Déplacement de la cuisinière.....................................................38
IMPORTANT:
Save for local electrical inspector's use.
IMPORTANT :
À conserver pour consultation par l'inspecteur local des installations électriques.
W10253462A
RANGE SAFETY
Your safety and the safety of others are very important.
We have provided many important safety messages in this manual and on your appliance. Always read and obey all safety
messages.
This is the safety alert symbol.
This symbol alerts you to potential hazards that can kill or hurt you and others.
All safety messages will follow the safety alert symbol and either the word “DANGER” or “WARNING.”
These words mean:
You can be killed or seriously injured if you don't immediately
DANGER
WARNING
All safety messages will tell you what the potential hazard is, tell you how to reduce the chance of injury, and tell you what can
happen if the instructions are not followed.
A child or adult can tip the range and be killed.
Connect anti-tip bracket to rear range foot.
Reconnect the anti-tip bracket, if the range is moved.
Failure to follow these instructions can result in death or serious burns to children and adults.
follow instructions.
can be killed or seriously injured if you don't
You
instructions.
WARNING
Tip Over Hazard
follow
2
INSTALLATION REQUIREMENTS
Tools and Parts
Gather the required tools and parts before starting installation.
Read and follow the instructions provided with any tools listed
here.
Tool s ne e de d
■ Tape measure
■ Level
■ Phillips screwdriver
■ Flat-blade screwdriver
■ Saber or keyhole saw
■ Marker or pencil
Parts supplied
Check that all parts are included.
■ 3 - #10-32 hex nuts (attached to terminal block)
■ 3 - Terminal lugs
■ 2 or 3 - Oven racks (depending on your model)
■ Blower motor
■ 2 - vent clamps
■ Flexible vent
■ Flow tester card
■ Blower location template
■ 4 - #8 x ¾" screws (for mounting blower motor bracket)
■ Anti-tip bracket (taped to package containing literature in
oven cavity)
Anti-tip bracket must be securely mounted to back wall or
floor. Thickness of floor may require longer screws to anchor
bracket to subfloor. Longer screws are available from your
local hardware store.
Parts needed
■ One of the following Jenn-Air wall caps:
®
Jenn-Air
Order Part Number A405.
Jenn-Air
Order Part Number A406.
Jenn-Air
Damper. Order Part Number A403.
To order, see the “Assistance or Service” section of the Use
and Care Guide.
■ Metal ducting
■ Vent clamps
■ Concrete anchors (for concrete floor mounting)
■ 2 - 2" x 4" x 8¾" (5.0 x 10.2 x 22.2 cm) wood spacers (for left
or right side venting)
5" (12.7 cm) Round Surface Wall Cap Damper.
®
6" (15.2 cm) Round Surface Wall Cap Damper.
®
3¼" x 10" (8.3 x 25.4 cm) Surface Wall Cap
■ Wrench or pliers
■ ⁵⁄₁₆" nut driver
■ ¼" nut driver
■ Drill
■ ¹⁄₈" (3.2 mm) drill bit
■ ³⁄₁₆" (4.8 mm) carbide-tipped
masonry drill bit (for concrete/
ceramic floors)
If using a power supply cord:
■ A UL listed power supply cord kit marked for use with ranges.
The cord should be rated at 250 volts minimum, 40 amps or
50 amps that is marked for use with nominal 1³⁄₈" (3.5 cm)
diameter connection opening and must end in ring terminals
or open-end spade terminals with upturned ends.
■ A UL listed strain relief.
Check local codes. Check existing electrical supply. See
“Electrical Requirements” section.
It is recommended that all electrical connections be made by a
licensed, qualified electrical installer.
Location Requirements
IMPORTANT: Observe all governing codes and ordinances.
■ It is the installer’s responsibility to comply with installation
clearances specified on the model/serial rating plate. The
model/serial rating plate is located on the right-hand side of
the oven frame behind the storage drawer panel.
■ The range should be located for convenient use in the
kitchen.
■ To eliminate the risk of burns or fire by reaching over heated
surface units, cabinet storage space located above the
surface units should be avoided. If cabinet storage is to be
provided, the risk can be reduced by installing a range hood
that projects horizontally a minimum of 5" (12.7 cm) beyond
the bottom of the cabinets.
