Johnson Controls B1HA036, B1HA060, B1HA042, B1HA048 Installation Manual

Page 1
INSTALLATION MANUAL
CONTENTS
GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
INSPECTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
REFERENCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
REPLACEMENT PARTS. . . . . . . . . . . . . . . . . . . . . . . . .3
PRODUCT NOMENCLATURE . . . . . . . . . . . . . . . . . . . .3
INSTALLATION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
SEQUENCE OF OPERATION. . . . . . . . . . . . . . . . . . . .13
MAINTENANCE. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
See the following page for a complete Table of Contents.
AFFINITY™ SERIES
SINGLE PACKAGE HEAT PUMPS
MODEL: B1HA036 thru 060
3 thru 5 Ton
(10 SEER)
NOTES, CAUTIONS AND WARNINGS
Installer should pay particular attention to the words: NOTE, CAUTION, and WARNING. Notes intended to clarify or make the installation easier. Cautions Warnings injury and/or equipment damage may result if instal­lation procedure is not handled properly.
CAUTION: READ ALL SAFETY GUIDES BEFORE YOU BEGIN TO INSTALL YOUR UNIT.
SAVE THIS MANUAL
are given to prevent equipment damage.
are given to alert installer that personal
are
ISO 9001
Certified Quality
341849-YIM-A-0108
Page 2
TABLE OF CONTENTS
341849-YIM-A-0108
GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
INSPECTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
REFERENCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
REPLACEMENT PARTS . . . . . . . . . . . . . . . . . . . . . . . . . . .3
PRODUCT NOMENCLATURE . . . . . . . . . . . . . . . . . . . . . .3
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
LIMITATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
LOCATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
RIGGING AND HANDLING . . . . . . . . . . . . . . . . . . . . 4
CLEARANCES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
DUCTWORK . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
FILTERS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
CONDENSATE DRAIN . . . . . . . . . . . . . . . . . . . . . . . . 5
SERVICE ACCESS . . . . . . . . . . . . . . . . . . . . . . . . . . 5
THERMOSTAT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
POWER AND CONTROL WIRING . . . . . . . . . . . . . . . 5
COMPRESSORS . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
CHECKING SUPPLY AIR CFM . . . . . . . . . . . . . . . . .9
SEQUENCE OF OPERATION . . . . . . . . . . . . . . . . . . . . . .13
ANTI-SHORT CYCLE TIMER . . . . . . . . . . . . . . . . . . 13
COOLING OPERATION . . . . . . . . . . . . . . . . . . . . . . 13
HEATING OPERATION . . . . . . . . . . . . . . . . . . . . . . 13
DEFROST OPERATION . . . . . . . . . . . . . . . . . . . . .13
HEAT PUMP SAFETY SWITCH OPERATION . . . . 14
ELECTRIC HEAT LIMIT SWITCH OPERATION . . .14
MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
NORMAL MAINTENANCE . . . . . . . . . . . . . . . . . . . . 15
LIST OF FIGURES
Fig. # Pg. #
1 CENTER OF GRAVITY . . . . . . . . . . . . . . . . . . . . . . . .4
2 TYPICAL FIELD WIRING DIAGRAM . . . . . . . . . . . . . . 6
3 COIL DELTA P VS. SUPPLY AIR CFM . . . . . . . . . . . .9
4 DIMENSIONS AND CLEARANCES . . . . . . . . . . . . . .12
5 TYPICAL WIRING DIAGRAM (230-3-60 POWER
SUPPLY) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
Fig. # 6 TYPICAL WIRING DIAGRAM BHA MODELS
(460-3-60 AND 575-3-60 POWER SUPPLY) . . . . . . . 17
7 TYPICAL WIRING DIAGRAM LEGEND . . . . . . . . . . . 18
8 TYPICAL WIRING DIAGRAM NOTES . . . . . . . . . . . . 18
Pg. #
LIST OF TABLES
Tbl. # Pg. #
1 UNIT APPLICATION DATA . . . . . . . . . . . . . . . . . . . . . 4
2 UNIT DIMENSIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
3 PHYSICAL DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
4 ELECTRICAL DATA (HEAT PUMP /
ELECTRIC HEAT) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
5 ELECTRICAL DATA (BASIC UNIT) . . . . . . . . . . . . . . . 7
6 SIDE & BOTTOM SUPPLY AIR BLOWER
PERFORMANCE 230/460/575 VOLTS . . . . . . . . . . . . 8
7 SIDE & BOTTOM SUPPLY AIR BLOWER
PERFORMANCE 208 VOLTS . . . . . . . . . . . . . . . . . . . 8
8 ADDITIONAL STATIC PRESSURE RESISTANCE . . . 8 9 COOLING SUPERHEAT AT COMPRESSOR SUCTION,
AIRFLOW = 1,200 CFM (B1HA036) . . . . . . . . . . . . . . 10
10 HEATING SUPERHEAT AT COMPRESSOR SUCTION,
AIRFLOW = 1,200 CFM (B1HA036) . . . . . . . . . . . . . . 10
11 COOLING SUPERHEAT AT COMPRESSOR SUCTION,
AIRFLOW = 1,400 CFM (B1HA042) . . . . . . . . . . . . . . 10
12 HEATING SUPERHEAT AT COMPRESSOR SUCTION,
AIRFLOW = 1,400 CFM (B1HA042) . . . . . . . . . . . . . . 10
13 COOLING SUPERHEAT AT COMPRESSOR SUCTION,
AIRFLOW = 1,600 CFM (B1HA048) . . . . . . . . . . . . . . 11
14 HEATING SUPERHEAT AT COMPRESSOR SUCTION,
AIRFLOW = 1,600 CFM (B1HA048) . . . . . . . . . . . . . . 11
15 COOLING SUPERHEAT AT COMPRESSOR SUCTION,
AIRFLOW = 2,000 CFM (B1HA060) . . . . . . . . . . . . . . 11
16 HEATING SUPERHEAT AT COMPRESSOR SUCTION,
AIRFLOW = 2,000 CFM (B1HA060) . . . . . . . . . . . . . . 11
17 THERMOSTAT SIGNALS (THREE PHASE
UNITS) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
2 Johnson Controls Unitary Products
Page 3
341849-YIM-A-0108
GENERAL
YORK Model B1HA units are factory assembled heat pumps designed for outdoor installation on a rooftop or a slab. Field-installed electric heater accessories are available to provide supplemental electric heat com­bined with electric cooling and heating.
The units are completely assembled on rigid, remov­able base rails. All piping, refrigerant charge, and elec­trical wiring is factory installed and tested. The units require only electric power and duct connections at the point of installation.
The electric heaters have nickel-chrome resistance wire elements and utilize single point power connection.
INSPECTION
As soon as a unit is received, it should be inspected for possible damage during transit. If damage is evident, the extent of the damage should be noted on the car­rier's freight bill. A separate request for inspection by the carrier's agent should be made in writing.
