Déplacement de la cuisinière.....................................................38
IMPORTANT:
Save for local electrical inspector's use.
IMPORTANT :
À conserver pour consultation par l'inspecteur local des installations électriques.
W10253462A
RANGE SAFETY
Your safety and the safety of others are very important.
We have provided many important safety messages in this manual and on your appliance. Always read and obey all safety
messages.
This is the safety alert symbol.
This symbol alerts you to potential hazards that can kill or hurt you and others.
All safety messages will follow the safety alert symbol and either the word “DANGER” or “WARNING.”
These words mean:
You can be killed or seriously injured if you don't immediately
DANGER
WARNING
All safety messages will tell you what the potential hazard is, tell you how to reduce the chance of injury, and tell you what can
happen if the instructions are not followed.
A child or adult can tip the range and be killed.
Connect anti-tip bracket to rear range foot.
Reconnect the anti-tip bracket, if the range is moved.
Failure to follow these instructions can result in death or serious burns to children and adults.
follow instructions.
can be killed or seriously injured if you don't
You
instructions.
WARNING
Tip Over Hazard
follow
2
INSTALLATION REQUIREMENTS
Tools and Parts
Gather the required tools and parts before starting installation.
Read and follow the instructions provided with any tools listed
here.
Tool s ne e de d
■ Tape measure
■ Level
■ Phillips screwdriver
■ Flat-blade screwdriver
■ Saber or keyhole saw
■ Marker or pencil
Parts supplied
Check that all parts are included.
■ 3 - #10-32 hex nuts (attached to terminal block)
■ 3 - Terminal lugs
■ 2 or 3 - Oven racks (depending on your model)
■ Blower motor
■ 2 - vent clamps
■ Flexible vent
■ Flow tester card
■ Blower location template
■ 4 - #8 x ¾" screws (for mounting blower motor bracket)
■ Anti-tip bracket (taped to package containing literature in
oven cavity)
Anti-tip bracket must be securely mounted to back wall or
floor. Thickness of floor may require longer screws to anchor
bracket to subfloor. Longer screws are available from your
local hardware store.
Parts needed
■ One of the following Jenn-Air wall caps:
®
Jenn-Air
Order Part Number A405.
Jenn-Air
Order Part Number A406.
Jenn-Air
Damper. Order Part Number A403.
To order, see the “Assistance or Service” section of the Use
and Care Guide.
■ Metal ducting
■ Vent clamps
■ Concrete anchors (for concrete floor mounting)
■ 2 - 2" x 4" x 8¾" (5.0 x 10.2 x 22.2 cm) wood spacers (for left
or right side venting)
5" (12.7 cm) Round Surface Wall Cap Damper.
®
6" (15.2 cm) Round Surface Wall Cap Damper.
®
3¼" x 10" (8.3 x 25.4 cm) Surface Wall Cap
■ Wrench or pliers
■ ⁵⁄₁₆" nut driver
■ ¼" nut driver
■ Drill
■ ¹⁄₈" (3.2 mm) drill bit
■ ³⁄₁₆" (4.8 mm) carbide-tipped
masonry drill bit (for concrete/
ceramic floors)
If using a power supply cord:
■ A UL listed power supply cord kit marked for use with ranges.
The cord should be rated at 250 volts minimum, 40 amps or
50 amps that is marked for use with nominal 1³⁄₈" (3.5 cm)
diameter connection opening and must end in ring terminals
or open-end spade terminals with upturned ends.
■ A UL listed strain relief.
Check local codes. Check existing electrical supply. See
“Electrical Requirements” section.
It is recommended that all electrical connections be made by a
licensed, qualified electrical installer.
Location Requirements
IMPORTANT: Observe all governing codes and ordinances.
■ It is the installer’s responsibility to comply with installation
clearances specified on the model/serial rating plate. The
model/serial rating plate is located on the right-hand side of
the oven frame behind the storage drawer panel.
■ The range should be located for convenient use in the
kitchen.
■ To eliminate the risk of burns or fire by reaching over heated
surface units, cabinet storage space located above the
surface units should be avoided. If cabinet storage is to be
provided, the risk can be reduced by installing a range hood
that projects horizontally a minimum of 5" (12.7 cm) beyond
the bottom of the cabinets.
■ Cabinet opening dimensions that are shown must be used.
Given dimensions are minimum clearances.
■ The floor anti-tip bracket must be installed. To install the anti-
tip bracket shipped with the range, see “Install Anti-Tip
Bracket” section.
■ Grounded electrical supply is required. See “Electrical
Requirements” section.
IMPORTANT: To avoid damage to your cabinets, check with your
builder or cabinet supplier to make sure that the materials used
will not discolor, delaminate or sustain other damage. This oven
has been designed in accordance with the requirements of UL
and CSA International and complies with the maximum allowable
wood cabinet temperatures of 194°F (90°C).
Mobile Home - Additional Installation Requirements
The installation of this range must conform to the Manufactured
Home Construction and Safety Standard, Title 24 CFR, Part 3280
(formerly the Federal Standard for Mobile Home Construction
and Safety, Title 24, HUD Part 280). When such standard is not
applicable, the Standard for Manufactured Home Installations,
ANSI A225.1/NFPA 501A or with local codes.
Mobile home installations require:
■ When this range is installed in a mobile home, it must be
secured to the floor during transit. Any method of securing
the range is adequate as long as it conforms to the standards
listed above.
■ Four-wire power supply cord or cable must be used in a
mobile home installation. The appliance wiring will need to be
revised. See “Electrical Connection” section.
3
Product Dimensions
Cabinet Dimensions
Cabinet opening dimensions shown are for 25" (64.0 cm)
countertop depth, 24" (61.0 cm) base cabinet depth and
A
36" (91.4 cm) countertop height.
A
B
C
F
B*
E**
D
A. 30³⁄₄" (78.1 cm)
B. 35³⁄₄" (90.8 cm) height to underside
of cooktop edge with leveling legs
screwed all the way in*
C. Model/serial number plate (located
on the right-hand side of the
bottom oven frame)
D. 29⁷⁄₈" (75.9 cm)
E. 29¹⁄₁₆" (73.8 cm) from
handle to standoff at back
of range**
F. 23½" (59.7 cm)
countertop notch to rear
of cooktop
C
*Range can be raised approximately 1" (2.5 cm) by adjusting
the leveling legs.
**When installed in a 24" (61 cm) base cabinet with 25" (63.5 cm)
countertop; front of oven door protrudes 2¹⁄₂" (6.4 cm) beyond
24" (61.0 cm) base cabinet.
H
F
A. 13" (33.0 cm) upper cabinet
depth
B. 30" (76.2 cm) min. opening
width
C. For minimum clearance to the
top of the cooktop,
see NOTE*.
D. 23¹⁄₄" (59.1 cm) opening
depth
E. 30" (76.2 cm) min. opening
width
D
E
I
I
G
F. Junction box - 5.5" (14.0 cm)
min. from either cabinet,
10" (25.4 cm) max. from floor
Outlet must be flush.
Nothing located in shaded
area can extend more than
2" (5.1 cm) from wall or range
will not slide all the way back.
G. Cabinet door or hinge should
not extend into cutout.
H. 18" (45.7 cm)
I. 3" (7.6 cm) min. clearance from
both sides of the range to the
side wall or other combustible
material.
NOTE: 24" (61.0 cm) minimum when bottom of wood or metal
cabinet is covered by not less than ¹⁄₄" (0.64 cm) flame retardant
millboard covered with not less than No. 28 MSG sheet steel,
0.015" (0.4 mm) stainless steel, 0.024" (0.6 mm) aluminum or
0.020" (0.5 mm) copper.
30" (76.2 cm) minimum clearance between the top of the cooking
platform and the bottom of an uncovered wood or metal cabinet.
4
Venting Requirements
A
IMPORTANT: This range must be exhausted outdoors. See
“Venting Methods” section.
■ Do not terminate the vent system in an attic or other enclosed
area.
■ Use a Jenn-Air wall cap.
■ Vent system must terminate to the outside.
■ Use only a 6" (15.2 cm) round metal vent or a 3¼ x 10"
(8.3 cm x 25.4 cm) rectangular vent, except as follows:
5" (12.7 cm) round metal vent may be used for venting
straight out the back of the range and directly through the
wall for vent lengths of 10 ft (3.0 m) or less.
■ Rigid metal vent is recommended. For best performance, do
not use plastic or metal foil vent.
■ Before making cutouts, make sure there is proper clearance
within the wall or floor for the exhaust vent.
■ Do not cut a joist or stud unless absolutely necessary. If a
joist or stud must be cut, then a supporting frame must be
constructed.
■ The size of the vent should be uniform.
■ The vent system must have a damper. If roof or wall cap has a
damper, do not use damper supplied with the range hood.
■ Use vent clamps to seal all joints in the vent system.
■ Use caulking to seal exterior wall or roof opening around the
cap.
■ Determine which venting method is best for your application.
For Best Performance:
■ Use 26-gauge minimum galvanized or 25-gauge minimum
aluminum metal vent. Poor quality pipe fittings can reduce
airflow. Flexible metal vent is not recommended.
NOTE: Local codes may require a heavier gauge material.
■ Metal duct may be reduced to 30-gauge galvanized steel or
26-gauge aluminized steel if allowed by local codes. This
reduction is based on information in the International
Residential Codes Section M1601.1 (2006 edition).
■ Do not install 2 elbows together.
■ Use no more than three 90° elbows.
■ If an elbow is used, install it as far away as possible from the
hood’s vent motor exhaust opening.
■ Make sure there is a minimum of 18" (45.7 cm) of straight
vent between the elbows if more than one elbow is used.
■ Elbows too close together can cause excess turbulence that
reduces airflow.
■ Do not use a 5" (12.7 cm) elbow in a 6" (15.2 cm) or 3¹⁄₄" x 10"
(8.3 x 25.4 cm) system.
■ Do not reduce to a 5" (12.7 cm) system after using a
6" (15.2 cm) or 3¹⁄₄" x 10" (8.3 x 25.4 cm) fittings.
■ Avoid forming handmade crimps. Handmade crimps may
restrict airflow.
■ Use a Jenn-Air vent cap for proper performance. If an
alternate wall or roof cap is used, be certain the cap size is
not reduced and that it has a backdraft damper.
■ Use vent clamps to seal all joints in the vent system.
■ Use caulking to seal exterior wall or roof opening around the
cap.
The length of vent system and number of elbows should be kept
to a minimum to provide efficient performance.
The maximum equivalent length of the vent system is
60 ft (18.3 m). For altitudes above 4,500 ft (1272 m), reduce
recommended vent run by 20% for best performance.
Cold Weather Installations
An additional backdraft damper should be installed to minimize
backward cold air flow and a thermal break installed to minimize
conduction of outside temperatures as part of the vent system.
The damper should be on the cold air side of the thermal break.
Makeup Air
Local building codes may require the use of makeup air systems
when using ventilation systems greater than specified CFM of air
movement. The specified CFM varies from locale to locale.
Consult your HVAC professional for specific requirements in your
area.
Ventin g Meth ods
Common venting methods are shown for a downdraft range. The
downdraft range may be vented through the wall or floor.
