the
refrigerant piping may rapture due to an excessive refrigerant pressure. Besides, pay attention to the piping thickness when using copper refrigerant piping. The thickness of copper refrigerant piping differs depending on its material.
The refrigerant R410A is adopted. The refrigerant oil tends to be affected by foreign matters such
as moisture, oxide lm, (or fat). Perform the installation work with care to prevent moisture, dust, or
different refrigerant from entering the refrigerant cycle. Foreign matter can be introduced into the cycle from such parts as expansion valve and the operation may be unavailable.
To avoid the possibility of different refrigerant or refrigerant oil being introduced into the cycle, the sizes of the charging connections have been changed from R407C type and R22 type. It is necessary to prepare the appropriate tools before performing installation work.
Use refrigerant pipes and joints which are approved for use with R410A.
A compressor/unit comprises a pressurized system. Never loosen threaded joints while the system is under pressure and never open pressurized system parts.
Before installation is complete, make sure that the refrigerant leak test has been performed. If
refrigerant gases escape into the air, turn OFF the main switch, extinguish any open ames and
contact your service contractor. Refrigerant (Fluorocarbon) for this unit is odorless. If the refrigerant
should leak and come into contact with open ames, toxic gas could be generated. Also, because the uorocarbons are heavier than air, they settle to the oor, which could cause asphyxiation.
When installing the unit, and connecting refrigerant piping, keep all piping runs as short as possible, and make sure to securely connect the refrigerant piping before the compressor starts operating. If the refrigerant piping is not connected and the compressor activates with the stop valve opened, the refrigerant cycle will become subjected to extremely high pressure, which can
cause an explosion or re.
Tighten the are nut with a torque wrench in the specied manner. Do not apply excessive force to the are nut when tightening. If you do, the are nut can crack and refrigerant leakage may occur.
When maintaining, relocating, and disposing of the unit, dismantle the refrigerant piping after the compressor stops.
When pipes are removed out from under the piping cover, after the insulation work is completed,
cover the gap between the piping cover and pipes by a packing (eld-supplied). If the gap is not
covered, the unit may be damaged if snow, rain water or small animals enter the unit.
Do not apply an excessive force to the spindle valve at the end of opening. Otherwise, the spindle
valve ies out due to refrigerant pressure. At the test run, fully open the gas and liquid valves,
otherwise, these devices will be damaged. (It is closed before shipment.)
If the arrangement for outdoor units is incorrect, it may cause owback of the refrigerant and result in failure of the outdoor unit.
The refrigerant system may be damaged if the slope of the piping connection kit exceeds +15
o
.
TC-16004-rev.2
v
Electrical Precautions
Take the following precautions to reduce the risk of electric shock, re or
explosion resulting in serious injury or death.
Highly dangerous electrical voltages are used in this system. Carefully refer to the wiring diagram and these instructions when wiring. Improper connections and inadequate grounding can cause serious injury or death.
Perform all electrical work in strict accordance with this installation and maintenance manual and all the relevant regulatory standards.
Before servicing, open and tag all disconnect switches. Never assume electrical power is disconnected. Check with meter and equipment.
Only use electrical protection equipment and tools suited for this installation.
Insulate a wired controller against moisture and temperature extremes.
Use specied cables between units.
The new air conditioner may not function normally in the following instances:
If electrical power for the new air conditioner is supplied from the same transformer as the device*
referred to below.
If the power source cables for this device* and the new air conditioner unit are located in close
proximity to each other.
Device*: (Example): A lift, container crane, rectier for electric railway, inverter power device,
arc furnace, electric furnace, large-sized induction motor and large-sized switch.
Regarding the cases mentioned above, surge voltage may be inducted into the power supply cables for the packaged air conditioner due to a rapid change in power consumption of the device and an activation of a switch.
Check eld regulations and standards before performing electrical work in order to protect the
power supply for the new air conditioner unit.
Communication cabling shall be a minimum of AWG18 (0.82mm
2
), 2-Conductor, Stranded Copper. Shielded cable must be considered for applications and routing in areas of high EMI and other sources of potentially excessive electrical noise to reduce the potential for communication errors. When shielded cabling is applied, proper bonding and termination of the cable shield is required
as per Johnson Controls guidelines. Plenum and riser ratings for communication cables must be
considered per application and local code requirements.
The polarity of the input terminals is important, so be sure to match the polarity when using contacts that have polarity.
Use an exclusive power supply for the air conditioner at the unit’s rated voltage.
Highly dangerous electrical voltages may be used in this system. Carefully refer to the wiring diagram and these instructions when wiring. Improper connections and inadequate grounding can cause serious injury or death.
Before installing the controller or remote devices, ensure that the indoor and outdoor unit operation
has been stopped. Further, be sure to wait at least ve minutes before turning off the main power
switch to the indoor or outdoor units. Otherwise, water leakage or electrical breakdown may result.
Do not open the service cover or access panel to the indoor or outdoor units without turning OFF the main power supply. Before connecting or servicing the controller or cables to indoor or outdoor units, open and tag all disconnect switches. Never assume electrical power is disconnected. Check with a meter and equipment.
This equipment can be installed with a Ground Fault Circuit Breaker (GFCI), which is a recognized measure for added protection to a properly grounded unit. Install appropriate sized breakers / fuses / overcurrent protection switches, and wiring in accordance with local, state and NEC codes and requirements. The equipment installer is responsible for understanding and abiding by applicable codes and requirements.
vi
TC-16004-rev.2
- CONTENTS -
1. General Information (Features) .................................................................................................................. 1-1
2. Ducted Medium Static (EconoFresh) Type ................................................................................................ 2-1
2.1 Unit Nomenclature ............................................................................................................................. 2-1
2.2 Line-up .............................................................................................................................................. 2-1
2.3 General Data ..................................................................................................................................... 2-2
2.4 Dimensional Data .............................................................................................................................. 2-3
2.5 Structure ............................................................................................................................................ 2-4
2.6 Component Data ............................................................................................................................... 2-5
2.7 Operation Space ............................................................................................................................... 2-6
2.8 Sensible Heat Factor (SHF) .............................................................................................................. 2-6
2.9 Combinations of Outdoor Units and Indoor Units .............................................................................. 2-7
2.10 Damper Minimum Setting (Optional Function d7) ............................................................................. 2-7
2.11 Working Range .................................................................................................................................. 2-8
2.12 Fan Performance ............................................................................................................................... 2-10
2.13 Electrical Data ................................................................................................................................... 2-11
2.14 Sound Data ....................................................................................................................................... 2-12
2.15 Control System .................................................................................................................................. 2-13
2.15.1 Refrigerant System .................................................................................................................. 2-13
2.15.2 Standard Operation Sequence ................................................................................................ 2-14
2.15.3 Safety and Control Device Setting ........................................................................................... 2-17
2.15.4 Wiring Diagram ........................................................................................................................ 2-18
IMPORTANT NOTICE AND SAFETY SUMMARY ......................................................................................... i
1. Introduction ................................................................................................................................................ i
2. Important Safety Instructions ..................................................................................................................... i
TC-16004-rev.2
vii
- CONTENTS -
3. Optional Parts ............................................................................................................................................ 3-1
3.1 Line Up .............................................................................................................................................. 3-1
3.2 Optional Air Filter: KW-PP456E ........................................................................................................ 3-2
3.2.1 Procedures .............................................................................................................................. 3-2
3.2.2 Service and Maintenance ........................................................................................................ 3-2
3.3 Infrared (IR) Receiver Kit: CWDIRK01 .............................................................................................. 3-3
3.3.1 Specications ........................................................................................................................... 3-3
3.3.2 Dimensions .............................................................................................................................. 3-3
3.3.3 Applicable Models .................................................................................................................... 3-3
3.3.4 Accessories / Options .............................................................................................................. 3-4
3.3.5 Installation ................................................................................................................................ 3-4
3.3.6 Electrical Wiring ....................................................................................................................... 3-7
3.3.7 Setting DIP Switches on Indoor Unit Side ............................................................................... 3-7
3.3.8 Setting DIP Switch on IR Receiver Kit Side ............................................................................. 3-8
3.3.9 Identifying Indoor Units Installed in a Side-by-Side Operation ................................................ 3-9
3.3.10 Simultaneous Operation .......................................................................................................... 3-10
3.3.11 Test Run by Wireless Controller (CIR01) ................................................................................. 3-12
3.3.12 Alarm Indication ....................................................................................................................... 3-12
3.4 3P Connector Cable: PCC-1A ........................................................................................................... 3-13
3.5 Remote Sensor: THM-R2A ................................................................................................................ 3-13
3.6 Relay and 3 Pin Connector Kit: PSC-5RA ......................................................................................... 3-14
4. Selection Data ............................................................................................................................................ 4-1
4.1 Selection Guide ................................................................................................................................. 4-1
4.2 Capacity Table ................................................................................................................................... 4-1
4.2.1 Cooling Capacity ...................................................................................................................... 4-1
4.2.2 Heating Capacity ..................................................................................................................... 4-2
FEATURES
TC-16004-rev.2
1-1
VRF Air Conditioners
Johnson Controls proudly introduces new Variable Refrigerant Flow (VRF) air conditioners, a highly-efcient
and reliable air-conditioning system. Recently, increased numbers of buildings are requiring "intelligent"
facilities that include communication networks, ofce automation, and a comfortable environment. In particular, a comfortable environment is becoming more of a year-around requirement in ofce buildings.