REFERENCE
Additional information on the design, installation, oper­ation and service of this equipment is available in the following reference forms:
REPLACEMENT PARTS
Contact your local York® parts distribution center for authorized replacement parts.
This product must be installed in strict compli­ance with the enclosed installation instructions and any applicable local, state, and national codes including, but not limited to, building, electrical, and mechanical codes.
Improper installation may create a condition where the operation of the product could cause personal injury or property damage.
De-energize the electrical power to the unit before attempting to inspect, repair or perform maintenance to the unit.
341849 - General Installation
035-16605-003 - Electric Heater Accessory
PRODUCT NOMENCLATURE
B 1 H A A
PRODUCT CATEGORY
B = Single Package Heat Pumps (Air Cooled)
PRODUCT GENERATION
1 = NEW or Current Design
PRODUCT IDENTIFIER
HA = Heat Pump (10 SEER)
PRODUCT NOMENCLATURE
30 6 2 5
NOMINAL COOLING
CAPACITY (MBH)
036 = 36,000 BTUH 042 = 42,000 BTUH 048 = 48,000 BTUH 060 = 60,000 BTUH
VOLTAGE CODE
25 = 208/230-3-60 46 = 460-3-60 58 = 575-3-60
FACTORY
INSTALLED ELECTRIC HEAT
A = No Electric Heat Installed
Johnson Controls Unitary Products 3
Page 4
341849-YIM-A-0108
INSTALLATION
LIMITATIONS
These units must be installed in accordance with the following national and local safety codes.
1. National Electrical Code ANSI/NFPS No. 70 or Cana­dian Electrical Code Part 1, C22.1 (latest ed itions).
2. Local plumbing and waste water codes and other applicable local codes.
Refer to Table 1 for unit application data and to Table 4 for electric heat application data.
If components are to be added t o a unit to meet local codes, they are to be installed at the dealer's and/or the customer's expense.
Size of unit for proposed installation should be based on heat loss/heat gain calculations made in accor­dance with industry recognized procedures identified by the Air Conditioning Contractors of America.
TABLE 1: Unit Application Data
Voltage Variation,
Min./Max.
Wet Bulb Temperature (°F) of Air on
Dry Bulb Temperature (
1. Rated in accordance with ARI Standard 110, utilization range “A”.
2. “T1" transformer primary tap must be moved from the 230 volt connection to the 208 volt connection for low voltage applications of 208 volt and below.
3. A low ambient accessory is available for operation down to 0°F.
1
Evaporator Coil, Min./Max.
Condenser Coil, Min.
208/230 V
°F) of Air on
3
/Max.
2
460 V 414/504 575 V 518/630
LOCATION
187/253
57/72
45/120
installed components. Unit must be installed on a level roof curb or appropriate angle iron frame pro­viding adequate support under the compressor/ condenser section.
5. Maintain level tolerance of unit to 1/8" maximum.
RIGGING AND HANDLING
Care must be exercised when moving the unit. Do not remove any packaging until the unit is near the pla ce of installation. Rig unit with slings placed under the unit. Spreader bars of sufficient length should be used across the top of the unit.
BEFORE LIFTING A UNIT, MAKE SURE THAT ITS WEIGHT IS DISTRIBUTED EQUALLY ON THE CABLES SO THAT IT WILL LIFT EVENLY.
Units may also be moved or lifted with a fork-lift. Slot­ted openings in the skid are provided for this purpose. Forks must pass completely through the base.
Refer to Table 2 for unit weights and to Figure 1 for approximate center of gravity.
TABLE 2: Unit Dimensions
Shipping
Size
036 367 362 100 96 84 87 042 394 389 107 103 90 93 048 445 440 121 117 102 105 060 490 485 133 129 112 116
FRONT
OF
UNIT
Weight
(lbs.)
49 1/8
Operating
Weight
(lbs.)
“D”
“A”
“B”
25
Dimensions
“A” “B” “C” “D”
CENTER OF GRAVITY
“C”
22
49 1/4
Use the following guidelines to select a suitable loca­tion for these units.
1. Unit is designed for outdoor installation only.
2. Condenser must have an unlimited supply of air. Where a choice of location is possible, position unit on either north or east side of building.
3. For ground level installation, a level pad or slab should be used. The thickness and size of the pad or slab used should meet local codes and unit weight. Do not tie the slab to the building foundation.
4. For roof top installation, be sure the structure will support the weight of the unit plus any field
4 Johnson Controls Unitary Products
FIGURE 1 - Center of Gravity CLEARANCES
All units require certain clearances for proper operation and service. Refer to Figure 4 for the clearances required for construction, servicing and proper unit operation.
Do not permit overhanging structures or shrubs to obstruct the condenser air discharge outlets.
Page 5
341849-YIM-A-0108
DUCTWORK
These units are adaptable to downflow use as well as rear supply and return air duct openings. To convert to downflow, use the following steps:
1. Remove the duct covers found in the bottom return and supply air duct openings. There are four (4) screws securing each duct cover (save these screws to use later).
2. Install the duct covers, removed in step one, to the rear supply and return air duct openings. Secure with the four (4) screws used in step one.
3. Seal duct covers with silicone caulk.
Downflow units must have an “L”-shape d supply duct without any outlets or registers located below the outlet of the unit.
Duct work should be designed and sized according to the methods of the Air Conditioning Contractors of America (ACCA), as set forth in their Manual D.
A closed return duct system shall be used. This shall not preclude use of economizers or ventilation air intake. Flexible joints may be used in the supply and return duct work to minimize the transmission of noise.
CONDENSATE DRAIN
A condensate trap is required to be installed in the con­densate drain. The plumbing must conform to local codes. Use a sealing compound on male pipe threads. Install the condensate drain line (3/4“ NPTF) to spill into an open drain.
SERVICE ACCESS
Access to all serviceable components is provided by the following removable panels:
Blower service access
Electrical/Filter access
Compressor service access Refer to Figure 4 for locatio n of these access panels
and minimum clearances.
THERMOSTAT
The room thermostat should be located on an inside wall approximately 56" above the floor where it will not be subject to drafts, sun exposure or heat from electri­cal fixtures or appliances. Follow manufacturer's instructions enclosed with the thermostat for general installation procedure. Six color coded insulated wires (minimum #18 AWG) should be used to connect ther­mostat to unit. See Figure 2.
When fastening ductwork to side duct flanges on unit, insert screws through duct flanges only. DO NOT insert screws through casing. Outdoor ductwork must be insulated and waterproofed.
NOTE: Be sure to note supply and return openings. Refer to Figure 4 for information concerning rear and
bottom supply and return air duct openings.
FILTERS
A filter rack and high velocity filters are standard on three phase units.
