Jewell Instruments C901, C902 Specifications

Model C901, C902 Tulip 4-20mA
±
±
±
1
2
3
*Specifications subject to change without notice on account of continued development
; 1Resolution
calculated a
t .003 mA;
2Linear scale factor
The model C901 and C902 Tulip Uniaxial Clinometers deliver the same performance as our model A900-series, but with 4-20mA output. Units are available in horizontal (C901) or vertical (C902) mounting packages. The Tulip conveniently operates as a 2-wire 4-20mA current loop, and also includes an on-board thermistor for temperature measurement. Use the Tulip with industrial PLC’s, platform position and control, OEM assemblies, and all other applications with 4-20mA output requirements.
High-Gain Standard Wide-Angle Angular Range Resolution Repeatability Scale Factor* Non-Linearity Output 4-20mA Channels Tilt, Thermistor Kz Coefficient (deg/C) 10-20 arcsec/C (typical) Ks Coefficient (%/C) 0.03%/C (typical) Time Constant 0.15 sec Natural Frequency 10 Hz Output Impedance 270 ohms, short circuit protected Power (0.02 Ampere x R + 10 VDC) < Vs < 29 VDC Environmental -40 to +85 C operating and storage. 0-90% humidity Dimensions See Drawing (page2) Materials Glass electrolytic sensor, fiberglass PCB
10°
0.005° 0.01° 0.02°
0.01° 0.02° 0.04°
1.25°/mA 3.125°/mA 6.25°/mA
1% 2.5% 7%
25°
50°
calculated from BFSL through calibration curve; 3Linearity calculated as max % deviation from BFSL. 0.05% linearity achievable using a polynomial
Ordering Code: Pin-out/Wiring:
Jewell Instruments LLC 850 Perimeter Road, Manchester, NH 03103
sales@jewellinstruments.com • www.jewellinstruments.com • Tel (800) 227-5955
Pin Color Function
1 Red V+
2 Black GND
3 Blue Temp Excitation
4 Yellow/Orange
Temp Out
5 White Temp Return
L00254 Rev. A
Model C901, C902 Tulip 4-20mA
C901Tulip 4
-
20mA
Clino
meter (Horizontal)
C902
Tulip 4
-
20mA Clinometer (Vertical)
Circuit Diagram
Thermistor Output
Dimensions and Wiring:
1)
V
SUPPLY
2) GROUND
3) TEMPERATURE EXCITATION
4) TEMPERATURE OUT
5) TEMPERATURE RETURN
1)
SUPPLY
V
2) GROUND
3) TEMPERATURE EXCITATION
4) TEMPERATURE OUT
5) TEMPERATURE RETURN
Resistance (ohms) vs. Temp
(U.S. Sensors LR252B1K, Type-B Curve)
Degrees Celsius (°C)
T = 1/[A + B Ln(RT3) + C Ln(RT3)^3 + D Ln(RT3)^5] – 273.15
where T is in degrees Celsius and RT3 = thermistor resistance.
A = 7.34862E-04; B = 3.38205E-04; C = -1.30862E-07; D = 1.21751E-09