The VRF multi-split system air conditioner meets these requirements. The proven combination of the scroll
compressor and inverter provides the best air conditioning for small and medium ofce buildings.
■ VRF System
Johnson Controls has developed the VRF system with its customers in mind.
This system, which is unique in the world, allows the interconnection of indoor units for all our VRF air conditioners.
This system provides the consumer with greater exibility for installation, which means that the air­conditioning systems will integrate better within complex facility structures.
1. General Information (Features)
● Wide Range Line-up
Indoor Unit Type
Capacity (MBH)
6 8 12 15 18 24 30 36 48
Ducted Medium Static (EconoFresh) (H,Y,C)IDM_B21E
: Available
Table 1.1 Indoor Unit Type List
■ Ducted Medium Static (EconoFresh) Type Models (H,Y,C)IDM030B21E, (H,Y,C)IDM036B21E and (H,Y,C)IDM048B21E with EF-456NE
● Improvement of Energy-Saving
Air renewal has a downside of increased energy consumption. These models save energy while renewing
room air and reducing levels of CO
2
while also eliminating unpleasant smells, smoke and pollution.
(1) Supplies fresh new air into the room while keeping the correct indoor temperature, and also provides
natural cooling for increased energy saving (reducing energy consumption).
(2) Allows inow of fresh air into the room through the indoor unit, even when the thermostat is switched
off (Thermo-OFF*). Depending on the supply air and outlet air temperatures, this unit works like an
intelligent system, controlling the air ow by modifying the position of the damper.
NOTE:
Thermo-On: The outdoor unit and some indoor units are running. Thermo-OFF: The outdoor unit and some indoor units stay on, but don’t run.
(3) Effectively increases the installation performance when the outdoor temperature is lower than the
room temperature (in cooling mode), allowing the inlet of fresh air and cooling to the set temperature
without activating the outdoor unit. For example, it can supply up to 100% of fresh air and is able to
provide “natural cooling” through a damper when the outdoor temperature is lower than the set indoor
temperature (in cooling mode), leading to signicant energy savings particularly in spring and autumn.
(4) EconoFresh can operate with CO
2
or enthalpy sensors to control the air quality in the room.
NOTE:
The enthalpy sensor and CO
2
gas sensor cannot be installed together. The enthalpy sensor and CO2 gas sensor have no effect on the EconoFresh operation when the All Fresh process is activated.
FEATURES
1-2
TC-16004-rev.2
● Damper Control The EconoFresh kit is equipped with an outdoor air damper control mechanism, and the system provides
various operation modes, such as free cooling, all fresh, in cooling and heating mode. A micro-computer controls the angle of the damper according to air temperatures to adjust the fresh air
ow, thus keeping the room temperature constant with excellent comfort.
Selectable Minimum Damper Opening
The minimum opening for fresh outdoor air damper is selectable through the wired controller (d7 optional function setting). This allows establishing a minimum air volume renewal in the room.
Control Box
Suspension Bracket
Return Air Inlet
Damper
Outdoor Air Inlet
Supply Air Outlet
FEATURES
TC-16004-rev.2
1-3
● Standard and All Fresh Process Modes
Two different process modes are selectable:
(1) Standard Process
Standard Process in Cooling Mode In a situation where the outdoor ambient temperature is lower than 66
o
F (19oC), the compressor stops and
the indoor temperature is cooled down with an intake of outdoor fresh cold air controlled by the damper.
The minimum guaranteed fresh air intake can be set through the d7 setting (7% or more of the total outlet
air).
• Cooling Economizer
An energy saving control is adopted which uses fresh cold air from the outdoors for cooling the
intermediate seasons. The compressor is not used during this control, which results in outstanding energy saving.
• Three Different Economizer Cooling Controls
In order to optimize energy savings, EconoFresh can manage three types of control: normal cooling,
outdoor air cooling or fan cooling. Each type is managed according to the outdoor air temperature.
• Comfort Control
When Thermo OFF is requested, EconoFresh compares temperatures in order to offer a comfortable
environment in the room. EconoFresh control compares the set temperature (set in the wired controller) and the inlet air temperature in the Indoor Unit, and requests Thermo ON under certain conditions, in
order to achieve the requested room temperature as soon as possible.
Standard Process in Heating Mode
Depending on the temperature of indoor air return, the damper remains either opened for a minimum guaranteed intake of fresh air, or fully closed for 10 minutes. After this time, the damper is opened for a
minimum guaranteed intake of fresh air intake; this opening can be set through the d7 setting (7% or more
of the total outlet air).
23
(-5)39(4)
66
(19)
109 (43)
o
F
(
o
C)
100%
7%
Outdoor Temperature
Fresh Air
Working Area
14
(-10)
32 (0)
50
(10)
68
(20)
86
(30)
104 (40)
0
50
100
150
200
250
(h/year)
Outdoor Temperature
Time
Example of Temperature Distribution (8:00-21:00)
Compressor not used for Cooling
o
F
(
o
C)
FEATURES
1-4
TC-16004-rev.2
(2) All Fresh Process in Cooling and Heating Mode
This operation mode is very useful for buildings with many tenants, or for public buildings.
Basically, the damper is fully opened (100% fresh air) when activated through the wired controller (E1
optional function setting).
The following parameters are controlled by the All Fresh process in an independent fashion:
* Thermo ON/OFF status * Damper opening * Fan speed
Thermo ON/OFF Status
The general principle is that the compressor remains stopped when the outdoor ambient temperature is lower than 63
o
F (17oC) in cooling mode and higher than 75oF (24oC) in heating mode.
Damper Opening The damper is set to be either fully open or closed to the minimum opening to ensure an intake of fresh air
(7% or more of the total outlet air, by the d7 setting).
Additionally, the damper is closed to the minimum opening to ensure an intake of fresh air, under certain temperature combinations.
Fan Speed
The fan speed is adjusted one tap lower when the air outlet temperature...
* rises higher than 68oF (20oC) in cooling mode * drops lower than 86oF (30oC) in heating mode
In the above cases, the fan speed is changed from high to medium, or from medium to low.
The fan speed is adjusted back to fan setting tap when air outlet temperature returns to the following ranges:
* 59
o
F (15oC) or lower in cooling mode
* 95oF (35oC) or higher in heating mode
Draft Prevention Control Additionally, while the All Fresh process is activated, the EconoFresh control keeps monitoring and
comparing several temperature parameters. The damper may be closed to the minimum opening to ensure the intake of fresh air under certain circumstances, and in order to avoid discomfort and unwanted changes to room temperature due to inlet outdoor air conditions.
This function is active if the outdoor ambient temperature is
* 9
o
F (5oC) higher than the setting temperature in cooling thermo-OFF
* 9oF (5oC) lower than the setting temperature in heating thermo-OFF
100%
7%
39 (4)
o
F
(
o
C)
Outdoor Temperature
Fresh Ai
r
● Easy Installation Equipped with AC drain pump to force condensates up to 33-7/16 inch (850mm) in height in relation to the
unit. The pump is automatically enabled when the accumulated water level is too high.
