Johnson Controls CBL-22/2-NS-PVC Data Sheet

Johnson Controls CBL-22/2-NS-PVC Data Sheet

 

GENERAL PURPOSE 22-2C NONSHIELDED NONPLENUM

PART NO.

CBL-22/2-NS-PVC

 

 

 

 

 

Description

22/2 stranded nonshielded PVC communications cable

 

 

 

 

 

Construction

This cable consists of a) two bare copper-insulated conductors and

 

b) an overall jacket. The cable has a rip cord for easy jacket removal.

 

Approvals

UL Standard 444, NEC Article 800 – CMR, CE, RoHS

 

 

 

 

 

CONSTRUCTION PARAMETERS

 

 

 

 

 

 

 

 

Conductor and Stranding

22 AWG bare copper 7x30

 

 

 

 

Insulation Material and Thickness

PVC, 0.010"

Number of Conductors

2

 

 

 

 

 

 

 

Shield

None

 

 

 

 

Jacket Material and Thickness

PVC, 0.015"

 

Overall Cable Diameter

0.128" nominal

 

 

 

Approximate Cable Weight

8.4 lbs/1,000 ft

 

 

 

Flame Rating

UL: UL1666 Riser Flame Test

 

C(UL): FT4

 

 

 

 

 

ELECTRICAL AND ENVIRONMENTAL PROPERTIES

 

 

 

 

 

 

 

Temperature Rating

-20˚ to +75˚C

 

 

 

Operating Voltage

300 V rms (maximum)

 

Capacitance Between Conductors @ 1 kHz

25 pF/ft

 

 

 

Nominal Conductor DC Resistance @ 20˚C

16.1 ohms/1,000 ft

 

 

 

Maximum Recommended Current

2.8 amps per conductor @ 25˚C

 

 

 

 

 

APPEARANCE AND PACKAGING

 

 

 

 

 

 

 

Insulation Colors

Black, red

 

 

 

Jacket Color

Grey

 

Legend (Surface Ink Print)

22 AWG (UL) Type CMR 75C

 

C(UL) ROHS

 

Packaging

Available in 1,000-foot reels and pull-out boxes.

 

 

 

 

The jacket is sequentially footmarked.

Loading...