Wall Venting
B
A. Wall cap
B. 6" (15.2 cm) round roof venting
Floor Venting
Venting Between Floor Joists
A
B
A. Wall cap
B. 6" (15.2 cm) round roof venting
5
Left or Right Side Venting
A
F
Venting Behind Cabinet Kickplate
B
A. Wall cap
B. 6" (15.2 cm) round roof venting
Concrete Slab Installations - Exhaust Through Wall
B
Calculating Vent System Length
IMPORTANT: This range is rated at 60 ft (18.3 m) of straight duct.
Low range is up to 30 ft (9.1 m); high range is 31 ft (9.4 m) to
60 ft (18.3 m).
If equivalent duct length exceeds 30 ft (18.3 m), the blower must
be converted to high range.
■ Do not convert to high range for shorter lengths. This will
cause excessive noise, conditioned air loss and affect the
flame pattern on gas ranges.
■ To convert blower for high range installations, see the
“Install Downdraft System” section.
To calculate the length of the system you need, add the
equivalent feet (meters) for each vent piece used in the system.
Vent Piece6" (15.2 cm) Round
45° elbow2.5 ft
(0.8 m)
A
L
K
J
C
I
D
E
G
H
A. Wall cap
B. 6" (15.2 cm) round metal vent
C. 16" (40.6 cm) maximum
D. 6" (15.2 cm) round PVC sewer pipe
E. Concrete slab
F. 6" (15.2 cm) round PVC sewer pipe
G. 6" (15.2 cm) round 90° PVC sewer pipe elbow
H. Tightly pack gravel or sand completely around pipe.
I. 30 ft (9.1 m) max.
J. 6" (15.2 cm) round 90° PVC sewer pipe elbow
K. 6" (15.2 cm) round PVC coupling
L. 12" (30.5 cm) minimum
Concrete Slab Installations Exhaust Through Window Well
IMPORTANT: Window well installation for electric models only.
B
D
A
K
J
C
E
H
F
G
I
90° elbow5.0 ft
(1.5 m)
6" (15.2 cm)
wall cap
3¹⁄₄" x 10" (8.3 cm x 25.4 cm)
to 6" (15.2 cm) transition
6" (15.2 cm) to 3¹⁄₄" x 10"
(8.3 cm x 25.4 cm) transition
3¹⁄₄" x 10" (8.3 cm x 25.4 cm)
to 6" (15.2 cm) 90° elbow
0.0 ft
(0.0 m)
4.5 ft
(1.4 m)
1 ft
(0.3 m)
5.0 ft
(1.5 m)
transition
6" (15.2 cm) to 3¹⁄₄" x 10"
(8.3 cm x 25.4 cm) 90° elbow
5.0 ft
(1.5 m)
transition
3¹⁄₄" x 10" (8.3 cm x 25.4 cm)
90° elbow
5.0 ft
(1.5 m)
A. Wall cap
B. 12" (30.5 cm) minimum
C. Concrete slab
D. 6" (15.2 cm) round PVC sewer pipe
E. 6" (15.2 cm) round PVC sewer pipe
F. 6" (15.2 cm) round 90° PVC sewer pipe elbow
G. Tightly pack gravel or sand completely around pipe.
H. 42 ft (12.8 m) max.
I. 6" (15.2 cm) round PVC coupling
J. 6" (15.2 cm) minimum
K. Window well
6
3¹⁄₄" x 10" (8.3 cm x 25.4 cm)
flat elbow
3¹⁄₄" x 10" (8.3 cm x 25.4 cm)
wall cap
12.0 ft
(3.7 m)
0.0 ft
(0.0 m)
Example vent system
90˚ elbow
6 ft (1.8 m)
wall cap
Range Rating*Specified Rating of
Power Supply Cord Kit
and Circuit Protection
120/240 Volts120/208 VoltsAmps
2 ft
(0.6 m)
Maximum length= 60 ft (18.3 m)
1- 90° elbow= 5 ft (1.5 m)
8 ft (2.4 m) straight= 8 ft (2.4 m)
1 - wall cap= 0 ft (0 m)
System length= 13 ft (3.9 m)
NOTE: For external venting, flexible vent is not recommended.
Flexible vent creates back pressure and air turbulence that
greatly reduce performance.
Electrical Requirements - U.S.A. Only
If codes permit and a separate ground wire is used, it is
recommended that a qualified electrical installer determine that
the ground path and wire gauge are in accordance with local
codes.
Do not use an extension cord.
Be sure that the electrical connection and wire size are adequate
and in conformance with the National Electrical Code, ANSI/
NFPA 70-latest edition and all local codes and ordinances.
A copy of the above code standards can be obtained from:
National Fire Protection Association
One Batterymarch Park
Quincy, MA 02269.
WARNING: Improper connection of the equipment-grounding
conductor can result in a risk of electric shock. Check with a
qualified electrician or service technician if you are in doubt as to
whether the appliance is properly grounded. Do not modify the
power supply cord plug. If it will not fit the outlet, have a proper
outlet installed by a qualified electrician.
Electrical Connection
To properly install your range, you must determine the type of
electrical connection you will be using and follow the instructions
provided for it here.
■ Range must be connected to the proper electrical voltage
and frequency as specified on the model/serial number rating
plate. The model/serial number rating plate is located behind
the control panel or on the oven frame behind the storage
drawer panel. Refer to the figures in the “Product
Dimensions” section of the “Location Requirements” section.
■ This range is manufactured with the neutral terminal
connected to the cabinet. Use a 3-wire, UL listed, 40- or
50-amp power supply cord (pigtail) (see following Range
Rating chart). If local codes do not permit ground through the
neutral, use a 4-wire power supply cord rated at 250 volts,
40 or 50 amps and investigated for use with ranges.
8.8 - 16.5 KW
16.6 - 22.5 KW
7.8 - 12.5 KW
12.6 - 18.5 KW
40 or 50**
50
*The NEC calculated load is less than the total connected load
listed on the model/serial rating plate.
**If connecting to a 50-amp circuit, use a 50-amp rated cord with
kit. For 50-amp rated cord kits, use kits that specify use with a
nominal 1³⁄₈" (34.9 mm) diameter connection opening.
■ A circuit breaker is recommended.
■ The range can be connected directly to the circuit breaker
box (or fused disconnect) through flexible or nonmetallic
sheathed, copper or aluminum cable. See “Electrical
Connection.”
■ Allow 2 to 3 ft (61.0 cm to 91.4 cm) of slack in the line so that
the range can be moved if servicing is ever necessary.
■ A UL listed conduit connector must be provided at each end
of the power supply cable (at the range and at the junction
box).
■ Wire sizes and connections must conform with the rating of
the range.
■ The wiring diagram is located on the back of the access
panel in a plastic bag.
If connecting to a 4-wire system:
This range is manufactured with the ground connected to the
neutral by a link. The ground must be revised so the green
ground wire of the 4-wire power supply cord is connected to the
cabinet. See “Electrical Connection.”
Grounding through the neutral conductor is prohibited for new
branch-circuit installations (1996 NEC); mobile homes; and
recreational vehicles, or an area where local codes prohibit
grounding through the neutral conductor.
When a 4-wire receptacle of NEMA Type 14-50R is used, a
matching UL listed, 4-wire, 250-volt, 40- or 50-amp, range power
supply cord (pigtail) must be used. This cord contains 4 copper
conductors with ring terminals or open-end spade terminals with
upturned ends, terminating in a NEMA Type 14-50P plug on the
supply end.
The fourth (grounding) conductor must be identified by a green or
green/yellow cover and the neutral conductor by a white cover.
Cord should be Type SRD or SRDT with a UL listed strain relief
and be at least 4 ft (1.22 m) long.
4-wire receptacle (14-50R)
The minimum conductor sized for the copper 4-wire power
cord are:
40-amp circuit
2 No.-8 conductors
1 No.-10 white neutral
1 No.-8 green grounding
7
If connecting to a 3-wire system:
Local codes may permit the use of a UL listed, 3-wire, 250-volt,
40- or 50-amp range power supply cord (pigtail). This cord
contains 3 copper conductors with ring terminals or open-end
spade terminals with upturned ends, terminating in a NEMA Type
10-50P plug on the supply end. Connectors on the appliance end
must be provided at the point the power supply cord enters the
appliance. This uses a 3-wire receptacle of NEMA Type 10-50R.
■ A time-delay fuse or circuit breaker is recommended.
■ This range is equipped with a CSA International Certified
Power Cord intended to be plugged into a standard 14-50R
wall receptacle. Be sure the wall receptacle is within reach of
range’s final location.
■ Do not use an extension cord.
3-wire receptacle (10-50R)
Electrical Requirements - Canada Only
WARNING
Electrical Shock Hazard
Electrically ground range.
Failure to do so can result in death, fire, or
electrical shock.
If codes permit and a separate ground wire is used, it is
recommended that a qualified electrical installer determine that
the ground path is adequate and wire gauge are in accordance
with local codes.
Be sure that the electrical connection and wire size are adequate
and in conformance with CSA Standard C22.1, Canadian
Electrical Code, Part 1 - latest edition, and all local codes and
ordinances.
A copy of the above code standards can be obtained from:
Canadian Standards Association
178 Rexdale Blvd.
Toronto, ON M9W 1R3 CANADA
■ Check with a qualified electrical installer if you are not sure
the range is properly grounded.
Countertop Preparation
(for Slide-in Ranges Only)
The cooktop sides of the slide-in range fit over the cutout edge of
your countertop.
If you have a square finish (flat) countertop and the opening width
is 30" (76.2 cm), no countertop preparation is required.
Formed front-edged countertops must have molded edge
shaved flat ³⁄₈" (1.0 cm) from each front corner of opening.
Tile countertops may need trim cut back ³⁄₈" (1.0 cm) from each
front corner and/or rounded edge flattened.
30"
(76.2 cm)
30 ¾"
(78.1 cm)
If countertop opening width is greater than 30" (76.2 cm), adjust
the ³⁄₈" (1.0 cm) dimension.
Countertop must be level. Place level on countertop, first side to
side, then front to back. If countertop is not level, range will not
be level. Range must be level for satisfactory baking conditions.
³⁄₈"
(1.0 cm)
Range Rating*Rating of
120/240 Volts120/208 VoltsAmpsAmps
8.8 - 16.5 KW
16.6 - 22.5 KW
*The NEC calculated load is less than the total connected load
listed on the model/serial rating plate.
7.8 - 12.5 KW
12.6 - 18.5 KW4050
Power
Supply Cord
Circuit
Protection
40 or 50
50
8
INSTALLATION INSTRUCTIONS
Unpack Range
WARNING
Excessive Weight Hazard
Use two or more people to move and install range.
Failure to do so can result in back or other injury.
1. Remove shipping materials, tape and film from the range.
Keep cardboard bottom under range.
2. Remove oven racks and parts package from inside oven.
3. To remove cardboard bottom, place range on its back, take
4 cardboard corners from the carton. Stack one cardboard
corner on top of another. Repeat with the other 2 corners.
Place them lengthwise on the floor behind the range to
support the range when it is laid on its back.
4. Using 2 or more people, firmly grasp the range and gently lay
it on its back on the cardboard corners.
