Johnson Controls CBL-22/3-NS-PVC Data Sheet

GENERAL PURPOSE 22-3C NONSHIELDED NONPLENUM
PART NO.
Description
Construction
Approvals
CONSTRUCTION PARAMETERS
Conductor and Stranding
Insulation Material and Thickness
Number of Conductors
Jacket Material and Thickness
Overall Cable Diameter
Approximate Cable Weight
Flame Rating
CBL-22/3-NS-PVC
22/3 stranded nonshielded PVC communications cable
This cable consists of a) three bare copper-insulated conductors and b) an overall jacket. The cable has a rip cord for easy jacket removal.
UL Standard 444, NEC Article 800 – CMR, CE, RoHS
22 AWG bare copper 7x30
PVC, 0.010"
3
None
PVC, 0.015"
0.135" nominal
11.6 lbs/1,000 ft
UL: UL1666 Riser Flame Test C(UL): FT4
ELECTRICAL AND ENVIRONMENTAL PROPERTIES
Temperature Rating
Operating Voltage
Capacitance Between Conductors @ 1 kHz
Nominal Conductor DC Resistance @ 20˚C
Maximum Recommended Current
APPEARANCE AND PACKAGING
Insulation Colors
Jacket Color
Legend (Surface Ink Print)
Packaging
–20˚C to +75˚C
300 V rms (maximum)
25 pF/ft
16.2 ohms/1,000 ft
2.8 amps per conductor @ 25˚C
Black, red, white
Grey
22 AWG (UL) Type CMR 75˚C C(UL) ROHS
Available in 1,000-foot reels and pull-out boxes.
The jacket is sequentially footmarked.