Johnson Controls CBL-18/2NAT-PLN Data Sheet

GENERAL PURPOSE 18-2C PLENUM
PART NO.
Description
Construction
Approvals
CONSTRUCTION PARAMETERS
Conductor and Stranding
Insulation Material and Thickness
Shield
Drain
Jacket Material and Thickness
Overall Cable Diameter
Approximate Cable Weight
Flame Rating
CBL-18/2NAT-PLN
18/2 shielded plenum communications cable
This cable consists of a) two bare copper-insulated conductors with an overall shield and drain wire and b) an overall jacket. The cable has a rip cord for easy jacket removal.
UL Standard 444, NEC Article 800–CMP, CE, RoHS
18 AWG bare copper, 7x26
Low smoke PVC, 0.009"
2
Alum/poly, 100% coverage
20 AWG 7x28 tinned copper
Low smoke PVC, 0.015"
0.162" nominal
21.4 lbs/1,000 ft
UL: UL 910 /NFPA 262 c(UL): FT6
ELECTRICAL AND ENVIRONMENTAL PROPERTIES
Temperature Rating
Operating Voltage
Capacitance Between Conductors @ 1 kHz
Nominal Conductor DC Resistance @ 20˚C
Maximum Recommended Current
APPEARANCE AND PACKAGING
Insulation Colors
Jacket Color
Legend (Surface Ink Print)
Packaging
0˚C to 75˚C
300 V rms maximum
70 pF/ft nominal
6.4 ohms/1,000 ft
5 amps per conductor @ 25˚C
Black, white
Natural
Johnson Controls MetaSys-General Purpose Cable 18 AWG (UL) TYPE CMP C (UL) TYPE CMP FT6 Northflex
Available in 1,000-foot reels and pull-out boxes.
The jacket is sequentially footmarked.