5. Pull cardboard bottom firmly to remove.
6. Use an adjustable wrench to loosen the leveling legs.
7. Place cardboard or hardboard in front of range. Using 2 or
more people, stand range back up onto cardboard or
hardboard.
NOTE: If height adjustment is made when range is standing,
tilt the range back to adjust the front legs, then tilt forward to
adjust the rear legs.
3. When the range is at the correct height, check that there is
adequate clearance under the range for the anti-tip bracket.
Before sliding range into its final location, check that the antitip bracket will slide under the range and onto the rear
leveling leg prior to anti-tip bracket installation.
Install Anti-Tip Bracket
1. Remove the anti-tip bracket that is taped to the package
containing literature.
2. Determine which mounting method to use: floor or wall.
If you have a stone or masonry floor you can use the wall
mounting method.
3. Determine and mark centerline of the cutout space. The
mounting bracket can be installed on either the left side or
right side of the cutout. Position mounting bracket in cutout
so that right (or left) edge of the bracket is 14¹⁄₄" (36.2 cm)
from centerline, as shown.
A
Adjust Leveling Legs
1. If range height adjustment is necessary, use a wrench or
pliers to loosen the 4 leveling legs.
This may be done with the range on its back or with the range
supported on 2 legs after the range has been placed back to
a standing position.
NOTE: To place range back up into a standing position, put a
sheet of cardboard or hardboard in front of range. Using 2 or
more people, stand range back up onto the cardboard or
hardboard.
WARNING
Tip Over Hazard
A child or adult can tip the range and be killed.
Connect anti-tip bracket to rear range foot.
Reconnect the anti-tip bracket, if the range is moved.
Failure to follow these instructions can result in death
or serious burns to children and adults.
B
A. Centerline
B. 14¹⁄₄" (36.2 cm)
4. Drill two ¹⁄₈" (3.0 mm) holes that correspond to the bracket
holes of the determined mounting method. See below.
Floor Mounting
A
A. #12 x 1⁵⁄₈" screws
B. Anti-tip bracket
B
2. Adjust the leveling legs to the correct height. Leveling legs
can be loosened to add up to a maximum of 1" (2.5 cm). A
minimum of ³⁄₁₆" (5 mm) is needed to engage the anti-tip
bracket.
9
Wall Mounting
B
2. Check for obstructions before marking the vent hole location.
Mark a horizontal line 8³⁄₁₆" (20.8 cm) from the floor. Mark a
vertical line up to a maximum of 2¼" (7.9 cm) from the righthand side of the cabinet centerline.
A
A. #12 x 1⁵⁄₈" screws
B. Anti-tip bracket
5. Using the Phillips screwdriver, mount anti-tip bracket to the
wall or floor with the two #12 x 1⁵⁄₈" screws provided.
Install Downdraft System
Determine Equivalent Length of Vent System
This range is equipped with a dual range blower. It is shipped
from the factory for Low Range installations. If vent system
equivalent length exceeds 30 ft (9.1 m), the downdraft blower
motor must be converted to High Range for best performance.
See “Calculating Vent System Length.”
To Con v ert :
Gently remove the spring loaded Restricter Ring from the blower
inlet by pressing one of the 3 springs.
A
B
A. Maximum 2¼" (7.9 cm) from
the right of center
B. 8
³⁄₁₆
" (20.8 cm) from floor
3. Draw and cut a 6¼" (15.8 cm) diameter hole.
A
A. 6¼" (15.8 cm)
4. Position blower motor in cabinet opening. Connect vent
system to blower motor outlet using a vent clamp.
Top View
B
A
A. Restricter ring
B. Spring
Determine which venting method to use: floor, rear wall, or left or
right side venting. Go to the section for your type of venting.
Rear Wall Venting
1. Mark the wall at the center of the cabinet opening.
E
C
D
A
B
A. 18¾" (47.6 cm) maximum from back
wall forward into cabinet opening
B. Inlet
C. Vent system
D. Vent clamp
E. Wall vent
10
5. Mount blower motor to the floor with 4 - #8 x ¾" hex head
screws provided.
Top View
NOTE: If the template is misplaced, the following
measurements can be used to determine the vent hole
location.
Top View
6. Go to the “Electrical Connection” section.
Floor Venting
1. Mark the floor at the center of the cabinet opening.
B
C
D
A
E
F
G
I
H
A. 9" (22.8 cm)
B. 3
¹⁄₈
" (7.9 cm)
³⁄₈
" (21.3 cm)
C. 8
³⁄₈
" (16.2 cm)
D. 6
E. 2¼" (5.7 cm)
F. 12½" (31.7 cm)
G. 18¾" (47.6 cm)
H. 1½" (3.8 cm)
I. 3½" (8.9 cm)
4. Draw and cut a 6¼" (15.8 cm) diameter hole (option 1 shown).
2. Position template on floor by matching the centerline of the
template to the centerline drawn on the floor and place
template 2¼" (5.7 cm) from the back wall.
3. Determine the correct position for the vent hole, depending
on obstructions (joists) in the floor.
The hole can be cut anywhere within the boundaries of either
hatched area.
Option 1: If using the back hatched area (bigger one), the
blower inlet must face the left side as shown on the template
Option 2: If using the front hatched area (smaller one), the
blower inlet must face the back.
Top View
Option 1Option 2
B
A
A
B
A
A. Option 1
B. Option 2
5. Position blower motor in cabinet opening and mount blower
motor to the floor.
Top View
Option 1Option 2
B
A
A
B
A. Inlet from range
B. Exhaust outlet
B
A. Inlet from range
B. Exhaust outlet
11
6. Connect vent system to blower motor outlet (option 1 shown)
with 4 - #8 x ¾" hex head screws provided.
3. Mark and cut a 14" x 11" (35.6 x 27.9 cm) opening in the floor
of the same cabinet as the vent hole opening.
Top View
A
B
C
A. Inlet
B. Vent clamp
C. Floor
D. Vent system
D
7. Go to the “Electrical Connection” section.
Left or Right Side Venting
1. Mark cabinet side for either a left or right side vent hole
location.
A
B
A
B
A. 11" (27.9 cm) from front of cabinet
B. 14" (35.6 cm) from left side of cabinet
4. Remove 4 locknuts on the motor side of the blower and
remove the bracket.
View from Motor Side of Blower
A
³⁄₁₆
" (79.2 cm) to top of cabinet
A. 31
B. 18" (45.7 cm) from back wall
2. Mark and cut a 5½" (13.9 cm) diameter hole in the desired
cabinet side.
A
A. 5½" (13.9 cm) diameter hole
A.Electrical connector
5. Lift and rotate the motor 180° to reposition the electrical
connection.
A
A. Electrical connector
6. Rotate bracket 180° and secure with 4 locknuts.
12
7. Remove the bracket from the other side of the blower motor,
rotate 180° and secure with 4 locknuts.
8. Position 2 wood spacers and mount them to the floor.
Top View
B
C
A
D
D
9. Mount blower motor to wood spacers using 4 - #8 x ¾" hex
head screws provided.
NOTE: Vent system will be connected after range has been
moved into it’s final location. “See Connect Range to
Downdraft System” section.
Top View
B
C
A
A. Wood spacers
B. Mounting bracket
C. Blower
10. Go to the “Electrical Connection” section.
A. 2" x 4" (5.0 x 10.2 cm) wood spacers
⁷⁄₉
" (7.3 cm) from back wall to edge of wood spacer
B. 2
C. 8¾" (22.2 cm)
D. 2
⁵⁄₁₆
" (5.8 cm) centerline of opening to wood spacer
13
Electrical Connection - U.S.A. Only
Power Supply CordDirect Wire
WARNING
Electrical Shock Hazard
Disconnect power before servicing.
Use a new 40 amp power supply cord.
Plug into a grounded outlet.
Failure to follow these instructions can result in death,
fire, or electrical shock.
1. Disconnect power.
2. Use Phillips screwdriver to remove the terminal block cover
screw located on the back of the range. Pull cover down and
toward you to remove cover.
WARNING
Electrical Shock Hazard
Disconnect power before servicing.
Use 8 gauge copper or 6 gauge aluminum wire.
Electrically ground range.
Failure to follow these instructions can result in death,
fire, or electrical shock.
Style 1: Power supply cord strain relief
■ Assemble a UL listed strain relief in the opening.
A
3. Remove plastic tag holding three 10-32 hex nuts from the
middle post of the terminal block.
4. Add strain relief.
A. UL listed strain relief
■ Feed the power supply cord through the opening in the
cord/conduit plate on bottom of range. Allow enough
slack to easily attach the wiring to the terminal block.
■ Tighten strain relief screw against the power supply cord.
14
Style 2: Direct wire strain relief
N
U
TS
W
IT
H
P
O
W
E
R
C
O
R
D
N
U
T
S
W
I
T
H
P
O
W
E
R
C
O
RD
■ Use Phillips screwdriver to remove screws from panel on
back of range.
E
E
S
S
D
D
U
U
R
R
!
!
O
O
G
G
C
C
A
A
T
T
R
R
E
E
E
E
A
A
V
V
W
W
T
T
O
O
O
O
E
E
M
M
P
P
U
U
E
E
Q
Q
H
H
I
I
R
R
S
T
T
T
T
I
I
A
E
E
C
W
W
A
A
R
L
L
L
L
E
TS
TS
E
E
UU
U
E
E
R
R
T
T
TN
N
I
I
A
A
S
O
O
T
T
U
U
A
C
C
C
C
Q
Q
I
I
L
E
E
R
R
E
N
N
T
T
S
O
O
C
CU
C
C
É
É
L
L
A
A
E
E
R
R
N
N
A
A
P
P
Ó
Ó
D
D
R
R
O
O
C
C
■ Lift range back panel up and off.
■ Replace cord/conduit plate and insert screws.
■ Assemble a UL listed conduit connector in the opening.
A
E
E
S
S
D
D
U
U
R
R
!
!
O
O
G
G
C
C
A
A
T
T
R
R
E
E
E
E
A
A
V
V
W
W
T
T
O
O
O
O
E
E
M
M
P
P
U
U
E
E
Q
Q
H
H
I
I
R
R
S
T
T
T
T
I
I
A
E
E
C
W
W
R
A
A
L
L
S
S
L
L
E
T
T
E
E
U
E
E
U
U
R
R
TT
T
N
N
I
I
A
A
S
O
O
T
T
U
U
A
C
C
C
C
Q
Q
I
I
LE
E
R
R
E
N
N
T
T
S
O
O
C
C
U
C
C
É
É
L
L
A
A
E
E
R
R
N
N
A
A
P
P
Ó
Ó
D
D
R
R
O
O
C
C
■ Use Phillips screwdriver to remove screws and slide
cord/conduit plate down and out.
■ Position cord/conduit plate as shown in the following
illustration.
B
A. Removable retaining nut
B. Strain relief
■ Feed the flexible conduit through the strain relief, allowing
enough slack to easily attach wiring to the terminal block.
■ Tighten strain relief screw against the flexible conduit.
5. Replace back panel and screws on rear of range.
6. Complete installation following instructions for your type of
electrical connection:
4-wire (recommended)
3-wire (if 4-wire is not available)
15
Electrical Connection Options
A
B
C
B
If your home has:And you will be
connecting to:
Go to Section:
3. Feed the power supply cord through the opening in the cord/
conduit plate on bottom of range. Allow enough slack to
easily attach the wiring to the terminal block.