Filters must always be used a nd must be kept clean. When filters become dirt laden, insufficient air will be delivered by the blower, decreasing your units effi­ciency and increasing operating costs and wear-and­tear on the unit and controls.
Filters should be checked monthly especially since this unit is used for both heating and cooling.
POWER AND CONTROL WIRING
Field wiring to the unit must conform to provisions of the current N.E.C. ANSI/NFPA No. 70 or C.E.C. and/or local ordinances. The unit must be electrically grounded in accordance with local codes or, in their absence, with the N.E.C./C.E.C. Voltage tolerances which must be maintained at the compressor terminals during starting and running conditions are indicated on the unit Rating Plate and Table 4.
The wiring entering the cabinet must be provided with mechanical strain relief.
A fused disconnect switch should be field provided for the unit. If any of the wire supplied with the unit must be replaced, replacement wire must be of the type shown on the wiring diagram.
Electrical line must be sized properly to carry the load. Each unit must be wired with a separate branch circuit fed directly from the meter panel and properly fused.
Refer to Figure 2 for typical field wiring and to the appropriate unit wiring diagram for control circuit and power wiring information.
Johnson Controls Unitary Products 5
Page 6
COMPRESSORS
Units are shipped with compressor mountings factory­adjusted for shipping.
CONTROL WIRING
341849-YIM-A-0108
Loosen compressor bolts half turn before operating unit.
THERMOSTAT
** = Minimum wire size of 18 AWG
wire should be used for all field installed 24 volt wire.
PROGRAMMABLE
THERMOSTAT ONLY
UNIT TERMINAL STRIP
**
*
NOTE: HEAT ANTICIPATOR SHOULD BE SET AT 0.25 AMPS FOR ALL MODELS.
24 VOLT TRANSFORMER
* = Only required on units with
supplemental electric heat.
CAUTION: Label all wires prior to disconnection when servicing controls. Wiring errors can
cause improper and dangerous operation. Verify proper operation after servicing.
POWER WIRING
REFER TO ELECTRICAL DATA
TABLES TO SIZE THE
DISCONNECT SWITCH,
WIRING & OVERCURRENT
PROTECTION.
FIGURE 2 - Typical Field Wiring DIagram
TABLE 3: Physical Data
Models
Indoor
Blower
Indoor
Coil
Outdoor
Fan
Outdoor
Coil
Charge Refrigerant 22 (Lbs./oz.) 5/5 6/0 9/0 10/0
Filter Face Area (Sq. Ft./qty./size) 4.28/2/14" x 22"
Compressor Hermetic Type, (Qty. = 1) Scroll Recip. Scroll Scroll
Centrifugal Blower (Dia. X Wd. In.)
Fan Motor Hp
Rows Deep
Fins Per Inch
Face Area (Sq. Ft.)
Propeller Dia. (In.)
Fan Motor Hp
Nom. CFM Total
Rows Deep
Fins Per Inch
Face Area (Sq. Ft.)
036 042 048 060
10 x 8 11 x 10 11 x 10 11 x 10
3/4 3/4 3/4 1
3333
15 15 16 16
4.38 4.38 5.62 5.62 22 22 22 22
1/41/41/41/4
2,400 2,400 2,800 2,800
1111
20 20 16 20
11.7 11.7 16.4 16.4
BHA
6 Johnson Controls Unitary Products
Page 7
341849-YIM-A-0108
TABLE 4: Electrical Data (Heat Pump / Electric Heat)
OD Fan
Motors
(each)
Size Volt
Compressors
(each)
RLA LRA FLA FLA Model Stages kW Amps
036 208/230-3-60 10.9 78.0 1.1 3.5
042 208/230-3-60 12.8 88.0 1.1 3.5
048 208/230-3-60 14.1 105.0 1.5 4.0
060 208/230-3-60 16.0 125.0 1.5 7.0
036 460-3-60 5.8 40.0 0.6 1.8
042 460-3-60 5.8 42.0 0.6 1.8
048 460-3-60 7.1 55.0 0.8 2.0
060 460-3-60 8.0 67.0 0.8 3.5
036 575-3-60 4.5 32.0 0.4 1.5
042 575-3-60 5.8 44.0 0.4 1.5
048 575-3-60 5.6 44.0 0.6 1.6
060 575-3-60 6.4 50.0 0.6 2.8
1. Dual element, time delay type.
2. Standard circuit breakers may be used in Canada and on applications over 60 amps where the heaters are separately fused.
3. KW listed is for 240 volts, use table at top of next page for 208 or 230 volts.
4. KW listed is for 480 volts, use table at top of next page for 460 volts.
5. KW listed is for 600 volts, use table at top of next page for 575 volts.
Supply Blower
Motor
Electric Heat Option
2NH04501025 1 7.5/10.0 2NH04501525 1 11.3/15.0 2NH04501025 1 7.5/10.0 2NH04501525 1 11.3/15.0 2NP04501025 1 7.5/10.0 2NP04501525 1 11.3/15.0 2NP04502025 2 15.0/20.0 2NH04502525 2 18.8/25.0 2NH04501025 1 7.5/10.0 2NH04501525 1 11.3/15.0 2NH04502025 2 15.0/20.0 2NH04502525 2 18.8/25.0 2NH04501046 1 10.0 2NH04501546 1 15.0 2NH04501046 1 10.0 2NH04501546 1 15.0 2NP04501046 1 10.0 2NH04501546 1 15.0 2NH04502046 2 20.0 2NH04502546 2 25.0 2NH04501046 1 10.0 2NH04501546 1 15.0 2NP04502046 2 20.0 2NP04502546 2 25.0 2NH04501058 1 10.0 2NH04501558 1 15.0 2NH04501058 1 10.0 2NH04501558 1 15.0 2NH04501058 1 10.0 2NH04501558 1 15.0 2NH04502058 2 20.0 2NH04502558 2 25.0 2NH04501058 1 10.0 2NH04501558 1 15.0 2NP04502058 2 20.0 2NP04502558 2 25.0
MCA
(Amps)
3
20.8/24.1 44.3/48.3 45/50 45/50
3
31.3/36.1 57.3/63.3 60/70 60/70
3
20.8/24.1 46.9/50.7 50/60 50/60
3
31.3/36.1 59.7/65.7 60/70 60/70
3
20.8/24.1 49.2/53.2 50/60 50/60
3
31.3/36.1 62.2/68.2 70/70 70/70
3
41.7/48.1 75.3/83.3 80/90 80/90
3
52.1/60.1 88.3/98.3 90/100 90/100
3
20.8/24.1 54.6/58.6 60/60 60/60
3
31.3/36.1 67.6/73.6 70/80 70/80
3
41.7/48.1 80.7/88.7 90/90 90/90
3
52.1/60.1 93.7/103.7 100/110 100/110