■ Cabinet opening dimensions that are shown must be used.
Given dimensions are minimum clearances.
■ The floor anti-tip bracket must be installed. To install the anti-
tip bracket shipped with the range, see “Install Anti-Tip
Bracket” section.
■ Grounded electrical supply is required. See “Electrical
Requirements” section.
IMPORTANT: To avoid damage to your cabinets, check with your
builder or cabinet supplier to make sure that the materials used
will not discolor, delaminate or sustain other damage. This oven
has been designed in accordance with the requirements of UL
and CSA International and complies with the maximum allowable
wood cabinet temperatures of 194°F (90°C).
Mobile Home - Additional Installation Requirements
The installation of this range must conform to the Manufactured
Home Construction and Safety Standard, Title 24 CFR, Part 3280
(formerly the Federal Standard for Mobile Home Construction
and Safety, Title 24, HUD Part 280). When such standard is not
applicable, the Standard for Manufactured Home Installations,
ANSI A225.1/NFPA 501A or with local codes.
Mobile home installations require:
■ When this range is installed in a mobile home, it must be
secured to the floor during transit. Any method of securing
the range is adequate as long as it conforms to the standards
listed above.
■ Four-wire power supply cord or cable must be used in a
mobile home installation. The appliance wiring will need to be
revised. See “Electrical Connection” section.
3
Product Dimensions
Cabinet Dimensions
Cabinet opening dimensions shown are for 25" (64.0 cm)
countertop depth, 24" (61.0 cm) base cabinet depth and
A
36" (91.4 cm) countertop height.
A
B
C
F
B*
E**
D
A. 30³⁄₄" (78.1 cm)
B. 35³⁄₄" (90.8 cm) height to underside
of cooktop edge with leveling legs
screwed all the way in*
C. Model/serial number plate (located
on the right-hand side of the
bottom oven frame)
D. 29⁷⁄₈" (75.9 cm)
E. 29¹⁄₁₆" (73.8 cm) from
handle to standoff at back
of range**
F. 23½" (59.7 cm)
countertop notch to rear
of cooktop
C
*Range can be raised approximately 1" (2.5 cm) by adjusting
the leveling legs.
**When installed in a 24" (61 cm) base cabinet with 25" (63.5 cm)
countertop; front of oven door protrudes 2¹⁄₂" (6.4 cm) beyond
24" (61.0 cm) base cabinet.
H
F
A. 13" (33.0 cm) upper cabinet
depth
B. 30" (76.2 cm) min. opening
width
C. For minimum clearance to the
top of the cooktop,
see NOTE*.
D. 23¹⁄₄" (59.1 cm) opening
depth
E. 30" (76.2 cm) min. opening
width
D
E
I
I
G
F. Junction box - 5.5" (14.0 cm)
min. from either cabinet,
10" (25.4 cm) max. from floor
Outlet must be flush.
Nothing located in shaded
area can extend more than
2" (5.1 cm) from wall or range
will not slide all the way back.
G. Cabinet door or hinge should
not extend into cutout.
H. 18" (45.7 cm)
I. 3" (7.6 cm) min. clearance from
both sides of the range to the
side wall or other combustible
material.
NOTE: 24" (61.0 cm) minimum when bottom of wood or metal
cabinet is covered by not less than ¹⁄₄" (0.64 cm) flame retardant
millboard covered with not less than No. 28 MSG sheet steel,
0.015" (0.4 mm) stainless steel, 0.024" (0.6 mm) aluminum or
0.020" (0.5 mm) copper.
30" (76.2 cm) minimum clearance between the top of the cooking
platform and the bottom of an uncovered wood or metal cabinet.
4
Venting Requirements
A
IMPORTANT: This range must be exhausted outdoors. See
“Venting Methods” section.
■ Do not terminate the vent system in an attic or other enclosed
area.
■ Use a Jenn-Air wall cap.
■ Vent system must terminate to the outside.
■ Use only a 6" (15.2 cm) round metal vent or a 3¼ x 10"
(8.3 cm x 25.4 cm) rectangular vent, except as follows:
5" (12.7 cm) round metal vent may be used for venting
straight out the back of the range and directly through the
wall for vent lengths of 10 ft (3.0 m) or less.