4-wire receptacle
(NEMA type 14-50R)
A UL listed,
250-volt
4-wire connection:
Power supply cord
minimum,
40-amp, range
power supply
cord
4-wire directA fused
disconnect or
4-wire connection:
Direct wire
circuit breaker
5"
(12.7 cm)
3-wire receptacle
(NEMA type 10-50R)
box
A UL listed,
250-volt
3-wire connection:
Power supply cord
minimum,
40-amp, range
power supply
cord
3-wire directA fused
1"
(2.5 cm)
disconnect or
circuit breaker
3-wire connection:
Direct wire
box
3"
(7.6 cm)
4-wire connection: Power Supply Cord
Use this method for:
■ New branch-circuit installations (1996 NEC)
■ Mobile homes
■ Recreational vehicles
■ In an area where local codes prohibit grounding through the
neutral
1. Part of metal ground strap must be cut out and removed.
A
C
D
A. Terminal block
B. Ground-link screw
C. Cord/conduit plate
D. Power supply cord wires
4. Use Phillips screwdriver to connect the green ground wire
from the power supply cord to the range with the ground-link
screw. The ground wire must be attached first.
5. Use ³⁄₈" nut driver to connect the neutral (white) wire to the
center terminal block post with one of the 10–32 hex nuts.
A
F
A. Metal ground strap
B. Discard
C. Ground-link screw
2. Use Phillips screwdriver to remove the ground-link screw
from the back of the range. Save the ground-link screw and
the end of the ground-link under the screw.
16
B
C
E
D
A. 10–32 hex nut
B. Ground-link screw
C. Line 1 (black)
D. Green ground wire
E. Neutral (center) wire
F. Line 2 (red)
6. Connect line 1 (black) and line 2 (red) wires to the outer
terminal block posts with 10-32 hex nuts.
7. Securely tighten hex nuts.
NOTE: For power supply cord replacement, only use a power
cord rated at 250 volts minimum, 40 amps or 50 amps that is
marked for use with nominal 1³⁄₈" (3.5 cm) diameter
connection opening, with ring terminals and marked for use
with ranges.
8. Replace terminal block access cover.
3-wire connection: Power Supply Cord
B
A
B
C
Direct Wire Installation: Copper or Aluminum Wire
Use this method only if local codes permit connecting chassis
ground conductor to neutral wire of power supply cord.
1. Feed the power supply cord through the opening in the cord/
conduit plate on bottom of range. Allow enough slack to
easily attach the wiring to the terminal block.
A
C
D
A. Terminal block
B. Ground-link screw
C. Cord/conduit plate
D. Power supply cord wires
This range may be connected directly to the fuse disconnect or
circuit breaker box. Depending on your electrical supply, make
the required 3-wire or 4-wire connection.
1. Strip outer covering back 3" (7.6 cm) to expose wires. Strip
the insulation back 1" (2.5 cm) from the end of each wire.
1"
(2.5 cm)
3"
(7.6 cm)
2. Allow enough slack in the wire to easily attach the wiring
terminal block.
3. Complete electrical connection according to your type of
electrical supply (4-wire or 3-wire connection).
4-wire Connection: Direct Wire
Use this method for:
■ New branch-circuit installations (1996 NEC)
■ Mobile homes
■ Recreational vehicles
■ In an area where local codes prohibit grounding through the
neutral
1. Part of metal ground strap must be cut out and removed.
2. Use ³⁄₈" nut driver to connect the neutral (white) wire to the
center terminal block post with one of the 10–32 hex nuts.
A
B
D
E
C
A. 10–32 hex nut
B. Line 1 (black)
C. Ground-link screw
D. Neutral (white) wire
E. Line 2 (red)
3. Connect line 1 (black) and line 2 (red) wires to the outer
terminal block posts with 10-32 hex nuts.
4. Securely tighten hex nuts.
NOTE: For power supply cord replacement, only use a power
cord rated at 250 volts minimum, 40 amps or 50 amps that is
marked for use with nominal 1³⁄₈" (3.5 cm) diameter
connection opening, with ring terminals and marked for use
with ranges.
5. Replace terminal block access cover.
A. Metal ground strap
B. Discard
C. Ground-link screw
2. Use Phillips screwdriver to remove the ground-link screw
from the back of the range. Save the ground-link screw and
the end of the ground-link under the screw.
17
3. Pull the conduit through the strain relief on cord/conduit plate
B
C
on bottom of range. Allow enough slack to easily attach
wiring to the terminal block.
A
5. Use Phillips screwdriver to connect the bare (green) ground
wire to the range with the ground-link screw. The ground wire
must be attached first and must not contact any other
terminal.
6. Use ³⁄₈" nut driver to connect the neutral (white) wire to the
center terminal block post with one of the 10–32 hex nuts.
B
C
G
F
A. Terminal block
B. Ground-link screw
C. Cord/conduit plate
D. Line 2 (red) wire
E
E. Neutral (white) wire
F. Line 1 (black) wire
G. Bare (green) ground wire
D
4. Attach terminal lugs to line 1 (black), neutral (white), and line 2
(red) wires. Loosen (do not remove) the set screw on the front
of the terminal lug and insert exposed wire end through
bottom of terminal lugs. Securely tighten set screw to torque
as shown in the following Bare Wire Torque Specifications
chart.
A
A
G
B
F
D
E
C
A. 10–32 hex nut
B. Line 1 (black)
C. Bare (green) ground wire
D. Ground-link screw
E. Neutral (white) wire
F. Line 2 (red)
G. Terminal lug
7. Connect line 1 (black) and line 2 (red) wires to the outer
terminal block posts with 10-32 hex nuts.
8. Securely tighten hex nuts.
9. Replace terminal block access cover.
3-wire connection: Direct Wire
Use this method only if local codes permit connecting ground
conductor to neutral supply wire.
1. Pull the conduit through the hole and conduit plate on bottom
of range. Allow enough slack to easily attach the wiring to the
terminal block.
C
DE
A. Terminal lug
B. Set screw
C. Line 1 (black) wire
D. Neutral (white) wire
E. Line 2 (red) wire
Bare Wire Torque Specifications
Attaching terminal lugs to the terminal block - 20 lbs-in. (2.3 N-m)
A. Terminal block
B. Ground-link screw
C. Cord/conduit plate
B
D
E
D. Line 2 (red) wire
E. Bare (green) ground wire
F. Line 1 (black) wire
18
2. Attach terminal lugs to line 1 (black), bare (green) ground, and
B
B
line 2 (red) wires. Loosen (do not remove) the set screw on the
front of the terminal lug and insert exposed wire end through
bottom of terminal lugs. Securely tighten set screw to torque
as shown in the following Bare Wire Torque Specifications
chart.
A
Connect Range to Downdraft System
1. Attach flexible vent (provided) to the blower motor inlet using
a vent clamp.
C
DE
A. Terminal lug
B. Set screw
C. Line 1 (black) wire
D. Bare (green) ground wire
E. Line 2 (red) wire
Bare Wire Torque Specifications
Attaching terminal lugs to the terminal block - 20 lbs-in. (2.3 N-m)
3. Use ³⁄₈" nut driver to connect the bare (green) ground wire to
the center terminal block post with one of the 10–32 hex nuts.
1
2
1
A
B
A. Inlet flexible vent
B. Vent clamp
2. Check countertop height to allow range top to clear
countertop. Adjusting leveling legs if necessary.
3. Remove access panel by grasping both sides, pulling
upward, and lifting out.
4. Move range close to cabinet opening.
5. Plug range into grounded outlet (if using a power supply
cord).
6. Plug range electrical connector into the downdraft blower
motor.
A
F
E
B
D
C
A. 10–32 hex nut
B. Line 1 (black)
C. Ground-link screw
D. Bare (green) ground wire
E. Line 2 (red)
F. Te r mi na l lu g
4. Connect line 1 (black) and line 2 (red) wires to the outer
terminal block posts with 10-32 hex nuts.
5. Securely tighten hex nuts.
6. Replace terminal block access cover.
A
A. Power supply cord (on some installations)
B. Range electrical connector to blower motor
7. Remove cardboard or hardboard from under the range. Using
2 or more people, gently move range into its final location.
19
8. Check that the anti-tip bracket is installed and that electrical
cords are not kinked. Use a flashlight to look underneath the
bottom of the range.
■ Look for the anti-tip bracket securely attached to floor or
wall.
■ Slide range back so rear range foot is under anti-tip
bracket.
Floor Venting
Top View
B
A
9. Level the range.
a.) Place rack in oven.
b.) Place level on rack and check levelness of the range, first
side to side; then front to back.
c.) If range is not level, pull range forward until rear leveling
leg is removed from the anti-tip bracket.
d.) Use a wrench or pliers to adjust leveling legs up or down
until range is level.
e.) Push range back into position.
f.) Check that rear leveling leg is engaged in anti-tip bracket.
NOTE: Range must be level for satisfactory baking performance.
10. Depending on your installation, connect the flexible vent from
the blower motor inlet to the range using a vent clamp.
Wall Venting
Top View
B
C
A. Range
B. Floor venting outlet
C. Vent clamp
Side Venting (left side venting shown)
Connect flexible vent duct to range and connect vent system
to blower motor outlet.
Top View
A
E
BLOWER
D
C
B
A. Flexible vent duct to range
B. Vent clamp
C. Range
D. Vent system
E. Side venting outlet
20
11. Replace access panel.
A
C
A. Range
B. Wall venting outlet
C. Vent clamp
12. Insert downdraft vent filter and place vent cover over
opening.
B
If you need Assistance or Service:
Please reference the “Assistance or Service” section of the Use
and Care Guide or contact the dealer from whom you purchased
your range.
A
A. Filter
B. Grate
13. Reconnect power.
Complete Installation
1. Check that all parts are now installed. If there is an extra part,
go back through the steps to see which step was skipped.
2. Check that you have all of your tools.
3. Dispose of/recycle all packaging materials.
4. Check that the range is level. See “Connect Range to
Downdraft System.”
5. Use a mild solution of liquid household cleaner and warm
water to remove waxy residue caused by shipping material.
Dry thoroughly with a soft cloth. For more information, read
the “Range Care” section of the Use and Care Guide.
6. Read “Range Use” in the range Use and Care Guide.
7. Turn on surface burners and oven. See the Use and Care
Guide for specific instruction on range operation.
If range does not operate, check the following:
■ Household fuse is intact and tight; or circuit breaker has not
tripped.
■ Range is plugged into an outlet.
■ Electrical supply is connected.
■ See “Troubleshooting” in the Use and Care Guide.
When the range has been on for 5 minutes, check for heat. If
range is cold, turn off the range and contact a qualified
technician.
8. Use the Flow Tester Card provided with your range to check
the airflow (see card for step-by-step instructions).
Moving the Range
WARNING
Tip Over Hazard
A child or adult can tip the range and be killed.
Connect anti-tip bracket to rear range foot.
Reconnect the anti-tip bracket, if the range is moved.
Failure to follow these instructions can result in death
or serious burns to children and adults.
