SENSOR ACTUATOR (SA) BUS CABLE 22-2P SHIELDED PLENUM
PART NO.
Description
Construction
Approvals
CONSTRUCTION PARAMETERS
Conductor and Stranding
Insulation Material and Thickness
Number of Pairs
Shield
Drain
Jacket Material and Thickness
Overall Cable Diameter
Approximate Cable Weight
Flame Rating
CBL-22/2P-SA-PLN
22/2 pair stranded shielded plenum SA Bus communication cable
This cable consists of a) two pairs of bare copper-insulated conductors with an overall
shield and drain wire and b) an overall jacket. The cable has a rip cord for easy jacket
removal.
UL Standard 444, NEC Article 800 – CMP, CE, RoHS
22 AWG bare copper 7x30
Low smoke PVC, 0.009"
2 pairs (4 conductors total)
Alum/poly, 100% coverage
24 AWG 7x32 tinned copper
Low smoke PVC, 0.015"
0.203" nominal
20.7 lbs/1,000 ft
UL: UL910/NFPA262
C(UL): FT6
ELECTRICAL AND ENVIRONMENTAL PROPERTIES
Temperature Rating
Operating Voltage
Capacitance Between Conductors @ 1 kHz
Nominal Conductor DC Resistance @ 20˚C
Maximum Recommended Current
APPEARANCE AND PACKAGING
Insulation Colors
Jacket Color
Legend (Surface Ink Print)
Packaging
0˚C to +75˚C
300 V rms (maximum)
33 pF/ft
16.3 ohms/1,000 ft
2.2 amps per conductor @ 25˚C
Pair no. 1: black & white, Pair no. 2: blue & brown
Brown
JCI SA Bus Cable 22AWG (UL) Type CMP
C(UL) Type CMP FT6 Northflex ROHS
Available in 1,000-foot reels and pull-out boxes.
The jacket is sequentially footmarked.