4
12.8 24.6 25 25
4
18.0 32.2 35 35
4
12.0 24.7 25 25
4
18.0 32.2 35 35
4
12.0 26.7 30 30
4
18.0 34.2 35 35
4
24.1 41.7 45 45
4
30.1 49.3 50 50
4
12.0 29.4 30 30
4
18.0 36.9 40 40
4
24.1 44.4 45 45
4
30.1 51.9 60 60
5
9.6 19.6 20 20
5
14.4 25.6 30 30
5
9.6 21.1 25 25
5
14.4 27.2 30 30
5
9.6 21.3 25 25
5
14.4 27.3 30 30
5
19.2 33.3 35 35
5
24.1 39.3 40 40
5
9.6 23.4 25 25
5
14.4 29.5 30 30
5
19.2 35.5 40 40
5
24.1 41.5 45 45
Max Fuse/
Breaker Size
(Amps)
Max HACR
1
Breaker Size
2
TABLE 5: Electrical Data (Basic Unit)
Voltage
Size Volt
Limitations Min. Max. RLA LRA FLA FLA
036 208/230-3-60 187 253 10.9 78.0 1.1 3.5 18.2 25 25 .96 75 042 208/230-3-60 187 253 12.8 88.0 1.1 3.5 20.6 25 25 .96 75 048 208/230-3-60 187 253 14.1 105.0 1.5 4.0 23.1 30 30 .96 75 060 208/230-3-60 187 253 16.0 125.0 1.5 7.0 28.5 40 40 .96 75 036 460-3-60 414 504 5.8 40.0 0.6 1.8 9.6 15 15 .96 75 042 460-3-60 414 504 5.8 42.0 0.6 1.8 9.7 15 15 .96 75 048 460-3-60 414 504 7.1 55.0 0.8 2.0 11.7 15 15 .96 75 060 460-3-60 414 504 8.0 67.0 0.8 3.5 14.3 20 20 .96 75 036 575-3-60 518 630 4.5 32.0 0.4 1.5 7.6 15 15 .96 75 042 575-3-60 518 630 5.8 44.0 0.4 1.5 9.1 15 15 .96 75 048 575-3-60 518 630 5.6 44.0 0.6 1.6 9.3 15 15 .96 75 060 575-3-60 518 630 6.4 50.0 0.6 2.8 11.4 15 15 .96 75
1. Rated in accordance with ARI Standard 110, utilization range “A”.
2. Dual element, time delay type.
Johnson Controls Unitary Products 7
1
Compressors
(each)
OD Fan
Motors
(each)
Supply Blower
Motor
MCA
(Amps)
Max Fuse
2
Size
(Amps)
Max HACR
Breaker Size
Unit Power
Factor
Transformer
Size (VA)
Page 8
341849-YIM-A-0108
kW. Capacity
Multiplier
Electric Heat
Correction
Factors
Nominal Voltage Voltage
240 480 460 .92
600 575 .92
208 .75 230 .92
TABLE 6: Side & Bottom Supply Air Blower Performance 230/460/575 Volts
Blower
Size
Speed
High - - - - - - - - 1414 617 1317 688 1219 660 1116 533 1013 507 910 480 - -
036
Medium - - - - 1472 647 1394 626 1297 495 1199 465 1102 435 985 397 - - - - - -
Low 1462 526 1400 506 1337 486 1275 467 1167 440 1100 414 1012 387 - - - - - - - -
High - - - - - - - - 1697 740 1580 706 1463 672 1339 640 1216 608 1092 576 - -
042
Medium - - - - - - 1673 830 1566 594 1439 558 1322 522 1182 476 - - - - - -
Low - - 1680 607 1608 584 1630 660 1425 528 1320 496 1214 464 1050 420 - - - - - -
High - - - - - - 1947 882 1867 857 1786 832 1706 807 1637 782 1569 757 1500 732 - -
048
Medium 1876 792 1829 772 1783 753 1736 733 1668 706 1599 680 1531 653 1434 622 1337 591 1240 560 - -
Low 1544 620 1508 610 1472 600 1436 590 1375 573 1313 557 1252 540 - - - - - - - -
High - - - - - - 2499 1290 2391 1233 2283 1177 2175 1120 2067 1080 1958 1040 1850 1000 - -
036
Medium - - 2454 1163 2387 1117 2320 1070 2229 1023 2137 977 2046 930 1950 887 1854 843 1758 800 - -
Low 2242 1090 2201 1053 2161 1017 2120 980 2041 927 1962 873 1883 820 1797 787 1711 753 1625 720 - -
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 1.1
CFM W CFM W CFM W CFM W CFM W CFM W CFM W CFM W CFM W CFM W CFM W
External Static Pressure (Inch Water Gauge)
TABLE 7: Side & Bottom Supply Air Blower Performance 208 Volts
Blower
Size
Speed
High - - - - 1440 608 1381 571 1273 656 1185 530 1097 604 1004 480 912 456 - - - -
036
Medium 1465 631 1395 512 1325 492 1255 473 1167 446 1079 419 952 392 - - - - - - - -
Low 1316 473 1260 455 1204 438 1148 420 1069 396 990 372 911 348 - - - - - - - -
High - - - - 1728 725 1633 697 1527 666 1422 636 1317 606 1205 676 1094 547 - - - -
042
Medium - - 1674 614 1590 590 1506 567 1400 636 1296 602 1190 470 1063 428 - - - - - -
Low 1679 867 1612 646 1449 526 1377 504 1282 476 1188 447 1093 418 - - - - - - - -
High - - 1982 870 1939 850 1897 830 1813 800 1728 770 1644 740 1559 707 1474 673 1389 640 - -
048
Medium 1694 690 1662 673 1629 657 1597 640 1542 623 1486 607 1431 590 1336 563 1240 537 - - - -
Low 1385 520 1349 510 1312 500 1276 490 1235 480 - - - - - - - - - - - -
High - - - - 2450 1213 2366 1165 2282 1117 2198 1068 2114 1020 1989 993 1864 967 1739 940 - -
036
Medium 2339 1170 2275 1118 2211 1067 2147 1015 2083 963 2019 912 1955 860 1854 824 1753 788 1652 752 - -
Low 1929 940 1877 903 1824 867 1772 830 1720 793 1667 757 1615 720 1586 706 1557 691 1528 677 - -
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 1.1
CFM W CFM W CFM W CFM W CFM W CFM W CFM W CFM W CFM W CFM W CFM W
External Static Pressure (Inch Water Gauge)
TABLE 8: Additional Static Press ure Resistance
Description
500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000
Wet Indoor Coil 0.01 0.01 0.01 0.02 0.02 0.03 0.03 0.04 0.04 0.04 0.04 0.04 0.05 0.05 0.06 0.07 Economizer 0.00 0.00 0.00 0.01 0.01 0.01 0.01 0.02 0.03 0.04 0.05 0.06 0.07 0.07 0.08 0.08 Filter/Frame Kit 0.01 0.02 0.02 0.02 0.02 0.02 0.03 0.03 0.03 0.03 0.04 0.05 0.05 0.06 0.06 0.07 Electric Heat 0.02 0.03 0.03 0.03 0.04 0.04 0.05 0.06 0.07 0.08 0.09 0.10 0.01 0.11 0.11 0.12
1. Deduct these resistance values from the available external static pressures shown in the respective Blower Perf ormance Table.