< 33-7/16 inch (850mm)
TC-16004-rev.2
2-1
DUCTED MEDIUM STATIC (ECONOFRESH)
2. Ducted Medium Static (EconoFresh) Type
2.1 Unit Nomenclature
Model Descriptions
Example
H I DM 030 B 2 1 E
Nomenclature Description
H = Hitachi Brand Y = York Brand
C = Coleman Brand
H
Indoor Unit I Indoor Unit Type
DM = Medium Static
DM
Capacity (MBH) 030 Refrigerant Type
B = R410A
B
Voltage 2 = 208/230Volts - 1Phase - 60Hz
2
1 = 1st Generation 1
E = Economizer Type E
2.2 Line-up
Type
Capacity
Model
RT MBH
Indoor Unit
Ducted Medium Static (EconoFresh)
2.5 30 (H,Y,C)IDM030B21E
3.0 36 (H,Y,C)IDM036B21E
4.0 48 (H,Y,C)IDM048B21E
2-2
TC-16004-rev.2
DUCTED MEDIUM STATIC (ECONOFRESH)
2.3 General Data
NOTES: *1. Nominal capacity is based on combinations within the VRF system and the following conditions:
Cooling Operation Conditions Heating Operation Conditions
Indoor Air Inlet Temperature: 80°F DB (26.7°C DB) Indoor Air Inlet Temperature: 70°F DB (21.1°C DB) 67°F WB (19.4°C WB) Outdoor Air Inlet Temperature: 47°F DB (8.3°C DB)
Outdoor Air Inlet Temperature: 95°F DB (35.0°C DB) 43°F WB (6.1°C WB) Piping Length: 24 ft. 7-3/16 in. (7.5m) Piping Lift: 0 ft. (0m)
*2. The sound pressure level is based on the following conditions.
4.9 ft. (1.5m) beneath the unit, connection with the EconoFresh Kit, EconoFresh Pressure Mode Setting, damper opening
is OA 50% and RA 50%, at rated airow volume and lter is not used. The above data was measured in an anechoic chamber so that reected sound should be taken into consideration in the eld.
*3. The data for external pressure is based on a connection with the EconoFresh Kit (with a damper setting of maximum
pressure drop (damper opening at OA 100%)), EconoFresh Pressure Mode Setting and the lter is not used.
Indoor Unit Type Model (H,Y,C)IDM030B21E (H,Y,C)IDM036B21E (H,Y,C)IDM048B21E Indoor Unit Power Supply Nominal Cooling Capacity *1 Btu/h 48,000
(kW) (14.1)
Nominal Heating Capacity *1 Btu/h 54,000
(kW) (15.8)
dB
Outer Dimensions
Height in. (mm) 10-7/8 (275) 10-7/8 (275) 10-7/8 (275) Width in. (mm) 58-1/16 (1474) 58-1/16 (1474) 58-1/16 (1474)
Depth in. (mm) 23-5/8 (600) 23-5/8 (600) 23-5/8 (600) Net Weight lbs (kg) 106 (48) 106 (48) 106 (48) Refrigerant Indoor Fan
Air Flow Rate *3 cfm
(Hi-Me-Lo)
(m
3
/min)
External Pressure *3
in.W.G (Hi-Me-Lo) (Pa) Refrigerant Piping
Liquid Line in. (mm) 3/8 (9.52) 3/8 (9.52) 3/8 (9.52) Gas Line in. (mm) 5/8 (15.88) 5/8 (15.88) 5/8 (15.88)
Condensate Drain VP25
OD in. (mm) 1-1/4 (32) 1-1/4 (32) 1-1/4 (32) ID in. (mm) 1 (25) 1 (25) 1 (25)
Adaptable EconoFresh Kit Model Outer Dimensions
Height in. (mm) Width in. (mm) Depth in. (mm) Net Weight lbs. (kg)
(35-31-28)
40-36-33
1271-1130-1024
(36-32-29)
0.15-0.11-0.09 0.13-0.11-0.09 0.11-0.10-0.08
1059-953-847
R410A
(30-27-24)
Ducted Medium Static (EconoFresh)
Sound Pressure Level *2 (Overall A Scale)
30,000 36,000
(8.8) (10.5)
34,000 40,000
(10.0) (11.7)
AC 1 Phase, 208/230V, 60Hz
38-35-32 39-35-33
1236-1094-988
EF-456NE
VP25 VP25
(37-27-22) (32-28-22) (27-25-20)
(12.5)
10
55-1/2
12-3/16
28
(254) (1410) (270)
TC-16004-rev.2
2-3
DUCTED MEDIUM STATIC (ECONOFRESH)
2.4 Dimensional Data
Unit: inch (mm)
Models: (H,Y,C)IDM030B21E, (H,Y,C)IDM036B21E and (H,Y,C)IDM048B21E with EconoFresh Kit EF-456NE
NOTE: Connect the EconoFresh kit directly to the indoor unit.
2-4
TC-16004-rev.2
DUCTED MEDIUM STATIC (ECONOFRESH)
2.5 Structure
Models: (H,Y,C)IDM030B21E, (H,Y,C)IDM036B21E and (H,Y,C)IDM048B21E with EconoFresh Kit EF-456NE,C
Unit: inch (mm)
Condensate Pan
Electronic Expansion Valve
Condensate Pump
TC-16004-rev.2
2-5
DUCTED MEDIUM STATIC (ECONOFRESH)
2.6 Component Data
Indoor Heat Exchanger and Fan
TubMaterial
Outer Diameter φin. (mm) 1/4 (7.0) 1/4 (7.0) 1/4 (7.0) Rows Number of Tube/Coil
Fin Material
Pitch in. (mm) 0.071 (1.8) 0.071 (1.8) 0.063 (1.6)
psi (MPa) 601 (4.15) 601 (4.15) 601 (4.15)
ft
2
(
m
2
)
Number/Unit Outer Diameter φin.
(mm) Nominal Air Flow cfm (Hi-Me-Lo)
(
m3/min
)
Starting Method Nominal Output W Quantity Insulation Class
7-1/16
3.20
2
Copper Tube
Model (H,Y,C)IDM030B21E (H,Y,C)IDM036B21E (H,Y,C)IDM048B21E
Multi-Pass Cross Finned TubeHeat Exchanger Type
EEE
111
250 250 250
7-1/16
1059-953-847 1236-1094-988 1271-1130-1024
(180) (180)
(30-27-24) (35-31-28) (36-32-29)
Drip-Proof Type Enclosure
DC Motor
(180)
7-1/16
Aluminum
22
111
Multi-Blade Centrifugal Fan
3.20
Indoor Fan Motor
444
Indoor Fan
Number of Coil/Unit
Maximum Operating Pressure
Total Face Area 3.20
(0.30) (0.30) (0.30)
48 48 48
2-6
TC-16004-rev.2
DUCTED MEDIUM STATIC (ECONOFRESH)
2.7 Operation Space
2.8 Sensible Heat Factor (SHF)
Models: (H,Y,C)IDM030B21E, (H,Y,C)IDM036B21E and (H,Y,C)IDM048B21E with EconoFresh Kit EF-456NE
Model SHF*
(H,Y,C)IDM030B21E 0.83 (H,Y,C)IDM036B21E 0.85 (H,Y,C)IDM048B21E 0.85
NOTE: SHF is based on combinations within the VRF system and the following conditions:
Cooling Operation Conditions
Indoor Air Inlet Temperature: 80
o
F DB (26.7oC DB) 67oF WB (19.4oC WB) Outdoor Air Inlet Temperature: 95oF DB (35.0oC DB)
Piping Length: 24 ft. 7-3/16 in. (7.5m) Piping Lift: 0 ft. (0m)
Rear Side
≥ 15-3/4
(400)
≥ 39-3/8
(1000)
View from Top
Front Side
(5-1/8 (130))
≥ 23-5/8 (600)
≥ 23-5/8 (600)
Electrical Box
Unit: inch (mm)
Service Access Door (≥ □17-11/16 (450))
If the ceiling board cannot be found for servicing, prepare a service access door below the indoor unit for removing the indoor unit.
TC-16004-rev.2
2-7
DUCTED MEDIUM STATIC (ECONOFRESH)
NOTES:
● If the Damper Minimum Setting (optional function d7) of this indoor unit is set to a higher step, then this
will affect the air outlet temperature of other standard indoor units.
● Airow volume must be at the lower limit for All Fresh operation.
● Make sure to enable the EconoFresh Pressure Mode (optional function C5) on the wired controller
before operation. Otherwise, this unit will not operate effectively. EconoFresh Pressure Mode is “01”. (Optional function C5 on the wired controller is set to “00” by default)
2.9 Combinations of Outdoor Units and Indoor Units
Indoor units can be connected with the outdoor unit (VRF system).
2.10 Damper Minimum Setting (Optional Function d7)
Relationship between damper minimum opening (optional function d7) and OA airow volume ratio should
be referred to below table. However, OA airow volume ratio will change by duct installation. For example if the OA intake duct is long then the ratio becomes small.
In case precise OA airow volume ratio is required then nd out from outdoor air temperature, indoor
temperature and air outlet temperature during fan mode.
NOTE: When the opening is bigger, the outdoor air intake increases and this become additional load.