When moving range, slide range onto cardboard or hardboard to
avoid damaging the floor covering.
If removing the range is necessary for cleaning or maintenance:
For power supply cord-connected ranges:
1. Disconnect range from downdraft vent system.
2. Slide range forward.
3. Unplug the power supply cord.
4. Complete cleaning or maintenance.
5. Plug in power supply cord
6. Check that anti-tip bracket is installed, remove access panel
and use a flashlight to look underneath the bottom of the
range:
■ Look for the anti-tip bracket securely attached to floor or
wall.
■ Slide range back so rear range foot is under anti-tip
bracket.
If there is not sufficient airflow, review the “Venting
Requirements” and “Venting Methods” sections.
7. Check that range is level.
8. Reconnect range to downdraft vent system.
21
For direct-wired ranges:
WARNING
Electrical Shock Hazard
Disconnect power before servicing.
Replace all parts and panels before operating.
Failure to do so can result in death or electrical shock.
4. Complete cleaning or maintenance.
5. To check that anti-tip bracket is installed, remove access
panel and use a flashlight and look underneath the bottom of
the range:
■ Look for the anti-tip bracket securely attached to floor or
wall.
■ Slide range back so rear range foot is under anti-tip
bracket.
1. Disconnect power.
2. Disconnect range from downdraft vent system.
3. Slide range forward.
6. Check that range is level.
7. Reconnect range to the downdraft vent system.
8. Reconnect power.
22
SÉCURITÉ DE LA CUISINIÈRE
Votre sécurité et celle des autres est très importante.
Nous donnons de nombreux messages de sécurité importants dans ce manuel et sur votre appareil ménager. Assurez-vous de
toujours lire tous les messages de sécurité et de vous y conformer.
Voici le symbole d’alerte de sécurité.
Ce symbole d’alerte de sécurité vous signale les dangers potentiels de décès et de blessures graves à vous
et à d’autres.
Tous les messages de sécurité suivront le symbole d’alerte de sécurité et le mot “DANGER” ou
“AVERTISSEMENT”. Ces mots signifient :
Risque possible de décès ou de blessure grave si vous ne
DANGER
AVERTISSEMENT
Tous les messages de sécurité vous diront quel est le danger potentiel et vous disent comment réduire le risque de blessure et
ce qui peut se produire en cas de non-respect des instructions.
AVERTISSEMENT
suivez pas immédiatement les instructions.
Risque possible de décès ou de blessure grave si vous
ne suivez pas les instructions.
Risque de basculement
Un enfant ou une personne adulte peut faire basculer la cuisinière ce qui peut causer un décès.
Joindre la bride antibasculement au pied arrière de la cuisinière.
Joindre de nouveau la bride antibasculement si la cuisinière est déplacée.
Le non-respect de ces instructions peut causer un décès ou des brûlures graves aux enfants et
aux adultes.
23
EXIGENCES D’INSTALLATION
Outils et pièces
Rassembler les outils et composants nécessaires avant
d’entreprendre l’installation. Lire et observer les instructions
fournies avec chacun des outils de la liste ci-dessous.
Outils nécessaires
■ Mètre-ruban
■ Niveau
■ Tournevis Phillips
■ Tournevis à lame plate
■ Scie sauteuse ou scie à
guichet
■ Marqueur ou crayon
Pièces fournies
Vérifier que toutes les pièces sont présentes.
■ 3 écrous hexagonaux de #10-32 (vissés au boîtier de
connexion)
■ 3 attaches de bornes
■ 2 ou 3 grilles de four (en fonction du modèle)
■ Moteur du ventilateur
■ 2 brides pour conduit
■ Conduit flexible
■ Fiche de test du débit
■ Gabarit pour l’emplacement du ventilateur
■ 4 vis n° 8 x ¾" (pour le montage de la bride du ventilateur)
■ 2 vis n° 12 x 1⁵⁄₈" (pour le montage de la bride
antibasculement)
■ Bride antibasculement (fixée par du ruban adhésif à la
pochette contenant la documentation dans la cavité du four)
La bride antibasculement doit être bien fixée à la cloison
arrière ou au plancher. La profondeur du plancher peut
nécessiter des vis plus longues pour l’ancrage de la bride
dans le sous-plancher. Des vis plus longues sont disponibles
auprès de votre quincaillerie locale.
Pièces nécessaires
■ L’une des bouches de décharge murales Jenn-Air suivantes :
Clapet de décharge mural en surface rond Jenn-Air
5" (12,7 cm). Commander la pièce n° A405.
Clapet de décharge mural en surface rond Jenn-Air
6" (15,2 cm). Commander la pièce n° A406.
Clapet de décharge mural en surface Jenn-Air
(8,3 x 25,4 cm). Commander la pièce n° A403.
Pour commander, voir la section “Assistance ou service” du
Guide d’utilisation et d’entretien.
■ Conduit métallique
■ Brides pour conduit
■ Chevilles à béton (pour montage sur sol en béton)
■ 2 cales en bois 2" x 4" x 8¾" (5 x 10,2 x 22,2 cm) (pour
évacuation par la gauche ou par la droite)
■ Clé ou pince
■ Tourne-é c r ou d e ⁵⁄₁₆"
■ Tourne-é c r ou d e ¼ "
■ Perceuse
■ Foret de ¹⁄₈" (3,2 mm)
■ Foret à maçonnerie à pointe
carburée de ³⁄₁₆" (4,8 mm)
(pour planchers en béton/
céramique)
®
de
®
de
®
3¼" x 10"
En cas d’utilisation d’un cordon d’alimentation électrique :
■ Cordon d’alimentation (homologation UL) conçu pour
l’utilisation avec une cuisinière. Pour service 250 volts
minimum, 40 A ou 50 A, compatible avec une ouverture de
diamètre nominal 1³⁄₈" (3,5 cm) pour le raccordement, et avec
cosses rondes ou en fourche à pointes relevées à l’extrémité
de chaque conducteur.
■ Un serre-câble (homologation UL).
Consulter les codes locaux. Vérifier l’alimentation électrique
existante. Voir la section “Spécifications électriques”.
Il est recommandé de faire réaliser tous les raccordements
électriques par un électricien qualifié agréé.
Exigences d’emplacement
IMPORTANT : Observer les dispositions de tous les codes et
règlements en vigueur.
■ C’est à l’installateur qu’incombe la responsabilité de
respecter les distances de séparation exigées, spécifiées sur
la plaque signalétique de l’appareil. La plaque signalétique
est située sur le côté droit du châssis du four, derrière le
panneau du tiroir de remisage.
■ La cuisinière doit être installée à un endroit pratique dans la
cuisine.
■ Afin de supprimer le risque de brûlures ou d’incendie lié au
fait de se pencher au-dessus des plaques de cuisson
chaudes, les meubles de rangement au-dessus des plaques
doivent être évités. Si des placards de rangement sont
envisagés, le risque peut être réduit par l’installation d’une
hotte de cuisine dépassant le bas des placards d’au moins 5"
(12,7 cm) horizontalement.
■ Respecter les dimensions indiquées pour les ouvertures à
découper dans les placards. Ces dimensions constituent les
valeurs minimales des dégagements.
■ La bride antibasculement de plancher doit être installée. Pour
l’installation de la bride antibasculement fournie avec la
cuisinière, voir la section “Installation de la bride
antibasculement”.
■ Une source d’électricité avec liaison à la terre est nécessaire.
Voir la section “Spécifications électriques”.
IMPORTANT : Afin d’éviter d’endommager les placards,
consulter le constructeur de la maison ou le fabricant des
placards pour déterminer si les matériaux utilisés peuvent subir
un changement de couleur, une déstratification ou d’autres
dommages. Ce four a été conçu conformément aux exigences
des normes UL et CSA International et respecte les températures
maximales permises de 194°F (90°C) pour les placards en bois.
Résidence mobile – Spécifications additionnelles à
respecter lors de l’installation
L’installation de cette cuisinière doit être conforme aux
dispositions de la norme Manufactured Home Construction and
Safety Standard, Title 24 CFR, Part 3280 (anciennement Federal
Standard for Mobile Home Construction and Safety, Title 24,
HUD Part 280). Lorsque cette norme n’est pas applicable,
l’installation doit satisfaire aux critères de la norme Standard for
Manufactured Home Installations, ANSI A225.1/NFPA 501A ou
aux dispositions des codes locaux.
24
Autres critères à respecter pour une installation en résidence
mobile :
■ Dans le cas de l’installation de cette cuisinière dans une
résidence mobile, la cuisinière doit être fixée au plancher
durant tout déplacement du véhicule. Toute méthode de
fixation de la cuisinière est adéquate dans la mesure où elle
satisfait aux critères des normes mentionnées ci-dessus.
■ Pour une installation en résidence mobile, un câble ou cordon
d’alimentation à quatre fils doit être utilisé. Le câblage de
l’appareil devra être révisé. Voir la section “Raccordement
électrique”.
Dimensions du placard
Les dimensions de l’espace entre les placards correspondent à
une installation entre des placards de 24" (61,0 cm) de
profondeur, avec plan de travail de 25" (64 cm) de profondeur et
de 36" (91,4 cm) de hauteur.
A
B
C
Dimensions du produit
A
F
B*
E**
D
A. 30³⁄₄" (78,1 cm)
B. Hauteur jusqu’à la partie
inférieure du bord de la
table de cuisson avec les
pieds de nivellement
complètement rétractés :
35³⁄₄" (90,8 cm)*
C. Plaque signalétique (située
en bas à droite du châssis
du four)
D. 29⁷⁄₈" (75,9 cm)
E. 29¹⁄₁₆" (73,8 cm) de la
poignée au support à
l’arrière de la cuisinière**
F. 23½" (59,7 cm) du coin du
plan de travail à l’arrière
de la table de cuisson
*La cuisinière peut être surélevée d’environ 1" (2,5 cm) en
ajustant les pieds de nivellement.
**Dans le cas d’une installation entre des placards de
24" (61 cm) avec plan de travail de 25" (63,5 cm), l’avant
de la porte du four dépassera les placards inférieurs de
24" (61 cm) d'une distance de 2¹⁄₂" (6,4 cm).
C
H
E
D
I
I
F
G
A. Profondeur des placards
supérieurs : 13" (33 cm)
B. Largeur de l’ouverture
30" (76,2 cm) min.
C. Pour le dégagement vertical
minimal de la table de
cuisson, voir la REMARQUE*.
D. Profondeur d'ouverture de
¹⁄₄" (59,1 cm)
E. Largeur de l’ouverture
30" (76,2 cm) min.
F. Boîtier de connexion :
5,5" (14 cm) min. de l’un des
deux placards, 10" (25,4 cm)
max. du plancher. La prise
doit être en affleurement.
Aucun élément situé dans la
zone ombrée ne doit
dépasser de plus de
2" (5,1 cm) du mur, sinon il
sera impossible de glisser la
cuisinière jusqu’au fond.
G. La porte ou charnière du
placard ne doit pas dépasser
à l’intérieur de l’ouverture.
H. 18" (45,7 cm)
I. Dégagement de 3" (7,6 cm)
min. entre les deux côtés de
la cuisinière et les parois
latérales ou d’autres
matériaux combustibles.