2. The pressure thru the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return air duct system is less than
0.25 IWG, the unit will deliver less CFM during full economizer operation.
8 Johnson Controls Unitary Products
1,2
Resistance, IWG
CFM
Page 9
341849-YIM-A-0108
CHECKING SUPPLY AIR CFM
To check the supply air CFM after the initial balancing has been completed:
1. Remove the two ¼ inch dot plugs in the duct panel.
2. Insert at least 8 inches of ¼ inch tubing into each of these holes for sufficient penetration into the air­flow on both sides of the indoor coil.
3. Using an inclined m anometer, determine the pres­sure drop across the dry evaporator coil. Since the moisture on an evaporator coil may vary greatly, measuring the pressure drop across a wet coil under field conditions would be inaccurate. To ensure a dry coil, the compressors should be deac­tivated while the test is being run.
B1HA Coil Delta
4. Knowing the pressure drop across a dry coil, the actual CFM through the unit can be determined from the curve in Coil Delta P vs. Supply Air CFM Figure 3.
Failure to properly adjust the total system air quantity can result in extensive system damage.
After readings have been obtained, remove the tubes and reinstall the two ¼ inch plugs removed in Step 1.
NOTE: De-energize the compressors before taking any
test measurements to ensure a dry indoor coil.
B1HA036
B1HA048-60
B1HA042
Delta Static (IWG)
FIGURE 3 - Coil Delta P vs. Supply Air CFM
Linear B1HA036 Linear B1HA042 Linear B1HA048-60
Airflow (CFM)
Johnson Controls Unitary Products 9
Page 10
341849-YIM-A-0108
TABLE 9: Cooling Superheat at Compressor Suction, Airflow = 1,200 CFM (B1HA036)
Outdoor
Temperature
°F
65 12.8 16.1 19.3 22.5 25.8 29.0 32.2 35.0 37.7 40.4 43.1 70 11.4 14.3 17.2 20.1 22.9 25.8 28.7 31.6 34.4 37.3 40.1 75 9.9 12.5 15.0 17.6 20.1 22.7 25.2 28.2 31.1 34.1 37.1 80 8.5 10.7 12.9 15.1 17.3 19.5 21.7 24.8 27.9 31.0 34.0 85 7.0 8.9 10.8 12.6 14.5 16.3 18.2 21.4 24.6 27.8 31.0 90 5.6 7.1 8.6 10.1 11.7 13.2 14.7 18.0 21.3 24.7 28.0
95 - 5.3 6.5 7.7 8.8 10.0 11.2 14.6 18.1 21.5 25.0 100 - - 5.1 6.0 6.9 7.8 8.7 11.7 14.7 17.7 20.7 105 - - - - - 5.6 6.2 8.7 11.3 13.9 16.4 110 - - - - - - - 5.8 7.9 10.0 12.2 115 ---------6.27.9
55 57 59 61 63 65 67 69 71 73 75
Indoor WB Temperature, °F
TABLE 10: Heating Superheat at Compressor Suction, Airflow = 1,200 CFM (B1HA036)
Indoor DB
Temperature
°F
55 9.7 10.1 10.7 11.8 13.7 17.0 22.6 32.2
70 - - - - 4.6 7.8 13.4 23.0
80 ------7.316.9
-10 0 10 20 30 40 50 60
Heating Superheat at Compressor Suction, °F
TABLE 11: Cooling Superheat at Compressor Suction, Airflow = 1,400 CFM (B1HA042)
Outdoor
Temperature
°F
65 34.0 34.2 34.4 34.6 34.8 35.0 35.2 36.2 37.3 38.4 39.4
70 31.1 31.5 31.9 32.2 32.6 33.0 33.4 34.8 36.3 37.7 39.2
75 28.3 28.8 29.4 29.9 30.5 31.0 31.6 33.4 35.3 37.1 39.0
80 25.4 26.1 26.9 27.6 28.3 29.1 29.8 32.0 34.3 36.5 38.7
85 22.6 23.5 24.4 25.3 26.2 27.1 28.0 30.6 33.2 35.9 38.5
90 19.7 20.8 21.9 23.0 24.0 25.1 26.2 29.2 32.2 35.2 38.3
95 16.9 18.1 19.4 20.6 21.9 23.2 24.4 27.8 31.2 34.6 38.0 100 14.5 15.6 16.6 17.7 18.7 19.7 20.8 24.4 27.9 31.5 35.1 105 12.2 13.1 13.9 14.7 15.5 16.3 17.1 20.9 24.6 28.4 32.1 110 9.9 10.5 11.1 11.7 12.3 12.9 13.5 17.4 21.3 25.3 29.2 115 7.6 8.0 8.4 8.8 9.1 9.5 9.9 14.0 18.1 22.1 26.2
55 57 59 61 63 65 67 69 71 73 75
Indoor WB Temperature, °F
TABLE 12: Heating Superheat at Compressor Suction, Airflow = 1,400 CFM (B1HA042)
Indoor DB
Temperature
°F
55 5.1 5.5 6.2 7.4 9.6 13.5 20.3 32.4
70 - - - - 5.0 8.9 15.7 27.8
80 - - - - - 5.4 12.2 24.3
-10 0 10 20 30 40 50 60
Outdoor Temperature, °F
10 Johnson Controls Unitary Products
Page 11
341849-YIM-A-0108
TABLE 13: Cooling Superheat at Compressor Suction, Airflow = 1,600 CFM (B1HA048)
Outdoor
Temperature
°F
65 11.4 12.4 13.5 14.6 15.7 16.8 17.9 19.3 20.7 22.1 23.5 70 10.3 11.2 12.2 13.1 14.0 14.9 15.9 17.4 18.9 20.4 21.9 75 9.3 10.0 10.8 11.6 12.3 13.1 13.9 15.4 17.0 18.6 20.2 80 8.2 8.8 9.4 10.0 10.6 11.2 11.8 13.5 15.2 16.9 18.5 85 7.2 7.7 8.1 8.5 9.0 9.4 9.8 11.6 13.4 15.1 16.9 90 6.5 7.0 7.4 7.9 8.3 8.8 9.2 10.6 12.0 13.4 14.8
95 5.9 6.3 6.8 7.2 7.7 8.1 8.6 9.6 10.6 11.6 12.6 100 - 5.5 6.1 6.6 7.2 7.8 8.4 9.3 10.3 11.3 12.3 105 - - 5.4 6.1 6.8 7.5 8.2 9.1 10.1 11.0 11.9 110 - - - 5.5 6.3 7.2 8.0 8.9 9.8 10.7 11.6 115 - - - - 5.9 6.9 7.8 8.7 9.5 10.4 11.2
55 57 59 61 63 65 67 69 71 73 75
Indoor WB Temperature, °F
TABLE 14: Heating Superheat at Compressor Suction, Airflow = 1,600 CFM (B1HA048)
Indoor DB
Temperature
°F
55 8.3 8.4 8.6 9.0 10.1 12.4 17.4 28.6
70 -----4.29.220.4