Outdoor Unit Type Combinations of Outdoor Units and Indoor Units
VRF Standard
VRF Less Module
Ducted (EconoFresh)
only
Total capacity of Ducted (EconoFresh) is
70%~100% of the outdoor unit capacity.
Ducted (EconoFresh)
+
Other Standard
Indoor Unit
Total capacity of Ducted (EconoFresh) is
30% or below the outdoor unit capacity.
AND
Total capacity of indoor unit (including Ducted (EconoFresh)) is
70%~100% of the outdoor unit capacity.
VRF Low Ambient
Ducted (EconoFresh)
only
Total capacity of Ducted (EconoFresh) is
55%~80% of the outdoor unit capacity.
Ducted (EconoFresh)
+
Other Standard
Indoor Unit
Total capacity of Ducted (EconoFresh) is
20% or below the outdoor unit capacity.
AND
Total capacity of indoor unit (including Ducted (EconoFresh)) is
55%~80% of the outdoor unit capacity.
Mini VRF
Ducted (EconoFresh)
only
Single Ducted (EconoFresh) only
AND Total capacity of Ducted (EconoFresh) is within 100% of the outdoor unit capacity.
Wired Controller Set Description
C5 01 EconoFresh Pressure Mode
C5 00 Not Available (Factory Setting)
C5 02 Not Available
Relationship between Optional Function d7 and OA Airow Volume Ratio
d7 Setting Conditions OA Airow Volume Ratio OA Damper Opening (Angle)
00 5%
01 9% 12°
02 13% 18°
03 17% 24°
04 21% 30°
05 25% 36°
06 29% 42°
07 34% 48°
2-8
TC-16004-rev.2
DUCTED MEDIUM STATIC (ECONOFRESH)
< Heating Mode Operation Range >
23
(-5)
32 (0)
50
(10)
(*1) (*2)68
(20)
86
(30)
104 (40)
109 (43)
92
(33.5)95(35)
89 (32)
Air Inlet Wet Bulb Temperature
(Outdoor Temperature) (
o
F (
o
C) WB)
Air Inlet Dry Bulb Temperature
(Outdoor Temperature) (
o
F (oC) DB)
75
(24)
41 (5)
Normal Heating
Outdoor Air
Heating
Relative Humidity : 30%RH
Relative Humidity : 90%RH
NOTES:
1. Make sure to apply extra insulation on the unit and duct to prevent condensation when the outdoor temperature is low.
2. Make sure the air inlet wet bulb temperature (outdoor temperature) is below 59
o
F WB (15oC WB).
3. Outdoor air damper of this unit may remain opened at “Damper Minimum Opening” setting (optional function d7) or prohibits OA intake for All Fresh mode below 41oF (5oC). (*1)
4. Unit may not operate when the outdoor temperature is high for All Fresh mode. (*2)
5. Compressor is stopped during outdoor air heating.
6. Air inlet dry bulb temperature (outdoor temperature) indicates the temperature detected by the unit's outdoor thermistor
.
2.11 Working Range
This heat pump air conditioner has been designed for the following temperatures. Operate the heat pump air conditioner within this range.
< Cooling Mode Operation Range >
23
(-5)
32 (0)
50
(10)
(*1) (*2)68
(20)
86
(30)
104 (40)
109 (43)
92
(33.5)95(35)
89 (32)
64
(18)
Air Inlet Wet Bulb Temperature
(Outdoor Temperature) (
o
F (
o
C) WB)
Air Inlet Dry Bulb Temperature
(Outdoor Temperature) (
o
F (oC) DB)
41 (5)
Relative Humidity : 90%RH
Relative Humidity : 30%RH
Normal Cooling
Outdoor Air
Cooling
Normal Cooling
NOTES:
1. Make sure to apply extra insulation on the unit and duct to prevent condensation when the outdoor temperature is low.
2. Outdoor air damper of this unit may remain opened at “Damper Minimum Opening” setting (optional function d7) or prohibits OA intake for All Fresh mode below 41
o
F (5oC). (*1)
3. Unit may not operate when the outdoor temperature is high for All Fresh mode. (*2)
4. Compressor is stopped during outdoor air cooling.
5. Air inlet dry bulb temperature (outdoor temperature) indicates the temperature detected by the unit's outdoor thermistor.
TC-16004-rev.2
2-9
DUCTED MEDIUM STATIC (ECONOFRESH)
< Operation Sequence >
14
(-10)
32 (0)
50
(10)
64
(18)
23
(-5)
41 (5)
75
(24)
109 (43)
86
(30)
104
(40)
68
(20)
step1 (*)
ON OFFON
step15 (**)
ON OFFON
step1step controlstep1
ON/OFF
ON OFF
step1step15
ON
step1
step15
step1
Backup Compressor
Cooling
Mode
Compressor
All-Fresh
Compressor
Damper
Heating
Mode
All-Fresh
All-Fresh
All-Fresh
Standard
Economizer
Standard
Economizer
Standard
Economizer
Damper
Fan
Mode
Dry
Mode
Damper
Damper
Compressor
Compressor
ON
step1
Standard
Economizer
Damper
Compressor
Outdoor Temperature
o
F (ºC)
(*) Damper Step 1: Fresh Outdoor Air Damper Minimum Opened
(**) Damper Step 15: Fresh Outdoor Air Damper Fully Opened
Compressor operation and the angle (step) of the damper are controlled according to both room air
temperature and outdoor temperature to adjust the fresh air ow, thus keeping the room temperature
constant.
2-10
TC-16004-rev.2
DUCTED MEDIUM STATIC (ECONOFRESH)
2.12 Fan Performance
NOTE:
Field-supplied duct should be installed so that it does not exceed the upper limit of airow volume. When the internal pressure drop of the duct is limited, the airow volume is higher.
This will cause abnormal stoppage, malfunction, and water splash. Therefore, ensure that the internal pressure drop of the duct is equal to external static pressure by adjusting the damper.
Above gure shows when the EconoFresh Pressure Mode is selected on the wired controller. It is recommended to use at lower limit of airow volume during the All Fresh mode.
(H,Y,C) IDM030B21E with EF-456NE
(H,Y,C) IDM036B21E with EF-456NE
(H,Y,C) IDM048B21E with EF-456NE
TC-16004-rev.2
2-11
DUCTED MEDIUM STATIC (ECONOFRESH)
2.13 Electrical Data
VOL: Rated Unit Power Supply Voltage (V) PH: Phase HZ: Frequency (Hz) MCA: Maximum Circuit Ampacity (A) MFA: Maximum Fuse Ampacity (A) OPT: Rated Motor Output (kW) FLA: Full Load Ampacity (A)
Model
Unit Main Power Applicable Voltage Power Supply
Indoor
Fan Motor
Unit
VOL PH HZ Maximum Minimum MCA MFA OPT FLA
(H,Y,C)IDM030B21E
208/230 1 60 253 188
1.7 15 0.25 1.3
(H,Y,C)IDM036B21E 2.2 15 0.25 1.7
(H,Y,C)IDM048B21E 2.3 15 0.25 1.8
NOTE:
Power supply voltage should be satised with the following.
Supply Voltage: Rated Voltage within ±10% Starting Voltage: Rated Voltage within -15% Operating Voltage: Rated Voltage within ±10%
2-12
TC-16004-rev.2
DUCTED MEDIUM STATIC (ECONOFRESH)
2.14 Sound Data
NOTES:
1. The sound pressure level is based on the following: Measurement Point: 4.9 ft. (1.5m) beneath the unit.
2. The above data was measured in an anechoic chamber so that reected sound should be taken into consideration in the eld.
3. Above gure shows when the EconoFresh Pressure Mode is selected on the wired controller, damper opening is OA 50% and RA 50% and at rated airow volume.
(H,Y,C)
(H,Y,C)
Model: (H,Y,C) IDM048B21E with EF-456NE
Model: (H,Y,C) IDM030B21E with EF-456NE
Model: (H,Y,C) IDM036B21E with EF-456NE
TC-16004-rev.2
2-13
DUCTED MEDIUM STATIC (ECONOFRESH)
2.15 Control System
2.15.1 Refrigerant System
Mark Part Name
1
Heat Exchanger
2
Distributor
3
Strainer
4
Electronic Expansion Valve
Models: (H,Y,C)IDM030B21E, (H,Y,C)IDM036B21E and (H,Y,C)IDM048B21E
Unit: inch (mm)
Model Distributor
(A) Gas Pipe
Connection
(B) Liquid Pipe
Connection
(C) (OD×T) (D) (OD×T)
(H,Y,C)IDM030B21E 10 Pass
f
5/8
(15.88)
f
3/8
(9.52)
f
3/4×t0.047
(19.05×1.2)
f
1/2×t0.031
(12.7×0.8)
(H,Y,C)IDM036B21E 10 Pass
f
5/8
(15.88)
f
3/8
(9.52)
f
3/4×t0.047
(19.05×1.2)
f
1/2×t0.031
(12.7×0.8)
(H,Y,C)IDM048B21E 10 Pass
f
5/8
(15.88)
f
3/8
(9.52)
f
3/4×t0.047
(19.05×1.2)
f
1/2×t0.031
(12.7×0.8)
Design Pressure
601 PSIG
(4.15 MPa)
2-14
TC-16004-rev.2
DUCTED MEDIUM STATIC (ECONOFRESH)
2.15.2 Standard Operation Sequence
I.U.: Indoor Unit
Auto Cooling/Heating
Operation
I.U. Air
Intake Temp.
