For questions about features, operation/performance, parts, accessories, or service in the U.S.A., call:
1-800-JENNAIR (1-800-536-6247) or visit our website at www.jennair.com.
In Canada, call: 1-800-807-6777, or visit our website at www.jennair.ca.
Instructions d’installation et Guide d’utilisation et d’entretien
Au Canada, pour assistance, installation ou service, composez le 1-800-807-6777 ou visitez notre site web à www.jennair.ca.
Table of Contents/Table des matières ..................2
IMPORTANT: READ AND SAVE THESE INSTRUCTIONS.
FOR RESIDENTIAL USE ONLY.
IMPORTANT : LIRE ET CONSERVER CES INSTRUCTIONS.
POUR UTILISATION RÉSIDENTIELLE UNIQUEMENT.
LI3URB/W10274314C
TABLE OF CONTENTS
TABLE DES MATIÈRES
RANGE HOOD SAFETY .................................................................2
Your safety and the safety of others are very important.
We have provided many important safety messages in this manual and on your appliance. Always read and obey all safety
messages.
This is the safety alert symbol.
This symbol alerts you to potential hazards that can kill or hurt you and others.
All safety messages will follow the safety alert symbol and either the word “DANGER” or “WARNING.”
These words mean:
You can be killed or seriously injured if you don't immediately
DANGER
WARNING
All safety messages will tell you what the potential hazard is, tell you how to reduce the chance of injury, and tell you what can
happen if the instructions are not followed.
follow instructions.
can be killed or seriously injured if you don't
You
instructions.
follow
2
IMPORTANT SAFETY INSTRUCTIONS
WARNING: TO REDUCE THE RISK OF FIRE, ELECTRIC
SHOCK, OR INJURY TO PERSONS, OBSERVE THE
FOLLOWING:
■ Use this unit only in the manner intended by the
manufacturer. If you have questions, contact the
manufacturer.
■ Before servicing or cleaning the unit, switch power off at
service panel and lock the service disconnecting means to
prevent power from being switched on accidentally. When
the service disconnecting means cannot be locked,
securely fasten a prominent warning device, such as a tag,
to the service panel.
■ Installation work and electrical wiring must be done by
qualified person(s) in accordance with all applicable codes
and standards, including fire-rated construction.
■ Do not operate any fan with a damaged cord or plug.
Discard fan or return to an authorized service facility for
examination and/or repair.
■ Sufficient air is needed for proper combustion and
exhausting of gases through the flue (chimney) of fuel
burning equipment to prevent backdrafting. Follow the
heating equipment manufacturer's guideline and safety
standards such as those published by the National Fire
Protection Association (NFPA), the American Society for
Heating, Refrigeration and Air Conditioning Engineers
(ASHRAE), and the local code authorities.
■ When cutting or drilling into wall or ceiling; do not damage
electrical wiring and other utilities.
■ Ducted fans must always be vented outdoors.CAUTION: For general ventilating use only. Do not use
to exhaust hazardous or explosive materials and vapors.
CAUTION: To reduce risk of fire and to properly exhaust
air, be sure to duct air outside - do not vent exhaust air into
spaces within walls or ceilings, attics or into crawl spaces,
or garages.
WARNING: TO REDUCE THE RISK OF FIRE, USE ONLY
METAL DUCTWORK.
WARNING: TO REDUCE THE RISK OF A RANGE TOP
GREASE FIRE:
■ Never leave surface units unattended at high settings.
Boilovers cause smoking and greasy spillovers that may
ignite. Heat oils slowly on low or medium settings.
■ Always turn hood ON when cooking at high heat or when
■ Clean ventilating fans frequently. Grease should not be
allowed to accumulate on fan or filter.
■ Use proper pan size. Always use cookware appropriate for
the size of the surface element.
WARNING: TO REDUCE THE RISK OF INJURY TO
PERSONS IN THE EVENT OF A RANGE TOP GREASE
FIRE, OBSERVE THE FOLLOWING:
■ SMOTHER FLAMES with a close fitting lid, cookie sheet, or
metal tray, then turn off the burner. BE CAREFUL TO
PREVENT BURNS. If the flames do not go out
immediately, EVACUATE AND CALL THE FIRE
DEPARTMENT.
■ NEVER PICK UP A FLAMING PAN - you may be burned.
■ DO NOT USE WATER, including wet dishcloths or towels -
a violent steam explosion will result.
■ Use an extinguisher ONLY if:
– You know you have a class ABC extinguisher, and you
already know how to operate it.
