Johnson Controls CBL-18/3BLU-PVC Data Sheet

N-2 BUS CABLE 18-3C NONPLENUM
PART NO.
Description
Construction
Approvals
CONSTRUCTION PARAMETERS
Conductor and Stranding
Insulation Material and Thickness
Shield
Drain
Jacket Material and Thickness
Overall Cable Diameter
Approximate Cable Weight
Flame Rating
CBL-18/3BLU-PVC
18/3 stranded shielded CMR FT4 cable
This cable consists of a) three bare copper-insulated conductors with an overall shield and drain wire and b) and an overall jacket. The cable has a rip cord for easy jacket removal.
UL Standard 444, NEC Article 800–CMR, CE, RoHS
18 AWG bare copper, 7x26
PVC, 0.010"
3
Alum/poly, 100% coverage
20 AWG 7x28 tinned copper
PVC, 0.015"
0.175" nominal
27.7 lbs/1,000 ft
UL: UL 1666 Riser Flame Test c(UL): FT4
ELECTRICAL AND ENVIRONMENTAL PROPERTIES
Temperature Rating
Operating Voltage
Capacitance Between Conductors @ 1 kHz
Nominal Conductor DC Resistance @ 20˚C
Maximum Recommended Current
APPEARANCE AND PACKAGING
Insulation Colors
Jacket Color
Legend (Surface Ink Print)
Packaging
–20˚C to 75˚C
300 V rms maximum
62 pF/ft nominal
6.5 ohms/1,000 ft
5 amps per conductor @ 25˚C
Black, white, blue
Blue
Johnson Controls MetaSys-N2 Bus Cable 18 AWG (UL) TYPE CMR C (UL) TYPE CMR FT4 Northflex
Available in 1,000-foot reels and pull-out boxes.
The jacket is sequentially footmarked.