REMARQUE : Distance de séparation minimale de 24" (61 cm)
lorsque le fond d’un placard de bois ou de métal est protégé par
une planche ignifugée d’au moins ¹⁄₄" (0,64 cm) recouverte d’une
feuille métallique d’épaisseur égale ou supérieure à : acier calibre
28 MSG, acier inoxydable 0,015" (0,4 mm), aluminium
0,024" (0,6 mm), ou cuivre 0,020" (0,5 mm).
Distance de séparation minimale de 30" (76,2 cm) ou plus entre le
dessus de la table de cuisson et le fond d’un placard de bois ou
de métal non protégé.
25
Exigences concernant l’évacuation
IMPORTANT : Cette cuisinière doit être ventilée vers l’extérieur.
Voir la section “Méthodes d’évacuation”.
■ Ne pas terminer le circuit d’évacuation dans un grenier ou
dans un autre espace fermé.
■ Utiliser une bouche de décharge murale Jenn-Air.
■ Le circuit doit évacuer l’air à l’extérieur.
■ Utiliser uniquement un conduit métallique rond de
6" (15,2 cm) ou un conduit rectangulaire de 3¼ x 10"
(8,3 cm x 25,4 cm), sauf dans les cas suivants :
Un conduit métallique rond de 5" (12,7 cm) peut être utilisé
pour une évacuation directement depuis l’arrière de la
cuisinière à travers le mur sur une longueur de 10 pi (3,0 m)
au maximum.
■ Un conduit en métal rigide est recommandé. Pour des
performances optimales, ne pas utiliser de conduit de
plastique ou d’aluminium.
■ Avant d’effectuer des découpes, s’assurer que l’espace est
suffisant sur le mur ou le plancher pour le conduit
d’évacuation.
■ On ne doit couper un poteau de colombage ou une solive
que si c’est absolument nécessaire. Dans ce cas, on devra
construire une structure de support appropriée.
■ La taille du conduit doit être uniforme.
■ Le circuit d’évacuation doit comporter un clapet anti-retour.
Si la bouche de décharge murale ou par le toit comporte un
clapet, ne pas utiliser le clapet fourni avec la hotte de
cuisinière.
■ Pour assurer l’étanchéité de toutes les jonctions du circuit
d’évacuation, utiliser des brides pour conduit.
■ À l’aide d’un produit de calfeutrage, assurer l’étanchéité
autour de la bouche de décharge à l’extérieur (à travers le
mur ou le toit).
■ Déterminer la méthode d’évacuation la plus appropriée.
Pour obtenir des performances optimales :
■ Utiliser un conduit métallique en acier galvanisé de calibre
26 minimum ou en aluminium de calibre 25 minimum. Des
raccords de tube de qualité médiocre peuvent réduire la
circulation d’air. On déconseille l’emploi d’un conduit en
métal flexible.
REMARQUE : Les codes locaux peuvent imposer un
matériau d’épaisseur supérieure.
■ Les conduits métalliques peuvent être réduits à de l’acier
galvanisé de calibre 30 ou de l’acier aluminisé de calibre 26 si
les codes locaux l’autorisent. Cette réduction repose sur les
informations du document International Residential Codes
Section M1601.1 (édition 2006).
■ Ne pas installer 2 coudes successifs.
■ Ne pas utiliser plus de trois coudes à 90°.
■ Si un coude est utilisé, on doit le placer le plus loin possible
de l’ouverture de décharge du ventilateur de la hotte.
■ Veiller à incorporer une section de conduit rectiligne d’au
moins 18" (45,7 cm) entre deux raccords coudés adjacents.
■ Des coudes trop rapprochés peuvent occasionner une
turbulence excessive qui réduit la circulation de l’air.
■ Ne pas utiliser de coude de 5" (12,7 cm) dans un circuit de
6" (15,2 cm) ou 3¹⁄₄" x 10" (8,3 x 25,4 cm).
■ Ne pas effectuer de réduction en un circuit de 5" (12,7 cm)
après avoir utilisé des raccords de 6" (15,2 cm) ou 3¼" x 10"
(8,3 x 25,4 cm).
■ Éviter les assemblages par sertissage à la main. Les
sertissages à la main peuvent réduire la circulation d’air.
■ Utiliser une bouche de décharge Jenn-Air. Si une autre
bouche de décharge de toit ou murale est utilisée, s’assurer
que ses dimensions ne sont pas plus petites et qu’elle est
équipée d’un clapet anti-retour.
■ Pour assurer l’étanchéité de toutes les jonctions du circuit
d’évacuation, utiliser des brides pour conduit.
■ À l’aide d’un produit de calfeutrage, assurer l’étanchéité
autour de la bouche de décharge à l’extérieur (à travers le
mur ou le toit).
La longueur du système d’évacuation et le nombre de coudes
doit être réduit au minimum pour une performance optimale.
La longueur équivalente maximale du circuit d’évacuation est de
60 pi (18,3 m). À une altitude supérieure à 4500 pi (1272 m),
réduire la longueur de 20 % pour une meilleure performance.
Installations dans les régions au climat froid
On devrait installer un clapet anti-retour additionnel pour
minimiser le reflux d’air froid et installer une barrière thermique
pour minimiser la conduction des températures extérieures par
l’intermédiaire du conduit d’évacuation. Le clapet anti-retour être
placé du côté air froid de la barrière thermique.
Air d’appoint
Les codes locaux en bâtiment peuvent imposer l’emploi d’un
circuit de renouvellement de l’air/introduction d’air d’appoint, lors
de l’utilisation d’un circuit d’aspiration de débit supérieur à une
valeur spécifiée en pieds cubes par minute. Le débit spécifié en
pieds cubes par minute varie d’une juridiction à l’autre. Consulter
un professionnel des installations de chauffage/ventilation/
climatisation au sujet des exigences spécifiques applicables
dans la juridiction locale.
26
Méthodes d’évacuation
A
A
F
Les méthodes communes d’évacuation sont illustrées pour une
cuisinière à aspiration par le bas. L’évacuation de la cuisinière à
aspiration par le bas peut se faire par le mur ou le plancher.
Installations sur dalle de béton - Évacuation par le mur
B
Évacuation par le mur
A. Bouche de décharge murale
B. Conduit de dia. 6" (15,2 cm) –
sortie à travers le toit
Évacuation par le plancher
Évacuation entre solives de plancher
A
L
K
J
C
I
D
E
G
H
A. Bouche de décharge murale
B. Conduit métallique rond de dia. 6" (15,2 cm)
C. 16" (40,6 cm) maximum
D. Conduit PVC dia. 6" (15,2 cm) (pour égout)
E. Dalle de béton
F. Conduit PVC dia. 6" (15,2 cm) (pour égout)
G. Coudé à 90° PVC dia. 6" (15,2 cm) (pour égout)
B
H. Gravier ou sable compacté tout autour du tuyau
I. 30 pi (9,1 m) max.
J. Coudé à 90° PVC dia. 6" (15,2 cm) (pour égout)
K. Raccord PVC dia. 6" (15,2 cm)
L. 12" (30,5 cm) minimum
Installations sur dalle de béton
- Évacuation par un puits de fenêtre
IMPORTANT : Installation à travers un puits de fenêtre pour
modèles électriques uniquement.
B
D
A
C
A
B
A. Bouche de décharge murale
B. Conduit de dia. 6" (15,2 cm) – sortie à travers le toit
Évacuation par la gauche ou par la droite
Évacuation derrière les garde-pieds des placards
B
A. Bouche de décharge murale
B. Conduit de dia. 6" (15,2 cm) – sortie à travers le toit
E
K
J
A. Bouche de décharge murale
B. 12" (30,5 cm) minimum
C. Dalle de béton
D. Conduit PVC dia. 6" (15,2 cm) (pour égout)
E. Conduit PVC dia. 6" (15,2 cm) (pour égout)
F. Coudé à 90° PVC dia. 6" (15,2 cm) (pour égout)
G. Gravier ou sable compacté tout autour du tuyau
H. 42 pi (12,8 m) max.
I. Raccord PVC dia. 6" (15,2 cm)
J. 6" (15,2 cm) minimum
K. Puits de fenêtre
H
I
F
G
27
Calcul de la longueur effective du circuit d’évacuation
IMPORTANT : Cette cuisinière accepte jusqu’à 60 pi (18,3 m)
de conduit droit. Le mode à faible aspiration admet jusqu’à
30 pi (9,1 m); le mode à forte aspiration admet de 31 pi (9,4 m) à
60 pi (18,3 m).
Si la longueur équivalente de conduit dépasse 30 pi (18,3 m), le
ventilateur doit être converti au mode à forte aspiration.
■ Ne pas convertir au mode à forte aspiration pour les
longueurs plus courtes. Il en résulterait un bruit excessif,
une perte d’air conditionné et une déformation des
flammes sur les cuisinières à gaz.
■ Pour convertir le ventilateur dans le cas d’une installation
dans le mode à forte aspiration, voir la section
“Installation du circuit d’évacuation par le bas”.
Pour calculer la longueur effective du circuit d’évacuation
nécessaire, additionner les longueurs équivalentes (en pieds ou
mètres) de tous les composants utilisés dans le système.
ComposantConduit de diamètre de 6"
(15,2 cm)
Coude à 45°2,5 pi
(0,8 m)
Coudé à 90° de
6" (15,2 cm) vers 3¹⁄₄" x 10"
5 pi
(1,5 m)
(8,3 cm x 25,4 cm)
Coude à 90° de 3¹⁄₄" x
10" (8,3 cm x 25,4 cm)5 pi
(1,5 m)
Coude plat de 3¹⁄₄" x
10" (8,3 cm x 25,4 cm)12 pi
(3,7 m)
Bouche de décharge murale de
3¹⁄₄" x 10" (8,3 cm x 25,4 cm)0 pi
(0 m)
Exemple de circuit d’évacuation
Coude à 90°5 pi
(1,5 m)
Bouche de décharge murale
de 6" (15,2 cm)
Raccord de 3¹⁄₄" x 10" (8,3 cm
x 25,4 cm) vers 6" (15,2 cm)
Raccord de 6" (15,2 cm) vers
3¹⁄₄" x 10" (8,3 cm x 25,4 cm)
Coudé à 90° de 3¹⁄₄" x 10"
(8,3 cm x 25,4 cm) vers
0 pi
(0 m)
4,5 pi
(1,4 m)
1 pi
(0,3 m)
5 pi
(1,5 m)
6" (15,2 cm)
coude à 90˚
2 pi
(0,6 m)
bouche de décharge murale
6 pi (1,8 m)
Longueur maximum= 60 pi (18,3 m)
1 coude à 90°= 5 pi (1,5 m)
Section droite de 8 pi
= 8 pi (2,4 m)
(2,4 m)
1 bouche de décharge
= 0 pi (0 m)
murale
Longueur totale= 13 pi (3,9 m)
REMARQUE : On déconseille l’emploi d’un conduit flexible pour
une évacuation vers l’extérieur. Un conduit flexible peut causer
une contre-pression et des turbulences d’air, qui réduisent
considérablement la performance.
28
Spécifications électriques
AVERTISSEMENT
Risque de choc électrique
Relier la cuisinière à la terre.