– The fire is small and contained in the area where it
started.
– The fire department is being called.
– You can fight the fire with your back to an exit.
a
Based on "Kitchen Fire Safety Tips" published by NFPA.
■ WARNING: To reduce the risk of fire or electrical shock,
do not use this fan with any solid-state speed control
device.
a
READ AND SAVE THESE INSTRUCTIONS
3
INSTALLATION REQUIREMENTS
Tools and Parts
Gather the required tools and parts before starting installation.
Read and follow the instructions provided with any tools listed
here.
Tools n e ed e d
■ Level
■ Drill with 1¼" (3.0 cm), ³⁄₈" (9.5 mm), and ⁵⁄₁₆" (7.9 mm)
drill bits
■ Pencil
■ Wire stripper or utility knife
■ Tape measure or ruler
■ Pliers
■ Caulking gun and weatherproof caulking compound
■ Vent clamps
■ Jigsaw or keyhole saw
■ Flat-blade screwdriver
■ Metal snips
■ Phillips screwdriver
■ Metric Allen wrench set
Parts needed
■ Home power supply cable
■ ½" (12.7 mm) UL listed or CSA approved strain relief
■ 3 UL listed wire connectors
For vented installations, you will also need:
■ 1 wall or roof cap
■ Metal vent system
For non-vented (recirculating) installations, you will also
need:
■ Recirculation Kit Part Number W10272062 for non-vented
(recirculating) installations only. See “Assistance or Service”
section to order.
■ 8" (20.0 cm) dia. round metal vent duct - length required is
determined by ceiling height.
Parts supplied
Remove parts from packages. Check that all parts are included.
■ Hood canopy assembly with ventilator and light bulbs
installed
■ Vent transition with back draft dampers installed
■ Metal grease filter
■ Vent cover support bracket
■ Mounting template
■ 2-piece vent cover
■ 8 - 4 x 8 screws
■ 6 - 5 x 45 mm mounting screws
■ 3¼" x 10" (8.3 x 25.4 cm) rectangular damper
■ 2 - 8 x 40 mm wall anchors
■ 4 - 10 x 50 mm wall anchors
Location Requirements
IMPORTANT: Observe all governing codes and ordinances.
Have a qualified technician install the range hood. It is the
installer's responsibility to comply with installation clearances
specified on the model/serial rating plate. The model/serial rating
plate is located behind the left filter on the rear wall of the vent
hood.
Canopy hood location should be away from strong draft areas,
such as windows, doors and strong heating vents.
Cabinet opening dimensions that are shown must be used. Given
dimensions provide minimum clearance.
Grounded electrical outlet is required. See “Electrical
Requirements” section.
The canopy hood is factory set for venting through the roof or
wall. For non-vented (recirculating) Installation see “Connect Vent
System” section. Recirculation Kit Part Number W10272062 is
available from your dealer or an authorized parts distributor.
All openings in ceiling and wall where canopy hood will be
installed must be sealed.
For Mobile Home Installations
The installation of this range hood must conform to the
Manufactured Home Construction Safety Standards, Title 24
CFR, Part 328 (formerly the Federal Standard for Mobile Home
Construction and Safety, Title 24, HUD, Part 280) or when such
standard is not applicable, the standard for Manufactured Home
Installation 1982 (Manufactured Home Sites, Communities and
Setups) ANSI A225.1/NFPA 501A, or latest edition, or with local
codes.
Product Dimensions
10¹⁄₂"
(26.7 cm)
13"
(33.0 cm)
*43³⁄₄" (111.1 cm) min.
56³⁄₄" (144.1 cm) max.
**43³⁄₄" (111.1 cm) min.
53" (134.6 cm) max.
15¹⁄₄"
(38.7 cm)
26"
(66.0 cm)
20¹⁄₂"
32"
(81.3 cm)
*For non-vented (recirculating) installations
**For vented installations
(52.1 cm)
4
Cabinet Dimensions
10" (25.4 cm) min.
13" (33.0 cm) max.
9¹⁄₂" (24.1 cm)
10" (25.4 cm) min.
13" (33.0 cm) max.
Side
cabinet
32" (81.3 cm)
"X"
bottom of
canopy
to cooking
surface
*For non-vented (recirculating) installations
IMPORTANT:
Minimum distance "X": 18" (45.7 cm) from electric cooking
surface.
Minimum distance "X": 22" (55.9 cm) from gas cooking
surfaces.