■ Rigid metal vent is recommended. For best performance, do
not use plastic or metal foil vent.
■ Before making cutouts, make sure there is proper clearance
within the wall or floor for the exhaust vent.
■ Do not cut a joist or stud unless absolutely necessary. If a
joist or stud must be cut, then a supporting frame must be
constructed.
■ The size of the vent should be uniform.
■ The vent system must have a damper. If roof or wall cap has a
damper, do not use damper supplied with the range hood.
■ Use vent clamps to seal all joints in the vent system.
■ Use caulking to seal exterior wall or roof opening around the
cap.
■ Determine which venting method is best for your application.
For Best Performance:
■ Use 26-gauge minimum galvanized or 25-gauge minimum
aluminum metal vent. Poor quality pipe fittings can reduce
airflow. Flexible metal vent is not recommended.
NOTE: Local codes may require a heavier gauge material.
■ Metal duct may be reduced to 30-gauge galvanized steel or
26-gauge aluminized steel if allowed by local codes. This
reduction is based on information in the International
Residential Codes Section M1601.1 (2006 edition).
■ Do not install 2 elbows together.
■ Use no more than three 90° elbows.
■ If an elbow is used, install it as far away as possible from the
hood’s vent motor exhaust opening.
■ Make sure there is a minimum of 18" (45.7 cm) of straight
vent between the elbows if more than one elbow is used.
■ Elbows too close together can cause excess turbulence that
reduces airflow.
■ Do not use a 5" (12.7 cm) elbow in a 6" (15.2 cm) or 3¹⁄₄" x 10"
(8.3 x 25.4 cm) system.
■ Do not reduce to a 5" (12.7 cm) system after using a
6" (15.2 cm) or 3¹⁄₄" x 10" (8.3 x 25.4 cm) fittings.
■ Avoid forming handmade crimps. Handmade crimps may
restrict airflow.
■ Use a Jenn-Air vent cap for proper performance. If an
alternate wall or roof cap is used, be certain the cap size is
not reduced and that it has a backdraft damper.
■ Use vent clamps to seal all joints in the vent system.
■ Use caulking to seal exterior wall or roof opening around the
cap.
The length of vent system and number of elbows should be kept
to a minimum to provide efficient performance.
The maximum equivalent length of the vent system is
60 ft (18.3 m). For altitudes above 4,500 ft (1272 m), reduce
recommended vent run by 20% for best performance.
Cold Weather Installations
An additional backdraft damper should be installed to minimize
backward cold air flow and a thermal break installed to minimize
conduction of outside temperatures as part of the vent system.
The damper should be on the cold air side of the thermal break.
Makeup Air
Local building codes may require the use of makeup air systems
when using ventilation systems greater than specified CFM of air
movement. The specified CFM varies from locale to locale.
Consult your HVAC professional for specific requirements in your
area.
Ventin g Meth ods
Common venting methods are shown for a downdraft range. The
downdraft range may be vented through the wall or floor.
Wall Venting
B
A. Wall cap
B. 6" (15.2 cm) round roof venting
Floor Venting
Venting Between Floor Joists
A
B
A. Wall cap
B. 6" (15.2 cm) round roof venting
5
Left or Right Side Venting
A
F
Venting Behind Cabinet Kickplate
B
A. Wall cap
B. 6" (15.2 cm) round roof venting
Concrete Slab Installations - Exhaust Through Wall
B
Calculating Vent System Length
IMPORTANT: This range is rated at 60 ft (18.3 m) of straight duct.
Low range is up to 30 ft (9.1 m); high range is 31 ft (9.4 m) to
60 ft (18.3 m).
If equivalent duct length exceeds 30 ft (18.3 m), the blower must
be converted to high range.
■ Do not convert to high range for shorter lengths. This will
cause excessive noise, conditioned air loss and affect the
flame pattern on gas ranges.
■ To convert blower for high range installations, see the
“Install Downdraft System” section.
To calculate the length of the system you need, add the
equivalent feet (meters) for each vent piece used in the system.
