INSTALLATION
Built-In 27²²²² &30²
²
²²
INSTRUCTIONS
Electric Wall Ovens
27² SINGLE WALL OVEN
111/4² Dia. Conduit Access Hole*
11/8² ToCenterOfHole From Side Wall and Back Wall
25/8² Plywood Floor (Must Support 142 lbs.)
DIMENSIONS
in cm
A 27 MIN 68.58
B 24 MIN 60.96
C 277/16+
D 23 1/2 MIN 59.69
E251/2+
F 29 73.66
G 26 3/4 67.95
H 247/16 62.07
I 4 to 33 10.2 to 83.8
1/16 69.69
1/16 64.77
403 WEST FOURTH STREET, NORTH D NEWTON, IA 50208
27² DOUBLE WALL OVEN
111/4² Dia. Conduit Access Hole*
11/8² ToCenter Of Hole F rom Side Wall and Back Wall
25/8² Plywood Floor (Must Support 250 lbs.)
DIMENSIONS
in cm
A 27 MIN 68.58
B 24 MIN 60.96
C495/8+
D 23 1/2 MIN 59.69
E251/2+
F 51 3/16 130.02
G 26 3/4 67.95
H 247/16 62.07
I 4 to 12 10.2 to 30.5
1/16 126.05
1/16 64.77
30² SINGLE WALL OVEN
111/4² Dia. Conduit Access Hole*
11/8² ToCenterOfHole From Side Wall and Back Wall
25/8² Plywood Floor (Must Support 142 lbs.)
DIMENSIONS
in cm
A 30 MIN 76.20
B 24 MIN 60.96
C 277/16+
D 23 1/2 MIN 59.69
E 283/16+
F 29 73.66
G 29 3/4 75.57
H 247/16 62.07
I 4 to 33 10.2 to 83.8
1/16 69.69
1/16 71.60
111/4² Dia. Conduit Access Hole*
25/8² Plywood Floor (Must Support 250 lbs.)
A 30 MIN 76.20
B 24 MIN 60.96
C495/8+
D 23 1/2 MIN 59.69
E 283/16+
F 51 3/16 130.02
G 29 3/4 75.57
H 247/16 62.07
I 4 to 12 10.2 to 30.5
30² DOUBLE WALL OVEN
11/8² ToCenter Of Hole F rom Side Wall and Back Wall
DIMENSIONS
in cm
1/16 126.05
1/16 71.60
NOTES: Do not block air intake slots along bottom of oven. Wall oven must be on separate 120/240 or 120/208 Volt 60 Hz AC circuits.
8101P418-60
(10-01-00)
CAUTION
For European style cabinets (flush front) the required
clearance for operation of the oven door is minimum
spacing of 7/8² between the cutout and the door, hinge
or drawer of the cabinet.
Some built-in cabinets may not be wide enough, dueto
their construction, to allow this installation.
Electrical Connections
Unit to be properly circuit protected and wired according
to local electrical code and National Electrical Code.
It is advisable that the electrical wiring and hookup be
accomplished by a competent electrician.
120/240 VAC or 120/208 VAC 60 Hz. See serial plate on
front of unit for power requirements.
1. Cut hole in cabinet to mount oven. Cutout in cabinet
should be level and straight.
NOTE: There are no provisions to level the unit after it
is installed. An oven that is not level could cause poor
baking results.
2. Install plywood floor as shown.
3. Place oven in cabinet.
4. Oven mounting holes are provided in side trim. Pre-drill
holes in cabinet for attachment screws using 1/8² drill.
Attach unit to the cabinet with four No. 8x1² screws
supplied with unit inside of envelope containing these
instructions.
5. See instructions at right for electrical hook-up.
6. See Use and Care Manual for operating instructions.
Installing Bottom Trim Piece
The neutral of this unit is grounded to the frame through
the green or solid grounding wire. (The green and the
white wires are twisted together at the termination of the
conduit.) If used on new branch-circuit installations (1996
NEC), mobile homes, recreational vehicles, or in an area
where local codes prohibit grounding through the neutral
conductor, untwist or disconnect the green wire and
connect the green wire to ground in accordance with local
code. Connect the white neutral to the service neutral.
Connect all wires to the branch circuit with approved
connectors. Use copper or aluminum wire. If aluminum
wire is used, use connectors recognized for joining
aluminum to copper.
The chart below recommends the minimum circuit
protection and wire size if the appliance is the only unit on
the circuit.
K.W.RATING
ON SERIALPLATE
0-- 4.8
4.9 -- 6.9
7.0 -- 9.9
10.0 -- 11.9
12.0 -- 14.9
RECOMMENDED MINIMUM
CIRCUIT PROTECTION
IN AMPERS
20
30
40
50
60
WIRE SIZE
(AWG)
12
10
8
8
6
Service
Interrupt the source of electricity to the unit when
attempting to repair or service the oven. Failure to do this
could result in a dangerous or even fatal shock.
IMPORTANT - SAVE FOR LOCAL ELECTRICAL INSPECTOR’S USE