Le non-respect de cette instruction peut causer
un décès, un incendie ou un choc électrique.
Si l’on utilise un conducteur distinct de liaison à la terre lorsque
les codes le permettent, il est recommandé qu’un électricien
qualifié vérifie que la liaison à la terre est adéquate et la section
des fils conforme aux codes locaux.
Vérifier que le raccordement à la source d’électricité et le calibre
des conducteurs sont conformes aux prescriptions de la plus
récente édition de la norme CSA C22.1, partie 1 – Code canadien
de l’électricité, et de tout code ou règlement local en vigueur.
Pour obtenir un exemplaire des normes des codes ci-dessus,
contacter :
Canadian Standards Association
178 Rexdale Blvd.
Toronto, ON M9W 1R3 CANADA
■ En cas de doute quant à la qualité de la liaison à la terre de la
cuisinière, consulter un électricien qualifié.
Préparation du plan de travail
(cuisinières encastrées uniquement)
Les flancs de la cuisinière encastrable s'ajustent par-dessus le
bord de la découpe du plan de travail.
Si le plan de travail est plat aux arêtes carrées et la largeur de
l'ouverture est de 30" (76,2 cm), aucune préparation du plan de
travail n'est nécessaire.
Dans le cas d'un plan de travail à bords avant bombés, on devra
usiner une surface plane dans le bord moulé de ³⁄₈" (1,0 cm) à
chaque coin avant de l'ouverture.
Dans le cas d'un plan de travail de carrelage, il peut être
nécessaire de réduire le revêtement de ³⁄₈" (1 cm) à chaque coin
avant et/ou d'aplanir le bord avant arrondi.
30"
(76,2 cm)
30 ¾"
(78,1 cm)
Si la largeur de l'ouverture du plan de travail est supérieure à
30" (76,2 cm), ajuster la dimension ³⁄₈" (1,0 cm).
Le plan de travail doit être d’aplomb. Placer un niveau sur le plan
de travail, d'abord transversalement, puis dans la profondeur. Si
le plan de travail n’est pas d'aplomb, la cuisinière ne le sera pas.
La cuisinière doit être d'aplomb pour pouvoir obtenir des
résultats de cuisson satisfaisants.
³⁄₈"
(1,0 cm)
Puissance nominale de la
cuisinière*
120/240 volts120/208 voltsAA
8,8 - 16,5 kW
16,6 - 22,5 KW
*La charge NEC calculée est inférieure à la charge totale
connectée indiquée sur la plaque signalétique.
■ On recommande d’utiliser un fusible ou un disjoncteur
temporisé.
■ Cette cuisinière est équipée d’un cordon électrique
homologué par la CSA International à brancher dans une
prise murale standard 14-50R. Veiller à ce que la prise murale
se trouve à proximité de l’emplacement définitif de la
cuisinière.
■ Ne pas utiliser de câble de rallonge.
7,8 - 12,5 kW
12,6 - 18,5 KW4050
Calibre du
cordon
d’alimentation
Protection
du circuit
40 ou 50
50
29
INSTRUCTIONS D’INSTALLATION
Déballage de la cuisinière
AVERTISSEMENT
Risque du poids excessif
Utiliser deux ou plus de personnes pour déplacer et
installer la cuisinière.
Le non-respect de cette instruction peut causer
une blessure au dos ou d'autre blessure.
1. Ôter les matériaux d’emballage, le ruban adhésif et la
pellicule protectrice de la cuisinière. Garder la base de carton
sous la cuisinière.
2. Retirer les grilles de four et le sachet de pièces de l’intérieur
du four.
3. Pour retirer la base en carton, placer la cuisinière sur sa partie
postérieure, prendre les 4 coins de protection du carton
d’emballage. Empiler l’un des coins sur un autre. Répéter
avec les 2 autres coins. Les disposer sur le plancher dans le
sens de la longueur derrière la cuisinière, à titre de support de
la cuisinière lorsque celle-ci est placée sur sa partie
postérieure.
4. À 2 personnes ou plus, saisir fermement la cuisinière et la
déposer délicatement sur sa partie postérieure, sur les coins
de protection du carton.
5. Tirer fermement sur la partie inférieure du carton pour le
retirer.
6. Utiliser une clé à molette pour desserrer les pieds de
nivellement.
7. Placer le carton ou le panneau de fibres dur devant la
cuisinière. À l’aide d’au moins 2 personnes, relever la
cuisinière et la placer sur le carton ou le panneau de fibres
dur.
Réglage des pieds de nivellement
1. Si un ajustement de la hauteur de la cuisinière est nécessaire,
utiliser une clé ou une pince pour desserrer les 4 pieds de
nivellement.
Cette opération doit être effectuée alors que la cuisinière
repose sur sa partie postérieure ou qu’elle est supportée par
2 pieds après avoir été replacée en position verticale.
REMARQUE : Pour placer à nouveau la cuisinière en position
verticale, placer un carton ou un panneau de fibres dur
devant la cuisinière. À l'aide d'au moins 2 personnes,
redresser la cuisinière et la placer sur le carton ou le panneau
de fibres dur.
AVERTISSEMENT
Risque de basculement
Un enfant ou une personne adulte peut faire basculer
la cuisinière ce qui peut causer un décès.
Joindre la bride antibasculement au pied arrière de
la cuisinière.
Joindre de nouveau la bride antibasculement si la
cuisinière est déplacée.
Le non-respect de ces instructions peut causer un
décès ou des brûlures graves aux enfants et aux
adultes.
2. Ajuster les pieds de nivellement à la hauteur nécessaire. Les
pieds de nivellement peuvent être desserrés pour ajouter une
hauteur maximale de 1" (2,5 cm). Une longueur minimale de
³⁄₁₆" (5 mm) est nécessaire pour engager la bride
antibasculement.
REMARQUE : Si un ajustement de la hauteur est effectué
alors que la cuisinière est debout, incliner la cuisinière vers
l’arrière pour ajuster les pieds avant, puis incliner la cuisinière
vers l’avant pour ajuster les pieds arrière.
3. Lorsque la cuisinière est à la hauteur souhaitée, vérifier que
l’espace sous la cuisinière est suffisant pour loger la bride
antibasculement. Avant de faire glisser la cuisinière à son
emplacement final, vérifier qu’il sera possible de faire glisser
la bride antibasculement sous la cuisinière et sur le pied de
nivellement arrière avant l’installation de la bride
antibasculement.
30
Installation de la bride antibasculement
B
B
1. Ôter la bride antibasculement fixée par du ruban adhésif à la
pochette contenant la documentation.
2. Déterminer la méthode de montage à utiliser : au plancher ou
au mur.
Pour un plancher en pierre ou en briquetage, on peut utiliser
la méthode de montage au mur.
3. Déterminer et marquer l’axe central de l’espace à découper.
On peut installer la bride de montage du côté gauche ou droit
de la découpe. Positionner la bride de montage dans la zone
découpée de façon à ce que le bord (droit ou gauche) de la
bride se trouve à 14¹⁄₄" (36,2 cm) de l’axe central, tel
qu’illustré.
A
Montage mural
A
A. Vis n° 12 x 1⁵⁄₈"
B. Bride antibasculement
5. À l’aide d’un tournevis Phillips, monter la bride
antibasculement sur le mur ou sur le plancher avec les deux
vis n° 12 x 1⁵⁄₈" fournies.
B
A. Axe central
B. 14¹⁄₄" (36,2 cm)
4. Percer deux trous de ¹⁄₈" (3,0 mm) qui correspondent aux
trous de la bride selon la méthode de montage déterminée.
Voir ci-dessous.
Montage au plancher
A
A. Vis n° 12 x 1⁵⁄₈"
B. Bride antibasculement
B
Installation du circuit d’évacuation
par le bas
Déterminer la longueur équivalente du circuit
d’évacuation
Cette cuisinière est équipée d’un ventilateur à deux débits. Sa
configuration d’usine concerne les installations à faible
aspiration. Si la longueur équivalente du système d’évacuation
par le bas dépasse 30 pieds (9,1 m), le moteur du ventilateur
d’aspiration doit être converti au mode à forte aspiration pour
une meilleure performance. Voir “Calcul de la longueur effective
du circuit d’évacuation”.
Pour effectuer la conversion :
Retirer doucement l’anneau de réduction à ressort de l’entrée du
ventilateur en appuyant sur l’un des trois ressorts.
A
A. Anneau de réduction
B. Ressort
Déterminer la méthode d’évacuation à utiliser : par le plancher, le
mur arrière, le côté droit ou le côté gauche. Consulter la section
se rapportant à votre type d’évacuation.
31
Évacuation par le mur arrière
1. Tracer sur le mur l’axe central de l’ouverture entre les
placards.
4. Placer le ventilateur dans l’ouverture entre les placards.
Raccorder le circuit d'évacuation à la sortie du ventilateur à
l’aide d’une bride pour conduit.
Vue de dessus
E
2. Vérifier l’absence d’obstruction avant de tracer
l’emplacement du trou d’évacuation. Tracer une ligne
horizontale à 8³⁄₁₆" (20,8 cm) du sol. Tracer une ligne verticale
à droite de l’axe central entre les placards, distante de
2¼" (7,9 cm) au maximum de l’axe central.
A
B
A. 2¼" (7,9 cm) maximum à droite
de l’axe central
B. 8³⁄₁₆" (20,8 cm) du sol
3. Tracer et découper un trou de 6¼" (15,8 cm) de diamètre.
C
D
A
B
A. 18¾" (47,6 cm) maximum entre l’ouverture
entre les placards et le mur arrière
B. Entrée
C. Circuit d’évacuation
D. Bride pour conduit
E. Évacuation murale
5. Fixer le ventilateur au sol avec les 4 vis n° 8 x ¾" à tête
hexagonale fournies.
Vue de dessus
A
A. 6¼" (15,8 cm)
6. Voir la section “Raccordement électrique”.
32
Évacuation par le plancher
Vue de dessus
1. Tracer au sol l’axe central de l’ouverture entre les placards.
2. Placer le gabarit sur le sol à 2¼" (5,7 cm) du mur arrière en
faisant correspondre son axe central avec l’axe central tracé
au sol.
3. Déterminer la position correcte du trou d’évacuation en
fonction des obstructions (solives) dans le plancher.
Le trou peut être découpé partout dans les limites de l’une
des zones hachurées.
Option 1 : En cas d’utilisation de la zone hachurée arrière (la
plus grande), l’entrée du ventilateur doit faire face au côté
gauche, comme illustré sur le gabarit.
Option 2 : En cas d’utilisation de la zone hachurée avant (la
plus petite), l’entrée du ventilateur doit faire face au mur
arrière.
Vue de dessus
Option 1Option 2
B
C
D
A
E
F
G
I
H
A. 9" (22,8 cm)
B. 3¹⁄₈" (7,9 cm)
C.8³⁄₈" (21,3 cm)
D. 6³⁄₈" (16,2 cm)
E. 2¼" (5,7 cm)
F. 12½" (31,7 cm)
G. 18¾" (47,6 cm)
H. 1½" (3,8 cm)
I. 3½" (8,9 cm)
4. Tracer et découper un trou de 6¼" (15,8 cm) de diamètre
(option 1 illustrée).