Suggested maximum distance "X": 24" (61.0 cm)
For vented installations, the chimneys can be adjusted for
ceilings between 7’ 11" (2.4 m) and 9' 3" (2.8 m).
For non-vented (recirculating) installations, the chimneys can
be adjusted for ceilings between 7’ 11" (2.4 m) and 9' 7" (2.9 m).
*NOTE: The range hood chimneys are adjustable and designed
to meet varying ceiling or soffit heights depending on the
distance “X” between the bottom of the range hood and the
cooking surface. For higher ceilings, a Chimney Extension Kit
Part Number W10272075 (stainless) or W10272074 (white) is
available from your dealer or an authorized parts distributor. The
chimney extension replaces the upper chimney shipped with the
range hood.
2" (5.1 cm) min.
9" (22.9 cm) min.*
17" (43.2 cm)*
Centerline
Cooking surface
Vent and power
supply cable
entry location
Side
cabinet
Venting Requirements
■ Vent system must terminate to the outside, except for non-
vented (recirculating) installations.
■ Do not terminate the vent system in an attic or other enclosed
area.
■ Do not use 4" (10.2 cm) laundry-type wall caps.
■ Use metal vent only. Rigid metal vent is recommended. Do
not use plastic or metal foil vent.
■ The length of vent system and number of elbows should be
kept to a minimum to provide efficient performance.
For the most efficient and quiet operation:
■ Use no more than three 90° elbows.
■ Make sure there is a minimum of 24" (61 cm) of straight vent
between the elbows if more than 1 elbow is used.
■ Do not install 2 elbows together.
■ Use clamps to seal all joints in the vent system.
■ The vent system must have a damper. If the roof or wall cap
has a damper, do not use the damper supplied with the range
hood.
■ Use caulking to seal exterior wall or roof opening around the
cap.
■ The size of the vent should be uniform.
Cold weather installations
An additional back draft damper should be installed to minimize
backward cold air flow. A thermal break should be installed to
minimize conduction of outside temperatures as part of the vent
system. The damper should be on the cold air side of the thermal
break.
The break should be as close as possible to where the vent
system enters the heated portion of the house.
Makeup air
Local building codes may require the use of makeup air systems
when using ventilation systems greater than specified CFM of air
movement. The specified CFM varies from locale to locale.
Consult your HVAC professional for specific requirements in your
area.
Venting Methods
This range hood is factory set for 8" (20.3 cm) round venting
through the roof or wall. An 8" (20.3 cm) round vent system is
needed for installation (not included). To vent through the wall, a
90° elbow is needed.
This range hood can also be set for 3¼" x 10" (8.3 x 25.4 cm)
rectangular venting out the back using the 3¼" x 10" (8.3 x
25.4 cm) rectangular damper (supplied). See the “Connect Vent
System” section for details for installing the damper and vent
system.
NOTE: Flexible vent is not recommended. Flexible vent creates
back pressure and air turbulence that greatly reduce
performance.
NOTE: This hood can be installed without the chimney covers
when venting directly out the back or when using the recirculation
kit with the top grill cap. See “For non-vented (recirculating)
installations without vent only:” section.
5
For non-vented (recirculating) installations
If it is not possible to vent cooking fumes and vapors to the
outside, the hood can be used in the non-vented (recirculating)
version, fitting a charcoal filter and the deflector for installations
using vent covers or fitting a charcoal filter and top grille cap for
installations without the vent covers.
Roof VentingWall VentingRear Venting
A
Example Vent System
90 elbow
2 ft
(0.6 m)
6 ft (1.8 m)
Wall cap
B
B
B
A
A
A. Roof cap
B. 8" (20.3 cm)
round vent
Non-vented
(recirculating) with
vent covers
A. Wall cap
B. 8" (20.3 cm)
round vent
without vent covers
A. Wall cap
B. 3¼" x 10" (8.3 x
25.4 cm) vent
Non-vented
(recirculating)
A
B
A. Deflector
B. 8" (20.3 cm)
round vent
A
A. Top grille cap
Calculating Vent System Length
To calculate the length of the system you need, add the
equivalent feet (meters) for each vent piece used in the system.
Vent piece8" (20.3 cm) round
45° elbow2.5 ft
(0.8 m)
The following example falls within the maximum vent length of
35 ft (10.7 m).
1 - 90° elbow= 5.0 ft (1.5 m)
1 - wall cap= 0.0 ft (0.0 m)
8 ft (2.4 m) straight= 8.0 ft (2.4 m)
System length= 13 ft (3.9 m)
Electrical Requirements
Observe all governing codes and ordinances.
