Johnson Controls CD-Pxx-00-0 Series Catalog Page

Duct Mount Transmitter with Conduit
Adaptor and Mounting Flange
CD-Pxx-00-0 Series Duct Mount CO2 Transmitter
Description
Johnson Controls offers a complete line of carbon dioxide (CO measuring and transmitting CO ranging from 0 to 2,000 parts per million (ppm), within HVAC applications. These compact, duct mounted devices offer a choice of 0 to 10 V or 0 to 20 mA output signals and feature an optional relay output with or without a digital display. Johnson Controls® CO transmitters are easy to install and to operate.
The silicon-based CARBOCAP® sensor delivers high accuracy and long-term measurement stability (±100 ppm) over a 5-year period without calibration. The diffusion-aspirated, single-beam, dual-wavelength sensor structure is remarkably simple. It consists of an infrared (IR) source, a sample cell, an IR detector, and a tunable interference filter that enables measurements at two wavelengths. Reference measurements made using a tunable interference filter eliminate the typical weakness of dual-beam sensors and permit shifting the optical pass band electronically. This innovative design provides precise reference readings that eliminate the typically broad deviation expected from a traditional
sensor.
CO
2
Refer to the CD-Pxx-00-1 Series Duct Mount
Transmitter Product Bulletin (LIT-
CO
2
216525) for important product application
information.
) transmitters for
2
levels,
2
2
Features
• DCV strategies offer a potential for 10 to 70% energy savings
• CARBOCAP single-beam, dual-wavelength design provides superior performance compared to other technologies
• CARBOCAP silicon, micro-machined construction provides reliable CO measurement in duct environments
2
• calibration reliability offers 5 years of reliable calibration
• adjustable duct probe depth permits optimal placement of sensing tip in a duct
• optional features offer relay output for fan control
Applications
The new CO2 transmitters are easy to install, offer a full 3-year warranty, and require no maintenance or field calibration. They are designed to work:
• in stand-alone mode
• in support of demand control ventilation (DCV)
• with fresh air and indoor air quality (IAQ) systems
• as part of any integrated Building Automation System (BAS)
• with rooftop air handling Economizer controls systems
• connected to Metasys® system or the AD-DME Series
Repair Information
If the CD-Pxx-00-0 Series Transmitter fails to operate within its specifications, replace the unit. For a replacement CO contact the nearest Johnson Controls® representative.
transmitter,
2
Selection Charts
CD-Pxx-00-0 Series Duct Mount CO2 Transmitter
Code Number Description
CD-P00-00-0 Duct Mount CO2 Transmitter CD-PR0-00-0 Duct Mount CO
Accessories
Code Number Description
ACC-CD-S Relay Setpoint Software Kit; inludes software and interface cable to reset the On and Off relay setpoints for CD-PR0-00-0 Y65T31-0 Multiple Primary Transformer, 40 VA,
Maintenance Parts
Code Number Description
ACC-CD-R Relay Output Module for use in CD-PR0-00-0 ACC-CD-CFK1 Conduit Adaptor Kit
The performance specifications are nomina l and conf orm to accep table industr y standar ds. For ap plications a t condition s beyond th ese specification s, consult the local Johnson Controls o ffice. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2016 Johnson Controls, Inc.
Transmitter with Relay
2
120/208/230 V Primary, 24 V Class 2 Secondary with Screw Terminals: Foot Mounting or 4 x 4 in. (101.6 x 101.6 mm) Plate
www.johnsoncontrols.com
1
Mounting Flange Dimensions, in. (mm)
Center
Hole
FIG:dim
Transmitter Dimensions, in. (mm)
0.59
1.50
(38.10)
3.13
(79.38)
FIG:trn_dim
CD-Pxx-00-0 Series Duct Mount CO2 Transmitter (Continued)
1.54 (42)
2.52 (64.00)
3.14 to 5. 51 (80.00 to 140.00)
0.87 (22)
1.65 (42)
Technical Specifications
CD-Pxx-00-0 Series Duct Mount CO2 Transmitter
Measuring Range 0 to 2,000 ppm CO Accuracy at 77°F (25°C) < ±[30 ppm CO2 + 2.0% of reading] (includes manufacturing deviation and drift). All accuracy
Non-Linearity < 0.5% of Full Scale Temperature of Dependence of Output < 0.56% of Full Scale/F ° (< 0 .1% of Full Scale/C°) Long-Term Stability < ±5.0% of Full Scale/5 Years Response Time (0 to 63%) 1 Minute Operating Temperature Range 23 to 113°F (-5 to 45°C) Storage Temperature Range -4 to 158°F (-20 to 70°C) Humidity Range 0 to 85% noncondensing Transmitter Output Signal CO
Recommended External Load Current Output: Maximum 500 ohms Load Resistance
Power Supply Range 20 to 30 VAC (18 to 30 VDC), Class 2 Power Consumption < 2.5 W Average, 4.1 VA Warm-up Time < 5 minutes Air Flow Range 0 to 7,500 ft/Minute (o to 2,286 m/Minute) Duct Probe Material Duct Probe Meets Plenum Rating Requirements of UL 1995, Heating and Cooling Equipment Housing Material ABS Plastic Dimensions (H x W x D) 3-5/32 x 3-3/16 x 8 in. (80 x 81 x 204 mm) Shipping Weight 0.3 lb (140g) Compliance United States UL Listed, CCN XAPX
2
Canada UL, LIsted XAPX7 Europe CE Mark – Johnson Controls, Inc., declares that the CD-Pxx-00-0 Duct Mount CO
specifications reflect testing the transmitters using high-grade, certified gases. Transmitters are intended for an altitude range of 0 to 1,969 ft (0 to 600 m) above sea level without compensation.
Jumper Selectable: 0 to 20 mA or 4 to 20 mA or 0 to 10 VDC (Default) Maximum Output Current: 25 mA; Maximum Output V oltage: 12.5 V Maximum 30 V, 0.5A, Class 2
Voltage Output: Minimum 1,000 ohms Load Resistance
compliance with the essential requirements and other relevant provisions of the EMC Directive .
2
Transmitters are in
2
(15.00)
The performance specifications are no minal and co nform t o acceptab le ind ustry standar ds. For appl ications at condition s beyond these specifica tions, consult the local Johnson Co ntrols office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2016 Johnson Controls, Inc.