Controls Group 507 E. Michigan Street
P.O. Box 423, Milwaukee, WI 53202
Code No. LIT-1928250
AS-XFR Series
3/4 or 1-1/2 in. (19.0 or 38.1 mm) |
|
3/4 in. (19.0 mm) |
Knockout |
|
Knockout |
|
|
|
|
|
|
Power Switch
Wire Passage |
7-3/8 |
Knockout |
4-5/8 |
|
6-3/4 |
XFR100
For Optional
Mount Method /16 in. (4.76 mm)
DIN Rail Clamp
Box Fingers
DIN Rail |
XFR100 |
AS-XFR Transformer Module
Selection Chart
Description
The AS-XFR Series Transformer Module is a UL Class 2 device used to power digital controllers and input/output loads. It provides 120 VAC to 24 VAC isolation. Three different models are available (see selection chart below), all of which include a split-bobbin for added noise immunity and a manually resetable breaker on the secondary connection. The secondary connection includes a modular connector for use with AHU controllers and Companion products. Ground wires are electrically and mechanically connected to the transformer frame.
The XFR100 is a 100 VA transformer pre-mounted in an EN-ENC100 enclosure. It includes a power switch and a utility outlet. The enclosure can be vertically mounted with a DIN rail or directly mounted to a wall, and supports multiple 3/4 in. and 1-1/2 in. conduit connections.
The XFR010 is a 100 VA transformer without an enclosure. It can be used in any appropriate UL-listed enclosure and is used as a replacement transformer for the XFR100 or in EWC35/45 Series enclosures.
The XFR050 is a 50 VA transformer without an enclosure. It can be used in any appropriate UL-listed enclosure and is used as a replacement transformer for the EWC15/25 Series enclosures.
Features
•choice of 50 VA or 100 VA power rating
•color-coded wire leads for simple installation
•split-bobbin design for better noise immunity
•resetable breaker on the secondary that trips on shorts or overloads
Applications
XFR Series Transformers are used to power digital controllers and input/output loads. To determine which transformer is correct for your application, see mounting and wiring instructions for individual controllers.
To Order
Specify the code number from the following selection chart.
|
Power |
|
Primary |
|
Secondary |
|
|
Code Number |
|
Electrical |
|
Electrical |
Enclosure |
||
Rating |
Voltage |
Voltage |
|||||
|
Connection |
Connection |
|
||||
|
|
|
|
|
|||
|
|
|
|
|
|
|
|
AS-XFR100-1 |
100 VA |
|
18 AMG, 12 in., |
|
16 AMG, 20 in., brown, orange, MOLEX connector |
AS-ENC100 |
|
|
|
|
|
|
|
||
AS-XFR010-1 |
100 VA |
120 |
black, white, green/yellow, |
24 |
18 AMG, 20 in., brown, orange, green/yellow, |
None |
|
|
|
|
Stripped 3/8 in. |
|
MOLEX connector |
||
AS-XFR050-0 |
50 VA |
|
|
||||
|
|
|
|||||
|
|
|
|
|
|
|
Specifications
AS-XFR Series Transformer Module
Electrical Rating |
|
100 VA, primary, 120 VAC/60 Hz |
|
|
secondary, 24 VAC/60 Hz |
||
|
|
||
|
|
|
|
Operating Conditions |
|
0 to 50°C (32 to 120°F) |
|
|
|
|
|
Agency Compliance |
|
UL 864/916 and CSA C22.2 No. 205 |
|
|
|
|
|
Agency Listings |
|
UL Listed and CSA Certified |
|
|
|
|
|
|
AS-XFR100-1 6.75 in. x 7.38 |
in. x 4.63 in. |
|
Dimensions H x W x D |
|
|
|
AS-XFR010-1 3.75 in. x 3.75 |
in. x 3.50 in. |
||
|
|
|
|
|
AS-XFR050-0 |
2.80 in. x 4.50 |
in. x 3.25 in. |
|
|
|
|
|
AS-XFR100-1 |
3.05 kg (6.7lbs.) |
|
Shipping Weight |
|
|
|
AS-XFR010-1 |
2.15 kg (4.7 lbs.) |
||
|
|
|
|
|
AS-XFR050-0 |
1.2 kg (2.6 lbs) |
|
|
|
|
|
The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond t hese specifications, consult the local Johnson
Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. |
© 06/01 Johnson Controls, Inc |
1/1