80 ------5.716.9
-10 0 10 20 30 40 50 60
Heating Superheat at Compressor Suction, °F
TABLE 15: Cooling Superheat at Compressor Suction, Airflow = 2,000 CFM (B1HA060)
Outdoor
Temperature
°F
65 26.7 27.6 28.5 29.4 30.3 31.2 32.1 33.0 33.9 34.8 35.7
70 21.9 23.0 24.1 25.2 26.3 27.4 28.5 30.0 31.4 32.8 34.3
75 17.0 18.3 19.7 21.0 22.3 23.7 25.0 27.0 28.9 30.9 32.9
80 12.2 13.7 15.3 16.8 18.4 19.9 21.5 24.0 26.5 29.0 31.4
85 7.3 9.1 10.8 12.6 14.4 16.2 17.9 20.9 24.0 27.0 30.0
90 7.2 8.3 9.4 10.6 11.7 12.8 13.9 17.3 20.6 23.9 27.2
95 7.0 7.5 8.0 8.5 9.0 9.5 9.9 13.6 17.2 20.8 24.4 100 7.2 7.6 8.0 8.3 8.7 9.1 9.5 12.4 15.3 18.2 21.1 105 7.4 7.7 7.9 8.2 8.5 8.7 9.0 11.2 13.4 15.6 17.8 110 7.6 7.8 7.9 8.1 8.2 8.4 8.5 10.0 11.5 13.0 14.4 115 7.8 7.8 7.9 7.9 8.0 8.0 8.1 8.8 9.6 10.3 11.1
55 57 59 61 63 65 67 69 71 73 75
Indoor WB Temperature, °F
TABLE 16: Heating Superheat at Compressor Suction, Airflow = 2,000 CFM (B1HA060)
Indoor DB
Temperature
°F
55 5.5 5.7 6.2 6.8 8.0 9.9 13.1 18.6
70 -----4.88.013.4
80 ------5.611.0
-10 0 10 20 30 40 50 60
Outdoor Temperature, °F
Johnson Controls Unitary Products 11
Page 12
341849-YIM-A-0108
HIGH VOLTAGE CONN.
LOW VOLTAGE CONN.
" DIA. KNOCKOUT
SIDE SUPPLY AIR OPENING
SIDE RETURN
AIR OPENING
LOW VOLTAGE
CONN.
" DIA. KNOCK
HIGH VOLTAGE CONN.
" DIA. KNOCKOUT
" DIA. KNOCKOUT
-
49
(OVERALL)
FRONT
2
1
4
HIGH VOLTAGE
CONN.
KNOCKOUT
" x " DIA.
FRONT
“A”
(OVERALL)
2
COMPRESSOR
SERVICE ACCESS
COMPARTMENT PANEL
UNIT SIZE
036 - 042
048 - 060
HIGH VOLTAGE CONN.
(OVERALL)
UNIT CONDENSATE
CONNECTION
(TRAP REQUIRED)
" NPTI
All dimensions are in inches. They are subject to change without notice. Certified dimensions will be provided upon request.
DIMENSION
“A”
33
41
REFRIGERANT
CONNECTIONS
ELECTRICAL/FILTER
SERVICE ACCESS
COMPARTMENT PANEL
" DIA. KNOCKOUT
6
CONDENSATE DRAIN
" NPTI
BOTTOM SUPPLY
AIR OPENING
CLEARANCES
(Minimum) Front 12" Back 0" Left Side (Filter Access) 24" Right Side 24" Below Unit
Above Unit
1. Units may be installed on combustible floors made from wood or class A, B or C roof covering material.
2. Units must be installed outdoors. Overhanging structures or shrubs should not obstruct outdoor air discharge outlet.
1
2
0" 36"
(For Condenser Air Discharge)
OUTDOOR
COIL
1
SIDE SUPPLY AIR OPENING
BACK
SIDE RETURN
AIR OPENING
2
15
15
1
15
1
4
BOTTOM RETURN
AIR OPENING
FIGURE 4 - Dimensions and Clearances
12 Johnson Controls Unitary Products
Page 13
341849-YIM-A-0108
SEQUENCE OF OPERATION
ANTI-SHORT CYCLE TIMER
This unit has an anti-short cycle timer built in to the defrost control. This timer will not permit the compres­sor to start within five minutes after the completion of the last cycle or power interruption. To bypass the anti­short cycle feature, short the “TEST” pins together for 2 seconds.
The following sequences of operation are based on using a standard single-stage heat pump thermostat.
COOLING OPERATION
WITH POWER TO UNIT AND THERMOSTAT IN COOLING MODE.
1. If the fan switch on the thermostat is in the “ON” posi­tion, the 24 volts at “G” will energize the “K1" relay on the fan control board, close the ”K1" relay contacts, and energize the indoor blower motor. If the fan switch on the thermostat is in the “AUTO” position, the blower will operate only when there is a call for cooling by the thermostat.
2. On a call for cooling, the thermostat will send 24 volts to “Y” and “O” on the fan control board. After the anti-short cycle period is complete ,The 24 volt signal will energize contactor “M1", and the revers­ing valve solenoid. Power will be supplied to the compressor and outdoor fan mo to r, and the revers­ing valve will switch to the cooling position. If the fan switch on the thermostat is on the ”AUTO" posi ­tion, the fan control will energize the indoor blower.
3. When the demand for cooling has been satisfied, the 24 volt “Y” signal is removed and the “M1" con­tactor will be de-energized. If the fan switch on the thermostat is in the ”ON" position, the indoor blower will continue to run. If the fan switch is in the “AUTO” position, the “K1" relay will open and de-energize the indoor blower motor after a 60 second delay,
HEATING OPERATION
WITH POWER TO UNIT AND THERMOSTAT IN HEATING MODE.
1. If the fan switch on the thermostat is in the “ON” posi­tion, the 24 volts at “G” will energize the “K1" relay on the fan control board, close the ”K1" relay contacts, and energize the indoor blower motor. If the fan switch on the thermostat is in the “AUTO” position, the blower will operate only when there is a call for heating by the thermostat.