Vent Piece6" (15.2 cm) Round
45° elbow2.5 ft
(0.8 m)
A
L
K
J
C
I
D
E
G
H
A. Wall cap
B. 6" (15.2 cm) round metal vent
C. 16" (40.6 cm) maximum
D. 6" (15.2 cm) round PVC sewer pipe
E. Concrete slab
F. 6" (15.2 cm) round PVC sewer pipe
G. 6" (15.2 cm) round 90° PVC sewer pipe elbow
H. Tightly pack gravel or sand completely around pipe.
I. 30 ft (9.1 m) max.
J. 6" (15.2 cm) round 90° PVC sewer pipe elbow
K. 6" (15.2 cm) round PVC coupling
L. 12" (30.5 cm) minimum
Concrete Slab Installations Exhaust Through Window Well
IMPORTANT: Window well installation for electric models only.
B
D
A
K
J
C
E
H
F
G
I
90° elbow5.0 ft
(1.5 m)
6" (15.2 cm)
wall cap
3¹⁄₄" x 10" (8.3 cm x 25.4 cm)
to 6" (15.2 cm) transition
6" (15.2 cm) to 3¹⁄₄" x 10"
(8.3 cm x 25.4 cm) transition
3¹⁄₄" x 10" (8.3 cm x 25.4 cm)
to 6" (15.2 cm) 90° elbow
0.0 ft
(0.0 m)
4.5 ft
(1.4 m)
1 ft
(0.3 m)
5.0 ft
(1.5 m)
transition
6" (15.2 cm) to 3¹⁄₄" x 10"
(8.3 cm x 25.4 cm) 90° elbow
5.0 ft
(1.5 m)
transition
3¹⁄₄" x 10" (8.3 cm x 25.4 cm)
90° elbow
5.0 ft
(1.5 m)
A. Wall cap
B. 12" (30.5 cm) minimum
C. Concrete slab
D. 6" (15.2 cm) round PVC sewer pipe
E. 6" (15.2 cm) round PVC sewer pipe
F. 6" (15.2 cm) round 90° PVC sewer pipe elbow
G. Tightly pack gravel or sand completely around pipe.
H. 42 ft (12.8 m) max.
I. 6" (15.2 cm) round PVC coupling
J. 6" (15.2 cm) minimum
K. Window well
6
3¹⁄₄" x 10" (8.3 cm x 25.4 cm)
flat elbow
3¹⁄₄" x 10" (8.3 cm x 25.4 cm)
wall cap
12.0 ft
(3.7 m)
0.0 ft
(0.0 m)
Example vent system
90˚ elbow
6 ft (1.8 m)
wall cap
Range Rating*Specified Rating of
Power Supply Cord Kit
and Circuit Protection
120/240 Volts120/208 VoltsAmps
2 ft
(0.6 m)
Maximum length= 60 ft (18.3 m)
1- 90° elbow= 5 ft (1.5 m)
8 ft (2.4 m) straight= 8 ft (2.4 m)
1 - wall cap= 0 ft (0 m)
System length= 13 ft (3.9 m)
NOTE: For external venting, flexible vent is not recommended.
Flexible vent creates back pressure and air turbulence that
greatly reduce performance.
Electrical Requirements - U.S.A. Only
If codes permit and a separate ground wire is used, it is
recommended that a qualified electrical installer determine that
the ground path and wire gauge are in accordance with local
codes.
Do not use an extension cord.
Be sure that the electrical connection and wire size are adequate
and in conformance with the National Electrical Code, ANSI/
NFPA 70-latest edition and all local codes and ordinances.
A copy of the above code standards can be obtained from:
National Fire Protection Association
One Batterymarch Park
Quincy, MA 02269.
WARNING: Improper connection of the equipment-grounding
conductor can result in a risk of electric shock. Check with a
qualified electrician or service technician if you are in doubt as to
whether the appliance is properly grounded. Do not modify the
power supply cord plug. If it will not fit the outlet, have a proper
outlet installed by a qualified electrician.
Electrical Connection
To properly install your range, you must determine the type of
electrical connection you will be using and follow the instructions
provided for it here.
■ Range must be connected to the proper electrical voltage
and frequency as specified on the model/serial number rating
plate. The model/serial number rating plate is located behind
the control panel or on the oven frame behind the storage
drawer panel. Refer to the figures in the “Product
Dimensions” section of the “Location Requirements” section.