I.U. Air
Intake Temp.
< Set Temp.
< Set Temp.
> Set
Temp.
> Set Temp.
> Set Temp.
> Set Temp. +1
o
F
(0.5oC)
> Set Temp. +3
o
F (2oC)< Set Temp. -3oF (2oC)
< Set Temp. -1oF (0.5oC)
Heating
Mode
Cooling
Mode
I.U. Air
Intake Temp.
Fan
Mode
Fan
Mode
I.U. Air
Intake Temp.
I.U. Air
Intake Temp.
< Set Temp.
NOTE: I.U fan operates continuously when in Cooling, Heating and Fan Mode.
■ Cooling Operation
The sequence may be different depending on the outdoor unit model to be connected. Refer to the “Outdoor Unit Engineering Manual” for details.
■ Dry Operation
The sequence may be different depending on the outdoor unit model to be connected. Refer to the “Outdoor Unit Engineering Manual” for details.
■ Heating Operation
The sequence may be different depending on the outdoor unit model to be connected. Refer to the “Outdoor Unit Engineering Manual” for details.
■ Automatic Cooling and Heating Operation
It is applicable only for the Heat Recovery System.
■ Defrosting Operation
The sequence may be different depending on the outdoor unit model to be connected. Refer to the “Outdoor Unit Engineering Manual” for details.
TC-16004-rev.2
2-15
DUCTED MEDIUM STATIC (ECONOFRESH)
Power Supply
No
Yes
No
No
Yes
Yes
Cooling Operation
Cooling Operation
> 32
o
F(0oC)
< 32oF(0oC)
> 58
o
F(14oC)
< 58oF(14oC)
Gas or Liquid Pipe
Surface Temp. of
Indoor Heat Exchanger
Is it continuous for more than 3 min.?
Is it continuous
for more than 3 min.?
(6 min. in case of
Dry Operation)
Is compressor
operated for more than
15 min.?
*
* The check interval differs depending on the conditions.
I.U. Electronic Expansion Valve: Completely Closed
No
No
Yes
MIF Operation at Set Fan Speed
(In case of Dry Operation,
MIF Operation: OFF for 6 min.)
Gas or Liquid Pipe
Surface Temp. of
Indoor Heat Exchanger
Yes
Elapsed Time:
15 min.
Either of Pipe Surface
Temp.
*2)
> 36oF(2oC)
I.U.: Indoor Unit
a
a
*2): Pipe Surface Temp. NOT adopted at .
MIF : Motor for Indoor Fan
■ Freeze Protection Control during Cooling or Dry Operation
2-16
TC-16004-rev.2
DUCTED MEDIUM STATIC (ECONOFRESH)
> 149oF(65oC)
< 149oF(65oC)
Thermo-ON/OFF Control for Indoor Unit
I.U.: Indoor Unit
Heating Operation
I.U. Air
Outlet
Temp.
Thermo-OFF
Yes
No
< 149
o
F(65oC)
> 149
o
F(65oC)
No
Yes
I.U. Air
Outlet
Temp.
Elapsed Time:
3 min.
Thermo-ON
Set Temp. is
lower than
Air Intake Temp.
■ Prevention Control for Excessively High Outlet Air Temperature (High Outlet Air Temperature Heat Lockout)
NOTE: Thermo-ON: The outdoor unit and some indoor units are running. Thermo-OFF: The outdoor unit and some indoor units stay on, but don't run.
TC-16004-rev.2
2-17
DUCTED MEDIUM STATIC (ECONOFRESH)
2.15.3 Safety and Control Device Setting
Model (H,Y,C)IDM030B21E, (H,Y,C)IDM036B21E, (H,Y,C)IDM048B21E
For Evaporator Fan Motor
Internal Thermostat Automatic Reset, Non-Adjustable
Cut-Out
o
F
(
o
C)
248+13
(120+7)
Cut-In
o
F
(
o
C)
230+13 (110+7)
For Control Circuit
Fuse Capacity A 5
2-18
TC-16004-rev.2
DUCTED MEDIUM STATIC (ECONOFRESH)
2.15.4 Wiring Diagram
Ground
DIP
DIP
DIP
DIP
DIP
DIP
Electronic Expansion Valve
TC-16004-rev.2
3-1
OPTIONAL PART
Item No. Optional Parts
Optional Parts
Model Name
3.2 Optional Air Filter KW-PP456E
3.3 Infrared (IR) Receiver Kit CWDIRK01
3.4 3P Connector Cable PCC-1A
3.5 Remote Sensor THM-R2A
3.6 Relay and 3 Pin Connector Kit PSC-5RA
3.7 Wired Controller CIW01
3.8 Simplied Wired Controller CIS01
3.9 Wireless Controller CIR01
3.10 Mini Central Controller CCM01
3.11 Large Central Controller CCL01
3.12 Computerized Central Controller Software / Adapter CCCS01 / CCCA01
Refer to the Engineering Manual of Control for details of item 3.7 to 3.12.
3. Optional Parts
3.1 Line Up
3-2
TC-16004-rev.2
OPTIONAL PART
3.2 Optional Air Filter: KW-PP456E
KW-PP456E is only available to be used in combination with the indoor unit ducted medium static (EconoFresh) type models.
3.2.1 Procedures
(1) Remove the support piece (three screws) from the indoor unit.
(2) Insert the Optional Air Filter and reattach the support piece.
NOTE:
1. During the installation or removal of the optional air lter if the insulation material attached on the cabinet is removed, then reapply and repair the insulation. Otherwise, condensation may occur when cold air enters.
2. It is recommended to follow below indications depending on the installation.
- Attach the Optional Air Filter in a situation where no Suction Duct has been applied. (Figure A)
- If applying a Suction Duct, it is recommended that the Air Filter is applied at the inlet point of the Suction Duct. (Figure B)
Optional Air Filter
EconoFresh Kit
Indoor Unit
Optional Air Filter Support
Optional Air Filter inserting direction
3.2.2 Service and Maintenance
Remove the Optional Air Filter from the ange. Vacuum dust. Use a cleaner or wash the air lter with water or neutral detergent to clean the air lter. Dry the air lter away from direct light.
Dimensions:
Unit: inch (mm)
Name Illustration
Optional Air Filter
50-11/16 (1288)
9-9/16
(243)
1/8 (3)
Optional Air Filter
(Field-Supplied)
Figure
A
Air Filter (Field-Supplied)
Figure
B
Suction Duct
A
A
TC-16004-rev.2
3-3
OPTIONAL PART
To Terminal Block (A, B) in Electrical Control Box of Indoor Unit
1-1/8 [28]
IR Receiver Part
4-3/4 [120]
3-9/16 [90]
Accessory Cable
(about 16.4ft [5m])
HEAT
COOL
TIMER
FILTER
DEF
RUN
EMERGENCY
3.3.2 Dimensions
3.3.3 Applicable Models
Model CWDIRK01
Applicable Indoor Unit Model
General-Purpose
(Ducted and Wall Mount Type)
Applicable Wireless Controller CIR01
3.3 Infrared (IR) Receiver Kit: CWDIRK01
This IR receiver kit is installed with the ducted and wall mount types to use with the wireless controller.
3.3.1 Specications
Model CWDIRK01
Outer Dimension
< W × H × D >
3-9/16 × 4-3/4 × 1-1/8 inch
(90 × 120 × 28 mm)
Unit: inch [mm]
3-4
TC-16004-rev.2
OPTIONAL PART
3.3.4 Accessories / Options
No. Accessory Qty Remarks
1
IR Receiver Kit CWDIRK01
1 With Connecting Cable
2
Cable Band 1 For Clamping Cable
3
Securing Screw 4 For Installing IR Receiver Kit
4
Securing Screw 2 For Fixing Cable Clamp
5
Cable Clamp 2 For Clamping Cable
3.3.5 Installation
● Turn OFF the power supply completely before setting the DIP switch, installation work, and electrical
wiring work for the IR receiver kit. If not, it may cause an electric shock.
