24 V AC 18-2C NONPLENUM
PART NO.
Description
Construction
Approvals
CONSTRUCTION PARAMETERS
Conductor and Stranding
Insulation Material and Thickness
Number of Conductors
Shield
Drain
Jacket Material and Thickness
Overall Cable Diameter
Approximate Cable Weight
Flame Rating
CBL-18/2GRY-PVC
18/2 stranded shielded CMR FT4 cable
This cable consists of a) two bare copper-insulated conductors with an overall shield
and drain wire and b) an overall jacket. The cable has a rip cord for easy jacket removal.
UL Standard 444, NEC Article 800–CMR, CE, RoHS
CABLE CROSS-SECTION
18 AWG bare copper, 7x26
PVC, 0.010"
2
Alum/poly, 100% coverage
20 AWG 7x28 tinned copper
PVC, 0.015"
0.165" nominal
20.9 lbs/1,000 ft
UL: 1666 Riser Flame Test
c(UL): FT4
ELECTRICAL AND ENVIRONMENTAL PROPERTIES
Temperature Rating
Operating Voltage
Capacitance Between Conductors @ 1 kHz
Nominal Conductor DC Resistance @ 20˚C
Maximum Recommended Current
APPEARANCE AND PACKAGING
Insulation Colors
Jacket Color
Legend (Surface Ink Print)
Packaging
–20˚C to 75˚C
300 V rms maximum
65 pF/ft nominal
6.5 ohms/1,000 ft
5 amps per conductor @ 25˚C
Black, grey
Grey
Johnson Controls MetaSys-24 VAC Cable (VAC) 18 AWG
(UL) TYPE CMR C (UL) TYPE CMR FT4 Northflex
Available in 1,000-foot reels and pull-out boxes.
The jacket is sequentially footmarked.