Johnson Controls CBL-22/3-FC-PVC Data Sheet

FIELD CONTROLLER (FC) BUS CABLE 22-3C SHIELDED NONPLENUM
PART NO.
Description
Construction
Approvals
CONSTRUCTION PARAMETERS
Conductor and Stranding
Insulation Material and Thickness
Shield
Drain
Jacket Material and Thickness
Overall Cable Diameter
Approximate Cable Weight
Flame Rating
CBL-22/3-FC-PVC
22/3 stranded shielded PVC FC Bus communication cable
This cable consists of a) three bare copper-insulated conductors with an overall shield and drain wire and b) an overall jacket. The cable has a rip cord for easy jacket removal.
UL Standard 444, NEC Article 800 – CMR, CE, RoHS
22 AWG bare copper 7x30
PVC, 0.010”
3
Alum/poly, 100% coverage
24 AWG 7x32 tinned copper
PVC, 0.015"
0.138" nominal
13.7 lbs/1,000 ft
UL: UL1666 Riser Flame Test C(UL): FT4
ELECTRICAL AND ENVIRONMENTAL PROPERTIES
Temperature Rating
Operating Voltage
Capacitance Between Conductors @ 1 kHz
Nominal Conductor DC Resistance @ 20˚C
Max. Recommended Current
APPEARANCE AND PACKAGING
Insulation Colors
Jacket Color
Legend (Surface Ink Print)
Packaging
–20˚C to +75˚C
300 V rms (maximum)
31 pF/ft
16.4 ohms/1,000 ft
2.8 amps per conductor @ 25˚C
Black, blue, white
Blue
JCI FC Bus Cable 22AWG (UL) Type CMR C(UL) Type CMR FT-4 Northflex ROHS
Available in 1,000-foot reels and pull-out boxes.
The jacket is sequentially footmarked.