■ This range is manufactured with the neutral terminal
connected to the cabinet. Use a 3-wire, UL listed, 40- or
50-amp power supply cord (pigtail) (see following Range
Rating chart). If local codes do not permit ground through the
neutral, use a 4-wire power supply cord rated at 250 volts,
40 or 50 amps and investigated for use with ranges.
8.8 - 16.5 KW
16.6 - 22.5 KW
7.8 - 12.5 KW
12.6 - 18.5 KW
40 or 50**
50
*The NEC calculated load is less than the total connected load
listed on the model/serial rating plate.
**If connecting to a 50-amp circuit, use a 50-amp rated cord with
kit. For 50-amp rated cord kits, use kits that specify use with a
nominal 1³⁄₈" (34.9 mm) diameter connection opening.
■ A circuit breaker is recommended.
■ The range can be connected directly to the circuit breaker
box (or fused disconnect) through flexible or nonmetallic
sheathed, copper or aluminum cable. See “Electrical
Connection.”
■ Allow 2 to 3 ft (61.0 cm to 91.4 cm) of slack in the line so that
the range can be moved if servicing is ever necessary.
■ A UL listed conduit connector must be provided at each end
of the power supply cable (at the range and at the junction
box).
■ Wire sizes and connections must conform with the rating of
the range.
■ The wiring diagram is located on the back of the access
panel in a plastic bag.
If connecting to a 4-wire system:
This range is manufactured with the ground connected to the
neutral by a link. The ground must be revised so the green
ground wire of the 4-wire power supply cord is connected to the
cabinet. See “Electrical Connection.”
Grounding through the neutral conductor is prohibited for new
branch-circuit installations (1996 NEC); mobile homes; and
recreational vehicles, or an area where local codes prohibit
grounding through the neutral conductor.
When a 4-wire receptacle of NEMA Type 14-50R is used, a
matching UL listed, 4-wire, 250-volt, 40- or 50-amp, range power
supply cord (pigtail) must be used. This cord contains 4 copper
conductors with ring terminals or open-end spade terminals with
upturned ends, terminating in a NEMA Type 14-50P plug on the
supply end.
The fourth (grounding) conductor must be identified by a green or
green/yellow cover and the neutral conductor by a white cover.
Cord should be Type SRD or SRDT with a UL listed strain relief
and be at least 4 ft (1.22 m) long.
4-wire receptacle (14-50R)
The minimum conductor sized for the copper 4-wire power
cord are:
40-amp circuit
2 No.-8 conductors
1 No.-10 white neutral
1 No.-8 green grounding
7
If connecting to a 3-wire system:
Local codes may permit the use of a UL listed, 3-wire, 250-volt,
40- or 50-amp range power supply cord (pigtail). This cord
contains 3 copper conductors with ring terminals or open-end
spade terminals with upturned ends, terminating in a NEMA Type
10-50P plug on the supply end. Connectors on the appliance end
must be provided at the point the power supply cord enters the
appliance. This uses a 3-wire receptacle of NEMA Type 10-50R.
■ A time-delay fuse or circuit breaker is recommended.
■ This range is equipped with a CSA International Certified
Power Cord intended to be plugged into a standard 14-50R
wall receptacle. Be sure the wall receptacle is within reach of
range’s final location.
■ Do not use an extension cord.
3-wire receptacle (10-50R)
Electrical Requirements - Canada Only
WARNING
Electrical Shock Hazard
Electrically ground range.
Failure to do so can result in death, fire, or
electrical shock.
If codes permit and a separate ground wire is used, it is
recommended that a qualified electrical installer determine that
the ground path is adequate and wire gauge are in accordance
with local codes.
Be sure that the electrical connection and wire size are adequate
and in conformance with CSA Standard C22.1, Canadian
Electrical Code, Part 1 - latest edition, and all local codes and
ordinances.
A copy of the above code standards can be obtained from:
Canadian Standards Association
178 Rexdale Blvd.
Toronto, ON M9W 1R3 CANADA
■ Check with a qualified electrical installer if you are not sure
the range is properly grounded.
Countertop Preparation
(for Slide-in Ranges Only)
The cooktop sides of the slide-in range fit over the cutout edge of
your countertop.
If you have a square finish (flat) countertop and the opening width
is 30" (76.2 cm), no countertop preparation is required.