● Perform securely the installation work referring to this manual. If the installation is not completed
correctly, the IR receiver kit may fall and cause injury.
● Do not install the IR receiver kit where ammable gases may generate or enter. It may cause heat generation or a re.
● Correctly perform the electrical wiring work. If electrical work is not completed correctly, heat generation at the connection, a re or an electric shock may occur.
● Make sure that the electrical wires are securely xed so that no external force affects the terminal connections of the wiring. Not doing so may cause heat generation or a re.
● When the IR receiver kit is installed near ambient lighting, it may not receive a signal from the wireless
controller. Therefore, pay particular attention to the installation position of the IR receiver kit.
● Do not run the connecting cable for the IR receiver kit and the power supply cable (208/230V) in
parallel. It may cause a malfunction of the IR receiver kit.
● To ensure correct performance, read this manual together with the “Installation and Maintenance
Manual” for the indoor unit and the wireless controller. Forward this information to the building owner and request that they maintain all the equipment manuals.
● CWDIRK01 is for a general-purpose IR receiver kit. It is applied for ducted, cassette, wall mount, ceiling-suspended, and oor type indoor units.
TC-16004-rev.2
3-5
OPTIONAL PART
3
Install the IR receiver kit using the length of
connecting cable (accessory). The cable length is approximately 17 ft. (5m).
4
Open the cover of the IR receiver kit.
Push the slotted screwdriver with a tip width of approximately 1/4 inch (6mm) into the slot of the IR receiver kit cover and rotate it to open the
cover as shown in the gure at the right.
1
Perform the installation work for the IR receiver kit while the indoor unit is being installed.
2
Turn OFF the power supply for the indoor unit if the IR receiver kit is attached after the indoor unit is
installed.
5
Mount the IR receiver kit onto the wall or the ceiling surface as shown below.
Situation A
(1) Secure the bracket.
Situation B
(1) Prepare the eld-supplied switch box (JIS
Box). (JIS C8340)
Slot
IR Receiver Ki
t
Mounting Bracket
Rotate
Push and rotate.
Slotted Screwdriver
(Tip Width: A
pprox. 1/4 inch (6mm))
Securing Screw (Accessory)
Secure the bracket with four accessory securing screws.
Any of the following Switch Boxes can be utilized.
1. Switch Box for One Switch (Without Cover)
2. Small Switch Box for One Switch (Without Cover)
3. Switch Box for One Switch (With Cover)
Metal Conduit (larger than I.D. φ13/16 inch (φ20mm)
Two Securing Screws (M4, Field-Supplied)
3-6
TC-16004-rev.2
OPTIONAL PART
(2) Run the connecting cable into the metal
conduit.
(3) Lead the connecting cable through the
knock-out hole.
(3) Secure the bracket.
(4) Attach the IR receiver kit.
Do not pinch the cable between the bracket and the IR receiver kit cover when attaching the IR receiver kit. Attach the IR receiver kit cover following these directions.
(2) Select the connecting cable outlet direction
and cut out one of the knock-out holes on the cover.
Cover
Connecting Cable
Mounting Bracket
Cover
Hook the left side of the cover to the mounting bracket. Push the right side of the cover onto the bracket.
Click sound is heard when the cover is completely hooked onto the bracket.
Connecting
Cable
The connecting cable should not be exposed. Lead it through the metal conduit in the wall.
Connecting Cable
Securing Screw
(M4, Field-Supplied)
Mounting Bracket
Click sound is heard when the cover is completely hooked onto the bracket.
Cover
Hook the left side of the cover to the mounting bracket. Push the right side of the cover onto the bracket.
Do not loosen the connecting cable for the IR receiver kit. Otherwise, it may become pinched between the two components causing a malfunction of the indoor unit.
Select the connecting cable outlet direction and cut out of the knock-out holes ( ).
Secure the tabs of the cover into the slots on the left side of the bracket.
Situation A Situation B
TC-16004-rev.2
3-7
OPTIONAL PART
The terminal block (TB2) for the controller cable is located as shown in the gure below. Connect the
connecting cable for the IR receiver kit to terminals A and B at TB2. (There is no polarity between terminals
A and B.) The details for wiring methods can be found in the “Installation and Maintenance Manual” for the
indoor unit. The following wiring method is an example for wall mount indoor units
NOTE: After running the connecting cable, clamp the extra length of the connecting cable using the accessory cable band and place it in the electrical box.
Instructions for setting DIP switches for other indoor units can be found in the Installation and Maintenance Manual for indoor units. The following DIP switch setting is an example for wall mount indoor units.
1
The factory setting of SW2 before shipment is “Wireless”. When using an IR receiver kit (CWDIRK01), set
the SW2 to “Wired”. If not doing so, the operation is not available.
2
Turn OFF the power supply of the indoor and outdoor units completely before setting the DIP switch.
If not turning off the power, the setting becomes invalid.
3
The positions of the DIP switches are shown below.
Open the switch cover. After the DIP switch is set, re-attach the switch cover. The details for setting DIP switches for an indoor unit can be found in the Installation and Maintenance Manual for indoor units.
TIWM006 - 012B21S TIWM015 - 030B21S
TIWM006 - 012B21S TIWM015 - 030B21S DIP Switch PCB (PCB2)
Insert the connecting
cable from the rear side of indoor unit.
Switch Cover
PCB
2
Switch Cover
PCB2
DSW5
RSW2
RSW1
DSW6
DSW9 DSW2
SW1
SW2
DSW3
3.3.6 Electrical Wiring
3.3.7 Setting DIP Switches on Indoor Unit Side
A 12
Electrical Box Cover
Terminal Block for Power Supply (TB1)
Screw for
Ground Wiring Connection
Connecting Cable
for IR Receiver Kit
Fix the wires with cable clamp.
Terminal Block for Controller Cable (TB2)
Terminal Block for Power Supply (TB1)
Screw for
Ground Wiring Connection
Connecting Cable
for IR Receiver Kit
Terminal Block for Controller Cable (TB2)
AB1
3-8
TC-16004-rev.2
OPTIONAL PART
Review the following optional function settings when a function for the IR receiver kit is selected from the wireless controller or the centralized controller.
● The optional functions “Cooling Lower Limit for Setting Temperature” and “Heating Upper Limit for Setting
Temperature” are not available with the wireless controller.
● The optional function setting “Fixing of Setting Temperature” is not available. When the operation mode is
changed from the wireless controller, the indicated temperature on the wireless controller becomes the set temperature of the wired controller.
3
The DIP switch (DSW1) is for the optional function selection. If the optional function selection is required,
set the DIP switch as follows.
1
The following switches are on the IR receiver kit.
NOTE:
When the case is closed, pay particular attention to the outlet position for connecting cable.
Turn OFF the power supply completely before setting the DIP switch for an IR receiver kit. Not doing so may cause an electric shock.
3.3.8 Setting DIP Switch on IR Receiver Kit Side
3412 56
ON
RUN
DEF
FILTER
TIMER
COOL
HEAT
EMERGENCY
“COOL” Button
“HEAT” Button
CoverPCB
Outlet for Connecting Cable
Case Mounting Bracket
DIP Switch (DSW1) (Factory Setting)
(1) Remove the mounting
bracket. (2) Remove two securing screws to open the case.
2
Emergency Operation Setting
“COOL” and “HEAT” switches are used for emergency operation when the batteries for the wireless
controller are low.
(1) Switch “COOL”: Press “COOL” so that the cooling operation is started.
Press “COOL” again so that the cooling operation is stopped.
(2) Switch “HEAT”: Press “HEAT” so that the heating operation is started.
Press “HEAT” again so that the heating operation is stopped.
NOTE:
During an emergency operation, a yellow light “
” ashes (0.5 second ON/0.5 second OFF).
The temperature setpoint and the fan speed for the cooling/heating operation are the same as before starting an emergency operation.
Optional Function
DIP Switch Setting (DSW1)
Details
1 2 3 4 5 6
Main/Sub Setting O X X X X X
Change main (OFF setting)/ sub (ON setting) wireless
controller for a two-wireless controller system. Identifying of Indoor Unit
X O X X X X
It functions as B Mode (identication of indoor unit) of
the wireless controller when it is “ON”.
Invalidity of Emergency Operation
X X X O X X The switches for emergency operation are invalid.