2. On a call for heating, the thermostat will send 24 volts to “Y” on the fan control board. After the anti-short cycle period is complete, the 24 volts signal will ener­gize contactor coil “M1" and power will be supplied to the compressor and outdoor fan motor. The reversing valve will remain in the heating position. If the fan switch on the thermostat is in the ”AUTO" position, the fan control will energize the indoor blower.
3. For units equipped with supplementary electric heat, if the heat pump cannot meet the demand, the thermostat “W” will send 24 volts to “W2" on the fan control board. This signal will also be sent through the defrost control terminals ”W" and “W1/ 66" and back to the fan control ”W1". This 24 volt signal will energize all stages of electric heat.
4. When the heating demand is satisfied, the electric heat will be de-energized when the 24 volt “W” signal is removed, and the “M1" contactor will be de-energized when the 24 volt ”Y" signal is removed. If the fan switch on the thermostat is in the “ON” position, the indoor blower will continue to run. If the fan switch is in the “AUTO” position, the “K1" relay will open and de-energize the indoor blower motor after the appropriate time delay.
Please refer to Table 17 for more information.
DEFROST OPERATION
The minimum time between defrosts can be field selected at 30, 60 or 90 minutes. The default time is 90 minutes if the jumper is not installed.
Defrost will initiate when the defrost sensor, located on the outdoor coil, senses a temperature below 31°F and when the time since the last defrost is greater than the selected time on the defrost control. The defrost cycle terminates when either the defrost sensor reaches 55°F or the unit has been in defrost mode for 10 min­utes. If the room thermostat opens during defrost, the unit will resume operation in defrost when the thermo­stat re-closes.
During the defrost mode, the defrost control will provide a 24 volt signal from terminal “W1/66" to the fan control terminal ”W1". This signal will energize electric heat stage 1, if the unit is so equipped.
For trouble shooting purposes, the defrost cycle can be manually initiated by shorting the “TEST” pins together for 5 seconds. Defrost will terminate normally during the “TEST” mode.
Johnson Controls Unitary Products 13
Page 14
341849-YIM-A-0108
HEAT PUMP SAFETY SWITCH OPERATION
If the unit is equipped with the field installed upgrade safety package, the refrigeration system will be pro­tected against high or low refrigerant pressure and low indoor coil temperature. If any of these three safety switches opens, the unit will be shut off for the 5 minute anti-short cycle time. Once this has e xpired, a six hour elapsed run timer begins. If a second opening of a safety switch occurs during this six hour period, the compressor will be locked out.
Resetting the lockout function is accomplished by;
ELECTRIC HEAT LIMIT SWITCH OPERATION
The limit switch responds to over temperature condi­tions in the air duct. Opening of the device results in dropping power to the relays. The control logic will also respond by turning off the relays. After four limit cycle trips the unit goes into a 1 hour soft lockout period. If during this period the control “sees” another limit cycle, the unit will go into a hard lockout condition. Once in a hard lockout state, the fan is locked on and the heaters are disabled. Only a power cycle will clear the state.
During the soft lockout period, the fan responds to thermostat input but the heaters are enabled. This is
1. Removing power from the control's thermostat 1st stage (Y) input for a time not to exceed 5 seconds (ON-OFF-ON).
2. Removing power from “R” for more than 2 sec­onds.
to sense a failed heater relay. The limit cycle count is reset at the start of a heat request. If the limit remains open for period of 80 seconds or more, the control is immediately put into a hard lockout condi­tion. Only a power cycle will clear this state.
3. Shorting the “TEST” pins together for more than 2 seconds.
TABLE 17: Thermostat Signals (Three Phase Units)
SIGNAL STATE BOARD FUNCTION
“G”
“G” & “Y” & “O”
“G” & “Y”
“G” & “W”
“G” & “Y” & “W”
“W”
ON FAN INSTANT ON
OFF FAN INSTANT OFF
FAN INSTANT ON
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
COMPRESSOR AND OUTDOOR FAN INSTANT ON (AFTER ANTI-SHORT CYCLE DELAY) REVERSING VALVE ENERGIZED SYSTEM OPERATES IN COOLING
COMPRESSOR AND OUTDOOR FAN INSTANT OFF FAN 60 SEC. DELAY OFF FAN INSTANT ON COMPRESSOR AND OUTDOOR FAN INSTANT ON (AFTER ANTI-SHORT CYCLE DELAY) SYSTEM OPERATES IN HEATING COMPRESSOR AND OUTDOOR FAN INSTANT OFF FAN 60 SEC. DELAY OFF FAN INSTANT ON HEATER BANK 1, 2 & 3 ELEC. HEAT INSTANT ON HEATER BANK 4, 5 & 6 ELEC. HEAT 10 SEC. DELAY ON
HEATER BANK 4, 5 & 6 ELEC. HEAT INSTANT OFF HEATER BANK 1, 2 & 3 ELEC. HEAT 1/2 SEC. DELAY OFF FAN 10 SEC. DELAY OFF
FAN INSTANT ON COMPRESSOR AND OUTDOOR FAN INSTANT ON SYSTEM OPERATES IN HEATING HEATER BANK 1, 2 & 3 ELEC. HEAT INSTANT ON HEATER BANK 4, 5 & 6 ELEC. HEAT 10 SEC. DELAY ON COMPRESSOR AND OUTDOOR FAN INSTANT OFF HEATER BANK 4, 5 & 6 ELEC. HEAT INSTANT OFF HEATER BANK 1, 2 & 3 ELEC. HEAT 1/2 SEC. DELAY OFF FAN 60 SEC. DELAY OFF
FAN INSTANT ON HEATER BANK 1, 2 & 3 ELEC. HEAT INSTANT ON HEATER BANK 4, 5 & 6 ELEC. HEAT 10 SEC. DELAY ON
HEATER BANK 4, 5 & 6 ELEC. HEAT INSTANT OFF HEATER BANK 1, 2 & 3 ELEC. HEAT 1/2 SEC. DELAY OFF FAN 10 SEC. DELAY OFF
14 Johnson Controls Unitary Products
Page 15
341849-YIM-A-0108
MAINTENANCE
NORMAL MAINTENANCE
Prior to any of the following m aintenance pro­cedures, shut off all power to the unit, to avoid personal injury.
Periodic maintenance consists of changing or cleaning filters and general cleaning of the outdoor coil.
FILTERS - Inspect once a month. Replace Dis posable or clean Permanent Type as necessary. DO NOT replace Permanent Type with Disposable.
MOTORS - Indoor and outdoor fan motors are perma­nently lubricated and require no maintenance.
OUTDOOR COIL - Dirt should not be allowed to accu­mulate on the outdoor coil surf ace or oth er parts in th e air circuit. Cleaning should be as often as n eces sary t o keep the coil clean. Use a brush, vacuum cleaner attachment, or other suitable means. If water is used to clean the coil, be sure that the power to the unit is shut off prior to cleaning.
Exercise care when cleaning the coil so that the coil fins are not damaged.