Formed front-edged countertops must have molded edge
shaved flat ³⁄₈" (1.0 cm) from each front corner of opening.
Tile countertops may need trim cut back ³⁄₈" (1.0 cm) from each
front corner and/or rounded edge flattened.
30"
(76.2 cm)
30 ¾"
(78.1 cm)
If countertop opening width is greater than 30" (76.2 cm), adjust
the ³⁄₈" (1.0 cm) dimension.
Countertop must be level. Place level on countertop, first side to
side, then front to back. If countertop is not level, range will not
be level. Range must be level for satisfactory baking conditions.
³⁄₈"
(1.0 cm)
Range Rating*Rating of
120/240 Volts120/208 VoltsAmpsAmps
8.8 - 16.5 KW
16.6 - 22.5 KW
*The NEC calculated load is less than the total connected load
listed on the model/serial rating plate.
7.8 - 12.5 KW
12.6 - 18.5 KW4050
Power
Supply Cord
Circuit
Protection
40 or 50
50
8
INSTALLATION INSTRUCTIONS
Unpack Range
WARNING
Excessive Weight Hazard
Use two or more people to move and install range.
Failure to do so can result in back or other injury.
1. Remove shipping materials, tape and film from the range.
Keep cardboard bottom under range.
2. Remove oven racks and parts package from inside oven.
3. To remove cardboard bottom, place range on its back, take
4 cardboard corners from the carton. Stack one cardboard
corner on top of another. Repeat with the other 2 corners.
Place them lengthwise on the floor behind the range to
support the range when it is laid on its back.
4. Using 2 or more people, firmly grasp the range and gently lay
it on its back on the cardboard corners.
5. Pull cardboard bottom firmly to remove.
6. Use an adjustable wrench to loosen the leveling legs.
7. Place cardboard or hardboard in front of range. Using 2 or
more people, stand range back up onto cardboard or
hardboard.
NOTE: If height adjustment is made when range is standing,
tilt the range back to adjust the front legs, then tilt forward to
adjust the rear legs.
3. When the range is at the correct height, check that there is
adequate clearance under the range for the anti-tip bracket.
Before sliding range into its final location, check that the antitip bracket will slide under the range and onto the rear
leveling leg prior to anti-tip bracket installation.
Install Anti-Tip Bracket
1. Remove the anti-tip bracket that is taped to the package
containing literature.
2. Determine which mounting method to use: floor or wall.
If you have a stone or masonry floor you can use the wall
mounting method.
3. Determine and mark centerline of the cutout space. The
mounting bracket can be installed on either the left side or
right side of the cutout. Position mounting bracket in cutout
so that right (or left) edge of the bracket is 14¹⁄₄" (36.2 cm)
from centerline, as shown.
A
Adjust Leveling Legs
1. If range height adjustment is necessary, use a wrench or
pliers to loosen the 4 leveling legs.
This may be done with the range on its back or with the range
supported on 2 legs after the range has been placed back to
a standing position.
NOTE: To place range back up into a standing position, put a
sheet of cardboard or hardboard in front of range. Using 2 or
more people, stand range back up onto the cardboard or
hardboard.
WARNING
Tip Over Hazard
A child or adult can tip the range and be killed.
Connect anti-tip bracket to rear range foot.
Reconnect the anti-tip bracket, if the range is moved.
Failure to follow these instructions can result in death
or serious burns to children and adults.
B
A. Centerline
B. 14¹⁄₄" (36.2 cm)
4. Drill two ¹⁄₈" (3.0 mm) holes that correspond to the bracket
holes of the determined mounting method. See below.
Floor Mounting
A
A. #12 x 1⁵⁄₈" screws
B. Anti-tip bracket
B
2. Adjust the leveling legs to the correct height. Leveling legs
can be loosened to add up to a maximum of 1" (2.5 cm). A
minimum of ³⁄₁₆" (5 mm) is needed to engage the anti-tip
bracket.
9
Wall Mounting
B
2. Check for obstructions before marking the vent hole location.
Mark a horizontal line 8³⁄₁₆" (20.8 cm) from the floor. Mark a
vertical line up to a maximum of 2¼" (7.9 cm) from the righthand side of the cabinet centerline.