O: ON X: OFF
TC-16004-rev.2
3-9
OPTIONAL PART
Turn OFF the power supply completely before setting the DIP switch for the IR receiver kit. Not doing so can cause an electric shock.
When two indoor units are installed side by side, the commands from the wireless controller may be received by both indoor units. The function,
“Identifying of Indoor Units Installed Side by Side”
enables operation of the individual unit correctly without interfering with the other unit’s operation.
As shown in the gure at the right, the IR receiver
kit of A and B are set side by side. In this instance,
unit B is set as “Identifying Indoor Units Installed
Side by Side”.
Setting of Identifying of Indoor Units Installed Side by Side
1
IR Receiver Kit Setting
Set the Number 2 pin of the IR receiver kit DIP switch (DSW1) at the “Identied” Unit B “ON” side.
2
Wireless Controller
Set the wireless controller according to the Installation and Maintenance Manual for the Wireless Controller.
Cancellation of Identifying of Indoor Units Installed Side by Side
1
IR Receiver Kit Setting
Set the Number 2 pin of the IR receiver kit DIP switch (DSW1) “OFF” side for cancellation.
2
Wireless Controller
Cancel the wireless controller setting according to the Installation and Maintenance Manual for the Wireless Controller.
NOTE: This function setting is required at the receiver side. It should be set according to the Installation Manual for indoor units. Contact your distributor for details.
Indoor Unit
A
Indoor Unit
B
"Identified" IR Receiver Ki
t
"Identified"
Wireless Controller
IR Receiver
Kit A
IR Receiver
Kit B
3.3.9 Identifying Indoor Units Installed in a Side-by-Side Operation
3-10
TC-16004-rev.2
OPTIONAL PART
3.3.10 Simultaneous Operation
● Turn OFF the power supply completely before setting the DIP switch and electrical wiring work for the
IR receiver kit. Not doing so can cause an electric shock.
● Accurately perform the electrical wiring work. If the electrical work is not completed correctly, heat generation at the connection, a re, or an electric shock may occur.
● Make sure that the electrical wires are adequately clamped with a cable clamp and not in a manner that
applies too much external force to the terminal connections of the wirings. If done correctly, the result
could cause heat generation or a re.
● Do not run the connecting cable for IR receiver kit and the power supply cable (208/230V) in parallel.
It may cause a malfunction of the IR receiver kit.
(Example of 4-way cassette type indoor units.)
Up to 16 indoor units can be simultaneously controlled using one wireless controller. When multiple indoor units are installed in a large room, all the indoor units can be controlled to start/ stop with only one wireless controller.
NOTE: Do not apply a simultaneous operation for the indoor units installed separately in different rooms. Some units may be left without turning OFF the power supply.
Installation of IR Receiver Kit
In an instance of simultaneous operation of multiple (up to 16 ) indoor units by the wireless controller, install the IR receiver kit only to the unit to be operated. Other units should be the standard units without the IR receiver kit. If multiple IR receiver kits are required to be installed, two IR receiver kits are the maximum.
Wireless Controller
Indoor Unit
with IR Receiver Kit
Standard
Indoor Unit
Standard Indoor Unit or
Indoor Unit with IR Receiver Kit
Standard
Indoor Unit
Should be Standard Indoor Units
Available to Install IR Receiver Ki
t
Indoor Unit (Address setting is required.)
Wireless Controller
Control Cable between Indoor Units
Control Example of Simultaneous
Operation of Multiple Units
TC-16004-rev.2
3-11
OPTIONAL PART
3
Unit Number Setting
The indoor unit numbers are set by the auto-address function. Therefore, an indoor unit number setting
is not required. If the indoor unit number is xed, set the unit number of all indoor units respectively and serially. It is recommended that the unit number settings begin with “1”. The setting is set not to overlap
the unit number.
Electrical Wiring Connecting and Setting
1
Connection between Indoor Units
Perform the connection work as shown below.
2
Do not run the connected wireless controller cable and the power supply cable (208/230V) in parallel in
the indoor units. Stabilize the cable with cable bands. Along with the wiring outside the indoor units, the control cables
should not run with the power supply cable (208/230V). Keep a separation of more than 12 inches (30cm)
or run the cable through a grounded metal conduit.
OFF
ON
Unit Number Setting
DSW6 (Tens Digit) RSW1 (Units Digit)
1 2 3 4 5 6
Set No.1 pin ON.
OFF
ON
1 2 3 4 5 6
DSW6 RSW1
Ex.: Set for No. 16 Unit
Setting Position
Set by inserting slotted screwdriver into the groove.
Set at "6".
Factory setting for DSW6 and RSW1 were set to "0".
Max. 63 units are available for setting.
Indoor Unit No.1 Indoor Unit No.2 Indoor Unit No.3
Connecting Cable (Accessory)
Wired Controller Cable
Control Cable
(No Polarity)
Power
Supply
Cable
(208/230V)
IR Receiver Kit
For twin, triple or quad combinations, a communication cable for the wireless controller is not required.
Use the field-supplied communication cable (AWG18) for the wired controller cable. The total length should be within 1640ft (500m). If the total length is less than 98ft (30m), AWG22 cables can be used.
Power Supply Cable 208/230V
TB
1
TB
2
AB12
L
1
TB
1
L2N
TB
2
AB12
TB
2
AB12
TB
1
L1L2NL
1L2
N
3-12
TC-16004-rev.2
OPTIONAL PART
3.3.11 Test Run by Wireless Controller (CIR01)
After all installations are completed, a test run should be performed.
(1) Perform the test run according to the Installation Manual of the wireless controller.
(2) The test run from the wireless controller switch takes two hours to complete.
NOTE:
For the wall mount indoor units, if the TIMER indicator (green) is ashing (0.5 second ON/0.5 second
OFF) after two hours, an alarm may occur. Operate the indoor unit ,and check for abnormality.
3.3.12 Alarm Indication
● If a malfunction occurs, such as safety device actuation, during the test run or the normal operation, “RUN” (red light) ashes (0.5 second ON / 0.5 second OFF).
● The alarm codes are indicated by the number of LED ashes of “DEF” (green light) and “FILTER” (yellow
light).
The rst LED light is green. The number of times this LED ashes (0.5 second ON and
OFF) will tell you the “DEF” Alarm Code.
The second LED light is yellow. The number of times this LED ashes (0.5 second ON and
OFF) will tell you the “FILTER” Alarm Code.
Example
● ”RUN” (red light) ashing (1 second ON/1 second OFF) indicates an abnormal transmission (connector
loose, connector disconnection, broken wire, or incorrect wiring, or something similar) between the indoor unit and the IR receiver kit.
● When the IR receiver kit is connected to multiple indoor units, the alarm code is indicated for each
indoor unit in order.
Alarm Code Table
Further details for alarm codes can be found in the “Installation and Maintenance Manual” for the indoor unit.
"FILTER" (yellow light)
Alarm
3 5
"DEF" (green light)
"DEF" flashes three times (0.5 second ON/ 0.5 second OFF)
"FILTER" flashes five times (0.5 second ON/ 0.5 second OFF
)
These signals are repeated until the alarm is reset.
TC-16004-rev.2
3-13
OPTIONAL PART
3.4 3P Connector Cable: PCC-1A
This accessory connector is utilized to provide remote start/stop capability (binary input) to an indoor unit and
provide operating status (binary output) of an indoor unit's functions. (System Parts: One set contains ve
3P cords.)
3P Connector Cable
Cord
Sensor
2-φ4.5
1-15/16 (50)
1-1/4 (32)3/8 (9)
1-15/16 (50)
1-1/4 (32)3/8 (9)
9/16 (15)
Case
Base
Lead Wire AWG22 (0.3mm2)
Approximately
11-13/16inch (300mm)
Connector (“XARP-03V” of NIPPON A
CCHAKU TANSHI = JST)
If long cord is needed, connect field supplied wires [AWG22 (0.3 to 0.5mm
2
)]
with soldering.
Name 3P Connector Cable
Model PCC-1A
Remarks
One set contains ve 3P connector
cables.
Specications
Item Specication
Model THM-R2A
Case
Material ABS Resin
Color Silky White
Base
Material ABS Resin
Color Silky White
Sensor
Part Name Thermistor
Cord Length approx. 26 ft (8m)
3.5 Remote Sensor: THM-R2A
When a remote temperature sensor is installed with an indoor unit, the indoor unit is congurable to use the
temperature at the location of the remote sensor OR the average of the unit's return air temperature and
the temperature at the location of the remote sensor to control that unit. (reference the specic controller Installation Manual for function conguration details)
Unit: inch (mm)
3-14
TC-16004-rev.2
OPTIONAL PART
3.6 Relay and 3 Pin Connector Kit: PSC-5RA
This relay kit provides for basic input/output integration functionality (indoor unit ON/OFF, operating mode, alarm status) to third party controllers and Building Management Systems (BMS).