Do not permit the hot condenser air discharge to be obstructed by overhangin g structures or shrubs.
Johnson Controls Unitary Products 15
Page 16
341849-YIM-A-0108
DETAIL A
COMPR RELAY
222/Y
M1
M
FOR DEFROST CONTROL 031-09104-000A SEE DETAIL A
DEFROST CONTROL 031-01268-000B
BLU
DS
BLU
DFST STAT
R
C
FIGURE 5 - Typical Wiring Diagram (230-3-60 Power Supply)
16 Johnson Controls Unitary Products
Page 17
341849-YIM-A-0108
FIGURE 6 - Typical Wiring Diagram BHA Models (460-3-60 and 575-3-60 Power Supply)
Johnson Controls Unitary Products 17
Page 18
341849-YIM-A-0108
CB CCH COMPR DS F1 F2 F3 F4 F5 F6 F7 F8 F9 F24 FS HP HTR 1 HTR 2 HTR 3 HTR 4 HTR 5 HTR 6 K1 K2 K3 K7 LP LS M1 M2 M3 PTCR RC1/RC2 RC1 RC2 RC3 RVS S2/P2 S3/P3 S4/P4 S3/P3 T1 TB2
CIRCUIT BREAKER 24V, 3 AMP CRANKCASE HEATER (OPTIONAL) COMPRESSOR DEFROST SENSOR, CLOSES @ 31°F, OPENS @ 55°F. FUSES, LINE VOLTAGE - 60 AMP (10, 15, 20 & 25 KW ELEC HEAT) FUSES, LINE VOLTAGE - 30 AMP (10, 15, 20 & 25 KW ELEC HEAT) FUSES, LINE VOLTAGE - 30 AMP (20, 25 KW ELEC HEAT) FUSE 24V SECONDARY, 5 AMP FREEZESTAT SWITCH (OPTIONAL ACCESSORY) OPEN @ 26° F HIGH PRESSURE SWITCH (OPTIONAL ACCESSORY) OPENS @ 280 PSIG ELECTRIC HEATER (OPT. ACCSSRY: ALL KW ELEC HEAT) ELECTRIC HEATER (OPT. ACCSSRY: 7.5, 10, 15, 20 & 25 KW ELEC HEAT) ELECTRIC HEATER (OPT. ACCSSRY: 20 & 25 KW ELEC HEAT) ELECTRIC HEATER (OPT. ACCSSRY: 15, 20 & 25 KW ELEC HEAT) ELECTRIC HEATER (OPT. ACCSSRY: 20 & 25 KW ELEC HEAT) ELECTRIC HEATER (OPT. ACCSSRY: 20 & 25 KW ELEC HEAT) RELAY INDOOR FAN MOTOR RELAY ELECTRIC HEATER RELAY ELECTRIC HEATER, 24 VDC COIL RELAY LIMIT TRIP, 25 VDC COIL LOW PRESSURE SWITCH (OPTIONAL ACCESSORY) OPEN @ 7 PSIG LIMIT SWITCH, ELECTRIC HEAT (PART OF ELEC HEAT ACCESSORY) CONTACTOR, COMPRESSOR & OUTDOOR FAN CONTACTOR, ELECTRIC HEAT, 230V COIL CONTACTOR, ELECTRIC HEAT, 230V COIL START ASSIST (OPTIONAL DEVICE) COMPRESSOR START & OUTDOOR FAN RUN CAPACITOR COMPRESSOR START CAPACITOR (ALTERNATE) OUTDOOR FAN RUN CAPACITOR (ALTERNATE) INDOOR FAN RUN CAPACITOR REVERSING VALVE SOLENOID SOCKET/PLUG CONNECTION ON FAN CONTROL BOARD, LOW VOLTAGE SOCKET/PLUG CONNECTION ON FAN CONTROL BOARD, LINE VOLTAGE SOCKET/PLUG CONNECTION ON ID FAN MOTOR, 24V SOCKET/PLUG CONNECTION ON ID FAN MOTOR, 230V TRANSFORMER, 24V, 40 VA TERMINAL BLOCK ECM MOTOR "SPEED" CONNECTIONS IDENTIFIED TERMINAL ON RUN CAPACITOR ROOM THERMOSTAT 24V CONNECTIONS TB1 ON FAN/ELEC HEAT CONTROL BOARD FACTORY WIRING AND DEVICES OPTIONAL WIRING AND DEVICES FIELD WIRING
FIGURE 7 - Typical Wiring Diagram Legend (See Pages 16 and 17)
1. ALL FIELD WIRING TO BE ACCOMPLISHED FOLLOWING CITY, LOCAL AND/OR NATIONAL CODES IN EFFECT AT TIME OF INSTALLATION OF THIS UNIT.
2. CAUTION: LABEL ALL WIRES PRIOR TO DISCONNECTION WHEN SERVICING CONTROLS. WIRING ERRORS CAN CAUSE IMPROPER AND DANGEROUS OPERATION. IF ANY OF THE WIRE AS SUPPLIED WITH THIS UNIT MUST BE REMOVED, IT MUST BE REPLACED WITH TYPE 105° C, 600V WIRE OR EQUIVALENT CLEARLY RENUMBERED FOR IDENTIFICATION. VERIFY PROPER OPERATION AFTER SERVICING.
3. MOTORS ARE INHERENTLY PROTECTED.
4. UNIT FACTORY WIRED FOR 230 VOLT OPERATION. FOR 208 VOLT OPERATION MOVE '108/PR' WIRE FROM 240V TO 208V ON TRANSFORMER T1.
5. SEE UNIT NAMEPLATE FOR MAXIMUM FUSE SIZE AND MINIMUM CIRCUIT AMPACITY.
6. SELECT INDOOR BLOWER SPEED TO OBTAIN APPROX 400 CFM/TON IN COOLING.
7. IF OPTIONAL SAFETY SWITCH KIT IS INSTALLED, WIRE 219/BK IS REMOVED.
8. WIRE 204/BR IS REMOVED WHEN ELECTRIC HEAT IS INSTALLED.
9. ELECTRIC HEAT ACCESSORY WITH DUAL POINT SUPPLY POWER. SEE DETAIL A
10. SHUNT CONTACT ALSO USED WITH CRANKCASE HEATER. (OPTIONAL)
FIGURE 8 - Typical Wiring Diagram Notes (See Pages 16 and 17)
18 Johnson Controls Unitary Products
Page 19
341849-YIM-A-0108
Johnson Controls Unitary Products 19
Page 20
Subject to change without notice. Printed in U.S.A. 341849-YIM-A-0108 Copyright © 2007 by Johnson Controls, Inc. All rights reserved. Supersedes: 66269-YIM-A-0104/035-16004-002-A-010 4
Johnson Controls Unitary Products
5005 York Drive
Norman, OK 73069
Loading...