Ensure that the electrical installation is adequate and in
conformance with National Electrical Code, ANSI/NFPA 70 (latest
edition), or CSA Standards C22.1-94, Canadian Electrical Code,
Part 1 and C22.2 No. 0-M91 (latest edition) and all local codes
and ordinances.
If codes permit and a separate ground wire is used, it is
recommended that a qualified electrician determine that the
ground path is adequate.
A copy of the above code standards can be obtained from:
National Fire Protection Association
One Batterymarch Park
Quincy, MA 02269
CSA International
8501 East Pleasant Valley Road
Cleveland, OH 44131-5575
■ A 120 Volt, 60 Hz., AC only, 15-amp, fused electrical circuit is
required.
■ If the house has aluminum wiring, follow the procedure
below:
1. Connect a section of solid copper wire to the pigtail
leads.
2. Connect the aluminum wiring to the added section of
copper wire using special connectors and/or tools
designed and UL listed for joining copper to aluminum.
Follow the electrical connector manufacturer's recommended
procedure. Aluminum/copper connection must conform with
local codes and industry accepted wiring practices.
■ Wire sizes and connections must conform with the rating of
the appliance as specified on the model/serial rating plate.
The model/serial plate is located behind the filter on the rear
wall of the range hood.
■ Wire sizes must conform to the requirements of the National
Electrical Code, ANSI/NFPA 70 (latest edition), or CSA
Standards C22. 1-94, Canadian Electrical Code, Part 1 and
C22.2 No. 0-M91 (latest edition) and all local codes and
ordinances.
90° elbow5.0 ft
(1.5 m)
Maximum equivalent vent length is 35 ft (10.7 m).
6
INSTALLATION INSTRUCTIONS
Prepare Location
■ It is recommended that the vent system be installed before
hood is installed.
■ Before making cutouts, make sure there is proper clearance
within the ceiling or wall for exhaust vent.
■ Check your ceiling height and the hood height maximum
before you select your hood.
1. Disconnect power.
2. Determine which venting method to use: roof, wall, or non-
vented.
3. Select a flat surface for assembling the range hood. Place
covering over that surface.
8. Mark centers of the fastener locations through the template
to the wall. For rear venting through the wall, mark the
opening for the 3¼" x 10" (8.3 x 25.4 cm) rectangular vent.
IMPORTANT: All screws must be installed into wood. If there
is no wood to screw into, additional wall framing supports
may be required.
Remove the template.
9. Drill ³⁄₁₆" (4.8 mm) pilot holes at all locations where screws are
being installed into wood.
10. Install the 2 - 5 x 45 mm mounting screws. Leave a
¹⁄₄" (6.4 mm) gap between the wall and the back of the
screw head to slide range hood into place.
WARNING
Excessive Weight Hazard
Use two or more people to move and install
range hood.
Failure to do so can result in back or other injury.
4. Using 2 or more people, lift range hood onto covered surface.
Range Hood Mounting Screws Installation
5. Determine and mark the centerline on the wall where the
canopy hood will be installed.
6. Select a mounting height between a minimum of
18" (45.7 cm) for an electric cooking surface or a minimum of
22" (55.9 cm) for a gas cooking surface, and a suggested
maximum of 24" (61.0 cm) above the range to the bottom of
the hood. Mark a reference line on the wall.
7. Tape template in place, aligning the template centerline and
bottom of template with hood bottom line and with the
centerline marked on the wall.
1. Attach vent cover bracket to wall flush to the ceiling using
2 - 5 x 45 mm screws.
A
B
C
A. Ceiling
B. Wall
C. Centerline
A. Centerline
B. Mounting height reference
Complete Preparation
1. Determine and make all necessary cuts in the wall for the vent
system. Install the vent system before installing the hood. See
“Venting Requirements” section.
2. Determine the required height for the home power supply
cable and drill a 1¼" (3.2 cm) hole at this location.
3. Run the home power supply cable according to the National
B
Electrical Code or CSA Standards and local codes and
ordinances. There must be enough ½" conduit and wires from
the fused disconnect (or circuit breaker) box to make the
connection in the hood’s electrical terminal box.
NOTE: Do not reconnect power until installation is complete.
4. Use caulk to seal all openings.
7
Connect Vent System - For Rear Venting Installation Only
B
This range hood can be set for rear venting using the 3¼" x 10"
(8.3 x 25.4 cm) rectangular damper (supplied).