(PSC-5RA)
TB1
TB2
0.3mm2 (AWG22)
- 6 conductors
6.6ft (2m)
(Accessory)
Third Party Controller or BMS
PCB
Indoor
Unit
Wired Controlle
r
Connection Cable
(6 conductors)
Max. 229.7ft (70m)
(field-supplied)
Adapter
CN7
CN3*
Item Signal Description Specications
Third Party
Controller
or BMS
Input 1
Input level signal or pulse signal for voltage from the third party controller or BMS
Voltage: 12VDC, 10mA Voltage: 24VDC, 10mA
Pulse Range: 500ms or more
Input 2
Third Party
Controller
or BMS
Output 1
Output signal from the wired controller
24VDC
From 10mA to 1A
Output 2
Refer to the Indoor Unit Manual for Input/Output mode setting by the wired controller.
*: Refer to Service Manual for connector numbers.
Max. 4-1/2 (115)
4 (101)
3-3/8 (86)
1-1/4 (31.5)
1-1/2 (38)
5/16 (7.5)
4-15/16 (125)
4-5/16 (110)
9/16
(15)
3-3/4 (95)
1-9/16 (40)
72-13/16 (1850)
5/16
(7.5)
Connecting Cable for Indoor Unit
Opening for Controller or BMS (3rd Party) Cable
Fixing Hole: ɸ1/4 (6)
PCB
5-7/8 (150)
9/16
(15)
5/16
(7.5)
5/16 (7.5)
Name Relay and 3 Pin Connector Kit
Model PSC-5RA
Unit: inch (mm)
SELECTION DATA
TC-16004-rev.2
4-1
4. Selection Data
4.1 Selection Guide
Refer to Engineering Manual for the Outdoor Unit.
4.2 Capacity Table
4.2.1 Cooling Capacity
■ Ducted Medium Static (EconoFresh): (H,Y,C)IDM030B21E, (H,Y,C)IDM036B21E
and (H,Y,C)IDM048B21E
TC: Total Capacity SHC: Sensible Heat Capacity
NOTE: Above values for (H,Y,C)IDM-B21E series indicates when unit’s air inlet is indoor air only.
Refer to Outdoor Unit Capacity Tables as actual performance data affected by indoor and outdoor unit combination.
Indoor Air Temp
(
o
F WB)
Outdoor Air
Temp (
o
F DB)
TC
(MBH)
SHC
(MBH)TC(MBH)
SHC
(MBH)TC(MBH)
SHC
(MBH)TC(MBH)
SHC
(MBH)TC(MBH)
SHC
(MBH)TC(MBH)
SHC
(MBH)TC(MBH)
SHC
(MBH)
70
31.0 25.6 31.7 25.9 32.3 26.0 32.6 26.0 33.7 26.4 34.6 26.7 35.4 26.9
80
30.2 25.2 30.7 25.4 31.2 25.5 31.6 25.6 32.6 25.9 33.5 26.2 34.3 26.5
95
28.2 24.2 28.8 24.5 29.4 24.7 30.0 24.9 31.0 25.3 32.0 25.6 32.7 25.8
110
20.2 19.8 19.8 19.5 19.4 19.2 19.0 19.0 19.2 19.2 19.3 19.3 19.4 19.4
114
17.0 17.0 16.8 16.8 16.7 16.7 16.5 16.5 16.6 16.6 16.7 16.7 16.8 16.8
118
13.8 13.8 13.9 13.9 13.9 13.9 13.9 13.9 14.0 14.0 14.0 14.0 14.0 14.0
70
37.2 31.2 38.0 31.6 38.8 31.7 39.1 31.7 40.4 32.3 41.5 32.6 42.5 32.8
80
36.2 30.6 36.8 31.0 37.4 31.1 37.9 31.3 39.1 31.6 40.2 32.0 41.2 32.4
95
33.8 29.6 34.6 29.9 35.3 30.2 36.0 30.5 37.2 30.9 38.4 31.3 39.2 31.5
110
24.2 24.0 23.8 23.7 23.3 23.3 22.8 22.8 23.0 23.0 23.2 23.2 23.3 23.3
114
20.4 20.4 20.2 20.2 20.0 20.0 19.7 19.7 19.9 19.9 20.0 20.0 20.1 20.1
118
16.6 16.6 16.6 16.6 16.7 16.7 16.7 16.7 16.7 16.7 16.8 16.8 16.8 16.8
70
49.6 41.8 50.6 42.2 51.7 42.4 52.1 42.4 53.9 43.1 55.3 43.6 56.6 44.0
80
48.3 41.0 49.0 41.3 49.8 41.5 50.5 41.8 52.2 42.2 53.6 42.8 54.9 43.3
95
45.1 39.5 46.1 39.9 47.0 40.3 48.0 40.7 49.6 41.4 51.2 41.8 52.2 42.1
110
32.3 32.1 31.7 31.7 31.0 31.0 30.4 30.4 30.6 30.6 30.9 30.9 31.1 31.1
114
27.2 27.2 26.9 26.9 26.6 26.6 26.3 26.3 26.5 26.5 26.6 26.6 26.8 26.8
118
22.1 22.1 22.2 22.2 22.2 22.2 22.2 22.2 22.3 22.3 22.4 22.4 22.4 22.4
048
71 73
030
036
Indoor
Unit
Model
61 63 65 67 69
SELECTION DATA
4-2
TC-16004-rev.2
4.2.2 Heating Capacity
■ Ducted Medium Static (EconoFresh): (H,Y,C)IDM030B21E, (H,Y,C)IDM036B21E
and (H,Y,C)IDM048B21E
Indoor Air Temp
(
o
F DB)
63 66 68 70 74 77
Outdoor Air
Temp (
o
F WB)
TC
(MBH)
TC
(MBH)
TC
(MBH)
TC
(MBH)
TC
(MBH)
TC
(MBH)
21 26.7 26.7 26.8 26.8 26.5 26.3
25 28.1 28.1 28.1 28.1 27.7 27.4
29 29.4 29.4 29.4 29.4 28.9 28.5
33 30.7 30.7 30.7 30.7 30.1 29.5
37 32.1 32.1 32.0 32.0 31.2 30.6
41 33.4 33.4 33.4 33.3 32.4 31.7
43 34.1 34.0 34.0 34.0 33.0 32.3
47 35.4 35.4 35.3 35.3 34.0 32.3
51 36.8 36.7 36.7 36.3 34.0 32.3
55 38.6 38.1 37.2 36.3 34.0 32.3
59 38.6 38.1 37.2 36.3 34.0 32.3
21 31.4 31.4 31.5 31.5 31.2 30.9
25 33.0 33.0 33.0 33.1 32.6 32.2
29 34.6 34.6 34.6 34.6 34.0 33.5
33 36.2 36.1 36.1 36.1 35.4 34.7
37 37.8 37.7 37.7 37.7 36.7 36.0
41 39.3 39.3 39.2 39.2 38.1 37.3
43 40.1 40.1 40.0 40.0 38.8 38.0
47 41.7 41.6 41.6 41.5 40.0 38.0
51 43.3 43.2 43.1 42.7 40.0 38.0
55 45.4 44.8 43.8 42.7 40.0 38.0
59 45.4 44.8 43.8 42.7 40.0 38.0
21 42.4 42.4 42.5 42.6 42.1 41.7
25 44.6 44.6 44.6 44.6 44.0 43.5
29 46.7 46.7 46.7 46.7 45.8 45.2
33 48.8 48.8 48.8 48.8 47.7 46.9
37 51.0 50.9 50.9 50.9 49.6 48.6
41 53.1 53.0 53.0 53.0 51.5 50.4
43 54.2 54.1 54.0 54.0 52.4 51.2
47 56.3 56.2 56.1 56.1 54.0 51.2
51 58.4 58.3 58.2 57.7 54.0 51.2
55 61.2 60.5 59.1 57.7 54.0 51.2
59 61.2 60.5 59.1 57.7 54.0 51.2
Indoor
Unit
Model
030
036
048
TC: Total Capacity
NOTE: Above values for (H,Y,C)IDM-B21E series indicates when unit’s air inlet is indoor air only.
Refer to Outdoor Unit Capacity Tables as actual performance data affected by indoor and outdoor unit combination.
© 2016 Johnson Controls, Inc.
TC-16004-rev.2
Code No. LIT-12012293 Revised February 2018
Loading...