A
A. #12 x 1⁵⁄₈" screws
B. Anti-tip bracket
5. Using the Phillips screwdriver, mount anti-tip bracket to the
wall or floor with the two #12 x 1⁵⁄₈" screws provided.
Install Downdraft System
Determine Equivalent Length of Vent System
This range is equipped with a dual range blower. It is shipped
from the factory for Low Range installations. If vent system
equivalent length exceeds 30 ft (9.1 m), the downdraft blower
motor must be converted to High Range for best performance.
See “Calculating Vent System Length.”
To Con v ert :
Gently remove the spring loaded Restricter Ring from the blower
inlet by pressing one of the 3 springs.
A
B
A. Maximum 2¼" (7.9 cm) from
the right of center
B. 8
³⁄₁₆
" (20.8 cm) from floor
3. Draw and cut a 6¼" (15.8 cm) diameter hole.
A
A. 6¼" (15.8 cm)
4. Position blower motor in cabinet opening. Connect vent
system to blower motor outlet using a vent clamp.
Top View
B
A
A. Restricter ring
B. Spring
Determine which venting method to use: floor, rear wall, or left or
right side venting. Go to the section for your type of venting.
Rear Wall Venting
1. Mark the wall at the center of the cabinet opening.
E
C
D
A
B
A. 18¾" (47.6 cm) maximum from back
wall forward into cabinet opening
B. Inlet
C. Vent system
D. Vent clamp
E. Wall vent
10
5. Mount blower motor to the floor with 4 - #8 x ¾" hex head
screws provided.
Top View
NOTE: If the template is misplaced, the following
measurements can be used to determine the vent hole
location.
Top View
6. Go to the “Electrical Connection” section.
Floor Venting
1. Mark the floor at the center of the cabinet opening.
B
C
D
A
E
F
G
I
H
A. 9" (22.8 cm)
B. 3
¹⁄₈
" (7.9 cm)
³⁄₈
" (21.3 cm)
C. 8
³⁄₈
" (16.2 cm)
D. 6
E. 2¼" (5.7 cm)
F. 12½" (31.7 cm)
G. 18¾" (47.6 cm)
H. 1½" (3.8 cm)
I. 3½" (8.9 cm)
4. Draw and cut a 6¼" (15.8 cm) diameter hole (option 1 shown).
2. Position template on floor by matching the centerline of the
template to the centerline drawn on the floor and place
template 2¼" (5.7 cm) from the back wall.
3. Determine the correct position for the vent hole, depending
on obstructions (joists) in the floor.
The hole can be cut anywhere within the boundaries of either
hatched area.
Option 1: If using the back hatched area (bigger one), the
blower inlet must face the left side as shown on the template
Option 2: If using the front hatched area (smaller one), the
blower inlet must face the back.
Top View
Option 1Option 2
B
A
A
B
A
A. Option 1
B. Option 2
5. Position blower motor in cabinet opening and mount blower
motor to the floor.
Top View
Option 1Option 2
B
A
A
B
A. Inlet from range
B. Exhaust outlet
B
A. Inlet from range
B. Exhaust outlet
11
6. Connect vent system to blower motor outlet (option 1 shown)
with 4 - #8 x ¾" hex head screws provided.
3. Mark and cut a 14" x 11" (35.6 x 27.9 cm) opening in the floor
of the same cabinet as the vent hole opening.
Top View
A
B
C
A. Inlet
B. Vent clamp
C. Floor
D. Vent system
D
7. Go to the “Electrical Connection” section.
Left or Right Side Venting
1. Mark cabinet side for either a left or right side vent hole
location.
A
B
A
B
A. 11" (27.9 cm) from front of cabinet
B. 14" (35.6 cm) from left side of cabinet
4. Remove 4 locknuts on the motor side of the blower and
remove the bracket.
View from Motor Side of Blower
A
³⁄₁₆
" (79.2 cm) to top of cabinet
A. 31
B. 18" (45.7 cm) from back wall
2. Mark and cut a 5½" (13.9 cm) diameter hole in the desired
cabinet side.
A
A. 5½" (13.9 cm) diameter hole
A.Electrical connector
5. Lift and rotate the motor 180° to reposition the electrical
connection.
A
A. Electrical connector
6. Rotate bracket 180° and secure with 4 locknuts.
12
Loading...
+ 28 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.