1. Using 2 or more people, set range hood onto its back on a
covered surface.
2. Push in the bottom of the center glass to unlatch, and lift to
open. Remove the 2 screws that hold it to the canopy. Set the
glass cover and the mounting screws aside.
A
6. Remove the 4 screws holding the blower motor to the canopy
top. Push blower up to release the mounting tabs from the
keyhole slots. Remove blower motor. Set blower motor and
mounting screws aside.
A
B
A. Remove these screws.
3. Remove metal filter. See the “Range Hood Care” section.
4. Disconnect the blower wiring plug.
A
A. Blower wiring plug
B. Blower
5. Remove the 4 mounting screws holding the 8" (20.3 cm)
diameter transition damper to the canopy top. Set the
damper and mounting screws aside.
A
A. Keyhole slot
B. Mounting tab
7. Remove the 4 screws from the cover plate on the back of the
canopy.
8. Install cover plate over the rectangular top exhaust hole using
its 4 mounting screws. Tighten screws.
B
A
A. Remove cover plate from here.
B. Replace cover plate here.
A. Damper mounting screws
8
9. Position the blower motor inside the canopy so that the
B
C
mounting tabs are aligned with the large end of the keyhole
slots on the back panel. Push down to lock the blower motor
in place and align the holes for the mounting screws. Install
mounting screws and tighten.
A
B
A. Mounting tab
B. Blower motor mounting screws
10. Reconnect the blower wiring plug.
A
15. Install the 3¼" x 10" (8.3 x 25.4 cm) damper (supplied) to the
back of the canopy using 3 of the the screws removed from
the 8" (20.3 cm) diameter transition damper. Tighten screws.
A
A. Damper mounting screws
Install Range Hood
NOTE: For rear venting installations, the 3¼" x 10"
(8.3 x 25.4 cm) damper must be assembled to the back of the
hood before installing the range hood. See the “Connect Vent
System - For Rear Venting Installations Only” section for
instructions.
1. Using 2 or more people, hang range hood on 2 mounting
screws through the mounting slots on back of hood.
A
A. Blower wiring plug
B. Blower
11. Reattach center glass cover to canopy. Tighten screws.
12. Reinstall metal filter. See the “Range Hood Care” section.
13. Close center glass cover.
14. Using 2 or more people, set range hood onto its bottom on a
covered surface.
B
A. Mounting screws
B. Mounting slots
C. Lower mounting screws
2. Remove the grease filter. See “Range Hood Care” section.
3. Level the range hood and tighten upper mounting screws.
4. Install 2 - 5 x 45 mm lower mounting screws and tighten.
9
Connect Vent System
A
A
C
This range hood is factory set for 8" (20.3 cm) round venting
through the roof or wall. An 8" (20.3 cm) round vent system is
needed for installation (not included). To vent through the wall, a
90° elbow is needed.
This range hood can also be set for rear venting using the
3¼" x 10" (8.3 x 25.4 cm) rectangular damper (supplied). See the
“Connect Vent System - For Rear Venting Installation Only”
section.
For vented installations only:
1. Fit vent system over transition piece.
2. Seal connection with clamps.
3. Check that backdraft dampers work properly.
For non-vented (recirculating) installation with vent
cover only:
1. Assemble the air deflector with the duct cover bracket with
4 - assembly screws provided with the Recirculation Kit.
For non-vented (recirculating) installation without vent
cover only:
1. Push in the bottom of the center glass to unlatch, and lift to
open.
2. Remove metal filter. See the “Range Hood Care” section.
3. Remove the 4 mounting screws holding the 8" (20.3 cm)
diameter transition damper to the canopy top. Set the
damper and mounting screws aside.
A
B
C
A. Assembly screws
B. Air deflector
C. Duct cover bracket
2. Measure from the bottom of the air deflector to the bottom of
the hood exhaust outlet.
B
D
X
E
A. Air deflector
B. Vent clamp
C. X = length to cut vent duct
D. 8" (20.3 cm) dia. round vent duct
E. Hood exhaust outlet
3. Cut the duct to the measured size (X).
4. Remove the air deflector.
5. Slide the duct onto the bottom of the air deflector.
6. Place the assembled air deflector and duct over the exhaust
outlet from the hood.
7. Reassemble the air deflector to the duct cover bracket with
4 assembly screws.
8. Seal connections with vent clamps.
A. Damper mounting screws
4. Install the top grille cap using the mounting screws included
in the Recirculation Kit.
10
Loading...
+ 22 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.