B
A
A
B
A. Entrée depuis la cuisinière
B. Sortie d’évacuation
REMARQUE : Si le gabarit est égaré, les mesures suivantes
peuvent servir à déterminer l’emplacement du trou
d’évacuation.
B
A
A. Option 1
B. Option 2
5. Placer le moteur du ventilateur dans l’ouverture entre les
placards et le fixer au sol.
Vue de dessus
Option 1Option 2
B
A
A
B
A. Entrée depuis la
cuisinière
B. Sortie d’évacuation
33
6. Raccorder le circuit d’évacuation à la sortie du moteur du
ventilateur (option 1 illustrée) avec les 4 vis n° 8 x ¾" à tête
hexagonale fournies.
3. Tracer et découper une ouverture de 14" x 11" (35,6 x
27,9 cm) dans le plancher du placard portant la découpe du
trou d’évacuation.
Vue de dessus
A
B
C
A. Entrée
B. Bride pour conduit
C. Plancher
D. Circuit d’évacuation
D
7. Voir la section “Raccordement électrique”.
Évacuation par la gauche ou par la droite
1. Repérer sur le côté du placard l’emplacement du trou
d’évacuation à droite ou à gauche.
A
A. 31³⁄₁₆" (79,2 cm) jusqu’en haut du placard
B. 18" (45,7 cm) depuis le mur arrière
2. Tracer et découper un trou de 5½" (13,9 cm) de diamètre sur
le placard du côté souhaité.
B
A
B
A. 11" (27,9 cm) à partir de l’avant du placard
B. 14" (35,6 cm) à partir du côté gauche du placard
4. Dévisser les quatre écrous de blocage du côté moteur du
ventilateur et retirer la bride.
Vue du ventilateur côté moteur
A
A. Connecteur électrique
5. Soulever le moteur et le faire pivoter de 180° pour replacer la
connexion électrique.
34
A
A. Trou de 5½" (13,9 cm) de diamètre
A
A. Connecteur électrique
6. Faire pivoter le support de 180° et le fixer avec les 4 écrous
de blocage.
7. Dévisser le support de l’autre côté du ventilateur, le faire
B
pivoter de 180° et le fixer avec les 4 écrous de blocage.
Raccordement de la cuisinière au circuit
d’évacuation par le bas
1. Raccorder le conduit flexible (fourni) à l’entrée du ventilateur
à l’aide d’une bride pour conduit.
8. Placer 2 cales en bois et les fixer au sol.
Vue de dessus
B
C
A
A. Cales de 2" x 4" (5 x 10,2 cm) en bois
B. 2⁷⁄₉" (7.3 cm) entre l’arrière du mur et le bord de la
cale en bois
C. 8¾" (22,2 cm)
D. 2⁵⁄₁₆" (5,8 cm) entre l’axe central de l’ouverture et la
cale en bois
D
D
9. Fixer le ventilateur aux cales en bois avec les 4 vis n° 8 x ¾" à
tête hexagonale fournies.
REMARQUE : Le circuit d’évacuation sera raccordé une fois
la cuisinière à son emplacement final. Voir la section
“Raccordement de la cuisinière au circuit d’évacuation par le
bas”.
Vue de dessus
1
2
1
A
B
A. Conduit flexible d’entrée
B. Bride pour conduit
2. Vérifier la hauteur du plan de travail pour s’assurer que la
cuisinière passe dessous. Régler les pieds de nivellement le
cas échéant.
3. Déposer le panneau d’accès en le tirant vers le haut des deux
mains de chaque côté et en le soulevant pour l'extraire.
4. Déplacer la cuisinière près de l’ouverture d’encastrement.
5. Brancher la cuisinière à une prise reliée à la terre (en cas
d’utilisation d’un cordon d’alimentation).
6. Brancher le connecteur électrique de la cuisinière au
ventilateur d’évacuation par le bas.
A
B
C
A
A. Cales en bois
B. Bride de montage
C. Ventilateur
A. Cordon d’alimentation (sur certaines installations)
B. Connecteur électrique de la cuisinière au ventilateur
35
7. Retirer le carton ou le panneau de fibre dur de sous la
cuisinière. À deux personnes ou plus, déplacer doucement la
cuisinière à son emplacement final.
10. Selon votre installation, raccorder le conduit flexible d’entrée
du ventilateur à la cuisinière au moyen d’une bride pour
conduit.
Évacuation par le mur
Vue de dessus
B
8. Vérifier que la bride antibasculement est installée et que les
câbles électriques ne sont pas pincés. Au moyen d’une
torche électrique, inspecter le dessous de la cuisinière.
■ Vérifier que la bride antibasculement est bien fixée au
plancher ou au mur.
■ Faire glisser de nouveau la cuisinière de façon à ce que le
pied arrière de la cuisinière se trouve sous la bride
antibasculement.
9. Régler l’aplomb de la cuisinière.
a.) Placer la grille dans le four.
b.) Placer un niveau sur la grille et contrôler l’aplomb de la
cuisinière, d’abord transversalement, puis dans le sens
avant/arrière.
A
C
A. Cuisinière
B. Sortie d’évacuation murale
C. Bride pour conduit
Évacuation par le plancher
Vue de dessus
B
A
C
A. Cuisinière
B. Sortie d’évacuation par le plancher
C. Bride pour conduit
c.) Si la cuisinière n’est pas d’aplomb, la tirer de nouveau
pour que le pied de nivellement arrière se dégage de la
bride antibasculement.
d.) Utiliser une pince multiprise pour régler les pieds de
nivellement vers le haut ou vers le bas jusqu’à ce que la
cuisinière soit d’aplomb.
e.) Repousser la cuisinière pour la remettre en place.
f.) Vérifier que le pied de nivellement arrière est engagé dans
la bride antibasculement.
REMARQUE : La cuisinière doit être d’aplomb pour que les
résultats de cuisson au four soient satisfaisants.
36
Évacuation latérale (évacuation par la gauche illustrée)
Raccorder le conduit d’évacuation flexible à la cuisinière et le
circuit d’évacuation à la sortie du ventilateur.
Vue de dessus
A
E
BLOWER
D
C
B
A. Conduit flexible vers la
cuisinière
B. Bride pour conduit
C. Cuisinière
D. Circuit d’évacuation
E. Sortie d’évacuation
latérale
11. Replacer le panneau d’accès.
Achever l’installation
1. Vérifier que toutes les pièces sont maintenant installées. S’il
reste une pièce, passer en revue les différentes étapes pour
découvrir laquelle aurait été oubliée.
2. Vérifier la présence de tous les outils.
3. Éliminer/recycler les matériaux d’emballage.
4. Vérifier que la cuisinière est d’aplomb. Voir “Raccordement
de la cuisinière au circuit d’évacuation par le bas”.
5. Utiliser une solution d’eau tiède et de nettoyant ménager
doux pour éliminer tout résidu de cire laissé par les matériaux
d’emballage. Sécher parfaitement avec un linge doux. Pour
plus d’informations, lire la section “Entretien de la cuisinière”
dans le Guide d’utilisation et d’entretien.
6. Lire la section “Utilisation de la cuisinière” dans le Guide
d’utilisation et d’entretien.
7. Mettre en marche les brûleurs de surface et le four. Pour des
instructions spécifiques concernant l’utilisation de la
cuisinière, consulter le Guide d’utilisation et d’entretien.
Si la cuisinière ne fonctionne pas, contrôler ce qui suit :
■ Les fusibles du domicile sont intacts et serrés ; le disjoncteur
n’est pas déclenché.
■ La cuisinière est branchée sur une prise électrique.
■ La prise de courant est correctement alimentée.
■ Consulter la section “Dépannage” dans le Guide d’utilisation
et d’entretien.
Après 5 minutes de fonctionnement de la cuisinière, vérifier la
chaleur. Si la cuisinière est froide, l’éteindre et contacter un
technicien qualifié.
8. Utiliser la fiche de test du débit fournie avec votre cuisinière
pour contrôler la circulation d’air (voir la fiche pour obtenir
des instructions étape par étape).
12. Insérer le filtre d’évacuation par le bas et placer la plaque de
décharge par-dessus l’ouverture.
B
A
A. Filtre
B. Grille
13. Reconnecter la source de courant électrique.
Si la circulation d’air est insuffisante, consulter les sections
“Exigences concernant l’évacuation” et “Méthodes
d’évacuation”.
Si vous avez besoin d’assistance ou de service :
Consulter la section “Assistance ou service” du Guide
d’utilisation et d’entretien ou contacter le marchand chez qui
vous avez acheté votre cuisinière.
37
Déplacement de la cuisinière
AVERTISSEMENT
Risque de basculement
Un enfant ou une personne adulte peut faire basculer
la cuisinière ce qui peut causer un décès.
Joindre la bride antibasculement au pied arrière de
la cuisinière.
Joindre de nouveau la bride antibasculement si la
cuisinière est déplacée.
Le non-respect de ces instructions peut causer un
décès ou des brûlures graves aux enfants et aux
adultes.
7. Vérifier que la cuisinière est d’aplomb.
8. Reconnecter la cuisinière au circuit d’évacuation par le bas.
Pour les cuisinières avec câblage direct :
AVERTISSEMENT
Risque de choc électrique
Déconnecter la source de courant électrique avant
l'entretien.
Replacer pièces et panneaux avant de faire la remise
en marche.
Le non-respect de ces instructions peut causer
un décès ou un choc électrique.
Lorsqu’on déplace la cuisinière, la faire glisser sur une planche
de carton ou en matériau dur pour éviter d’endommager le
revêtement du sol.
Si le déplacement de la cuisinière est nécessaire pour le
nettoyage ou l’entretien :
Cuisinières alimentées par cordon d’alimentation :
1. Déconnecter la cuisinière du circuit d’évacuation par le bas.
2. Faire glisser la cuisinière vers l’avant.
3. Débrancher le cordon d’alimentation électrique.
4. Effectuer le nettoyage ou l’entretien.
5. Brancher le cordon d’alimentation électrique.
6. Retirer le panneau d’accès et inspecter à l’aide d’une lampe
de poche le dessous de la cuisinière pour vérifier que la bride
antibasculement est bien installée.
■ Vérifier que la bride antibasculement est bien fixée au
plancher ou au mur.
■ Faire glisser de nouveau la cuisinière de façon à ce que le
pied arrière de la cuisinière se trouve sous la bride
antibasculement.
1. Déconnecter la source de courant électrique.
2. Déconnecter la cuisinière du circuit d’évacuation par le bas.
3. Faire glisser la cuisinière vers l’avant.
4. Effectuer le nettoyage ou l’entretien.
5. Retirer le panneau d’accès et inspecter à l’aide d’une lampe
de poche le dessous de la cuisinière pour vérifier que la bride
antibasculement est bien installée.
■ Vérifier que la bride antibasculement est bien fixée au
plancher ou au mur.
■ Faire glisser de nouveau la cuisinière de façon à ce que le
pied arrière de la cuisinière se trouve sous la bride
antibasculement.
6. Vérifier que la cuisinière est d’aplomb.
7. Reconnecter la cuisinière au circuit d’évacuation par le bas.